Thermocouple/
Millivolt Input
User
Module Manual
(Cat. No. 1794-IT8)
Important User Information Because of the variety of uses for the products described in this
publication, those responsible for the application and use of this
control equipment must satisfy themselves that all necessary steps
have been taken to assure that each application and use meets all
performance and safety requirements, including any applicable laws,
regulations, codes and standards.
All other brand and product names are trademarks or registered trademarks of their respective companies.
New Information The following new information has been added to this manual:
Change Bars
The areas in this manual which are different from previous editions
are marked with change bars (as shown to the right of this paragraph)
to indicate the addition of new or revised information.
Publication 1794-6.5.7
ii Table of Contents
Publication 1794-6.5.7
Table of Contents iii
Specifications Appendix A
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A1
Derating Curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2
Resolution Curves for Thermocouples . . . . . . . . . . . . . . . . . . . . A3
Type B Thermocouple . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A3
Type E Thermocouple . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A3
Type C Thermocouple . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A4
Type J Thermocouple . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A4
Type K Thermocouple . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A5
Type R Thermocouple . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A5
Type S Thermocouple . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A6
Type T Thermocouple . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A6
Type N Thermocouple . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A7
Worst Case Accuracy for the Thermocouple/mV Module . . . . . . . A7
Error Due to Open Circuit Current Through Loop Resistance . . . . A8
Worst Case Repeatability for the Thermocouple/mV Input Module A8
Publication 1794-6.5.7
iv Table of Contents
Publication 1794-6.5.7
Preface
Preface Objectives Read this preface to familiarize yourself with this manual and to
learn how to use it properly and efficiently.
Overview of Flex I/O and Your Describes features, capabilities, and hardware
1
Thermocouple/mV Module components.
Writing Configuration to and Reading Describes block transfer write and block transfer read
4 Status from Your Module with a configurations, including complete bit/word descriptions.
Remote I/O Adapter
How Communication Takes Place Describes communication over the I/O backplane
5 and I/O Image Table Mapping with between the module and the adapter, and how data is
the DeviceNet Adapter mapped into the image table.
Appendix
For Additional Information For additional information on FLEX I/O systems and modules, refer
to the following documents:
Publications
Catalog Descr pt on
Description
Number Installation User
Instructions Manual
1787-MGR DeviceNetManager Software User Manual 1787-6.5.3
Industrial Automation Wiring and Grounding Guidelines 1770-4.1
1794 1794 FLEX I/O Product Data 1794-2.1
1794-ADN DeviceNet Adapter 1794-5.14 1794-6.5.5
1794-ASB/C Remote I/O Adapter 1794-5.46 1794-6.5.9
Summary This preface gave you information on how to use this manual
efficiently. The next chapter introduces you to the remote I/O
adapter module.
The FLEX I/O System FLEX I/O is a small, modular I/O system for distributed
applications that performs all of the functions of rack-based I/O. The
FLEX I/O system contains the following components shown below:
20125
How FLEX I/O Analog FLEX I/O thermocouple/mV modules are block transfer modules
Modules Communicate that interface analog signals with any Allen-Bradley programmable
with Programmable controllers that have block transfer capability. Block transfer
Controllers programming moves input or output data words between the
modules memory and a designated area in the processor data table.
Block transfer programming also moves configuration words from
the processor data table to module memory.
Publication 1794-6.5.7
12 Overview of FLEX I/O and your Thermocouple/mV Module
1 2
The adapter transfers your configuration data
External devices transmit
to the module using a BTW.
analog signals to the module.
Flexbus
Allen-Bradley Allen-Bradley 1794IT8
THERMOCOUPLE INPUT 8 CHANNEL
3
ADAPTER
ACTIVE FAULT
LOCAL
FAULT
24VDC
POWER SUPPLY
RIO ADAPTER
4 OK
1794-ASB INPUT 0 INPUT 1 INPUT 2 INPUT 3 INPUT 4 INPUT 5 INPUT 6 INPUT 7
+ + + + + + + +
Your ladder program instructs the
adapter to perform a BTR of the values
and stores them in a data table.
5
The adapter and module determine
that the transfer was made without error and
input values are within specified range.
3
The module converts analog signals
into binary format and stores these
values until the adapter requests
6 their transfer.
Your ladder program can use and/or move the data (if valid)
before it is written over by the transfer of new data in a
subsequent transfer.
7
Your ladder program performs BTWs to the module only when
you power it up, or any time you wish to reconfigure the module.
Publication 1794-6.5.7
Overview of FLEX I/O and your Thermocouple/mV Module 13
Features of your Modules The module label identifies the keyswitch position, wiring and
module type. A removable label provides space for writing
individual designations per your application.
1794-IT8
Module Type
Allen-Bradley 1794IT8
THERMOCOUPLE INPUT 8 CHANNEL
Removable Label
3 Keyswitch
Position
OK
INPUT 0 INPUT 1 INPUT 2 INPUT 3 INPUT 4 INPUT 5 INPUT 6 INPUT 7 Indicator (#3)
+ + + + + + + +
Input Designators
Power On Indicator
Chapter Summary In this chapter, you learned about the FLEX I/O system and the
thermocouple module, and how they communicate with
programmable controllers.
Publication 1794-6.5.7
14 Overview of FLEX I/O and your Thermocouple/mV Module
Publication 1794-6.5.7
Chapter 2
How to Install Your
Thermocouple/mV Input
Module
Before You Install Your Before installing your thermocouple/mV module in the I/O chassis:
Input Module
You need to: As described under:
European Union Directive If this product has the CE mark it is approved for installation within
Compliance the European Union and EEA regions. It has been designed and
tested to meet the following directives.
EMC Directive
Publication 1794-6.5.7
22 How to Install Your Thermocouple/mV Input Module
Power Requirements The wiring of the terminal base unit is determined by the current
draw through the terminal base. Make certain that the current draw
does not exceed 10A.
Publication 1794-6.5.7
How to Install Your Thermocouple/mV Input Module 23
24V dc Note: All modules must be analog modules for this configuration.
24V dc
24V dc or
120V ac
Note: Use this configuration if using any
24V dc noisy dc discrete I/O modules in your system.
24V dc
24V dc
Note: All modules powered by the same power supply
must be analog modules for this configuration.
Total current draw through any base unit must not be greater than 10A
Publication 1794-6.5.7
24 How to Install Your Thermocouple/mV Input Module
6
4
5
1. Rotate the keyswitch (1) on the terminal base unit (2) clockwise
to position 3 as required for the thermocouple/mV module.
2. Make certain the flexbus connector (3) is pushed all the way to
the left to connect with the neighboring terminal base/adapter.
You cannot install the module unless the connector is fully
extended.
3. Before installing the module, check to make sure that the pins on
the bottom of the module are straight so they will align properly
with the female connector in the base unit.
4. Position the module (4) with its alignment bar (5) aligned with
the groove (6) on the terminal base.
5. Press firmly and evenly to seat the module in the terminal base
unit. The module is seated when the latching mechanism (7) is
locked into the module.
6. Repeat the above steps to install the next module in its terminal
base unit.
Publication 1794-6.5.7
How to Install Your Thermocouple/mV Input Module 25
Connecting Wiring for the Thermocouple/mV module wiring is made through the terminal base
Thermocouple/mV Module unit on which the module mounts. The module comes with 2 cold
junction compensators for use when using the thermocouple module
in the thermocouple mode.
Compatible terminal base unit are:
Module 1794-TB2 1794-TB3 1794-TB3T1
1794-IT8 Yes2 Yes2 Yes
1 The 1794-TB3T terminal base unit contains connections for cold junction
compensation for use with thermocouple modules.
