Professional Documents
Culture Documents
Sprinklers
Sprinklers
Sprinklers
php
Sprinklers
What are the pressures and flows for the Model G Recessed Automatic Sprinkler?
Are there any height restrictions on the Reliable Model G VELO Pendent and the GXLO Upright Sprinkler?
Why do you not show the minimum spacing on all sprinklers in your bulletins?
What are the pressures and flows for your standard spray sprinklers?
Can your (SWC) concealed horizontal sidewall sprinkler be used in NFPA 13R systems?
Why does Reliable make both solder link and bulb sprinklers?
What is the maximum/minimum distance that the deflector will drop down below the ceiling surface when using the Model G4, G4FR, G4A or F4FR
concealed sprinklers with the 1/2" adjustable cover plate?
How do I determine the proper temperature rating for my sprinklers?
Is the installation of the retaining flange provided with the Model XL institutional sprinkler escutcheon kit a UL Listing requirement?
Are there listed/approved sprinkler guards for commercial extended coverage or residential sprinklers?
Are there listed/approved corrosion-resistant coatings for quick response or sprinklers containing fast-response thermal elements?
How do I determine which sprinkler temperature rating to when designing a sprinkler system?
Does Reliable make sprinklers that can be used with foam systems using foam liquid concentrates?
Valves
Why is the Model G Riser Check Valve for the LDX Dry Pipe Valve System gray?
What is the difference between the Model E3 variable pressure trim and constant pressure trim?
Does the DDX deluge valve require a check valve for preaction system applications?
What is the capacity needed for the open drain of my sprinkler riser?
Valve Accessories
How do I adjust the pressure switch on the Model B-1 Pressure Maintenance Device?
What is the difference between an accelerator used with a Model D dry valve and an accelerator used with the DDX-LP Low Pressure Dry System?
Why does Reliable use the Potter PFC 4410 Releasing Panel in the PrePak?
How do you properly size an air compressor for a dry pipe sprinkler system as well as for a double interlock preaction system?
What is the air pressure requirement for single interlock preaction systems?
Should the trim for a dry pipe system be black steel or galvanized?
What is the difference between the Model A-2 and Model B-1 Pressure Maintenance Devices?
What type of solenoid valve is used on Reliable electric actuated deluge and preaction systems?
What is the difference between single and double interlock preaction systems?
What is the difference between a Reliable Type D double interlock preaction system and a Type F double interlock
preaction system?
Sprinklers
What is the liquid in your glass bulb sprinklers?
The liquid used in our glass bulb sprinklers is a non-toxic proprietary glycerin solution that that expands when heated.
What are the pressures and flows for the Model G Recessed Automatic Sprinkler?
The Model G Recessed Automatic Sprinkler is a standard spray pendent sprinkler available with different orifices and
K Factors. The amount of water required is dependant on the spacing and density requirements in accordance with
NFPA 13. You must calculate the pressure required using the formula Q = K to calculate the flow or (P = 2
) to
determine the pressure. NFPA 13 requires a minimum pressure of 7 psi.
K = K Factor
What are the pressures and flows for your standard spray sprinklers?
Standard spray sprinklers both quick response and standard response are control sprinklers, and the minimum
pressure is 7 psi as per NFPA 13. Any pressure above that is calculated based on density (GPM per Sq. ft.) required
for your design. The amount of flow in GPM is based on the density curves in NFPA 13. The pressure to achieve that
flow is based on the sprinkler spacing and the K Factor of the sprinkler and the pressure available based on your
design and the available water supply. You must calculate the flow required using the formula Q= K√(P) and P = ( )2
to determine the pressure.
K = K Factor
With Extended Coverage, Residential and ESFR the pressures and flows are listed for each of the sprinklers based on
Why does Reliable make both solder link and bulb sprinklers?
Reliable has been a leader for years in solder link technology where solder link technology is appropriate. Reliable
uses bulbs where the need for aesthetics or other design considerations dictate their use.
What is the maximum/minimum distance that the deflector will drop down below the ceiling surface when
using the Model G4, G4FR, G4A or F4FR concealed sprinklers with the 1/2" adjustable cover plate?
Reliable concealed sprinklers are designed such that the deflector will always drop below the ceiling surface to
produce an unobstructed discharge pattern, as long as the cover plate and sprinkler cup assembly can be securely
attached. If these two assemblies cannot be attached securely, this would indicate that the branch line is too high, or
the drop nipple is too short. Installing the sprinkler in either case will result in the deflector not extending below the
ceiling surface. With no adjustment of the cover plate, the sprinkler deflector will drop approximately 5/8" below the
ceiling surface; at maximum adjustment, the sprinkler deflector will drop approximately 1/8" below the ceiling surface.
