Idec Door Interlock Catalog

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 58

Safety

Door Interlock
Switches

Overview
Selection Guide ........................................... 344

HS6B Series Subminiature Interlock


Switch ......................................................... 345

HS5B Series Miniature Interlock Switch .... 350

X Series E-Stops
HS2B Series Full Size Interlock Switch ...... 357

HS1B Series Full Size Interlock Switch ...... 361

HS6E Subminiature Interlock Switches with


NEW
Solenoid ...................................................... 365

HS5E Series Miniature Solenoid Locking

Door Interlock Switches


Switches...................................................... 376

HS1E Series Full Size Solenoid Locking


Switches...................................................... 384

HS1C Series Full Size Solenoid Locking


Switches...................................................... 392

Safety Precautions ...................................... 397


Operation Precautions ...................................399

Enabling Switches
Barriers

For more information on this product family, visit our website.


Additional resources include:
• New and updated product information • Downloadable manuals & CAD drawings
As-Interface Safety at Work

• Downloadable software demos & upgrades • Manufacturer’s suggested retail price list
• Part configuration tool & cross reference • Product training schedule & locations
• Online stock check & ordering • Advertising & trade show schedules
• IDEC field sales & distributor search • Press releases & FAQs
• Online literature request

www.idec.com/safety

Table of Contents Automation & Sensing - Pg. 1 Safety - Pg. 315 Switching & Controls - Pg. 439 Index - Pg. 911
Selection Guide Door Interlock Switches

Selection Guide
Door Interlock Switches
Series
Overview

HS6B HS5B HS2B HS1B HS6E HS5E HS1E HS1C


Model

NEW

Appearance
X Series E-Stops

Page 345 350 357 361 365 376 384 392


Size 104mm x 39.7mm 125 x 106 x
78 x 15 x 30mm 91 x 30 x 30mm 98 x 57 x 40mm 125 x 64 x 40mm 75 x 15 x 75mm 146 x 35 x 40mm
(mm) x 129mm 39.7mm
Plastic Housing Plastic Housing/
Body Die-cast alumi- Die-cast alumi-
Plastic Housing (metallic actuator Plastic Housing Plastic Housing Metallic Actuator Plastic Housing
Material num num
entry optional) Entry
Solenoid
No No No No Yes Yes Yes Yes
(Yes/No)
Door Interlock Switches

LED
No No Yes Yes Yes Yes Yes Yes
Indicator

Application Example

For information on the


Teaching Pendant visit
www.idec.com/oi/pendant
Enabling Switches
Barriers
AS-Interface Safety at Work

344 www.idec.com
Door Interlock Switches HS6B Series

HS6B Series Subminiature Interlock Switch


HS6B features:
• Only 78 x 30 x 15mm

Overview
• Allows highest level of safety by having 3 contacts: dual load contacts + monitoring
contact (ISO13849-1, EN954-1)
• Two actuator entrances provide flexibility for installation options
• Integral molded cable reduces wiring time
• IP67 (IEC60529) watertight sealing (contact is sealed, housing allows drainage)
• Direct Opening Action: Opening the door forces the contacts to disconnect even if the
contacts are welded (IEC/EN60947-5-1)
• Actuators comply with ISO14119 and EN1088

X Series E-Stops
GS-ET-15 Direct Opening Double
BG standard in Germany Action Insulation

Part Numbers
Part Number Part Number Key
Contact Configuration Cable Length
(Standard Stock in bold) HS6B - 12 B 01

Door Interlock Switches


1NC-1NO 1m HS6B-11B01
Zb
11 12 3m HS6B-11B03
33 34
5m HS6B-11B05 Cable Length
01: 1 meter
2NC 1m HS6B-02B01
Zb 03: 3 meters
11 12 3m HS6B-02B03 05: 5 meters
31 32
5m HS6B-02B05
2NC-1NO 1m HS6B-12B01 Head Color
Zb B (Black)
11 12 3m HS6B-12B03
21 22

Enabling Switches
31 32 5m HS6B-12B05 Contact Configuration
11: 1NO-1NC
3NC 1m HS6B-03B01 12: 1NO-2NC
Zb
11 12 3m HS6B-03B03 02: 2NC
21 22 03: 3NC
31 32 5m HS6B-03B05

Contact Configuration & Operation Chart


Type Contact Configuration Contact Operation Chart
0.8 (Actuator Mounting Reference Position)
0 5.5 5.8 28.2 (Travel: mm)
HS6B-11 1NC-1NO Zb

Barriers
11 12 11-12
33 34 33-34 : Contact ON (closed)

Zb : Contact OFF (open)


11 12 11-12
HS6B-02 2NC
31 32 31-32

Zb
11 12 11-12
HS6B-12 2NC-1NO 21 22 21-22
AS-Interface Safety at Work

33 34 33-34
Zb
11 12 11-12
HS6B-03 3NC 21 22 21-22
31 32 31-32
Actuator inserted completely Actuator removed completely

USA: 800-262-IDEC Canada: 888-317-IDEC 345


HS6B Series Door Interlock Switches

Actuator Keys
Appearance Part Number Shape Appearance Part Number Shape
Overview

Straight (Mainly for sliding adjustable actuator


HS9Z-A61 HS9Z-A65
doors) 90° angle

Right-angle (Mainly for adjustable actuator


HS9Z-A62 HS9Z-A66
hinged doors) 180° angle
X Series E-Stops

The actuators are not included, must be ordered separately.

Specifications
Conforming to Standards EN1088, IEC60947-5-1, EN60947-5-1, GS-ET-15, IEC60664-1, IEC60204-1, EN60204-1, UL508
Operating Temperature –25 to +70˚C (no freezing)
Storage Temperature –40 to +80˚C (no freezing)
Door Interlock Switches

Operating Humidity 45 to 85% RH (no condensation)


Storage Humidity 95% RH maximum (no condensation)
Altitude 2,000m maximum
Pollution Degree 3
Rated Insulation Voltage (Ui) 300V
Impulse Withstand Voltage (Uimp) 4kv
Between live & dead metal parts: 100MΩ maximum
Insulation Resistance
Between positive & negative live parts: 100MΩ minimum
Electric Shock Protection Class Class II
Enabling Switches

Degree of Protection IP67 (IEC60529)


Vibration Operating Extremes 5 to 55 Hz, half amplitude 0.5 mm
Resistance Damage Limits 30Hz, half amplitude 1.5mm
Contact Resistance 300mΩ maximum
Shock Operating Extremes 300m/s2 (30G)
Resistance Damage Limits 1000m/s2 (100G)
Direct Opening Travel 8 mm minimum
Direct Opening Force 60N minimum
Thermal Current (lth) 2.5A
Operating Voltage (Ue) 30V 125V 250V
Barriers

Resistive load (AC12) – 2.5A 1.5A


AC
Inductive load (AC15) – 1.5A 0.75A
Rated Operating Current (Ie) 2.5A 1.1A 0.55A
Resistive load (DC12)
(2A) (0.4)A (0.2A)
DC
2.3A 0.55A 0.27A
Inductive load (DC13)
(1A) (0.22A) (0.1A)
AS-Interface Safety at Work

Maximum Actuation Frequency 1200 operations/hour


Mechanical Life 1,000,000 operations (at full rated load)
Recommended Actuation Speed 0.05 to 1.0m/s
Wire Tensile Strength 50N minimum
Electrical Life 100,000 operations (at full rated load)
Conditional Short-Circuit Current 50A 250V (IEC60947-5-1, IEC60269-1, -2)
Weight 120g

346 www.idec.com
Door Interlock Switches HS6B Series

Installation Notes
Recommended Screw Torque Handling Cables
• Safety switch body installation (M4 screw): 1.0~1.5N-m • Do not tighten or loosen the fastened cable conduit of the safety switch

Overview
• Actuator installation (M4 screw): 1.0~1.5N-m • Minimum bend radius of installed cable: 40mm

Wiring Designations
Part Number Color Contact Part Number Color Contact
blue-blue/white NC HS6B-11B01 blue-blue/white NC
HS6B-12B01 (1NC-1NO)
brown-brown/white NC orange-orange/white NO
(2NC-1NO)
orange-orange/white NO blue-blue/white NC

X Series E-Stops
HS6B-02B01
blue-blue/white NC (2NC) orange-orange/white NC
HS6B-03B01
brown-brown/white NC
(3NC)
orange-orange/white NC

Dimensions (mm)
HS6B Installation
10.4
2

20 to 22
2.

(58)
1

Door Interlock Switches


2-M4 Screws
30
20
5.5

(ø4.3 or M4 tapped)
10.1

15 35
1

The interlock switch can be


78 (9) mounted in two directions.
Slot Plug (Note 1)
5.5
(supplied)
4

Note 1: Plug the unused actuator


entry slot using the slot plug
(ø7.6)
10.4

supplied with the interlock switch. 27.6


4

Using Angle Adjustable Actuator (HS9Z-


Using straight actuator (HS9Z-A61) Using Right-angle actuator (HS9Z-A62)

Enabling Switches
A65/A66) g j
(12.6±1) (25)
(21.4) 28.8 22.6±1
30.8 (5)
(14)

22.6±1 0.8
0.8
(14)
(5)

(25)

48.8
50.8

0.8
(41.4)
40.1±1
0.8
(30.1±1)

0.8

0.8
15.1±1

Actuator Stop Actuator Stop


(Note 2) (Note 2) (supplied) Actuator Stop
(supplied) (Note 2) (supplied)

Barriers
Straight actuator (HS9Z-A61) Right-angle actuator (HS9Z-A62) Actuator Installation
20.9 43.2 When mounted (33.8) 14
When Straight/Right-angle
(15.8) mounted (5.6) 0.8 Actuator
8.4
2-

2-M4 Screws
ø4

14 15 0.8
8.4
.3

(ø4.3 or M4 tapped)
14

Angle Adjustable Actuator


AS-Interface Safety at Work

When mounted (5)


2-ø9

14 25
mounted (5)

Rubber
Bushing 2-ø
4.3
10.4
When

2-M4 Screws
3.5
1.2

13.1 14

(ø4.3 or M4 tapped)
34
3.5

1.2

2-ø9 Actuator Stop (supplied)


(Note 2)
Rubber Bushing Actuator Stop (supplied)
(Note 2)

USA: 800-262-IDEC Canada: 888-317-IDEC 347


HS6B Series Door Interlock Switches

Adjustable Actuator (HS9Z-A65) Adjustable Actuator (HS9Z-A66)


Horizontal Adjustment The HS9Z-A65 and HS9Z-A66 have the
0.8 metal key inserted in opposite directions.
Orienting Insert

3.5
1.2
Horizontal Adjustment
Overview

Angle Adjustment
(M3 Hexagon Socket Head Screw)

20°

20°
Angle Adjustment Vertical Adjustment
(M3 Hexagon Socket Head Screw)
Angle Adjustment
Vertical Adjustment (M3 Hexagon Socket Head Screw)
13 28.2 Actuator Stop (supplied)
(Note 2)
7.5 2

5.5

20°
Orienting Insert

16.8
20°
X Series E-Stops

25
Orienting Insert
34

R2
15 2.5 Angle Adjustment (M
4 H .1
(M3 Hexagon ole
Socket Head Screw) s)

The orientation of actuator adjustment (horizontal/vertical) can be Horizontal Adjustment Vertical Adjustment
changed using the orienting insert (white plastic) installed on the
back of the actuator.
The base is made of glass-reinforced PA66 (66 nylon).
Angle adjustment screws are stainless steel. When using adhesive
on screws, take material compatibility into consideration.
Door Interlock Switches

Note 2: After mounting the actuator, remove the actuator


stop from the interlock switch.