2 For millivolt inputs only.
COM COM C C N0 C N1 C N2 C N3 C N4 C N5 C N6 C N7 C
B 1633 B
V V V C J C C J C V
C 3451 C
Publication 1794-6.5.7
26 How to Install Your Thermocouple/mV Input Module
Publication 1794-6.5.7
How to Install Your Thermocouple/mV Input Module 27
1794-TB3
+
Millivolt Millivolt input Channel 1
Source
Channel 0 (Terminals 0, 1 and 17)
1794-TB3T
CJC CJC
Publication 1794-6.5.7
28 How to Install Your Thermocouple/mV Input Module
Module Indicators The thermocouple/mV module has one status indicator that is on
when power is applied to the module. This indicator has 3 different
states:
Allen-Bradley 1794IT8
THERMOCOUPLE INPUT 8 CHANNEL
OK
INPUT 0 INPUT 1 INPUT 2 INPUT 3 INPUT 4 INPUT 5 INPUT 6 INPUT 7
+ + + + + + + +
B A
Chapter Summary In this chapter, you learned how to install your thermocouple/mV
module in an existing programmable controller system and how to
wire to the terminal base units.
Publication 1794-6.5.7
Chapter 3
Block transfer read (BTR) programming moves status and data from
the module to the processors data table. The processor user program
initiates the request to transfer data from the module to the processor.
The transferred words contain module status, channel status and
input data from the module.
Your program should monitor status bits and block transfer read
activity.
Publication 1794-6.5.7
32 Module Programming
Sample programs for The following sample programs show you how to use your analog
FLEX I/O Analog Modules module efficiently when operating with a programmable controller.
PLC-3 Programming
Block transfer instructions with the PLC-3 processor use one binary
file in a data table section for module location and other related data.
This is the block transfer control file. The block transfer data file
stores data that you want transferred to your module (when
programming a block transfer write) or from your module (when
programming a block transfer read). The address of the block
transfer data files are stored in the block transfer control file.
The same block transfer control file is used for both the read and
write instructions for your module. A different block transfer
control file is required for every module.
Figure 3.1
PLC-3 Family Sample Program Structure
BTR Enable
Program Action BLOCK XFER READ EN
Block Transfer
RACK: 7 12
Read Done Bit
B3:0 GROUP: 0 Done
At power-up in RUN mode, or when the 1 MODULE: 0 DN
processor is switched from PROG to RUN, CONTROL: #B3:0 15
the user program enables a block transfer 15 DATA FILE: #B4:0 Error
read. Then it initiates a block transfer write LENGTH: 11 ER
to configure the module. 13
Thereafter, the program continuously Block Transfer
performs read block transfers. Write Done Bit
Pushbutton BTW Enable
B3:0
Note: You must create the data file 2 BLOCK XFER WRITE EN
for the block transfers before you RACK: 7 02
enter the block transfer instructions. 05 GROUP: 0 Done
MODULE: 0
DN
Power-up Bit CONTROL: #B3:0 05
B4:10 DATA FILE: #B5:0
The pushbutton allows the user to Error
LENGTH: 3
manually request a block transfer write. ER
03
03
Publication 1794-6.5.7
Module Programming 33
PLC-5 Programming
The PLC-5 program is very similar to the PLC-3 program with the
following exceptions:
1. Block transfer enable bits are used instead of done bits as the
conditions on each rung.
2. Separate block transfer control files are used for the block
transfer instructions.
Figure 3.2
PLC-5 Family Sample Program Structure
Publication 1794-6.5.7
34 Module Programming
PLC-2 Programming
The 1794 analog I/O modules are not recommended for use with
PLC-2 family programmable controllers due to the number of digits
needed for high resolution.
Chapter Summary In this chapter, you learned how to program your programmable
controller. You were given sample programs for your PLC-3 and
PLC-5 family processors.
Publication 1794-6.5.7
Chapter 4
Writing Configuration to and
Reading Status from your
Module with a Remote I/O
Adapter
Configuring Your Because of the wide variety of possible configurations, you must
Thermocouple/mV Module configure your module to conform to the specific application that
you have chosen. The module is configured using a group of data
table words that are transferred to the module using a block transfer
write instruction.
Range Selection Individual input channels are configurable to operate with the
following sensor types:
Input Scaling Scaling lets you report each channel in actual engineering units.
Scaled values are in integer format.