The maximum ambient ceiling temperature that the sprinkler will be exposed to on a daily basis determines the
appropriate sprinkler temperature rating, except where the NFPA standards may dictate the temperature rating for
design considerations. Even then, one must still consider the maximum ambient ceiling temperature anticipated on a
daily basis. Ambient temperatures in excess of these maximums would cause stress on the thermal element,
eventually weakening its load carrying capacity and possibly causing the sprinkler to operate prematurely. Refer to the
"Temperature Ratings, Classifications, and Color Codings" Table in NFPA 13.
Is the installation of the retaining flange provided with the Model XL institutional sprinkler escutcheon kit a UL
Listing requirement?
No, installation of the retaining flange is not a UL Listing requirement. The tamper resistant and self-injury prevention
features of institutional sprinklers are not part of the UL Listing. They are design features provided by the sprinkler
manufacturer. For maximum tamper resistance, it is the responsibility of the installing contractor to secure the nipple
on which the sprinkler is installed to prevent the sprinkler and escutcheon assembly from being pulled away from the
wall or ceiling. The retaining flange is provided as a way of securing the branch line piping, in the form of a nipple or
arm-over, to prevent pipe movement initiated by the room occupant. If the retaining flange cannot be used due to
larger piping or over-sized wall sleeves, alternative devices approved by the installing contractor or design engineer
may be used to secure the piping from movement.
Are there listed/approved sprinkler guards for commercial extended coverage or residential sprinklers?
No, there are no listed/approved sprinkler guards for extended coverage or residential sprinklers. Because of the
extended discharge requirements and low flow characteristics associated with these types of sprinklers, the sprinkler
guard would act as a significant obstruction to sprinkler performance, requiring greater flows and pressure to meet
listing/approval requirements.
Are there listed/approved corrosion-resistant coatings for quick response or sprinklers containing fast-
response thermal elements?
No, only standard response sprinklers can be listed/approved with corrosion resistant coatings. Such coatings would
adversely affect the sensitivity of a quick response or fast response thermal element, causing the sprinkler to meet
only standard response sensitivity criteria.
How do I determine which sprinkler temperature rating to when designing a sprinkler system?
Sprinkler temperature rating is based on the following:
Does the Specific Application Listing stated for the Reliable Model G XLO and G VELO storage sprinklers limit their
use only to the criteria specified in the application listing, or can they be also be used as area/density sprinklers used
The Reliable Model G XLO and G VELO sprinklers are cULus Listed and FM Approved as control-mode, area/density
spray sprinklers for NFPA 13, 231, 231C storage applications. These sprinklers can be used in one of two ways. First,
they can be used as area/density sprinklers in accordance with the storage design requirements of NFPA 231, 231C
and NFPA 13, or FM Global Data Sheets. This design criteria is based on the use of the appropriate area/density
curves in the respective standard as a function of the type of commodity, storage height and configuration, sprinkler
Second, these sprinklers can be used as specific application sprinklers, based on the cULus Specific Application
Listing criteria stated in the Reliable literature. This specific application listing is an ADDITIONAL LISTING that must
meet the specific application criteria.
Valves
Why is the Model G Riser Check Valve for the LDX Dry Pipe Valve System gray?
Because of approvals and clapper construction, the gray color code is used to differentiate the Model G Riser Check
Valve used for the LDX System from the black color of the Model G Riser Check Valve used for preaction systems.
What is the difference between the Model E3 variable pressure trim and constant pressure trim?
The only difference between these two trims is the addition of a Model E1 retard chamber.
Does the DDX deluge valve require a check valve for preaction system applications?
No, the DDX utilizes an intermediate chamber in its seat design, which separates the inside of the valve body with the
alarm outlet piping which is open to atmosphere. Therefore, supervisory air pressure can fill the valve body and the
system piping without separation by a riser check valve.
What is the capacity needed for the open drain of my sprinkler riser?
All sprinkler systems should be properly drained. The drain outlet or drain manifold outlet should be piped to an open
drain able to handle this capacity, as well as assist in providing proper drainage for a main drain test. To estimate the
total flow from the drain connection of various drain sizes, the following formula can be used:
Valve Accessories
How do I adjust the pressure switch on the Model B-1 Pressure Maintenance Device?
The pressure switch used on the Model B-1 pressure maintenance device is a Furnas Model 69H. Removing the
cover, one finds two adjustment screws: a large metallic screw for adjusting the cut-in pressure (the pressure at which
the compressor comes on as system pressure decreases); and a small metallic screw for adjusting the cut-out
pressure (the pressure at which the compressor shuts off on rising pressure. Turn the large screw clockwise to
increase both cut-in and cut-out pressure, and turn the small screw clockwise to increase the cut-out pressure without
affecting the cut-in pressure.
