What Does LSIG Signify On Micrologic Trip Units?: Search
What Does LSIG Signify On Micrologic Trip Units?: Search
Environment:
Applies to circuit breakers with Micrologic Trip Units
Resolution:
The letters LSIG signify the type of protection and available adjustments on certain trip units.
L = Long Time (overload protection, analygous to the inverse-time thermal trip of a thermal/magnetic breaker)
S = Short Time (short circuit protection of low level faults)
I = Instantaneous (short current protection of high level faults, analygous to the instantaneous magnetic trip of a thermal/magnetic
breaker)
G = Ground Fault (equipment ground fault protection)
Therefore, LSIG = Long-time + Short-time + Instantaneous + Equipment Ground-fault Protection