You select input scaling using the designated words of the write
block transfer instruction. Refer to the Bit/Word description for write
word 0, bits 00 and 01.
Hardware First Notch Filter A hardware filter in the analog to digital converter lets you select a
frequency for the first notch of the filter. Selection of the filter
influences the analog to digital output data rate and changes the
module throughput. Module throughput is a function of the number
of inputs used and the first notch filter. Both of these influence the
time from a thermocouple input to arrival at the backplane.
Reading Data From Your Read programming moves status and data from the thermocouple
Module input module to the processors data table. The processors user
program initiates the request to transfer data from the
thermocouple/mV input module to the processor.
Mapping Data for the The following read and write words and bit/word descriptions
Analog Modules describe the information written to and read from the
thermocouple/mV input module. The module uses up to 11 words of
input image and up to 3 words of output image. Each word is
composed of 16 bits.
Reserved
Input Data Channel 0
Input Data Channel 1
I/O Image
Input Data Channel 2
Input Size
Input Data Channel 3
1 to 11 Words
Input Data Channel 4
Input Data Channel 5
Input Data Channel 6
Input Data Channel 7
Overrange Underrange
Calibration Status
Output Size
Calibration Mask Configuration
0 to 3 Words
Thermocouple Type
Thermocouple Type
Decimal Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Octal Bit 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
Read Word 0 Reserved
1 Channel 0 Input Data
2 Channel 1 Input Data
3 Channel 2 Input Data
4 Channel 3 Input Data
5 Channel 4 Input Data
6 Channel 5 Input Data
7 Channel 6 Input Data
8 Channel 7 Input Data
Decimal Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Octal Bit 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
9 Overrange Bits Underrange Bits
Bad Cal Cal Pwr Bad CJC CJC
10 0 0 0 0 0 0 Diagnostic Status
Cal Done Range Up Structure over Under
Dec. Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Octal Bit 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
Cal Cal hi
Write Word 0 8-Bit Calibration Mask Filter Cutoff FDF Data Type
Clk Cal lo
1 Thermocouple 3 Type Thermocouple 2 Type Thermocouple 1 Type Thermocouple 0 Type
2 Thermocouple 7 Type Thermocouple 6 Type Thermocouple 5 Type Thermocouple 4 Type
Where: FDF = fixed digital filter bit
Decimal Bit
Word (Octal Bit) Description
0 1 oF
Decimal Bit
Word (Octal Bit) Description
Chapter Summary In this chapter, you learned how to configure your modules features
and enter your data.
Polled I/O Structure Output data is received by the adapter in the order of the installed
I/O modules. The Output data for Slot 0 is received first, followed
by the Output data for Slot 1, and so on up to slot 7.
The first word of input data sent by the adapter is the Adapter Status
Word. This is followed by the input data from each slot, in the order
of the installed I/O modules. The Input data from Slot 0 is first after
the status word, followed by Input data from Slot 2, and so on up to
slot 7.
DeviceNet Adapter
Read Data
Adapter Status
Slot 0 Input Data
Network READ Slot 1 Input Data
...
...
Write Data
Read
Write
I/O Module I/O Module
Slot 0 Slot 1
... I/O Module
Slot 7
Slot 0 Output Data
Slot 1 Output Data
Network WRITE
...
...
Slot 7
Slot 6
Slot 5
Slot 4
Slot 3
Slot 2
Slot 1
Slot 0
Not Used
The adapter input status word bit descriptions are shown in the
following table.
System Throughput System throughput, from analog input to backplane, is a function of:
Mapping Data into the FLEX I/O thermocouple module data table mapping is shown below.
Image Table
Thermocouple/mV Input Module (1794-IT8) Image Table Mapping
Module Image
Reserved
Input Data Channel 0
Input Data Channel 1
I/O Image
Input Data Channel 2
Input Size
Input Data Channel 3
1 to 11 Words
Input Data Channel 4
Input Data Channel 5
Input Data Channel 6
Input Data Channel 7
Overrange Underrange
Calibration Status
Output Size
Calibration Mask Configuration
0 to 3 Words
Thermocouple Type
Thermocouple Type
Dec. Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Octal Bit 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
Read Word 1 Reserved
Read Word 2 Channel 0 Input Data
Read Word 3 Channel 1 Input Data
Read Word 4 Channel 2 Input Data
Read Word 5 Channel 3 Input Data
Read Word 6 Channel 4 Input Data
Dec. Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Octal Bit 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
Read Word 7 Channel 5 Input Data
Read Word 8 Channel 6 Input Data
Read Word 9 Channel 7 Input Data
Read Word 10 Overrange Bits Underrange Bits
Bad Cal Cal Pwr Bad CJC CJC
Read Word 11 0 0 0 0 0 0 Diagnostics
Cal Done Range Up Structure over Under
Dec. Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Octal Bit 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
Cal Cal hi
Write Word 1 8-Bit Calibration Mask Filter Cutoff FDF Data Type
Clk Cal lo
Write Word 2 Thermocouple 3 Type Thermocouple 2 Type Thermocouple 1 Type Thermocouple 0 Type
Write Word 3 Thermocouple 7 Type Thermocouple 6 Type Thermocouple 5 Type Thermocouple 4 Type
Where: FDF = fixed digital filter bit
Decimal Bit
Word (Octal Bit) Description
Read Word 11 03 (03) Powerup bit this bit is set (1) until configuration data is received by the module.
continu
continued
0406 (0406) Critical Fault bits If these bits are anything other than zero, return the module to the factory for repair.
07 (07) Unused set to 0
08 (10) Calibration Range bit set to 1 if a reference signal is out of range during calibration
09 (11) Calibration Done bit set to 1 after an initiated calibration cycle is complete.
10 (12) Calibration Bad bit set to 1 if the channel has not had a valid calibration.
1115 (1317) Unused set to 0
Write Word 1 0001 (0001) Module Data Type
Bit 01 00 Definition
0 0 oC (default)
0 1 oF
Decimal Bit
Word (Octal Bit) Description
Defaults Each I/O module has default values associated with it. At default,
each module will generate inputs/status and expect
outputs/configuration.
Factory defaults are the values assigned by the adapter when you:
You can change the I/O data size for a module by reducing the
number of words mapped into the adapter module, as shown in real
time sizes.
Real time sizes are the settings that provide optimal real time data to
the adapter module.
Tools and Equipment In order to calibrate your thermocouple input module you will need
the following tools and equipment:
Removing Lead Wire or The thermocouple/mV module has open circuit detection. This is
Thermocouple Extension accomplished by a 1A current source in the module. This current
Wire Resistance flowing through the lead wire or thermocouple extension wire
generates an error or offset voltage in the reading. Use the Error
Due to Open Circuit Current Through Loop Resistance in appendix
A to determine if the magnitude of the error is acceptable.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
0 15 A
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
1633 B
34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
3451 C
1794-TB3, -TB3T
a. Disconnect the lead wires at the terminal base unit.
b. Measure total loop resistance of both lead/extension wires and thermocouple.
c. If using a sensor other than a thermocouple, disconnect the lead wires at the
sensor and tie together for this measurement. Reconnect after measurement. Thermocouple
or
d. After measuring, remove ohmmeter. Sensor
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
2 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
0 15 A
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
1633 B
34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
3451 C
1794-TB3, -TB3T
Decade Box
a. Set decade box to value determined in step 1, and connect in series with a preci-
sion voltage source.
b. Connect to the input terminals of the particular channel you are calibrating. Thermocouple
or
Voltage Source c. Perform an offset and gain calibration as outlined later in this chapter. Sensor
Disconnected
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
3 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
0 15 A
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
1633 B
34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
3451 C
1794-TB3, -TB3T
Manually Calibrating your You must calibrate the module in a FLEX I/O system. The module
Thermocouple/mV Input must communicate with the processor and a programming terminal.
Module You can calibrate input channels in any order, or all at once.
Before calibrating your module, you must enter ladder logic into the
processor memory, so that you can initiate BTWs to the module, and
read inputs from the module.
Apply reference signal for offset Apply reference signal for gain
calibration to each channel to calibration to each channel to
be calibrated. be calibrated.
BTW BTW
BTW BTW
BTR BTR
NO NO
Caldone = 1 Caldone = 1
? ?
YES YES
NO NO Badcal = 0
Badcal = 0 Calrange = 0
Exit Calrange = 0 Exit
? ?
YES YES
Set calclk =0
Set calclk =0
and
cal hi/lo = 0
BTW
BTW
BTR
BTR
NO NO
Caldone = 0 Caldone = 0
? ?
YES YES
Clear corresponding bits in
the calibration mask
Legend:
BTW = block transfer write
BTW
BTR = block transfer read
Calibration Setups
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
0 15 A
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
1633 B
34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
3451 C
Precision Voltage Source These terminals not on 1794-TB2
1794-TB2, -TB3
Note: Use 1794-TB2 and -TB3 terminal base units for millivolt inputs only.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
0 15 A
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
1633 B
34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
3451 C
Precision Voltage Source CJC 1794-TB3T CJC
1 2 3 19 2 3 40
2 4 5 21 4 5 41
3 6 7 23 6 7 42
4 8 9 25 8 9 43
5 10 11 27 10 11 44
6 12 13 29 12 13 45
7 14 15 31 14 15 46
24V dc Common 16 thru 33 16, 17, 19, 21, 23, 25, 27, 29, 31 and 33
+24V dc power 1794-TB2 34 and 51; 1794-TB3 34 thru 51 34, 35, 50 and 51
1 Terminals 39 to 46 are chassis ground.
2 Terminals 36, 37, 38 and 47, 48, 49 are cold
junction compensator connections.
Dec. Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Octal Bit 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
Bad Cal Cal Pwr Bad CJC CJC
Read Word 10 0 0 0 0 0 0 Diagnostic Status
Cal Done Range Up Struct over Under
Cal Cal hi
Write Word 0 8-Bit Calibration Mask Filter Cutoff FDF Data Type
Clk Cal lo
Offset Calibration
Gain Calibration
Calibrating Your The following procedure assumes that you are using
Thermocouple/mV Module DeviceNetManager software (cat. no. 1787-MGR) and have the
using DeviceNetManager thermocouple/mV module installed in a working system.
Software
(Cat. No. 1787-MGR) Offset Calibration
Inputs can be calibrated one at a time or all at once. To calibrate the
offsets for all inputs at once, proceed as follows:
Gain Calibration
Make sure that you have calibrated the offset for this channel before
calibrating the gain.
31.2
19.2
25oC 40oC 50oC 55oC
= Safe operating area
Ambient Temperature
Type B Thermocouple
C
Resolution
F
1000Hz 500Hz 250Hz 10100Hz
102.4 25.60 6.40 0.80
184.3 46.08 11.52 1.44
89.60 22.40 5.60 0.70
161.3 40.32 10.08 1.26
76.80 19.20 4.80 0.60
138.2 34.56 8.64 1.08
64.00 16.00 4.00 0.50
115.2 28.80 7.20 0.90
51.20 12.80 3.20 0.40
92.16 23.04 5.76 0.72
38.40 9.60 2.40 0.30
69.12 17.28 4.32 0.54
25.60 6.40 1.60 0.20
46.08 11.52 2.88 0.36
12.80 3.20 0.80 0.10
23.04 5.76 1.44 0.18
0
300 150 0 150 300 450 600 750 900 1050 1200 1350 1500 1650 1800
508 238 32 302 572 842 1112 1382 1652 1922 2192 2462 2732 3002 3272
Temperature C
F
Type E Thermocouple
C
Resolution
F
1000Hz 500Hz 250Hz 10100Hz
64.00 16.00 4.00 0.50
115.2 28.80 7.20 0.90
0
300 150 0 150 300 450 600 750 900 1050 1200
508 238 32 302 572 842 1112 1382 1652 1922 2192
Temperature C
F
Type C Thermocouple
C
Resolution
F
1000Hz 500Hz 250Hz 10100Hz
32.00 8.00 2.00 0.25
57.60 14.4 3.60 0.45
0
300 0 300 600 900 1200 1500 1800 2100 2400
508 32 572 1112 1652 2192 2732 3272 3812 4352
Temperature C
F
Type J Thermocouple
C
Resolution
F
1000Hz 500Hz 250Hz 10100Hz
17.92 4.480 1.120 0.140
32.25 8.064 2.016 0.252
15.36 3.840 0.960 0.120
27.65 6.912 1.728 0.216
12.80 3.200 0.800 0.100
23.04 5.760 1.440 0.180
10.24 2.560 0.640 0.080
18.43 4.608 1.152 0.144
7.680 1.920 0.480 0.060
13.82 3.456 0.864 0.108
5.120 1.280 0.320 0.040
9.216 2.304 0.576 0.072
2.560 0.640 0.160 0.020
4.608 1.152 0.288 0.036
0
300 150 0 150 300 450 600 750 900 1050 1200
508 238 32 302 572 842 1112 1382 1652 1922 2192
Temperature C
F
Type K Thermocouple
C
Resolution
F
1000Hz 500Hz 250Hz 10100Hz
128.0 32.00 8.000 1.000
230.4 57.60 14.40 1.800
0
300 150 0 150 300 450 600 750 900 1050 1200 1350 1500
508 238 32 302 572 842 1112 1382 1652 1922 2192 2462 2732
Temperature C
F
Type R Thermocouple
C
Resolution
F
1000Hz 500Hz 250Hz 10100Hz
102.4 25.60 6.40 0.80
184.3 46.08 11.52 1.44
0
300 150 0 150 300 450 600 750 900 1050 1200 1350 1500 1650 1800
508 238 32 302 572 842 1112 1382 1652 1922 2192 2462 2732 3002 3272
Temperature C
F
Type S Thermocouple
C
Resolution
F
1000Hz 500Hz 250Hz 10100Hz
76.80 19.20 4.80 0.60
138.2 34.56 8.64 1.08
0
300 150 0 150 300 450 600 750 900 1050 1200 1350 1500 1650 1800
508 238 32 302 572 842 1112 1382 1652 1922 2192 2462 2732 3002 3272
Temperature C
F
Type T Thermocouple
Resolution C
F
1000Hz 500Hz 250Hz 10100Hz
102.4 25.60 6.40 0.80
184.3 46.08 11.52 1.44
89.60 22.40 5.60 0.70
161.3 40.32 10.08 1.26
76.80 19.20 4.80 0.60
138.2 34.56 8.64 1.08
64.00 16.00 4.00 0.50
115.2 28.80 7.20 0.90
51.20 12.80 3.20 0.40
92.16 23.04 5.76 0.72
38.40 9.60 2.40 0.30
69.12 17.28 4.32 0.54
25.60 6.40 1.60 0.20
46.08 11.52 2.88 0.36
12.80 3.20 0.80 0.10
23.04 5.76 1.44 0.18
0
300 150 0 150 300 450 600
508 238 32 302 572 842 1112
Temperature C
F
Type N Thermocouple
C
Resolution
F
1000Hz 500Hz 250Hz 10100Hz
128.0 32.00 8.00 1.00
230.4 57.60 14.40 1.80
0
300 150 0 150 300 450 600 750 900 1050 1200 1350
508 238 32 302 572 842 1112 1382 1652 1922 2192 2462
Temperature C
F
Type L Thermocouple
C
Resolution
F
1000Hz 500Hz 250Hz 10100Hz
0
200 150 100 0 50 100 200 300 400 500 600 700 800
328 238 148 32 122 212 392 572 752 932 1112 1292 1472
Temperature C
F
B 0.091oC 0.164oF
E 0.013oC 0.023oF
J 0.016oC 0.029oF
K 0.024oC 0.043oF
R 0.076oC 0.137oF
S 0.083oC 0.149oF
T 0.022oC 0.040oF
N 0.028oC 0.050oF
C 0.055oC 0.099oF
L 0.015oC 0.028oF
mV 0.417V (2.4 = 1 LSB of error)
General Following are some restrictions extracted from NBS Monograph 125
(IPTS68) issued March 1974 on thermocouples B, E, J, K, R, S
and T:
Publication 1794-6.5.7
B2 Thermocouple Restrictions
Publication 1794-6.5.7
Thermocouple Restrictions B3
Publication 1794-6.5.7
B4 Thermocouple Restrictions
Publication 1794-6.5.7
Thermocouple Restrictions B5
Publication 1794-6.5.7
B6 Thermocouple Restrictions
Use this template for your appendices. If it were not for the different
running head, this would be your chapter 4 document.
Publication 1794-6.5.7
Index
B D
bit/word description, thermocouple module, daisychaining wiring, 23
1794-IT8, 45, 54 default values, 57
block transfer derating curve, A2
read, 12 DeviceNetManager, software, 51
write, 12
DeviceNetManager software, 69
block transfer programming, 31
block transfer read, 44
1794-IT8, 44, 53 E
block transfer write example
1794-IT8, 45, 54 thermocouple/1794-TB3, 27
configuration block, 1794-IT8, 45, 54 thermocouple/1794-TB3T, 27
input range selection, 42
F
C features, of the module, 13
calibration first notch filter, 43
gain, 68 flow chart, calibration, 65
manual, 64
offset, 67
periodic, 61 G
preparation, 64
setups, 66 gain calibration, 68
tools, 62 using DeviceNetManager, 611
types of, 61
using decade box, 66
I
using DeviceNetManager, 69
using resistors, 66 I/O module fault, 52
calibration flow chart, 65 indicators
calibration words, 67 states, 28
status, 28
cold junction compensators, 13
input ranges, 42
cold junction connection wiring, 26
input scaling, 42
communication, between module and
adapter, 12 input status word, 52
compatible terminal bases, 25 installation, module, 24
configurable features, 41
connecting CJC, 26
Publication 1794-6.5.7
I2 Index
P
T
PLC2 programming, 34
terminal bases, compatible, 25
polled I/O, structure, 51
thermocouple input mapping, 1794-IT8,
power defaults, 57 44, 53
preparing for calibration, 64 thermocouple/1794-TB3T example, 27
programming example throughput, normal mode, 43
PLC3, 32
PLC5, 33
W
R wiring
connections, 66
range, selecting, 42 methods of, 23
read/write words, for calibration, 67 to terminal bases, 21
removing and replacing, under power wiring connections, 25
(RIUP), 24 1794-IT8, 26, 66
Publication 1794-6.5.7
Allen-Bradley
Publication Problem Report
If you find a problem with our documentation, please complete and return this form.
Cat. No. 1794-IT8 Pub. No. 1794-6.5.7 Pub. Date April 1997 Part No. 955112856
Clarity
What is unclear?
Sequence
What is not in the right order?
Other Comments
Use back for more comments.
Return to: Marketing Communications, Allen-Bradley Co., 1 Allen-Bradley Drive, Mayfield Hts., OH 44124-6118 Phone: (216)646-3176
FAX: (216)646-4320
Other Comments
PLEASE REMOVE
PLEASE FOLD HERE
NO POSTAGE
NECESSARY
IF MAILED
IN THE
UNITED STATES
1 ALLEN BRADLEY DR
MAYFIELD HEIGHTS OH 44124-9705
Support Services At Allen-Bradley, customer service means experienced
representatives at Customer Support Centers in key cities throughout
the world for sales service and support. Our value-added services
include:
Technical Support
SupportPlus programs
telephone support and 24-hour emergency hotline
software and documentation updates
technical subscription services
Technical Training
Worldwide representation.
Argentina Australia Austria Bahrain Belgium Brazil Bulgaria Canada Chile China, PRC Colombia Costa Rica Croatia Cyprus Czech Republic
Denmark Ecuador Egypt El Salvador Finland France Germany Greece Guatemala Honduras Hong Kong Hungary Iceland India Indonesia
Ireland Israel Italy Jamaica Japan Jordan Korea Kuwait Lebanon Malaysia Mexico Netherlands New Zealand Norway Pakistan Peru