Procedure
Wire the compressor and B-1 pressure maintenance device pressure switch in accordance with the wiring diagram.
Start with no pressure and energize the circuit. The compressor should start immediately. Allow the compressor to run
until it shuts down, recording the pressure reading. This is the current cut-out pressure setting. Next, bleed the air
pressure out of the system, watching the air pressure gauge, until the compressor restarts and note the pressure
reading. This is the current cut-in pressure setting. If the cut-in point needs to be changed, adjust the large metal
screw after the compressor stops. Repeat the bleeding and adjusting until the cut-in pressure is correct. Each time the
compressor stops, note the cut-out pressure which will be changing each time you adjust the large metal screw.
After the cut-in pressure is set to the desired setting, adjust the small metal screw to raise or lower the cut-out
pressure from the last noted pressure reading and repeat the bleeding procedure. The cut-in pressure should remain
It is important that a minimum differential pressure of 7 psi or more is maintained between the cut-in and cut-out
pressure settings to avoid "chattering" of the pressure switch contacts. Differential pressure is defined as the difference
between the cut-in and cut-out pressure. Below 7 psi, chattering of the pressure switch contacts may occur as the
pressure approaches the cut-out pressure. This will cause the compressor to cycle on and off rapidly which may
damage the compressor motor.
What is the difference between an accelerator used with a Model D dry valve and an accelerator used with the
DDX-LP Low Pressure Dry System?
There is no difference in the accelerator model used with either the Model D dry valve or the DDX-LP. Both dry
systems use the Reliable Model B-1 accelerator when a quick opening device is needed. However, the trim associated
with the accelerator for each system is different, as well as where the air pressure is directed from the outlet of the
accelerator. When used with a Model D dry valve, air pressure flowing through the accelerator is directed into the
intermediate chamber of the dry valve. Pressurizing this chamber destroys the differential between the air side and the
water side of the clapper, causing the dry valve to trip faster. On a DDX-LP system, the accelerator is mounted on the
valve trim near the low-pressure actuator and the accelerator outlet piping is open to atmosphere. Since the DDX-LP
system utilizes a hydraulically operated valve, the actuator is the releasing device for this system. The faster the air
pressure is removed off the air side of the actuator, the faster the DDX-LP system valve trips. Therefore, when the
accelerator operates, it exhausts the air pressure off the air side of the actuator to atmosphere, causing the valve to
trip faster. Therefore, there is less trim associated with the accelerator trim kit for the DDX-LP than the accelerator trim
kit used for the Model D dry valve.
Why does Reliable use the Potter PFC 4410 Releasing Panel in the PrePak?
The Potter PFC 4410 allows our customers to change the Preaction system from Single Interlock to Double Interlock
by a simple programming change. No wiring or piping changes are required.
How do you properly size an air compressor for a dry pipe sprinkler system as well as for a double interlock
preaction system?
NFPA 13 states that a compressor must have a capacity capable of restoring the required system pressure within 30
minutes, except for refrigerated spaces maintained below -5 deg. F, in which case the time requirement becomes 60
minutes. To properly size the compressor to meet these requirements, one must calculate the volume or capacity of
the entire sprinkler piping system in cubic feet. Once this is known, the horsepower of the compressor may be chosen
based on the cubic feet per minute of compressed air it provides. To determine the volume limitations stipulated by
NFPA 13 for these systems, the total piping volume must be converted from cubic feet to gallons (1 ft3 = 7.48 gal.).
What is the air pressure requirement for single interlock preaction systems?
NFPA 13 requires that sprinkler piping and fire detection devices for preaction systems must be automatically
supervised where there are more than 20 sprinklers on the system. The air pressure is only provided to ensure the
overall integrity of the piping system. NFPA makes no stipulation for minimum air pressure requirements for single
interlock preaction systems for two reasons:
1. Since a single interlock preaction system is considered a "wet" system, there will be adequate water pressure at the
2. The loss of pressurized air does not take part in the operation of the deluge valve.
Therefore, low air pressures, as little as 2 psi, may be used for sprinkler piping supervision. This can be accomplished
through the use of the Reliable Model B Air Compressor Panel, or, where a source of pressurized air is provided, with
Should the trim for a dry pipe system be black steel or galvanized?
Reliable offers both black steel and galvanized trim styles for use with our dry pipe valve trims. However, the installing
contractor needs to be aware the galvanized trim is a requirement in those jurisdictions following The National Fire
Alarm Code NFPA 72 (1991 or 1993 editions, section 5-7.2, and NFPA 72, 1990 edition and earlier, section 3-4.1.2)
regarding water-flow alarm initiating devices (pressure switches). This section requires that "piping between the
sprinkler system and a pressure actuated alarm-initiating device shall be galvanized or of nonferrous metal or other
approved corrosion-resistant material of not less than 3/8" nominal pipe size." This is not a concern with our Model
LDX Dry Pipe Valve Systems since the LDX trim only comes in galvanized. However, if just a water motor gong is
used, black steel trim is permitted.
What is the difference between the Model A-2 and Model B-1 Pressure Maintenance Devices?
The Model B-1 Pressure Maintenance Device is used where a small tankless air compressor with no start/stop
pressure switch is provided. By wiring the compressor motor to the electrical pressure switch of the Reliable Model B-1
Pressure Maintenance Device, the compressor is controlled by the pressure in the dry pipe valve or deluge dry pilot
system. The adjustable pressure range for the Model B-1 is 14 to 60 psi. The Model A-2 Pressure Maintenance Device
is designed for use where a controlled source of compressed air or nitrogen is available, such as compressors and
tank-mounted compressors that have their own start/stop pressure switch. The Model A-2 will maintain a constant
pressure in the system regardless of pressure fluctuations in the compressed air or nitrogen source. The adjustable
pressure range for the Model A-2 is 5 to 50 psi.
What type of solenoid valve is used on Reliable electric actuated deluge and preaction systems?
Reliable uses a solenoid valve manufactured by Skinner, a division of Parker Hannifin Corp. It is a 24VDC normally
closed, pilot operated solenoid valve, which requires a .41 amp holding current and 10 watts power. The Skinner P/N
is 73218BN4UNLVN0C111C2.
What is the difference between single and double interlock preaction systems?
Definiton of "<strong>interlock</strong>" - to lock together; to connect so that the motion or operation of
any part is constrained by another.
Preaction systems are interlocked systems that require a supplemental detection system in the same area as the
sprinkler system. Operation of the deluge (preaction) valve is dependent upon activation of a detector, or both a
detector and a sprinkler.
Single interlock preaction systems require that only a detector operate to cause the deluge valve to trip. Once the
valve trips, water fills the system piping. Water will not be discharged until a sprinkler operates due to the heat of the
fire. Given that water is present at the sprinkler at the time of sprinkler operation, single interlock preaction systems are
treated as wet systems from a design standpoint.
Double interlock preaction systems require that both a detector AND a sprinkler operate before causing the valve to
trip. A good analogy is a door with two locks. You must open both locks before the door will open. Once the valve trips,
water will flow into the system piping and discharge immediately out of the open sprinkler(s). Given that the water is
back at the valve at the time the sprinkler operates, double interlock preaction systems are treated as dry-pipe
systems from a design standpoint, and all of the rules governing the design of dry-pipe systems must be applied to
double interlock preaction systems.
What is the difference between a Reliable Type D double interlock preaction system and a Type F double
interlock preaction system?
All double interlock preaction systems require two events to occur before the preaction (deluge) valve actuates: both a
detector and a sprinkler must operate before the deluge valve flows water into the sprinkler system piping. Operation
of the sprinkler causes the supervisory pneumatic pressure in the system piping to decrease. This decrease in
pressure is the second interlock, which causes the preaction valve to trip. The difference between these two types of
double interlock preaction systems is based on the method of detecting the decrease in pneumatic pressure. For the
Type D system, the device that senses this decrease is a pressure switch installed on the pneumatic supply trim
piping. When the pressure switch activates, it provides a second signal to a cross-zoned releasing panel, causing the
releasing circuit to energize the solenoid valve. For a Type F system, a low-pressure pneumatic actuator, which is a
mechanical device, opens, causing the push-rod chamber of the deluge valve to depressurize. At this point, the
solenoid valve has already opened (energized) due to the activation of the detection device. For the Type F system,
the releasing panel does not have to be configured for cross-zoned operation. Type F systems are recommended for
freezer protection.
Type D systems are commonly referred to as electric/electric-pneumatic type systems, while Type F systems are
referred to as electric/pneumatic type systems. To provide a low air supervisory signal, rather than an alarm signal,
upon loss of air only for Type D double interlock preaction systems, the Potter PFC 4410 RC releasing panel must be
used. For Type F systems, either the RP1001 panel or the Potter PFC 4410RC panel may be used. Utilizing a RP1001
panel with a Type D double interlock preaction system will cause an alarm condition upon loss of supervisory air only.
This is because the releasing panel is in cross-zoned mode and the pressure switch is tied into an initiating circuit,
which is an alarm circuit.