Steel Frame Internal Wall Systems Single Stud
SYSTEM SPECIFICATION TYPICAL LAYOUT (CSR 005a shown)
B
STUD DEPTH mm 51 64 76 92 150
FRL SYSTEM
WALL LININGS CAVITY INFILL
Report/Opinion N Rw / Rw+Ctr
(Refer to Bradford)
CSR 005 Plus (a) Nil 28/20 29/21 30/22 30/23 34/27
(b) 50 GW Acoustigard 11kg 36/28 37/29 38/30 38/31 41/34
BOTH SIDES
(c) 75 GW Acoustigard 11kg 39/31 39/31 39/32 42/35
// 1 x 10mm Gyprock Plus
(d) MSB3 Polyester 34/26 35/27 36/28 36/29 39/32
plasterboard.
(e) 60NG SoundScreen 1.7 39/31 39/31 40/32 40/33 43/36
WALL THICKNESS mm 71 84 96 112 170
STUD DEPTH mm 64 76
FRL SYSTEM
WALL LININGS
Report/Opinion N CAVITY INFILL (Both Sides) Rw / Rw+Ctr
(Refer to Bradford)
CSR 100 Plus (a 50 GW Acoustigard 11kg 60/47 61/49
PKA-054
Discontinuous
Lining material as per system table. Construction
Gyprock SecurityWall Panel 27.
Cavity determined by track width.
Gyprock SecurityWall Panel 27.
PKA-054
Discontinuous
Lining material as per system table. Construction
PKA-054
Lining material as per system table.
Discontinuous
Gyprock SecurityWall Panel 50. Construction
Cavity determined by track width.
Gyprock SecurityWall Panel 50.
Lining material as per system table.
PKA-054
PKA-055
Cemintel RendaLine sheet on timber or steel battens.
Wall Wrap/Sarking.
Steel studs at 600mm maximum centres.
Lining material to internal side as per system table.
NOTE:
INTERNAL WALL SIDE (b) 75 Gold Batts 2.0 45/36 2.54 2.31
// 1 x 10mm Gyprock Plus
plasterboard. (c) 60 NG SoundScreen 1.7 46/38 2.23 2.03
PKA-055
Cemintel RendaLine sheet on timber or steel battens.
Wall Wrap/Sarking.
Lining material to external side as per system table.
Steel studs at 600mm maximum centres.
Lining material to internal side as per system table.
NOTE:
Thermal performance based on 35mm battens, wall wrap of Bradford Enviroseal
Proctorwrap RW.
NOTE:
Thermal performance based on 35mm battens, wall wrap of Bradford Enviroseal
Proctorwrap RW.
B
FRL SYSTEM STUD DEPTH mm 76 THERMAL
WALL LININGS
Report/Opinion N CAVITY INFILL (Refer to Bradford) Rw / Rw+Ctr Rt(WIN) Rt(SUM)
CSR 170 Plus (a) Nil 39/31 1.05 0.99
EXTERNAL SIDE
NOTES:
B Acoustic performance valid for studs (51/64mm x 0.50 BMT) (76/92 x 0.55 BMT)
(150mm x .075 BMT).
*ACR = Axial Capacity Reduction. Refer to The Red Book.
Thermal performance based on 35mm battens, wall wrap of Bradford Enviroseal
Proctorwrap RW.
Wall Wrap/Sarking.
Lining material to external side as per system table.
Steel studs at 600mm maximum centres.
Lining material to internal side of steel studs as per system
table.
NOTES:
Acoustic performance valid for studs (51/64mm x 0.50 BMT) (76/92 x 0.55 BMT)
B
(150mm x .075 BMT).
*ACR = Axial Capacity Reduction. Refer to The Red Book.
Thermal performance valid for wall wrap of Bradford Enviroseal Proctorwrap RW.
PKA-055
Fire rated masonry veneer wall.
Steel studs at 600mm maximum centres with 40mm
minimum gap to masonry.
Lining material as per system table.
NOTES:
Masonry to be minimum 90mm thick and 170kg/m2
Thermal performance valid for 110mm extruded brick to AS4859.
NOTES:
Acoustic performance valid for 35mm wide studs at 600mm centres.
CSR 352 Plus SIDE ONE (ANY ORDER) (a) Nil 36/29 38/31 40/33 41/35
1 x 10mm Gyprock Plus
/60/60 plasterboard. (b) 75 Gold Batts 1.5 41/34 43/36 45/38 46/40
and 1 x 13mm Gyprock
30/30/30 (c) 70NG SoundScreen 2.0 42/35 44/37 46/39 46/40
Fyrchek plasterboard.
FAR 2303 SIDE TWO (d) MSB3 Polyester 39/32 41/34 43/36 43/37
1 x 13mm Gyprock
Fyrchek plasterboard. WALL THICKNESS mm 106 126 156 176
NOTES: Unless otherwise specified, cavity infill is required in one stud row only.
PKA-018
Lining material as per system table.
Timber studs at 600mm maximum centres. Discontinuous
Construction
Cavity insulation as per system table.
20-40mm separation between frame and Gyprock Shaft
Liner Panel.
25mm Gyprock Shaft Liner Panel between steel H-Studs
at 600mm maximum centres.
20-40mm separation between frame and Gyprock Shaft
Liner Panel.
Cavity insulation as per system table.
Timber studs at 600mm maximum centres.
Lining material as per system table.
NOTES: Refer to GYP513 Gyprock Party Wall System for design considerations. C
STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL Both Sides
Report/Opinion N Rw / Rw+Ctr
(Refer to Bradford)
CSR 361 Plus
(a) 75 Gold Batts 2.0 62/49 63/51
NOTES: Refer to GYP513 Gyprock Party Wall System for design considerations.
STUD DEPTH mm 70 90
FRL SYSTEM
WALL LININGS CAVITY INFILL Both Sides
Report/Opinion N Rw / Rw+Ctr
(Refer to Bradford)
CSR 369 Plus
(a) 75 Gold Batts 2.0 64/52 65/53
PKA-051
Lining material as per system table.
Staggered timber studs at 600mm maximum centres each NOT
side. Deemed
Discontinuous
Minimum 20mm clearance between stud and opposing Construction
lining.
No noggings or any connection between studs.
Cavity insulation as per system table. (Insulation may need
to be cut and placed between studs).
Lining material as per system table.
60/60/60*
EXTERNAL WALL SIDE
1 x 16mm Gyprock Fyrchek
(a) Nil
38
0.67
2.07
0.61
1.84
C
from outside only MR plasterboard.
* ACR Group 2
INTERNAL WALL SIDE
(c) 70 NG SoundScreen 2.0 39 2.60 2.37
FAR 2303 1 x 10mm Gyprock Plus
plasterboard. TYPICAL WALL THICKNESS mm 157
44/37
0.47
2.40
0.45
2.20
from outside only MR plasterboard.
* ACR Group 1 INTERNAL WALL SIDE
(c) 70 NG SoundScreen 2.0 43/36 2.40 2.20
FAR 2303 1 x 10mm Gyprock Plus
plasterboard. WALL THICKNESS mm 120
59/50
2.16
3.22
1.99
2.94
C
Refer to masonry
manufacturer
1 x 10mm Gyprock Plus
plasterboard. WALL THICKNESS mm 250
Wall Wrap/Sarking.
Timber studs at 600mm maximum centres.
Cavity insulation as per system table.
Lining material as per system table to internal side.
NOTES:
Acoustic performance valid for 35mm wide studs at 600mm centres.
Thermal performance based on 35mm battens, wall wrap of Bradford
Enviroseal Proctorwrap RW.
Wall Wrap/Sarking.
1 x 16mm Gyprock Fyrchek MR plasterboard fixed to framing.
Timber stud framing as required.
1 layer x 10mm Gyprock Plus plasterboard fixed to framing.
NOTES: *ACR = Axial Capacity Reduction. (Refer to The Red Book Table C3).
Thermal performance based on 35mm battens, wall wrap of Bradford
Enviroseal Proctorwrap RW.
PKA-053
Discontinuous
Construction
Lining as per table, fixed to studs.
Steel stud framing, as per table, at 600mm max. centres.
Cavity infill as per table.
12mm minimum cavity between masonry and framing.
Single Brick, Block or Concrete wall with Rw as stated.
Plasterboard as per system table, direct fixed to masonry.
PKA-053
D Block or
Concrete
Wall with Rw
BOTH SIDES
1 x 10mm Gyprock Plus
(b) 90 Gold Batts 2.0 60/47 61/48
PKA-053
1 x 10mm Gyprock
// (b) 90 Gold Batts 2.0 40/32 80-85 60-65
Supaceil plasterboard.
1 x 10mm Gyprock
// (b) 90 Gold Batts 2.0 44/35 80-85 60-62
Supaceil plasterboard.
1 x 10mm Gyprock
// (b) 90 Gold Batts 2.0 44/37 80-85 60-62
Plus plasterboard.
PKA056
150mm concrete slab.
RONDO furring channel.
Cavity infill as per system table in 45mm cavity.
Ceiling lining as per system table, fixed to furring channel.
CSR 259
(a) Nil 55/43 70-75 40-45
E
SYSTEM SPECIFICATION TYPICAL LAYOUT (CSR 339a shown) ACOUSTIC
OPINION
CSR 339
(a) Nil 57/45 65-70 35-40
PKA056
125mm concrete slab.
RONDO Suspended Ceiling System.
Minimum 150mm cavity.
Cavity infill as per system table.
Ceiling lining as per system table, fixed to furring channel.
E Floor/Ceiling Systems
SYSTEM SPECIFICATION TYPICAL LAYOUT (CSR 557a shown) ACOUSTIC
OPINION
PKA056
125mm concrete slab.
RONDO Suspended Ceiling System with Gyprock
Resilient Mounts.
Minimum 150mm cavity.
Cavity infill as per system table.
Ceiling lining as per system table, fixed to furring channel.
CSR 949
(a) 165 Gold Batts 3.0 41/31 39/34 41/35
1 x 10mm Gyprock
// (b) 215 Gold Batts 4.1 42/33 40/35 42/37
Supaceil plasterboard.
1 x 10mm Gyprock
// (b) 215 Gold Batts 4.1 44/35 42/37 44/39
Plus plasterboard.
2 x 10mm Gyprock
// (b) 215 Gold Batts 4.1 47/38 45/40 47/42
Plus plasterboard.
PKA056
A pitched tiled roof with or without 350g/m2 sarking.
OR
A steel sheet roof minimum 0.42mm with minimum
Bradford Anticon 55 insulation over battens.
Ceiling Joists or Trusses.
RONDO Furring Channel clipped to Gyprock Resilient
Mounts.
Cavity infill as per system table.
Ceiling lining as per system table, fixed to furring channel.
1 x 10mm Gyprock
// (d) 215 Gold Batts 4.1 46/37 44/39 46/41
Supaceil plasterboard.
E Roof/Ceiling Systems
SYSTEM SPECIFICATION TYPICAL LAYOUT (CSR 896a shown) ACOUSTIC
OPINION
PKA056
CSR 896
(a) 140 Gold Batts 2.5 44/35
1 x 10mm Gyprock
//
Supaceil plasterboard.
PKA056
PKA052
FRL SYSTEM
CEILING LININGS CAVITY INFILL (Refer to Bradford) Rw / Rw+Ctr
Report/Opinion N
ABOVE (a) Nil 36/29
60/60/60
from top CSR 981 1 x 16mm Gyprock Fyrchek plasterboard. (b) 50 GW Acoustigard 11kg 43/36
only Plus BELOW
FAR 2358 (c) 90 Gold Batts 2.0 46/39
1 x 10mm Gyprock Plus plasterboard.
ABOVE (a) Nil 41/34
120/120/120
from top CSR 983 2 x 16mm Gyprock Fyrchek plasterboard.
only Plus BELOW (b) 75 GW Acoustigard 11kg 48/41
FAR 2358 1 x 10mm Gyprock Plus plasterboard.
PKA058
Maximum N
System N Linings Cavity Insulation Pipe Lagging Downlights Rw + Ctr
per 5m2
CSR SS04 Plus
(a) Nil Nil 0 25
PKA058
Maximum N
System N Linings Cavity Insulation Pipe Lagging Downlights Rw + Ctr
per 5m2
CSR SS13 Plus
(a) Nil Nil 0 23
2 x 10mm Gyprock Plus
plasterboard.
(b) 75 GW Acoustigard 11kg Acoustilag 45 5 41
Maximum N
System N Linings Cavity Insulation Pipe Lagging Downlights Rw
per 5m2
CSR SS34 Plus
(a) 75 GW Acoustigard 11kg Nil 5 30
PKA052
Service Shaft or Ceiling
Inner layer lining (as per system table) direct fixed to timber
or steel framing, to encase services.
Maximum N
Insulation
System N Linings Downlights Rw/Rw+Ctr
(Refer to System Specification)
per 5m2
CSR SS40 Plus
INNER LAYER (a) 50 GW Acoustigard 11kg Nil 46/35
PKAA031
Steel angle to Rondo DUO Two-way
support ceiling grid Steel Grid Ceiling
Floor or roof structure. 100mm System
System insulation min System insulation
200mm minimum cavity.
50mm Bradford Glasswool Acoustigard
11kg/m3 to extent specified in table.
Ceiling lining as per system table.
Wall with required sound rating. GYPROCK
Panel
Ceiling
System
EXTENT OF INSULATION
1200mm each side
SYSTEM N CEILING LININGS Nil Entire Ceiling
of the wall
Rw
(a) 10mm Gyprock plasterboard panel. 38 44 45
PKAA031
100mm
Floor or roof structure. System insulation min System insulation
PKAA031
600mm
PKAA031
600mm
Ceiling
framing
Floor or roof structure.
200mm minimum cavity.
600mm wide barrier of Bradford Glasswool
Acoustigard 11kg/m3, compressed 30%.
GYPROCK Tape and
Ceiling lining as per system table. plasterboard set or
Bradford
Glasswool
Acoustigard
11kg/m3
compressed 30%
PKAA031
50mm Bradford Glasswool
Acoustigard seal continuous 10mm GYPROCK
over wall, held in place with plasterboard min.
track or angle continuous over wall
and fixed to soffit
Floor or roof structure.
200mm minimum cavity.
10mm Gyprock Plus plasterboard barrier with
50mm Bradford Glasswool Acoustigard seal.
Ceiling lining as per system table. GYPROCK Panel Finish Bead as
Ceiling System in required
Wall with required sound rating, to underside Rondo DUO
of ceiling. Two-way Steel Fix track to ceiling
Grid frame with Rondo
Screw fix ceiling N704
tile to wall track
Continuous bead of
CSR Gyprock
Wall with required Sealant above wall
sound rating track
PKAA031
50mm Bradford Glasswool
Acoustigard seal continuous 10mm GYPROCK
over wall, held in place with plasterboard min.
track or angle continuous over wall
Floor or roof structure. and fixed to soffit
200mm minimum cavity. Ceiling frame
10mm Gyprock Plus plasterboard barrier min.
with 50mm Bradford Glasswool Acoustigard
seal.
Ceiling lining as per system table. GYPROCK
plasterboard Tape and set or
Wall with required sound rating, to underside ceiling system cornice finish
of ceiling. continuous
over wall
Fix wall track to
G
Wall with required ceiling framing
sound rating
PKAA031
Bradford Wavebar Quadzero
(4.0kg/m2) continuous over
wall and fixed to soffit 50mm Bradford
Acoustigard
Floor or roof structure. 300mm min. continuous over wall
PKAA031
50mm Bradford
Acoustigard
11kg/m3 1200mm
each side of wall
PKAA031
PKAA031
Sheet metal or
tiled roof
PKAA031
Roof structure.
500mm minimum average cavity height.
Bradford 75mm Gold Batts R1.5.
Ceiling lining as per system table fixed to framing.
CSR Party Wall system with required sound rating. Central
barrier extending to underside of roof battens.
Roof battens
Fill void between Roof sarking.
battens with Bradford For roofs without sarking,
Rockwool Fireseal, protect Rockwool with
Roof framing 300mm min. width Wall Clips at damp course under tiles
each H-Stud
both sides of wall
G No acoustically
untreated lights,
vents or similar
Tape and set or
cornice finish 200mm min.
No acoustically
untreated lights,
vents or similar
penetrations penetrations
Wall Clips at 4mm minimum gap
each H-Stud
both sides of wall
20-40mm gap
each side of wall
Tape and
Intersecting wall with set corners
required sound rating
GYPROCK
Steel Angle (75 x 75 x plasterboard as
0.7mm BMT) fixed to per system table
stud with panhead screw
at 600mm max. cts
CSR Gyprock
Staggered Studs
and Clips
10mm
Fix end stud to masonry nom. gap
at 500mm maximum from
vertical centres masonry
GYPROCK
plasterboard as to lining
per system table
GYPROCK
plasterboard as
per system table
system table.
Intersecting stud wall system, with required
sound rating.
Sealant
PKAA031
Wall system insulation
Dampcourse
Tape and
set corners
BARRIER
SYSTEM N WALL LININGS Nil 6mm Cemintel Wallboard
Rw / Rw+Ctr
(a) 1 x 10mm Gyprock Plus plasterboard. 38/29 58/49