Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Project Construction of 33 & 11 KV Network and construction of

33/11 KV Primary substation to feed power supply to Zeenat


Al Sahra farms at Seih Al Khairat in Wilayat thumrait Dhofar
Governorate
DIWAN OF ROYAL COURT (RCA) - RURAL AREAS
Client Date 30-07-2017
ELECTRICITY CO. SAOC
Contractor CIVIL CONTRACTING CO (CIVILCO) .LLC Report. No TLC58/TC/AR VT
Tender No. ---- Device 11KV Auto Recloser

Test Report for 11KV Auto Recloser VT

Location: DIWAN OF ROYAL COURT- 11KV Feeder

Potential Transformer Details:

Make ENERGO GROUP Serial No. 2313/16


PT Ratio 11000V/230V Type: VTOP -2-12

Core No. Ratio Burden in VA Class


1 (2a-2b) 11KV/230V 200 VA 3

Testing Equipment Details

Equipment Name Make & Model Serial Number Calibration Validity


Insulation Tester Kyoritsu, 3125 W2031578 24-8-2017
Digital Multimeter FLUKE,87 10010330 15-09-2017
Primary Injection Kit Omicron CPC100 PB976V (V1) 06.08.2018

1. Insulation Resistance Test:

Applied Voltage Circuit Ref Measured Value


(V)
5000 Pri - Earth >1 T
5000 Pri sec >1 T
250 Sec- Earth >1 T

2. Ratio Test:

VTRatio: VTRatio 1
Date/Time: 7/30/2017 9.56

Tested By Witnessed/Approved By
CIVIL CONTRACTING CO (CIVILCO) .LLC RURAL AREAS ELECTRICITY CO. SAOC
Sign: Sign;

Name: T. Satti Reddy, Name:


Date: 30-07-2017 Date:
Overload: NO
Assessment: OK
Range: AC 2kV
Nominal
values:
V prim.: 11000.0V
V sec.: 230.0V
Frequency: 50.0Hz
V test: 2000.0V
Automatic: YES
V sec manual: NO
Results:
V prim.: 1999.6V V prim Phase: 0.0
V sec.: 42.647724V V sec Phase: 0.03
Ratio: 11000.0V: 234.6091V 2.0%
Polarity: OK

3. Secondary Winding Resistance Test:

Core Between
R-YPHASE
Terminals
Core - 1 2a 2b 2.5

4. Remarks/Observations: ok

Tested By Witnessed/Approved By
CIVIL CONTRACTING CO (CIVILCO) .LLC RURAL AREAS ELECTRICITY CO. SAOC
Sign: Sign;

Name: T. Satti Reddy, Name:


Date: 30-07-2017 Date: