Professional Documents
Culture Documents
19.station - Service Transformer
19.station - Service Transformer
8 Check that the off load tap-changer is set at the nominal voltage tap.
2. ELECTRICAL TESTS:
Make :
Type of cooling :
Number of Phases :
Rated Frequency :
Rated KVA :
Vector Group :
% Impedance :
DIAGRAM :
Year of Manufacture :
Primary Current :
Secondary Current :
Primary :
Secondary :
Serial No :
Total Weight :
Temp.Rise of OIL :
Temp Rise Wdg :
Maximum withstands operating pressure :
Maximum withstands capability :
TAP POSITION HV LV
1
VOLT 2
AGE 3
(volts) 4
5
1
2
10
Test Instrument :
Make / Model No. :
Vector Group of Transformer :
Transformer was excited from H.V. winding with a suitable Low three phase power supply and
Vector Group checked.
Test connections:
Test Results:
Field Measurements:
Result :
FUNCTIONAL TEST
OPERATION
DEVICE FUNCTION SETTING REMARKS
PICK UP DROP OUT
Alarm
OTI
5. Calibration test of Oil temperature gauge by oil bath method and its alarms.
TEMPERATURE SETTING
Increase
Temp:
Gauge C
Decrease
6. Check LV and HV side phases match with the LV bus bar phasing in the distribution panels and with the main
transformer phases.
7. Check phasing at the automatic transfer switch (as applicable)
NOTE: 2
Calculated 75 C Rc = (Rm-Rx) x (234.5+75)
(234.5+Ta)
Rx = Resistance value of the measurement cable. Ta = Oil Temperature ____ C
Excitation current was measured by applying three phase source to H.V. side, keeping L.V. side
Open.
Make :
Model No. :
Sl. No. :
Multimeter (Voltage Range)
Criteria : 10 % of factory test report
Test connection
Test Instrument
a. 3 Phase supply
Make :
Sr. No. :
Calibration Certificate :
Procedure:
Three phase 380 V source is applied for 15 minutes to the secondary of Transformer keeping primary
open ( 34.5kV ). The condition of Transformer is observed.
Result:
The transformer insulating oil was tested for Dielectric strength using oil tester (ASTM Std.)
Result
Dielectric Strength ( kV ) ELECTR
No. Test Points Average
Number of Tests -ODE
GAP
CO2
CO
H2
CH4
C2H4
Respon C2H6
C2H2
sibilities Total gas
Legend
CSD Note: The tests for characteristics of oil as above will be carried out in an independent laboratory and test results will
be submitted.
14. TEST EQUIPMENT USED:
Item Description Make Equipment Sl. No Calibration Date Calibration Due Date