The document outlines the specifications of a power plant including two gas engines that generate a total gross electrical output of 5,356 kWe, two multi-energy absorption chillers with a total cooling capacity of 1,330 RT, three electrical centrifugal chillers (one standby) with a total cooling capacity of 3,150 RT, and a thermal energy storage tank with a charging/discharging capacity of 3,347 RT and storage capacity of 31,200 RTH.
The document outlines the specifications of a power plant including two gas engines that generate a total gross electrical output of 5,356 kWe, two multi-energy absorption chillers with a total cooling capacity of 1,330 RT, three electrical centrifugal chillers (one standby) with a total cooling capacity of 3,150 RT, and a thermal energy storage tank with a charging/discharging capacity of 3,347 RT and storage capacity of 31,200 RTH.
The document outlines the specifications of a power plant including two gas engines that generate a total gross electrical output of 5,356 kWe, two multi-energy absorption chillers with a total cooling capacity of 1,330 RT, three electrical centrifugal chillers (one standby) with a total cooling capacity of 3,150 RT, and a thermal energy storage tank with a charging/discharging capacity of 3,347 RT and storage capacity of 31,200 RTH.
Gross Electrical Power Output per Gas Engine, Generator Terminal 2,678 kWe Plant Gross Electrical Power Output 5,356 kWe Plant Net Electrical Power Output 5,196 kWe
Multi-Energy Absorption Chiller
Quantity of Chiller 2 Cooling Capacity per Chiller 665 RT Total Chiller Cooling Capacity 1,330 RT Chilled Water Temperature 13.5 / 6.7 C Cooling Water Temperature 32.0 / 38.0 C
Electrical Centrifugal Chiller
Quantity of Chiller( 1 Standby) 3 Cooling Capacity per Chiller 1,050 RT Chilled Water Temperature 10.2 / 5.0 C Cooling Water Temperature 30.8 / 36.3 C
Thermal Energy Storage Tank
Quantity of Thermal Energy Storage Tank 1 Charging / Discharging Capacity 3,347 RT Storage Capacity 31,200 RTH 4 1,140 RT 13.5 / 5.0 C 30.8 / 36.3 C