Minimum Radius of Hinged Door

• When using the interlock switch for a hinged door, refer to the minimum When using the HS9Z-A65/HS9Z-A66 Angle Adjustable
radius of doors shown below. For doors with small minimum radius, use angle (vertical) Actuator
adjustable actuators (HS9Z-A65 or HS9Z-A66).
• When the door hinge is on the extension line of the interlock switch surface:
Note: Because deviation or dislocation of hinged door may occur in actual applications, make sure Horizontal Swing Vertical Swing
of the correct operation before installation.
50 mm 50 mm
dius Minimum Radius
Minimum Ra
Door Hinge Door Hinge
HS9Z-A62 Actuator
Label
Enabling Switches

Label
• When the door hinge is on the extension line of the interlock switch surface: HS9Z-A65 HS9Z-A65
HS9Z-A66
HS9Z-A66

Door Hinge Door Hinge


50 mm 50 mm
Minimum Radiu Minimum Radiu
s s
M 1 M 1
in in
im 60 m im 60 m
um m um m
Ra Door Hinge Ra Door Hinge • When the door hinge is on extension line of the actuator mounting surface:
di di Horizontal Swing Vertical Swing
us us
s us
mm diu Door Hinge mm adi Door Hinge
70 m Ra 70 um R
i n imu i n im
• When the door hinge is on the extension line of the actuator mounting M M

surface: Label
Barriers

Label
HS9Z-A65 HS9Z-A65
HS9Z-A66
HS9Z-A66

Min 70 Min 7
imu mm
Door Hinge imu 0 mm Door Hinge
mR mR
adi adi
us us
M 2 M 2
in
in
im 30 m im 30 m
um m Actuator Angle Adjustment for the HS9Z-A65/HS9Z-A66
AS-Interface Safety at Work

um m
Ra Ra
di Door Hinge di Door Hinge • Using the angle adjustment screw, the actuator angle can be adjusted (see
us us
figures on page 370).
• Adjustable angle: 0 to 20°
• The larger the adjusted angle of the actuator, the smaller the applicable
radius of the door opening.
• After installing the actuator, open the door. Then adjust the actuator so that
its edge can enter properly into the actuator entry slot of the interlock switch.
• After adjusting the actuator angle, apply Loctite to the adjustment screw so
that the screw will not become loose.

348 www.idec.com
Door Interlock Switches HS6B Series

Safety Precautions
• In order to avoid electric shock or fire, turn power off before installation, • Do not place a PLC in the circuit between the interlock switch and the load.
removal, wiring, maintenance, or inspection of the interlock switch. Safety security can be endangered in the event of a malfunction of the PLC.

Overview
• If relays are used in the circuit between the interlock switch and the load, use • Do not disassemble or modify the interlock switch, otherwise a malfunction or
only safety relays, since welded or sticking contacts of standard relays may an accident may occur.
invalidate the functions of the interlock switch. Perform a risk assessment and
make a safety circuit which satisfies the requirements of the safety category. • Do not install the actuator in the location where a human body may come into
contact. Otherwise injury may occur.

Instructions
• Regardless of door types, do not use the interlock switch as a door stop. • Entry of a considerable amount of foreign objects into the interlock switch
Install a mechanical door stop at the end of the door to protect the interlock may affect the mechanism of the interlock switch and cause a malfunction.

X Series E-Stops
switch against excessive force.
• Do not store the interlock switches in a dusty, humid, or organic-gas atmo-
• Do not apply excessive shock to the interlock switch when opening or closing sphere.
the door. A shock to the interlock switch exceeding 1,000 m/s2 may cause
damage to the interlock switch. • Use proprietary actuators only. When other actuators are used, the interlock
switch may be damaged.
• If the operating atmosphere is contaminated, use a protective cover to pre-
vent the entry of foreign objects into the interlock switch through the actuator • Cover the unused actuator entry slot using the slot plug supplied with the
entry slots. interlock switch.

Door Interlock Switches


Mounting Wire Identification
Colored Insulation
Insulation Insulation
Mount the interlock switch on the machine. Mount the No. No.
Color Color Jacket
actuator key on the hinged door.
Note: When mounting an actuator key, make sure that the actuator 1 Orange/White 4 Brown
enters into the slot in the correct direction, as shown on the right.
2 Blue/White 5 Blue
Dummy Insulation
3 Brown/White 6 Orange (black)
Recommended Screw Tightening Torque
• Wires can be identified by color and/or a white line printed on the wire.
• Interlock switch (M4 screw): 1.0 to 1.5 N·m

• Actuator key (M4 screw): 1.0 to 1.5 N·m Terminal Number Identification

Enabling Switches
• Mounting bolts are not supplied, and must be purchased separately by the • When wiring, the terminal number on each contact can be identified by wire
user. color.
Note: The above recommended tightening torque of the mounting screw is the value with hex socket
head bolts. When other screws are used and tightened to a smaller torque, make sure that the • The following diagrams show a safety (main) contact and one or two auxiliary
screws do not become loose after mounting.
contacts for two-contact and three-contact types.

Cable 1NC-1NO
Zb
2NC
Zb
Blue 11 12 Blue/White Blue 11 12 Blue/White
• Do not fasten or loosen the gland at the bottom of the Orange 33 34 Orange/White Orange 31 32 Orange/White
interlock switch. um
nim ius
Mi ad
(100)

2NC-1NO 3NC
R
• When bending cable during wiring, make sure that Gland mm Zb Zb
40 Blue 11

Barriers
12 Blue/White Blue 11 12 Blue/White
the cable radius is kept at 40 mm minimum. Brown 21 22 Brown/White Brown 21 22 Brown/White
Orange 33
• When wiring, make sure that water or oil does not enter 34 Orange/White Orange 31 32 Orange/White

from the end of cable.


• When wiring, cut any dummy insulation (black) and any unused wires at the
end of the jacket to avoid incorrect wiring.
AS-Interface Safety at Work

USA: 800-262-IDEC Canada: 888-317-IDEC 349


HS5B Series Door Interlock Switches

HS5B Series Miniature Interlock Switch


HS5B features:
• 30mm x 30mm x 91mm Compact Housing
Overview

• Available with 2 Contact Configurations (1NO + 1NC or 2NC)


• Flexible Installation: By turning the head of the switch to the desired angle, the actua-
tor can be accessed from 8 directions
• Plastic Housing: Light weight
• Direct Opening Action: Opening the door forces the contacts to disconnect even if the
contacts are welded (IEC60947-5-1)
• Degree of Protection: IP67 (IEC60529)
X Series E-Stops

GS-ET-15 Direct Opening Double


BG standard in Germany Action Installation

Part Numbers
Conduit Part Number Part Number Key
Contact Configuration Port (Standard Stock in bold) HS5B - 11 Z BM
Size
Door Interlock Switches

Plastic Head Type Metal Head Type


1NC-1NO G1/2 HS5B-11B HS5B-11ZB
Zb Head Housing Color/
3 4 PG13.5 HS5B-11NP —
Conduit Port
1 2 M20 HS5B-11BM HS5B-11ZBM B: Black / G1/2
G1/2 HS5B-02B HS5B-02ZB BM: Black /M20
2NC
Zb NP: Gray PG13.5
3 4 PG13.5 HS5B-02NP —
1 2 Head Material
M20 HS5B-02BM HS5B-02ZBM
blank: Plastic
The actuators are not included, must be ordered separately. Z: Metal

Circuit Code
Enabling Switches

11: 1NO-1NC
02: 2NC

Actuator Keys Parts Description


Part Number
Appearance Description Right-angle Actuator
(Package Qty 1)
M3.5 Terminal
Screws Angle Adjustable
Straight HS9Z-A51 Actuator
(for hinged doors)
Barriers

Straight w/rubber
HS9Z-A51A
bushings

Right-angle HS9Z-A52
AS-Interface Safety at Work

Right-angle w/rubber Straight Actuator Straight Actuator


HS9Z-A52A
bushings Conduit Port w/rubber bushing
Right-angle Actuator (Use conduits or cable glands
which can maintain IP67
Actuator w/rubber bushing protection.)

Angle Adjustable
HS9Z-A55
(for hinged doors)

350 www.idec.com
Door Interlock Switches HS5B Series

Accessories
Appearance Description Part Number Weight
HS5B/HS5E Plug Actuator

Overview
(allows switch to be used as HS9Z-A5P 35g
interlock plug unit)

HS5B/HS5E Padlock Hasp


(prevents unauthorized HS9Z-PH5 35g
insertion of actuator)

Contact Configuration & Operation Chart


Model Contact Configuration Contact Operation Chart Contact Status

X Series E-Stops
Actuator Actuator
1NC-1NO inser ted removed
Zb completely completely
HS5B-11 3 4
1 2 3–4 ON (closed)
1–2
OFF (open)
2NC
Zb 3–4
HS5B-02 3 4
1 2 1–2

Door Interlock Switches


Specifications
Conforming to Standards EN1088, IEC60947-5-1, EN60947-5-1, GS-ET-15, UL508
Operating Temperature –20 to +70˚C (no freezing)
Storage Temperature –40 to +80˚C
Operating Humidity 85% RH maximum (no condensation)
Altitude 2,000m maximum
Rated Insulation Voltage (Ui) 300V
Impulse Withstand Voltage (Uimp) 4 kV
Insulation Resistance 100MΩ minimum (500V DC megger)

Enabling Switches
Electric Shock Protection Class Class II (IEC61140)
Pollution Degree 3 (IEC60664-1)
Degree of Protection IP67 (IEC60529)
Vibration Operating Extremes 10 to 55 Hz, amplitude 0.5 mm
Resistance Damage Limits 60 m/sec2 (approx. 6G)
Shock Resistance 1,000 m/sec2 (approx. 100G)
Actuator Operating Speed 1 m/sec maximum
Positive Opening Travel 8 mm minimum
Positive Opening Force 60N minimum
Thermal Current (Ith) 10A

Barriers
Operating Voltage (Ue) 30V 125V 250V
Resistive load (AC12) 10A 10A 6A
AC
Rated Operating Current (Ie) Inductive load (AC15) 10A 5A 3A
Resistive load (DC12) 8A 2.2A 1.1A
DC
Inductive load (DC13) 4A 1.1A 0.6A
Operating Frequency 900 operations/hour
AS-Interface Safety at Work

Mechanical Life 1,000,000 operations


Electrical Life 100,000 operations (rated load)
Conditional Short-circuit Current 100A (IEC60947-5-1)
Recommended Short
250V, 10A fuse (Type D01 based on IEC60269-1, 60269-2)
Circuit Protection
Weight Approx. 80g

USA: 800-262-IDEC Canada: 888-317-IDEC 351


HS5B Series Door Interlock Switches

Application Examples and Circuit Diagrams


HS5B-11 (1NO-1NC) HS5B-02 (2NC)
Status 1 Status 2 Status 1 Status 2
Overview

Door/ Door/
• Door Closed • Door opened • Door Closed • Door opened
Switch Switch
• Machine ready to operate • Machine cannot be started • Machine ready to operate • Machine cannot be started
Status Status

Door Door
X Series E-Stops

Auxiliary Circuit

Auxiliary Circuit

Auxiliary Circuit

Auxiliary Circuit
1 1 1 1

2 2 2 2
Main Circuit

Main Circuit

Main Circuit

Main Circuit
Circuit 3 3 Circuit 3 3
Door Interlock Switches

Diagram Diagram
4 4 4 4

+ + + +

- - - -

Main Main
3-4: Closed 3-4: Open 3-4: Closed 3-4: Open
Circuit Circuit
Aux. Aux.
1-2: Open 1-2: Closed 1-2: Closed 1-2: Open
Circuit Circuit

1. Main Circuit: used to enable the machine to start only when the main circuit is closed.
Enabling Switches

2. Auxiliary Circuit: used to indicate whether the machine circuit or door is open or closed.

Dimensions (mm)
Plastic Head - using the straight actuator (HS9Z-A51)
Plastic Head (black or gray) Plastic Head (black or gray)

RP Conduit Port RP Conduit Port


26.4 42.2 36 26.4
.2

.2

6.2 5.2 5.2 6.2


R2

R2
1

1
Barriers

30

30
28
20

20
28
20

20
1

Actuator 36.2 36.2


Actuator
Actuator Stop 91 91
Actuator Stop
RP: Actuator Mounting Reference Position 6±1
20 to 22

2-M4 Screws
AS-Interface Safety at Work

6±1

30

30

Slot Plug (supplied)


24

24
15

15

(Note)
Mounting Hole Layout

Plug the unused actuator insertion slot using the slot plug supplied with the interlock switch.

352 www.idec.com
Door Interlock Switches HS5B Series

Dimensions (mm), continued


Plastic Head – using the Right-angle actuator (HS9Z-A52)
Plastic Head (black or gray) Plastic Head (black or gray)

Overview
RP Conduit Port RP Conduit Port
27.7 41.5 35.3 27.7

.2

.2
R2

R2
1

1
20
30

20
30

30

20

20
30
1

1
Actuator
36.2 36.2
Actuator Cover Actuator Cover
91 91
Actuator Actuator Stop

X Series E-Stops
Actuator Stop 7.6±1
20 to 22
7.6±1

2-M4 Screws

30
30
Slot Plug (supplied)

24
24
15

15
(Note)
Mounting Hole Layout

Note: Plug the unused actuator entry slot using the slot plug supplied with the interlock switch.

Metal Head - using the straight actuator (HS9Z-A51A)

Door Interlock Switches


Metal Head Plastic (gray) Metal Head Plastic (gray)

RP Conduit Port RP Conduit Port


26.4 42.2 36 26.4
.2

.2
6.2 5.2 5.2 6.2
R2

R2
1

1
30

30
28
20

20
28
20

20
1

1
Actuator 36.2 36.2
Actuator
Actuator Stop 91 91
Actuator Stop
RP: Actuator Mounting Reference Position 6±1

Enabling Switches
20 to 22
2-M4 Screws
6±1

30

30
Slot Plug (supplied)
24

24
15

15
(Note)
Mounting Hole Layout

Metal Head – using the Right-angle actuator (HS9Z-A52A)


Metal Head Plastic (gray) Metal Head Plastic (gray)

RP Conduit Port RP Conduit Port


27.7 41.5 35.3 27.7
.2

.2
R2

R2
1

Barriers
20
30

20
30

30

20

20
30
1

Actuator
36.2 36.2
Actuator Cover Actuator Cover
91 91
Actuator Actuator Stop
Actuator Stop 7.6±1
20 to 22
AS-Interface Safety at Work

2-M4 Screws
7.6±1

30
30

Slot Plug (supplied)


24
24
15

15

(Note)
Mounting Hole Layout

Note: Plug the unused actuator insertion slot using the slot plug supplied with the interlock switch.

USA: 800-262-IDEC Canada: 888-317-IDEC 353


HS5B Series Door Interlock Switches

Actuator Key Dimensions (mm)


Straight Actuator - HS9Z-A51 Right-angle Actuator - HS9Z-A52 Adjustable Actuator - HS9Z-A55
(mainly for sliding doors) (mainly for hinged doors)
Horizontal Swing Angle Adjustment
6.2 32.4 33 3 (M3 Hexagon Socket Head Screw)
Overview

(6) 2 7.2 7.2 Orienting


5.2 0.8 Insert Actuator Stop
(Note)

30
28

15

20

49

26
38
23
28
20

15
26

20°
.4
ø4
2
4.5 0.8 2- 1.6 (M4 R2.1
2. 6.4 15 7 1 Hole
R s)
4- Actuator Stop (Note) 18.5 29 3.6
Actuator Stop (Note)
Vertical Swing

2
2

Orienting Actuator Stop


10

Insert (Note)
X Series E-Stops

• Actuator Mounting Hole Layout


(Straight, Right-angle) 0.8

2-M4 Screw Angle Adjustment


20 (M3 Hexagon Socket Head Screw)

2
20°
Straight Actuator with rubber bushings Right-angle Actuator with rubber bushings
- HS9Z-A51A (mainly for sliding doors) - HS9Z-A52A (mainly for hinged doors) • Actuator Mounting Hole Layout
(horizontal/vertical swing)
Door Interlock Switches

7.3 43.8 (39.7)


2-ø
4.3 15.3 0.8 (11.2) 0.8 2-M4 Screw 38
(20)
(20)

Actuator Orientation (Angle Adjustable)


30

15

30

15

12
12

The angle of actuator swing can be changed using the orient-


Actuator Stop (Note)
Washer (supplied
ing insert (white plastic) installed on the back of the actuator.
.3

Do not lose the orienting insert, otherwise the actuator will


ø4

Rubber with the actuator)


2-

Cushion not operate properly.


Washer (supplied with the actuator)
(5) 0.8 The actuator stop is supplied with the actuator and used
0.8

2-ø10 when adjusting the actuator position. Remove the actua-


2

tor stop after the actuator position is determined.


15.8

2
8.5

2-ø9
Enabling Switches

2-ø9

2-ø10
(5)

Rubber Cushion
Actuator Stop (Note)

• The mounting center distance is set to 12 mm at factory. When 20-mm distance is required, adjust the
distance by moving the rubber bushings.
• The actuator has flexibility to the directions indicated by the arrows. When 20-mm distance is selected, the
actuator swings vertically.
Actuator Mounting Hole Layout
(straight with rubber bushing, right-angle with rubber bushing)
2-M4 Screw 12

Mounting centers can be widened to


20 mm by moving the rubber cushions.
Accessory Dimensions (mm)
Barriers

HS9Z-A5P HS9Z-PH5
2- 8
R4 ø8
Rivet: Stainless Steel Spacer: Steel 2-
46 43
Handle: Aluminum
28

Thickness: 2
36

22
40

7.5 16.5

Material: SPCC
Actuator: 24 Thickness: 1.6
ø4

Area Stainless Steel 15.5 27.5


Washer: Steel Thickness: 2.5
AS-Interface Safety at Work

61.5 Area
30.5 Coating: Orange
10.5
(36.2)

2
9
7.5
10

(36.2)
6.5

32
(91)

Rivet:
Stainless Steel 38.5
Material: SPCC
48
6

(91)

Thickness: 2.0
R4

15.5 65

HS5B Interlock Switch


HS5B Interlock (30) (30)
(30) Switch (30)

354 www.idec.com
Door Interlock Switches HS5B Series

Mounting Examples Applicable Crimping Terminal


Mount the interlock switch as shown in the examples below. When using crimping terminals, be sure to install insulation tubes on the crimp-
ing terminals to prevent electric shocks.
Mounting on Sliding Doors
3.6 min. 3.5 max.

Overview
Wire Approx. 4 Crimping Terminal
Door

HS9Z-A51
Actuator

6.9 max.
Insulation Tube
ø3.6 min.

HS5B
Interlock Switch
Applicable Wire Size
Door Stop • 0.5 to 1.25 mm2 (AWG20 to AWG16)
Mounting on Hinged Doors

X Series E-Stops
Recommended Tightening Torque of Mounting Screws
Latch
HS9Z-A52 • Interlock Switch: 2.0 ± 0.2 N·m (two M4 screws) *
Actuator
• Actuator Keys
-HS9Z-A51: 2.0 ± 0.2 N·m (two M4 screws) *
Hinged
Door -HS9Z-A52: 1.0 ± 0.2 N·m (two M4 Phillips screws)
-HS9Z-A51A/A52A: 1.0 to 1.5 N·m (two M4 screws) *
-HS9Z-A55: 1.0 to 1.5 N·m (two M4 screws) *
*The above recommended tightening torques of the mounting screws are the
HS9Z-A51 values confirmed with hex socket head bolts. When other screws are used and

Door Interlock Switches


Actuator tightened to a smaller torque, make sure that the screws do not come loose
HS5B after mounting.
Interlock Switch

• Mounting bolts must be provided by user.


Mounting the HS5B Head
The metal head for the HS5E interlock switch cannot be used on the HS5B. Be • To avoid unauthorized or unintended removal of the interlock switch and the
sure to use the plastic head or metal head for the HS5B. Take care particularly actuator, it is recommended that the interlock switch and the actuator be
when using both HS5B and HS5E together. installed in an unremovable manner, for example using special screws or
HS5B HS5E
welding the screws.
Plastic Head Metal Head Metal Head • When installing HS9Z-A51A or HS9Z-A52A actuator keys, use the washer
Plastic Metal
(black or gray) (supplied with the actuator) on the hinged door, and mount tightly using two
(gray) (black) M4 screws.

Enabling Switches
Mounting Centers
12 mm (factory setting), adjustable to 20 mm
M4 Screw
Rotating the Head Washer
The head of the HS5B can be rotated by removing the four screws from the Rubber Bushing
corners of the HS5B head and reinstalling the head in the desired orientation.
When reinstalling the head, make sure that no foreign object enters the interlock Hinged Door
switch. Tighten the screws. If the screws are loose it may cause the switch to M4 Tapped Hole
malfunction.
Note: Choose mounting centers either 12 mm or 20 mm.

Barriers
Recommended screw tightening torque: 1.0 ±0.1 N·m
Factory Setting Alternative Head Orientations
Conduit Port Size Identification
Conduit port size is identified by the arrow on the back of the HS5B interlock
switch. The following example shows the identification of the M20 conduit port
size.

M20
M4 x 2

AS-Interface Safety at Work


20
22
PG

Arrow
Marking Conduit Port Size

G G1/2

PG PG13.5

M20 M20

USA: 800-262-IDEC Canada: 888-317-IDEC 355


HS5B Series Door Interlock Switches

Actuator Angle Adjustment • After installing the actuator, open the door. Then adjust the actuator so that
• Using the screw (M3 hex socket head screw), the actuator angle can be its edge can be inserted properly into the entry slot of the safety switch.
adjusted (refer to the dimensional drawing). Adjustable angle: (0˚) to 20˚
• Recommended tightening torque: 0.8 N-m (approx. 8.0 kgf-cm)
Overview

• The larger the adjusted angle of the actuator, the smaller the applicable
radius of the door opening. • After adjusting the actuator angle, apply loctite or the like to the adjustment
screw to prevent it from loosening.

Minimum Radius of Hinged Door Horizontal Swing


• When using the interlock switch on hinged doors, refer to the minimum radius
of doors shown below. When using on doors with small minimum radius, use
the angle adjustable actuator (HS9Z-A55).
Note: Because deviation or dislocation of hinged doors may occur in actual applications, make sure
of the correct operation before installation.
X Series E-Stops

M
in 50
im m
um m
Ra Door Hinge M
When using the HS9Z-A52 Actuator d iu
in 70
im m
s um m
• When the door hinge is on the extension line of the interlock switch surface: Ra
di Door Hinge
us

Vertical Swing
Min
190 um R
im
Mi

mm adiu
nim
17 m R
0 m ad
u
Door Interlock Switches

Door Hinge Door Hinge


m ius

M
s

in
im 50 m
um m
Ra Door Hinge M 7
in
di
us im 0 m
• When door hinge is on the extension line of the actuator mounting surface: um m
Ra
di Door Hinge
us

Actuator Angle Adjustment for the HS9Z-A55


Min
Mi

260 m Ra
23 m R
nim

imu

• Using the angle adjustment screw, the actuator angle can be adjusted (see
0 m ad

mm dius
u

Door Hinge
Door Hinge
figures on page 354). Adjustable angle: 0 to 20°
ius

• The larger the adjusted angle of the actuator, the smaller the applicable
Enabling Switches

radius of the door opening.


When using the HS9Z-A55 Angle Adjustable Actuator • After installing the actuator, open the door. Then adjust the actuator so that
• When door hinge is on the extension line of the interlock switch surface: its edge can be inserted properly into the actuator entry slot of the interlock
50 mm switch.
• When door hinge is on the extension line of the actuator mounting surface: • After adjusting the actuator angle, apply Loctite to the adjustment screw so
70 mm that the screw will not loosen.

Applicable Cable Glands


Use a cable gland with a degree of protection IP67 When Using Multi-core Cables (Example)
Barriers

30 max.

G1/2, PG13.5, M20 Conduit Port Size Plastic Cable Gland Metal Cable Gland
G1/2 SCS-10* ALS-16**
(Seiwa Electric) (Nihon Flex)
9 max.
PG13.5 ST13.5 ABS-**PG13.5
all dimensions in mm (K-MECS) (Nihon Flex)
When Using Flexible Conduits (Example) M20 ST-M20X1.5 ALS-**EC20
Flexible conduit example: VF-03 (Nihon Flex)
AS-Interface Safety at Work

(K-MECS) (Nihon Flex)


Conduit Port Size Plastic Cable Gland Metal Cable Gland
• Different cable glands are used depending on the cable sheath outside diameter. When
G1/2 — RLC-103 (Nihon Flex)
purchasing a cable gland, confirm that the cable gland is applicable to the cable sheath
PG13.5 — RBC-103PG13.5 (Nihon Flex) outside diameter.
• When using a 1/2-14NPT cable gland, use the HS5B interlock switch with M20 conduit
M20 — RLC-103EC20 (Nihon Flex)
port (Part No.: HS5B-***BM) together with an adapter (Part No.: MA-M/NPT 20X1.5
5402-0110, K-MECS) and a gasket (Part No.: GP M20, K-MECS). Install a gasket between
the interlock switch and the adapter. Apply sealing tape between the cable gland and
the adapter to make sure of IP67 protection for the enclosure.

356 www.idec.com
Door Interlock Switches HS2B Series

HS2B Series Full Size Interlock Switch


HS2B features:
• Direct Opening Action: If the door is forced open, the contacts are disconnected even if

Overview
they are welded or stuck
• Available with or without an indicator (red or green)
• Flexible Installation: Two actuator entries and three conduit ports are provided
• 1NC-1NO contacts
• Compact and lightweight plastic housing
• Degree of Contact Protection: IP67
EN1088 GS-ET-15
EN60947-5-1 BG standard in Germany
IEC60947-5-1

X Series E-Stops
Direct Opening Action Double Insulation

Part Numbers

Body Part Number Key


Contact
Model Pilot Light Part Number HS2B - 11 4 N B - R

Door Interlock Switches


Configuration

Without HS2B-11NB

HS2B With red LED HS2B-114NB-R Indicator Color


1NC-1NO
(plastic housing) R (Red),
G (Green)
With green LED HS2B-114NB-G

Indicator Rated Voltage


Order the actuators separately (not supplied with the switch). 4 (24V DC)
Blank (without indicator)

Enabling Switches
Not necessary to specify color if indicator option
Actuator Keys & Accessories not chosen.

Appearance Part Number Description

Straight Actuator
HS9Z-A1
(Mainly for sliding doors)

Right-angle Actuator
HS9Z-A2
(Mainly for rotating doors)

Barriers
HS9Z-A3 Adjustable Actuator

HS9Z-P1 Conduit Opening Plug


AS-Interface Safety at Work

USA: 800-262-IDEC Canada: 888-317-IDEC 357


HS2B Series Door Interlock Switches

Specifications
Conforming to Standards IEC60947-5-1, EN60947-5-1, GS-ET-15, UL508
Operating Temperature –25 to +70˚C (no freezing)
Overview

Storage Temperature –40 to +80˚C


Operating Humidity 85% RH maximum (no condensation)
Altitude 2,000m maximum
Rated Insulation Voltage (Ui) 300V (between LED and ground: 60V)
Impulse Withstand Voltage (Uimp) 4 kV (between LED and ground: 2.5 kV)
Between live and dead metal parts: 100 MΩ minimum
Between live metal part and ground: 100 MΩ minimum
Insulation Resistance
Between live metal parts: 100 MΩ minimum
Between terminals of the same pole: 100 MΩ minimum
X Series E-Stops

Electric Shock Protection Class Class II (IEC61140)


Pollution Degree 3 (IEC60947-5-1)
Degree of Protection IP67 (IEC60529)
Vibration Operating Extremes 10 to 55 Hz, amplitude 0.5mm
Resistance Damage Limits 60 m/sec2 (approx. 6G)
Shock Resistance 1,000 m/sec2 (approx. 100G)
Actuator Operating Speed 1 m/sec maximum
Door Interlock Switches

Positive Opening Travel 11 mm minimum


Positive Opening Force 36N minimum
Thermal Current (Ith) 10A
Operating Voltage (Ue) 30V 125V 250V
Resistive load (AC12) 10A 10A 6A
AC
Rated Operating Current (Ie) Inductive load (AC15) 10A 5A 3A
Resistive load (DC12) 8A 2.2A 1.1A
DC
Inductive load (DC13) 4A 1.1A 0.6A
Operating Frequency 900 operations/hour
Mechanical Life 1,000,000 operations
Enabling Switches

Electrical Life 100,000 operations (rated load)


Conditional Short-circuit Current 100A (IEC60947-5-1)
Recommended Short Circuit Protection 250V, 10A fuse (Type D01 based on IEC60269-1, 60269-2)
Operating Voltage 24V DC
Current 10 mA
Indicator
Light Source LED lamp
Lens Color Red or Green (12 mm dia. Lens)
Weight Approx. 130g
Barriers
AS-Interface Safety at Work

358 www.idec.com
Door Interlock Switches HS2B Series

Application Examples and Circuit Diagrams


HS2B
Status 1 Status 2

Overview
Door/
• Door Closed • Door opened
Switch
• Machine ready to operate • Machine cannot be started
Status

Door

X Series E-Stops
Auxiliary Circuit

Auxiliary Circuit
1 1

2 2
HS2B-11
(1NO-1NC)
Main Circuit

Main Circuit
3 3

Door Interlock Switches


Circuit 4 4
Diagram
+ +

- -

Main
3-4: Closed 3-4: Open
Circuit
Aux.
1-2: Open 1-2: Closed
Circuit

1. Main Circuit: used to enable the machine to start only when the main circuit is closed.

Enabling Switches
Auxiliary Circuit: used to indicate whether the main circuit or door is open or closed.
2. Terminals + and - are used for the LED indicator, and are isolated from door status.

Dimensions (mm)
HS2B - using the straight actuator (HS9Z-A1)
(Horizontal Mounting) (Vertical Mounting)
RP Conduit RP Conduit
30 56.7 36.5 54.3 30
Port G1/2 Port G1/2
9 13.8 13.8 9
.4

.4
ø5

ø5

Barriers
40
43
43
40

42
52
57

42

52
57
22
22

Actuator Actuator
Actuator Cover 37.4 Actuator Cover 37.4 36.5
96 96
98 98

8.5 ±1.0
AS-Interface Safety at Work
±1.0

2-M5 Screws
10
6.5

42
10

Slot Plug
40

40
35

35

(Note)
15
15

Interlock Switch
Mounting Hole Layout

USA: 800-262-IDEC Canada: 888-317-IDEC 359


HS2B Series Door Interlock Switches

Dimensions (mm), continued


HS2B - using the Right-angle actuator (HS9Z-A2)
(Horizontal Mounting) (Vertical Mounting)
Overview

RP Conduit Conduit
30 48.9 36.5 98
Port G1/2 RP Port G1/2
6 46.5 30 96
6 37.4 36.5

.4
ø5
43
40

42
52
57

42
22

52
57
22

40
43
Actuator Actuator

ø5
.4
Actuator Cover 37.4 Actuator Cover
X Series E-Stops

96
98
19.5 ±1.0
±1.0

11
17.5
11
10

2-M5 Screws

10
42
Slot Plug

40

40
35

35
(Note)
15

15
Interlock Switch
Mounting Hole Layout
Door Interlock Switches

Plug the unused actuator insertion slot using the slot plug supplied with the interlock switch.

Actuator Dimensions

Straight Actuator HS9Z-A1 Right-angle Actuator HS9Z-A2 Angle-adjustable Actuator HS9Z-A3


9 49.3 20 41.5 (Note) 18
19.3 11 11.5
2-M6 R3 Actuator Stop
.2 1 7.4 1
Screws 2-M6 Screws Film (attached)
Enabling Switches

29.2
22

40
22

43

29.2
22

40

43
22

29.2

58
44
58
72
Actuator 7.4 Actuator Cover .2
Mounting (red)
Actuator R3
Holes Mounting Actuator Cover
(red)
Holes
.2 2-M6 Screws
R3
4.1

5 2
2

20 Door hinge Actuator


2
Angle Adjustment Screw Mounting Holes
(M3 hexagon socket head screw)
4.1
90
°

30
(21)
33 max.

1
Barriers

20°
12

Adjustable Actuator
The actuator angle is adjustable (0˚ to 20˚) for hinged doors. • After installing the actuator, open the door. Then adjust the actuator so that
its edge can be inserted properly into the entry slot of the safety switch.
The minimum radius of the door opening can be as small as 100mm.
• Recommended tightening torque: 0.8 N-m (approx. 8.0 kgf-cm)
AS-Interface Safety at Work

Actuator Angle Adjustment • After adjusting the actuator angle, apply loctite or the like to the adjustment
• Using the screw (M3 hex socket head screw), the actuator angle can be screw to prevent it from loosening.
adjusted (refer to the dimensional drawing). Adjustable angle: (0˚) to 20˚

• The larger the adjusted angle of the actuator, the smaller the applicable
radius of the door opening.

360 www.idec.com
Door Interlock Switches HS1B Series

HS1B Series Full Size Interlock Switch


HS1B features:
• Rugged aluminum die-cast housing

Overview
• Direct Opening Action: If the door is forced open, the contacts are disconnected even if
they are welded or stuck
• Available with or without an indicator (red or green)
• Flexible Installation: Two actuator entries and three conduit ports are provided
• Select from two circuit configurations (1NO-1NC or 2NC).
• Degree of Contact Protection: IP67
EN1088 GS-ET-15
EN60947-5-1 BG standard in Germany
IEC60947-5-1

X Series E-Stops
Direct Opening Action

Part Numbers

Body Part Number Key


Contact

Door Interlock Switches


Model
Configuration
Pilot Light Part Number HS1B - 02 4 R - R
HS1B Without HS1B-11R
(alum. die-cast housing)
1NC-1NO With red LED HS1B-114R-R
Indicator Color
With green LED HS1B-114R-G R (Red),
G (Green)
Without HS1B-02R

2NC With red LED HS1B-024R-R Housing Color


R (Red)
With green LED HS1B-024R-G

Enabling Switches
1. The special key wrench (HS9Z-T1) for removing the cover and manual unlocking is
included with the switch. Indicator Rated Voltage
2. Order the actuators separately (not supplied with the switch). 4 (24V DC)
Blank (without indicator)

Circuit Configuration
Actuator Keys and Accessories 11: 1NO-1NC
02: 2NC
Appearance Part Number Description

Straight Actuator Not necessary to specify color if indicator option


HS9Z-A1 not chosen.
(Mainly for sliding doors)

Barriers
Right-angle Actuator
HS9Z-A2
(Mainly for rotating doors)

HS9Z-A3 Adjustable Actuator


AS-Interface Safety at Work

HS9Z-T1 Key Wrench (included with switch)

HS9Z-P1 Conduit Opening Plug

*Torx is a registered trademark of Camcar Textron.

USA: 800-262-IDEC Canada: 888-317-IDEC 361


HS1B Series Door Interlock Switches

Specifications
Conforming to Standards IEC60947-5-1, EN60947-5-1, GS-ET-15, UL508
Operating Temperature –25 to +70˚C (no freezing)
Overview

Storage Temperature –40 to +80˚C


Operating Humidity 85% RH maximum (no condensation)
Altitude 2,000m maximum
Rated Insulation Voltage (Ui) 300V (between LED and ground: 60V)
Impulse Withstand Voltage (Uimp) 4 kV (between LED and ground: 2.5 kV)
Between live and dead metal parts: 100 MΩ minimum
Between live metal part and ground: 100 MΩ minimum
Insulation Resistance
Between live metal parts: 100 MΩ minimum
Between terminals of the same pole: 100 MΩ minimum
X Series E-Stops

Electric Shock Protection Class Class I (IEC61140)


Pollution Degree 3 (IEC60947-5-1)
Degree of Protection IP67 (IEC60529)
Vibration Operating Extremes 10 to 55 Hz, amplitude 0.5mm p-p
Resistance Damage Limits 60 m/sec2 (approx. 6G)
Shock Resistance 1,000 m/sec2 (approx. 100G)
Actuator Operating Speed 1 m/sec maximum
Door Interlock Switches

Positive Opening Travel 11 mm minimum


Positive Opening Force 20N minimum
Thermal Current (Ith) 10A
Operating Voltage (Ue) 30V 125V 250V
Resistive load (AC12) 10A 10A 6A
AC
Rated Operating Current (Ie) Inductive load (AC15) 10A 5A 3A
Resistive load (DC12) 8A 2.2A 1.1A
DC
Inductive load (DC13) 4A 1.1A 0.6A
Operating Frequency 900 operations/hour
Mechanical Life 1,000,000 operations
Enabling Switches

Electrical Life 100,000 operations (rated load)


Conditional Short-circuit Current 100A (IEC60947-5-1)
Recommended Short Circuit Protection 250V, 10A fuse (Type D01 based on IEC60269-1, 60269-2)
Operating Voltage 24V DC
Current 10 mA
Indicator
Light Source LED lamp
Lens Color Red or Green (12 mm dia. Lens)
Weight Approx. 280g
Barriers
AS-Interface Safety at Work

362 www.idec.com
Door Interlock Switches HS1B Series

Application Examples and Circuit Diagrams


HS1B
Status 1 Status 2

Overview
Door/
• Door Closed • Door opened
Switch
• Machine ready to operate • Machine cannot be started
Status

Door

X Series E-Stops
Auxiliary Circuit

Auxiliary Circuit
1 1

2 2
HS1B-11
(1NO-1NC)
Main Circuit

Main Circuit
3 3

Door Interlock Switches


Circuit 4 4
Diagram
+ +

- -

Main
3-4: Closed 3-4: Open
Circuit
Aux.
1-2: Open 1-2: Closed
Circuit
Auxiliary Circuit

Auxiliary Circuit
1 1

Enabling Switches
2 2
HS1B-02
(2NC)
Main Circuit

Main Circuit

3 3

Circuit 4 4
Diagram
+ +

- -

Main
3-4: Closed 3-4: Open
Circuit

Barriers
Aux.
1-2: Closed 1-2: Open
Circuit

1. Main Circuit: used to enable the machine to start only when the main circuit is closed.
Auxiliary Circuit: used to indicate whether the main circuit or door is open or closed.
2. Terminals + and - are used for the LED indicator, and are isolated from door status.
Wire the terminals only when needed.
AS-Interface Safety at Work

USA: 800-262-IDEC Canada: 888-317-IDEC 363


HS1B Series Door Interlock Switches

Dimensions (mm)
HS1B - using the straight actuator (HS9Z-A1) HS1B - using the Right-angle actuator (HS9Z-A2)
(Horizontal Mounting) (Horizontal Mounting) RP
RP 30 61 36.5
30 68.8 36.5
6 2 10 Conduit Port
9 13.8
Overview

Conduit Port G1/2


2 10
.4

R2
G1/2
ø5

.7
.4

R
ø5

2.
7

43
40

42
52
64
22
43
40

42
52
64
22

Actuator
49.5
Actuator Actuator Cover
125
49.5
Actuator Cover
125

±1.0
±1.0

17.5
11
6.5
4.5

40
X Series E-Stops

35

40
35
Slot Plug
(Note) Slot Plug
(Note)

4
4

4.5
15

15
(Vertical Mounting)
125 (Vertical Mounting)
RP 125
54.3 30 49.5 36.5
Conduit Port RP
13.8 9 2 10 46.5 30 49.5 36.5
G1/2 6 2 10 Conduit Port
R2 .4
.7 ø5 G1/2
.4

R2
ø5

.7
42

52
64
22
40
43

42
22

52
64
40
43
Door Interlock Switches

Actuator
Actuator Cover 8.5 ±1.0 Actuator
Actuator Cover 19.5 ±1.0
11

2-M5 Screws
4.5

40

2-M5 Screws
42

35

4.5

40
42

35
4
15

15
4
Plug the unused actuator insertion slot using the slot plug supplied with the interlock switch.
Enabling Switches

Actuator Dimensions
Straight Actuator HS9Z-A1 Right-angle Actuator HS9Z-A2 Angle-adjustable Actuator HS9Z-A3
9 49.3 20 41.5 (Note) 18
19.3 11 11.5
2-M6 R3 Actuator Stop
.2 1 7.4 1
Screws 2-M6 Screws Film (attached)
29.2
22

40
22

43

29.2
22

40

43
22

29.2

58
44
58
Actuator 72
7.4 Actuator Cover .2
Mounting (red)
Actuator R3
Holes Mounting Actuator Cover
(red)
Holes
.2 2-M6 Screws
R3
4.1

5 2
2

20 Door hinge
Barriers

2 Actuator
Angle Adjustment Screw Mounting Holes
(M3 hexagon socket head screw)
4.1
90
°

30
(21)
33 max.

20°
12

Adjustable Actuator • The larger the adjusted angle of the actuator, the smaller the applicable
AS-Interface Safety at Work

radius of the door opening.


The actuator angle is adjustable (0˚ to 20˚) for hinged doors.
• After installing the actuator, open the door. Then adjust the actuator so that
The minimum radius of the door opening can be as small as 100mm. its edge can be inserted properly into the entry slot of the safety switch.

Actuator Angle Adjustment • Recommended tightening torque: 0.8 N-m (approx. 8.0 kgf-cm)

• Using the screw (M3 hex socket head screw), the actuator angle can be • After adjusting the actuator angle, apply loctite or the like to the adjustment
adjusted (refer to the dimensional drawing). Adjustable angle: (0˚) to 20˚ screw to prevent it from loosening.

364 www.idec.com
Door Interlock Switches HS6E Series

HS6E Subminiature Interlock Switches with Solenoid


HS6E features:
• Compact body: 75 × 15 × 75 mm

Overview
15-mm-wide, thinnest solenoid type interlock switch in the world.
• Reversible mounting and angled cable allow four actuator insertion directions.
• Energy saving. 24V DC, 110 mA (solenoid: 100 mA, LED: 10 mA)
• Manual unlocking possible on three sides.
• RoHS compliant
• LED indicator shows solenoid operation

Spring Lock Type


• Automatically locks the actuator without power applied to the solenoid

X Series E-Stops
• After the machine stops, unlocking is completed by the solenoid
• Manual unlocking is possible on three sides in the event of power failure
or maintenance

Solenoid Lock Type


• The actuator is locked when energized.
• The actuator is unlocked when de-energized.
• Flexible locking function can be achieved, for an application where locking is not

Door Interlock Switches


required and sudden stopping of a machine must be prevented

Direct Opening Double


Action Installation

Part Numbers
Part Number Part Number Key
Lock Circuit Cable
Contact Configuration (Standard Stock
Mechanism Number Length
in bold) HS6E - L 4 4 B 01 - G

Enabling Switches
(Actuator inserted) (Solenoid OFF)
(+) (–)
A2 A1
Indicator
Color
Main Circuit: 1NC + 1NC, Monitor Circuit: 2NC/1NO G (Green)
1m HS6E-L44B01-G
L 3m HS6E-L44B03-G Cable Length
Main Circuit: 11 12 41 42
5m HS6E-L44B05-G 01: 1m
Monitor Circuit: 21 22 53 54
31 32
03: 3m
Monitor Circuit:
05: 5m
Main Circuit: 1NC + 1NC, Monitor Circuit: 2NC/1NC
1m HS6E-M44B01-G Housing Color
M Main Circuit: 11 12 41 42 3m HS6E-M44B03-G B (Black)

Barriers
Monitor Circuit: 21 22 53 52
5m HS6E-M44B05-G
Monitor Circuit: 31 32
Indicator Rated Voltage
Spring Lock Main Circuit: 1NC + 1NC, Monitor Circuit: 1NC, 4 (24V DC)
1NO/1NO Blank (without indicator)
1m HS6E-N44B01-G
N 11 12 41 42 3m HS6E-N44B03-G Solenoid Unit Voltage/
Main Circuit:
Monitor Circuit: 21 22 53 54 5m HS6E-N44B05-G Lock Mechanism
Monitor Circuit: 33 34 4: Spring Lock
AS-Interface Safety at Work

7Y: Solenoid Lock


Main Circuit: 1NC + 1NC, Monitor Circuit: 1NC, Circuit Code
Main Circuit Door Monitor Circuit Lock Monitor Circuit
1NO/1NC L: 1NC + 1NC 2NC 1NO
1m HS6E-P44B01-G
M: 1NC + 1NC 2NC 1NC
P Main Circuit: 11 12 41 42 3m HS6E-P44B03-G
N: 1NC + 1NC 1NC, 1NO 1NO
Monitor Circuit: 21 22 51 52 5m HS6E-P44B05-G P: 1NC + 1NC 1NC, 1NO 1NC
Monitor Circuit: 33 34

The contact configurations show the contact status when the actuator is inserted and locked.
LED color is G (green) only.
Actuator keys are not supplied with the interlock switch and must be ordered separately.

USA: 800-262-IDEC Canada: 888-317-IDEC 365


HS6E Series Door Interlock Switches

Lock Circuit Cable Part Number


Contact Configuration
Mechanism Number Length (Standard Stock in bold)
(Actuator inserted) (Solenoid ON)
Overview

(+) (–)
A2 A1

Main Circuit: 1NC + 1NC, Monitor Circuit: 2NC/1NO


1m HS6E-L7Y4B01-G
L Main Circuit: 11 12 41 42 3m HS6E-L7Y4B03-G
Monitor Circuit: 21 22 53 54 5m HS6E-L7Y4B05-G
Monitor Circuit: 31 32

Main Circuit: 1NC + 1NC, Monitor Circuit: 2NC/1NC


X Series E-Stops

1m HS6E-M7Y4B01-G
M Main Circuit: 11 12 41 42 3m HS6E-M7Y4B03-G
Monitor Circuit: 21 22 51 52
5m HS6E-M7Y4B05-G
Monitor Circuit: 31 32
Solenoid Lock
Main Circuit: 1NC + 1NC, Monitor Circuit: 1NC, 1NO/1NO
1m HS6E-N7Y4B01-G
N Main Circuit: 11 12 41 42 3m HS6E-N7Y4B03-G
Monitor Circuit: 21 22 53 54
5m HS6E-N7Y4B05-G
Monitor Circuit: 33 34
Door Interlock Switches

Main Circuit: 1NC + 1NC, Monitor Circuit: 1NC, 1N0/1NC


1m HS6E-P7Y4B01-G
P Main Circuit: 11 12 41 42 3m HS6E-P7Y4B03-G
Monitor Circuit: 21 22 51 52
5m HS6E-P7Y4B05-G
Monitor Circuit: 33 34

The contact configurations show the contact status when the actuator is inserted and locked.
LED color is G (green) only.
Actuator keys are not supplied with the interlock switch and must be ordered separately.

Actuator Keys
Appearance Item Ordering Part Number Remarks
Enabling Switches

Straight Actuator The retention force of HS9Z-A61 actuator is 500N maximum.


HS9Z-A61
Do not apply excessive load.

The retention force of HS9Z-A62 actuator is 100N maximum.


Right-angle Actuator
HS9Z-A62 Do not apply excessive load.
When retention force of 100N or more is required, use the HS9Z-A62S actuator.

Right-angle Actuator
with The retention force of HS9Z-A62S actuator is 500N maximum.
HS9Z-A62S
Mounting Plate Do not apply excessive load.
Barriers

Horizontal/Vertical
Angle Adjustable
HS9Z-A65
Actuator
The HS9Z-A65 and HS9Z-A66 have their metal actuator installed in opposite directions.
Select actuator by determining the required moving direction in consideration of the door
and interlock switch.
See pages 370 and 373 for more information.
Horizontal/Vertical
The retention force of HS9Z-A65 and HS9Z-A66 500N maximum.
AS-Interface Safety at Work

Angle Adjustable
HS9Z-A66
Actuator

Accessory
Description Part Number
Manual Unlock Key (long type) HS9Z-T3

366 www.idec.com
Door Interlock Switches HS6E Series

Specifications
UL 508 (UL listed), CSA C22.2, No. 14 (c-UL listed), ISO 14119
IEC 60947-5-1, EN 60947-5-1 (TÜV approval), EN 1088 (TÜV approval),
Conforming to Standards
GS-ET-19

Overview
IEC 60204-1/EN 60204-1 (applicable standards for use)
Operating Temperature –25 to +50°C (no freezing)
Storage Temperature –40 to +80°C (no freezing)
Operating Humidity 45 to 85% (no condensation)
Rated Insulation Voltage (Ui) 300V (between LED and ground: 60V)
Main & lock monitor circuits: 1.5 KV
Impulse Withstand Voltage (Uimp) Door monitor circuit: 2.5 kV
Between solenoid/LED and ground: 0.5 kV

X Series E-Stops
Insulation Resistance Between live and dead metal parts: 100 MΩ minimum
(500V DC megger) Between terminals of different poles: 100 MΩ minimum.
300 mΩ maximum (initial value, 1m cable)
Contact Resistance 500 mΩ maximum (initial value, 3m cable)
700 mΩ maximum (initial value, 5m cable)
Electric Shock Protection Class Class II (IEC 61140)
Pollution Degree 3
Degree of Protection IP67 (IEC 60529)
Vibration Operating Extremes 10 to 55 Hz, amplitude 0.35mm

Door Interlock Switches


Resistance Damage Limits 30 Hz, amplitude 1.5 mm
Shock Operating Extremes 100 m/s2 (10G)
Resistance Damage Limits 1000 m/s2 (100G)
Actuator Operating Speed 0.05 to 1.0 m/s
Direct Opening Travel 8.0 mm minimum
Direct Opening Force 60N minimum
Actuator Retention Force 500N maximum (GS-ET-19)
Operating Frequency 900 operations/hour
Mechanical Life 1,000,000 operations minimum (GS-ET-19)

Enabling Switches
100,000 operations minimum (rated load)
Electrical Life 1,000,000 operations minimum (24V AC/DC, 100 mA)
(operating frequency 900 operations/hr)
Conditional Short-circuit Current 50A (250V) (Use 250V/10A fast-blow fuse for short-circuit protection.)
Cable UL2464, No. 22 AWG (12-core: 0.3 mm2 or equivalent/core)
Cable Diameter ø7.6 mm
Weight Approx. 200g

Barriers
AS-Interface Safety at Work

USA: 800-262-IDEC Canada: 888-317-IDEC 367


HS6E Series Door Interlock Switches

Solenoid/Indicator
Locking Mechanism Spring Lock Type or Solenoid Lock Type
Rated Voltage 24V DC
Overview

Current 110 mA (solenoid 100 mA, LED 10 mA)


Coil Resistance 240Ω (at 20°C)
Pickup Voltage Rated voltage × 85% maximum (at 20°C)
Dropout Voltage Rated voltage × 10% minimum (at 20°C)
Solenoid
Maximum Continuous Applicable Voltage Rated voltage × 110%
Maximum Continuous Applicable Time Continuous
Insulation Class Class F
Light Source LED
X Series E-Stops

Indicator
Illumination Color Green

Contact Ratings
300V (door monitor contact)
Rated Insulation Voltage (Ui) 150V (lock monitor contact)
30V (between LED or solenoid and ground)
Operating temperature 2.5A (up to 2 circuits)
(–25 to 35ºC) 1.0A (3 or more circuits)
Door Interlock Switches

Rated Thermal
Current (Ith) Operating temperature 1.0A (1 circuit)
(35 to 50ºC) 0.5A (2 or more circuits)
Operating Voltage (Ue) 30V 125V 250V
Resistive load (AC12) 2A
AC – –
Main and Lock Inductive load (AC15) 1A
Monitor Circuits Resistive load (DC12) 2A 0.4A
Rated Operating DC –
Inductive load (DC13) 1A 0.22A
Current (Ie)
Resistive load (AC12) 2.5A 1.5A
AC –
Inductive load (AC15) 1.5A 0.75A
Door Monitor Circuit
Resistive load (DC12) 2.5A 1.1A 0.55A
Enabling Switches

DC
Inductive load (DC13) 2.3A 0.55A 0.27A

Minimum applicable load (reference value): 3V AC/DC, 5 mA


UL, c-UL rating
Main/Lock monitor circuit:125V AC, 1A Pilot duty
125V DC, 0.22A Pilot duty
Door monitor circuit:240V AC, 0.75A Pilot duty
250V DC, 0.27A Pilot duty
TÜV rating
Main/Lock monitor circuit: AC-15 125V/1A, DC-13 125V/0.22A
Door monitor circuit: AC-15 240V/0.75A, DC-13 250V/0.27A
Barriers
AS-Interface Safety at Work

368 www.idec.com
Door Interlock Switches HS6E Series

Dimensions
Interlock Switch Mounting Hole Layout
5.5 Hole for Manual Unlocking 3-M4 Screw

Overview
ø12 (reference) (ø4.3 or M4 tapped hole)
10.1

10.4
4

15

30

20.5
4

37 15

46.1
41.8
ø4
.4 28.5 (22.5) (22.5)

X Series E-Stops
28.5
35
30

41.8
20.5

20 to 22
Manual Unlocking Key
75

R2

4 3-M4 Screw Hole for Manual Unlocking


.1

4 (ø4.3 or M4 tapped hole) ø12 (reference)


)
.3
(2

12
C

Door Interlock Switches


1 20 1

30
20.5
28.5

41.8
20 to 22

When using straight actuator When using right-angle actuator When using horizontal/vertical

Enabling Switches
(HS9Z-A61) (HS9Z-A62) angle adjustable actuator
(12.6±1)
22.6 ±1 (14) (HS9Z-A65/A66)
(6.2)

(5)
(25)
(14)

22.6 ±1
(42) (Note)
0.8

48.8
0.8
50.8
0.8

Actuator Stop
(supplied)

Actuator Stop Actuator Stop


(supplied) (supplied)

Barriers
Actuator Mounting Reference Position
As shown in the figure on the right, the mounting reference position of the actuator key when inserted Interlock Switch Door Stop
in the interlock switch is:
The actuator stop on the actuator lightly touches the interlock switch.
AS-Interface Safety at Work

Actuator Stop
0.8

After mounting the actuator, remove the actuator stop from the
actuator.

Door Stop

HS9Z-A61 Actuator

USA: 800-262-IDEC Canada: 888-317-IDEC 369


HS6E Series Door Interlock Switches

Actuator Key Dimensions (mm)


Straight Actuator (HS9Z-A61) Straight Actuator (HS9Z-A61) Right-angle Right-angle Actuator
Actuator (HS9Z-A62) with Mounting Plate (HS9Z-A62S)
Overview

20.9 43.2
(15.8) The retention force of the HS9Z-A62 actuator is 100N. Note: See page 373 for actuator installation.
When tensile force exceeding 100N is expected, use
2-

14 15 0.8
ø4

8.4
.3

When mounted (33.8)


the HS9Z-A62S actuator.
When mounted (6.2)
14

0.8

8.4
When mounted (33.8)
mounted (5)

When
mounted (5.6) 0.8

8.4
When

10.4

3.5
1.2

When mounted (10.2)


When mounted (6.2) 14

2-ø9
Note 1
X Series E-Stops

When mounted (5) Mounting Plate (supplied)

ø2-9
2-ø9 Actuator Stop (supplied) 14
2-ø
Rubber Bushing 2-ø4 4.2

41.1
14
Rubber Bushing .3

14
1.2

13.1
3.5
34
Rubber Bushing

3.5
1.2

13.1
(Note) Actuator Stop (supplied)
(Note) Actuator Stop (supplied)

The actuator stop is used to adjust the actuator position. Remove after the actuator position is mounted.
Door Interlock Switches

Angle Adjustable Actuator Angle Adjustable Actuator Actuator Adjustment


(HS9Z-A65) (HS9Z-A66) Orientation
Horizontal Adjustment The HS9Z-A65 and HS9Z-A66 have the The orientation of actuator adjustment (horizon-
Orienting Insert 0.8 metal actuator inserted in opposite direc- tal/vertical) can be changed using the orienting
tions. insert (white plastic) installed on the back of the
3.5

1.2

actuator.
Horizontal Adjustment
Angle Adjustment Orienting Insert
(M3 Hexagon Socket Head Screw)
20°

20°
Enabling Switches

Angle Adjustment
(M3 Hexagon Socket Head Screw)
Horizontal Adjustment Vertical Adjustment
Vertical Adjustment 13 28.2
Vertical Adjustment
7.5 2 Angle Adjustment
Orienting Insert (M3 Hexagon Socket Head Screw)
16.8
5.5

(Note 1)
20°

Actuator Stop (Supplied)


25
34

(Note)
20°

Actuator Stop (supplied)


Angle Adjustment (M R2.1
15 2.5 4H
(M3 Hexagon Socket ole
Head Screw) s)

Angle Adjustable Actuator Manual Unlock Key (plastic) Manual Unlock Key, HS9Z-T3 (metal)
(HS9Z-A65) (supplied with switch, not replaceable)
Barriers

25
3

ø4

2-M4 Screw
ø10

(ø4.3 or M4 tapping screw)


15 9
(24)

15

4
130
18 6.5
Accessory (24.5)

Description Part Number


AS-Interface Safety at Work

Manual Unlock Key (long type) HS9Z-T3

370 www.idec.com
Door Interlock Switches HS6E Series

Circuit Diagrams and Operating Characteristics


Spring Lock Type
Unlocking Using
Status 1 Status 2 Status 3 Status 4
Manual Unlock Key

Overview
• Door closed • Door opened • Door open • Door open • Door closed
• Machine ready to • Machine cannot be • Machine cannot be • Machine cannot be • Machine cannot be
Interlock Switch Status
operate operated operated operated operated
• Solenoid de-energized • Solenoid energized • Solenoid energized • Solenoid de-energized • Solenoid de-energized

Door Status UNLOCK

LOCK
Manually
Unlocked

X Series E-Stops
(+) (–) (+) (–) (+) (–) (+) (–)
A2 A1 A2 A1 A2 A1 A2 A1

Circuit Diagram (Example: HS6E-N4) 11 12 41 42 11 12 41 42 11 12 41 42 11 12 41 42


21 22 53 54 21 22 53 54 21 22 53 54 21 22 53 54
33 34 33 34 33 34 33 34

Door Closed (locked) Closed (unlocked) Open Open Closed (unlocked)


Main Circuit 11-42 ON (closed) OFF (open) OFF (open) OFF (open) OFF (open)
Door Lock

Door Interlock Switches


HS6E-L4 Monitor Monitor Door Monitor Circuit
(door closed) 21-22 ON (closed) ON (closed) OFF (open) OFF (open) ON (closed)
(+) (–)
A2 A1
Door Monitor Circuit
Main Circuit: 11 12 41 42 (door closed) 31-32 ON (closed) ON (closed) OFF (open) OFF (open) ON (closed)
Monitor Circuit: 21 22 53 54
Lock Monitor Circuit
Monitor Circuit: 31 32
(unlocked) 53-54 OFF (open) ON (closed) ON (closed) ON (closed) ON (closed)

HS6E-M4
Main Circuit 11-42 ON (closed) OFF (open) OFF (open) OFF (open) OFF (open)
Part Number and Circuit Diagram

Door Monitor Circuit


(door closed) 21-22 ON (closed) ON (closed) OFF (open) OFF (open) ON (closed)
Main Circuit: 11 12 41 42
21 22 51 52 Door Monitor Circuit
Monitor Circuit:
31 32 (door closed) 31-32 ON (closed) ON (closed) OFF (open) OFF (open) ON (closed)
Monitor Circuit:

Lock Monitor Circuit


(locked) 51-52 ON (closed) OFF (open) OFF (open) OFF (open) OFF (open)

Enabling Switches
HS6E-N4
Main Circuit 11-42 ON (closed) OFF (open) OFF (open) OFF (open) OFF (open)
Door Monitor Circuit
(door closed) 21-22 ON (closed) ON (closed) OFF (open) OFF (open) ON (closed)
Main Circuit: 11 12 41 42
Monitor Circuit: 21 22 53 54 Door Monitor Circuit
Monitor Circuit: 33 34 (door open) 33-34 OFF (open) OFF (open) ON (closed) ON (closed) OFF (open)
Lock Monitor Circuit
(unlocked) 53-54 OFF (open) ON (closed) ON (closed) ON (closed) ON (closed)

HS6E-P4
Main Circuit 11-42 ON (closed) OFF (open) OFF (open) OFF (open) OFF (open)
Door Monitor Circuit
(door closed) 21-22 ON (closed) ON (closed) OFF (open) OFF (open) ON (closed)
Main Circuit: 11 12 41 42
21 22 51 52 Door Monitor Circuit
Monitor Circuit:
Monitor Circuit: 33 34 (door open) 33-34 OFF (open) OFF (open) ON (closed) ON (closed) OFF (open)
Lock Monitor Circuit
ON (closed) OFF (open) OFF (open) OFF (open) OFF (open)

Barriers
(locked) 51-52

Solenoid Power A1-A2 (all types) OFF (de-energized) ON (energized) ON (energized) OFF (de-energized) OFF (de-energized)

Main circuit: Connected to the machine drive control circuit, sending the interlock signals of the protective door.
Monitor circuit: Sends the monitoring signals of open/closed and lock/unlocked statuses of the protective door.

Operation Characteristics (reference)


AS-Interface Safety at Work

0 (Actuator Insertion Position)


1.1 (Locked Position)
4.7 5.0 27.4 (stroke in mm)
Main Circuit
Door Monitor Circuit (door open, NO) : Contacts ON (closed)
Door Monitor Circuit (door closed, NC)
Lock Monitor Circuit (unlocked, NO) : Contacts OFF (open)
Lock Monitor Circuit (locked, NC)

The characteristics shown in the chart above are of the HS9Z-A61, -A62, -A65, and -A66 actuators. For the HS9Z-A62S actuator, subtract 0.6 mm.
The characteristics show the contact status when the actuator enters an entry slot of an interlock switch.

USA: 800-262-IDEC Canada: 888-317-IDEC 371


HS6E Series Door Interlock Switches

Solenoid Lock Type


Unlocking Using
Status 1 Status 2 Status 3 Status 4
Manual Unlock Key
• Door closed • Door closed • Door open • Door open • Door open
Overview

• Machine ready to • Machine cannot be • Machine cannot be • Machine cannot be • Machine cannot be
Interlock Switch Status
operate operated operated operated operated
• Solenoid energized • Solenoid de-energized • Solenoid de-energized • Solenoid de-energized • Solenoid de-energized

Door Status UNLOCK

LOCK
Manually
Unlocked
X Series E-Stops

(+) (–) (+) (–) (+) (–) (+) (–)


A2 A1 A2 A1 A2 A1 A2 A1

Circuit Diagram (Example: HS6E-N7Y) 11 12 41 42 11 12 41 42 11 12 41 42 11 12 41 42


21 22 53 54 21 22 53 54 21 22 53 54 21 22 53 54
33 34 33 34 33 34 33 34

Door Closed (locked) Closed (unlocked) Open Open Closed (unlocked)


Main Circuit 11-42 ON (closed) OFF (open) OFF (open) OFF (open) OFF (open)
Door Lock
HS6E-L7Y Monitor Monitor Door Monitor Circuit
(door closed) 21-22 ON (closed) ON (closed) OFF (open) OFF (open) ON (closed)
(+) (–)
Door Interlock Switches

A2 A1 Door Monitor Circuit


11 12 41 42 (door closed) 31-32 ON (closed) ON (closed) OFF (open) OFF (open) ON (closed)
Main Circuit:
Monitor Circuit: 21 22 53 54 Lock Monitor Circuit
Monitor Circuit: 31 32 (unlocked) 53-54 OFF (open) ON (closed) ON (closed) ON (closed) ON (closed)

HS6E-M7Y
Main Circuit 11-42 ON (closed) OFF (open) OFF (open) OFF (open) OFF (open)
Part Number and Circuit Diagram

Door Monitor Circuit


(door closed) 21-22 ON (closed) ON (closed) OFF (open) OFF (open) ON (closed)
Main Circuit: 11 12 41 42
Door Monitor Circuit
Monitor Circuit: 21 22 51 52
(door closed) 31-32 ON (closed) ON (closed) OFF (open) OFF (open) ON (closed)
Monitor Circuit: 31 32
Lock Monitor Circuit
(locked) 51-52 ON (closed) OFF (open) OFF (open) OFF (open) OFF (open)

HS6E-N7Y
Main Circuit 11-42 ON (closed) OFF (open) OFF (open) OFF (open) OFF (open)
Enabling Switches

Door Monitor Circuit


(door closed) 21-22 ON (closed) ON (closed) OFF (open) OFF (open) ON (closed)
Main Circuit: 11 12 41 42
Door Monitor Circuit
Monitor Circuit: 21 22 53 54
(door open) 33-34 OFF (open) OFF (open) ON (closed) ON (closed) OFF (open)
Monitor Circuit: 33 34
Lock Monitor Circuit
(unlocked) 53-54 OFF (open) ON (closed) ON (closed) ON (closed) ON (closed)

HS6E-P7Y
Main Circuit 11-42 ON (closed) OFF (open) OFF (open) OFF (open) OFF (open)
Door Monitor Circuit
(door closed) 21-22 ON (closed) ON (closed) OFF (open) OFF (open) ON (closed)
Main Circuit: 11 12 41 42
Door Monitor Circuit
Monitor Circuit: 21 22 51 52
(door open) 33-34 OFF (open) OFF (open) ON (closed) ON (closed) OFF (open)
Monitor Circuit: 33 34
Lock Monitor Circuit
(locked) 51-52 ON (closed) OFF (open) OFF (open) OFF (open) OFF (open)
OFF (de-energized)
Barriers

ON (energized)
Solenoid Power A1-A2 (all types) ON (energized) OFF (de-energized) OFF (de-energized) to ON (re-energized)
(Note 2)
(Note 1) (Note 2)

Main circuit: Connected to the machine drive control circuit, sending the interlock signals of the protective door. Note 1: Do not attempt manual unlocking while the solenoid is energized.
Monitor circuit: Sends the monitoring signals of open/closed and lock/unlocked statuses of the protective door. Note 2: Do not energize the solenoid for a long period of time while the door is open
or while the door is unlocked manually using the manual unlock key.

Operation Characteristics (reference)


AS-Interface Safety at Work

0 (Actuator Insertion Position)


1.1 (Locked Position)
4.7 5.0 27.4 (stroke in mm)
Main Circuit
Door Monitor Circuit (door open, NO) : Contacts ON (closed)
Door Monitor Circuit (door closed, NC)
Lock Monitor Circuit (unlocked, NO) : Contacts OFF (open)
Lock Monitor Circuit (locked, NC)

The characteristics shown in the chart above are of the HS9Z-A61, -A62, -A65, and -A66 actuators. For the HS9Z-A62S actuator, subtract 0.6 mm.
The characteristics show the contact status when the actuator enters an entry slot of an interlock switch.

372 www.idec.com
Door Interlock Switches HS6E Series

Operating Instructions

Minimum Radius of Hinged Door Actuator Angle Adjustment for the HS9Z-A65/HS9Z-A66

Overview
• When using the interlock switch on hinged doors, refer to the minimum radius • Using the angle adjustment screw, the actuator angle can be adjusted (see
of doors shown below. When using on doors with small minimum radius, use figures on page 370).
the angle adjustable actuator (HS9Z-A65 and HS9Z-A66). Adjustable angle: 0 to 20°
Note: Because deviation or dislocation of hinged doors may occur in actual applications, make sure • The larger the adjusted angle of the actuator, the smaller the applicable
of the correct operation before installation.
radius of the door opening.

When Using the HS9Z-A62/A62S Right-angle Actuator • After installing the actuator, open the door. Then adjust the actuator so that
its edge can enter properly into the actuator entry slot of the interlock switch.
• When door hinge is on the extension line of the interlock switch surface:
• After adjusting the actuator angle, apply Loctite to the adjustment screw so

X Series E-Stops
that the screw will not become loose.

Mounting Examples
M Application on Sliding Doors Application on Hinged Doors
ini
m M
16 um in
im
0 Ra u
m Door Hinge
m diu 16 m R
s 0 a HS9Z-A62S Actuator
m diu Door Hinge Door
m s

HS9Z-A61 Actuator

Door Interlock Switches


• When door hinge is on the extension line of the actuator mounting surface:
HS6E
Interlock Switch
Latch
Door Stop

Note: When mounting the actuator, make sure that the actuator enters
M M the slot in the correct direction, as shown on the right.
ini ini
m m
um u
23 Ra 23 m R
0
0
m dius m adiu
m Door Hinge m s Door Hinge

Enabling Switches
When using the HS9Z-A65/HS9Z-A66 Angle Adjustable Actuator
• When door hinge is on the extension line of the interlock switch surface
Horizontal Adjustment Vertical Adjustment
Minimum Minimum
Radius Radius
Door Hinge Door Hinge
50 mm 50 mm

HS9Z-A65 Label
HS9Z-A65

HS9Z-A66
HS9Z-A66

Door Hinge
50 mm 50 mm

Barriers
Door Hinge
Minimum Minimum
Radius Radius

• When door hinge is on the extension line of the actuator mounting surface
Horizontal Adjustment Vertical Adjustment
s s
diu Door Hinge diu Door Hinge
Ra Ra
imum mm imum mm
n 70 n 0
Mi Mi 7
AS-Interface Safety at Work

HS9Z-A65 Label
HS9Z-A65

HS9Z-A66
HS9Z-A66

M M
Rainimu Rainimu
d m d m
70 ius Door Hinge 70m ius Door Hinge
mm m

USA: 800-262-IDEC Canada: 888-317-IDEC 373


HS6E Series Door Interlock Switches

For Manual Unlocking Recommended Tightening Torque of Mounting Screws


Spring lock type • Interlock switch: 1.0 to 1.5 N·m (three M4 screws)

The HS6E allows manual unlocking of the actuator to pre-check proper door • Actuators: 1.0 to 1.5 N·m (two M4 screws)
Overview

operation before wiring or turning power on, as well as for emergency use such
as a power failure. • The above recommended tightening torques of the mounting screws are the
values with hex socket head bolts. When other screws are used and tightened
Solenoid lock type to a smaller torque, make sure that the screws do not become loose after
mounting.
The HS6E can be unlocked manually in an emergency.
• Mounting bolts are not supplied with the interlock and must be supplied by
When using the manual unlock key the user.
Manual Unlocking
(installed on both sides)
• To avoid unauthorized or unintended removal of the interlock switch and the
actuator, it is recommended that the interlock switch and the actuator are
X Series E-Stops

UNLOCK

installed in an unremovable manner, for example using special screws, rivets,


LOCK

or welding the screws.

• When installing the HS9Z-A62S actuator, use the mounting plate (supplied
with the actuator) on the hinged door, and secure the actuator tightly using
Normal Position Manual Unlocking
Position two M4 screws.

• The mounting plate has an orientation.


• When locking or unlocking the interlock switch manually, turn the actuator • Do not lose the mounting plate.
Door Interlock Switches

fully using the manual unlock key supplied with the switch.
M4 Screws
• Using the interlock switch with the actuator not fully turned (less than 90°)
may cause damage to the interlock switch or operation failures (when manu- Mounting Plate (supplied)
ally unlocked, the switch will keep the main circuit disconnected and the door
unlocked).
Rubber Bushing
• Do not apply excessive force (0.45 N·m or more) to the manual unlock part,
otherwise the manual unlock part will become damaged.
Hinged Door
• Do not leave the manual unlock key attached to the switch during operation.
This is dangerous because the switch can always be unlocked while the M4 Tapped Hole
machine is in operation.
Enabling Switches

Cables
Manual Unlock Key • Do not fasten or loosen the gland at the bottom of the interlock switch.
(supplied with the interlock switch)
• When bending the cable during wiring, make sure that the cable radius is kept
at 30 mm minimum.
When unlocking pushing the plate inside the interlock switch
• When wiring, make sure that water or oil does not enter from the end of the
• Remove the screw at the side of the interlock switch (the same side where
cable.
actuator is inserted) and insert a small screwdriver.
• Do not open the lid of the interlock switch. Otherwise the interlock switch will
• Push the plate inside the interlock switch toward the LED indicator using a
be damaged.
screwdriver until the actuator is unlocked.
• The solenoid has polarity. Make sure of the correct polarity when wiring.
Barriers

• Tighten the screw to a proper torque (0.3 to 0.5 N·m). Do not tighten with
excessive force, otherwise the interlock switch will be damaged. Be sure to
reinstall the screw, otherwise the waterproof capability will be lost.

Caution

Before manually unlocking the interlock switch, make sure that the machine Gland
AS-Interface Safety at Work

dius
has come to a complete stop. Manual unlocking during operation may unlock Minimum Ra
30 mm
the interlock switch before the machine stops, and the function of the interlock (70)
switch with solenoid is lost. While the solenoid is energized, do not unlock the
switch manually (solenoid lock type).
Rad um
30 ius
im

mm
Min

(50)

Gland

374 www.idec.com
Door Interlock Switches HS6E Series

Wire Identification
• Wires can be identified by color and or a white line printed on the wire.

No. Insulation Color No. Insulation Color

Overview
1 Blue/White 7 White
2 Gray 8 Black
3 Pink 9 Pink/White
4 Orange 10 Brown/White
5 Orange/White 11 Brown
6 Gray/White 12 Blue

X Series E-Stops
Terminal Number Identification
• When wiring, identify the terminal number of each contact by the color of the
insulation.

• The following table shows the identification of terminal numbers.

• When wiring, cut unused wires to avoid incorrect wiring.

Type Contact Arrangement

Door Interlock Switches


Door Monitor Lock Monitor

(+) (–)
White A2 A1 Black
HS6E-L
Main circuit: Blue 11 12 41 42 Blue/White
Monitor circuit: Brown 21 22 Brown/White Pink 53 54 Pink/White
Monitor circuit: Orange 31 32 Orange/White

Main circuit: Blue 11 12 41 42 Blue/White

HS6E-M Monitor circuit: Brown 21 22 Brown/White Pink 51 52 Pink/White


Monitor circuit: Orange 31 32 Orange/White

Enabling Switches
Main circuit: Blue 11 12 41 42 Blue/White
HS6E-N Monitor circuit: Brown 21 22 Brown/White Pink 53 54 Pink/White
Monitor circuit: Orange 33 34 Orange/White

Main circuit: Blue 11 12 41 42 Blue/White


HS6E-P Monitor circuit: Brown 21 22 Brown/White Pink 51 52 Pink/White
Monitor circuit: Orange 33 34 Orange/White

Note: The contact arrangements show the contact status when the actuator is inserted and locked.

Barriers
AS-Interface Safety at Work

USA: 800-262-IDEC Canada: 888-317-IDEC 375


HS5E Series Door Interlock Switches

HS5E Series Miniature Solenoid Locking Switches


HS5E features:
• World’s smallest 4 contact solenoid interlock switch. (35 x 40 x 146 mm)
Overview

• Four contacts
• Gold-plated contacts
• Spring lock type (unlocks when the solenoid is energized) and solenoid lock type (locks
when solenoid is energized) are available
• Flexible installation - the head can rotate, allowing 8 different actuator entries
• Metal actuator entry slot ensures long life
• Actuator locking strength is 1000N minimum (GS-ET-19)
• Integral molded cable reduces wiring time
• LED pilot light indicates the solenoid status
X Series E-Stops

• RoHS Directive Compliant


• Contacts are IP67 (IEC60529)
• NC contacts are direct opening (IEC/EN60947-5-1)
• Only proprietary actuators can be used, preventing unauthorized access (ISO14119,
EN1088)
• Double insulation structure - no grounding required

Spring Lock Type


Door Interlock Switches

• Automatically locks the actuator without power to the solenoid


• After the machine stops, unlocking is accomplished by energizing the solenoid, provid-
ing a high level of safety
• Manual unlocking is possible in the event of power failure or maintenance

Solenoid Lock Type EN1088 GS-ET-15


EN60947-5-1 BG standard
• The actuator is locked when energized
IEC60947-5-1 in Germany
• The actuator is unlocked when de-
Direct Opening Double
energized Insulation
Action
Enabling Switches

Straight Actuator
(mainly for sliding
doors

2 Actuator Entry Slots

Right-angle
Actuator

Manual Unlocking
Actuator Slot
Barriers

Integrated Cable

Green LED Indicator

Metallic Head
AS-Interface Safety at Work

Adjustable Actuator
(mainly for hinged doors)

L-shapted Actuator
(mainly for hinged
doors)

376 www.idec.com
Door Interlock Switches HS5E Series

Part Numbers
Body
Lock
Circuit Number Contact Arrangement Pilot Light Cable Length Part Number
Mechanism

Overview
Main Circuit: 1NC+1NC, Monitor Circuit: 1NO, 1NO 1m HS5E-A4001
(+) (–) Without 3m HS5E-A4003
A2 A1
5m HS5E-A4005
A 11 12 41 42
Main Circuit: 23 24 1m HS5E-A4401-G
Monitor Circuit: 53 54 With 3m HS5E-A4403-G
Monitor Circuit: 5m HS5E-A4405-G
Main Circuit: 1NC+1NC, Monitor Circuit: 1NO, 1NC 1m HS5E-B4001
Without 3m HS5E-B4003
5m HS5E-B4005

X Series E-Stops
Spring Lock B 11 12 41 42
Main Circuit: 23 24 1m HS5E-B4401-G
Monitor Circuit: 51 52 With 3m HS5E-B4403-G
Monitor Circuit: 5m HS5E-B4405-G
Main Circuit: 1NC+1NC, Monitor Circuit: 1NC, 1NC 1m HS5E-D4001
Without 3m HS5E-D4003
5m HS5E-D4005
D 11 12 41 42
Main Circuit: 21 22 1m HS5E-D4401-G
Monitor Circuit: 51 52 With 3m HS5E-D4403-G
Monitor Circuit: 5m HS5E-D4405-G

Door Interlock Switches


Main Circuit: 1NC+1NC, Monitor Circuit: 1NO, 1NO 1m HS5E-A7Y001
Without 3m HS5E-A7Y003
5m HS5E-A7Y005
A 11 12 41 42
Main Circuit: 23 24 1m HS5E-A7Y401-G
Monitor Circuit: 53 54 With 3m HS5E-A7Y403-G
Monitor Circuit: 5m HS5E-A7Y405-G
Main Circuit: 1NC+1NC, Monitor Circuit: 1NO, 1NC 1m HS5E-B7Y001
Without 3m HS5E-B7Y003
5m HS5E-B7Y005
Solenoid Lock B 11 12 41 42
Main Circuit: 23 24 1m HS5E-B7Y401-G

Enabling Switches
Monitor Circuit: 51 52
With 3m HS5E-B7Y403-G
Monitor Circuit: 5m HS5E-B7Y405-G
Main Circuit: 1NC+1NC, Monitor Circuit: 1NC, 1NC 1m HS5E-D7Y001
Without 3m HS5E-D7Y003
11 12 41 42 5m HS5E-D7Y005
D 21 22
Main Circuit: 1m HS5E-D7Y401-G
51 52
Monitor Circuit: With 3m HS5E-D7Y403-G
Monitor Circuit: 5m HS5E-D7Y405-G
Contact configuration shows the contact status when actuator is inserted and solenoid off for for spring lock or solenoid on for solenoid lock.

Actuator Keys Accessories

Barriers
Appearance Description Part Number Weight
Item Part Number Description
HS5B/HS5E Plug Actuator
(allows switch to be used as HS9Z-A5P 35g
HS9Z-A51 Straight interlock plug unit)

HS5B/HS5E Padlock Hasp


(prevents unauthorized HS9Z-PH5 35g
AS-Interface Safety at Work

insertion of actuator)
HS9Z-A52 Right-angle

Part Number Description


HS9Z-SP51 Mounting Plate
Horizontal/vertical operation (for
HS9Z-A55 HS9Z-T3 Manual unlock key (long type)
hinged doors) (see note below)

The actuator tensile strength is 500N


minimum.

USA: 800-262-IDEC Canada: 888-317-IDEC 377


HS5E Series Door Interlock Switches

Circuit Diagrams
Unlocking Using
Status 1 Status 2 Status 3 Status 4
Manual Unlock Key
Overview

• Door closed • Door opened • Door open • Door open • Door closed
• Machine ready to • Machine cannot be • Machine cannot be • Machine cannot be • Machine cannot be
Interlock Switch Status
operate operated operated operated operated
• Solenoid de-energized • Solenoid energized • Solenoid energized • Solenoid de-energized • Solenoid de-energized

Door Status
Locked Unlocked

Manual Unlocking
X Series E-Stops

(+) (–) (+) (–) (+) (–) (+) (–)


A2 A1 A2 A1 A2 A1 A2 A1

Circuit Diagram (Example: HS5E-A4) 11 12 41 42 11 12 41 42 11 12 41 42 11 12 41 42

23 24 53 54 23 24 53 54 23 24 53 54 23 24 53 54

Door Closed (locked) Closed (unlocked) Open Open Closed (unlocked)

HS5E-A4 Main Circuit 11-42 ON (closed) OFF (open) OFF (open) OFF (open) OFF (open)
(+) (–)
A2 A1 Monitor Circuit
Main Circuit: 11 12 41 42 (door open) 23-24 OFF (open) OFF (open) ON (closed) ON (closed) OFF (open)
Spring Lock Type Safety Switch

Monitor Circuit: 23 24
Door Interlock Switches

Monitor Circuit:
53 54 Monitor Circuit OFF (open) ON (closed) ON (closed) ON (closed) ON (closed)
(unlocked) 53-54

Main Circuit 11-42 ON (closed) OFF (open) OFF (open) OFF (open) OFF (open)
HS5E-B4
Main Circuit: 11 12 41 42 Monitor Circuit
Monitor Circuit: 23 24 (door open) 23-24 OFF (open) OFF (open) ON (closed) ON (closed) OFF (open)
Monitor Circuit: 51 52
Monitor Circuit
(unlocked) 51-52 ON (closed) OFF (open) OFF (open) OFF (open) OFF (open)

Main Circuit 11-42 ON (closed) OFF (open) OFF (open) OFF (open) OFF (open)
HS5E-D4
Main Circuit: 11 12 41 42 Monitor Circuit
Monitor Circuit: 21 22 (door open) 21-22 ON (closed) ON (closed) OFF (open) OFF (open) ON (closed)
Monitor Circuit: 51 52
Monitor Circuit
(unlocked) 51-52 ON (closed) OFF (open) OFF (open) OFF (open) OFF (open)
Enabling Switches

Solenoid Power A1-A2 (all types) OFF (de-energized) ON (energized) ON (energized) OFF (de-energized) OFF (de-energized)
Door Closed (locked) Closed (unlocked) Open Open Closed (unlocked)

HS5E-A7Y Main Circuit 11-42 ON (closed) OFF (open) OFF (open) OFF (open) OFF (open)
(+) (–)
A2 A1 Monitor Circuit
Main Circuit: 11 12 41 42 (door open) 23-24
OFF (open) OFF (open) ON (closed) ON (closed) OFF (open)
Monitor Circuit:
Solenoid Lock Safety Switch

23 24
Monitor Circuit: Monitor Circuit
53 54
(unlocked) 53-54 OFF (open) ON (closed) ON (closed) ON (closed) ON (closed)

Main Circuit 11-42 ON (closed) OFF (open) OFF (open) OFF (open) OFF (open)
HS5E-B7Y
Main Circuit: 11 12 41 42 Monitor Circuit
Monitor Circuit: 23 24 (door open) 23-24 OFF (open) OFF (open) ON (closed) ON (closed) OFF (open)
Monitor Circuit: 51 52
Monitor Circuit
(locked) 51-52 ON (closed) OFF (open) OFF (open) OFF (open) OFF (open)
Barriers

Main Circuit 11-42 ON (closed) OFF (open) OFF (open) OFF (open) OFF (open)
HS5E-D7Y
Main Circuit: 11 12 41 42 Monitor Circuit
Monitor Circuit: 21 22 (door open) 21-22 ON (closed) ON (closed) OFF (open) OFF (open) ON (closed)
Monitor Circuit: 51 52
Monitor Circuit
(locked) 51-52 ON (closed) OFF (open) OFF (open) OFF (open) OFF (open)
OFF (de-energized) to
Solenoid Power A1-A2 (all types) ON (energized) OFF (de-energized) OFF (de-energized) ON (energized) (note 4) ON (energized) (see
note 3) (see note 4)
AS-Interface Safety at Work

1. Main circuit: Connected to the control circuit of machine drive part, sending the interlock signals to the protective door.
2. Monitor circuit: Sends ON/OFF signals of main circuit and monitoring signals of open/closed status of protective door.
3. Do not attempt manual unlock when energized.
4. Do not energize the solenoid for a prolonged period of time when the door is open and when unlocking the door manually.

Operating Characteristics 0 (Key Insertion Position) The characteristics shown in the chart above are of the HS9Z-A61, -A62, -A65, and -A66 actuators. For the
(reference) 3.3 (Locked position)
5.3 6.9
HS9Z-A62S actuator, subtract 0.6 mm.
26.4 (stroke in mm)
The characteristics show the contact status when the actuator enters an entry slot of an interlock switch.
Main Circuit
Monitor Circuit (door open, NO) Contacts ON (closed)
Monitor Circuit (door closed, NC)
Monitor Circuit (Unlocked, NO) Contacts OFF (open)
Monitor Circuit (Locked, NC)

378 www.idec.com
Door Interlock Switches HS5E Series

Specifications
ISO14119, IEC60947-5-1, EN60947-5-1 (TÜV approval), EN1088, GS-ET-19 Part Number Key
Conforming Standards
(BG approval), UL508 (UL recognized), CSA C22.2, No. 14 (c-UL recognized)
Application Standards IEC60204-1/EN60204-1
HS5E - A 4 4 01 - G

Overview
Operating Temperature –25 to 50°C (no freezing)
Relative Humidity 45 to 85% (no condensation)
Pilot Light Color
Storage Temperature –40 to +80°C (no freezing) G (Green)
Cable Length
Operating Environment Degree of pollution: 3
01: 1m
Impulse Withstand Voltage 2.5 kV (between LED, solenoid and grounding: 0.5 kV) 03: 3m
Between live and dead metal parts: 100 MΩ minimum 05: 5m
Pilot Light Voltage
Insulation Resistance Between live metal part and ground: 100 MΩ minimum
4: 24V DC
(DC megger) Between live metal parts: 100 MΩ minimum

X Series E-Stops
0: without pilot light
Between Terminals of the same pole: 100 MΩ minimum
Solenoid Unit Voltage/
Electric Shock Protection Class Class II (IEC61140) Lock Mechanism
Degree of Protection IP67 (IEC60529) 4: 24V DC/Spring Lock
7Y: 24V DC/Solenoid Lock
Operating extremes: 100 m/s2 (10 G)
Shock Resistance Circuit Code
Damage limits: 1000 m/s2 (100 G)
Operating extremes: 10 to 55 H, amplitude 0.35 mm minimum Door Monitor Lock Monitor
Vibration Resistance Circuit Circuit
Damage limits: 30 Hz, amplitude 1.5 mm minimum
A: 1NC + 1NC 1NO + 1NO
Actuator Operating Speed 0.05 to 1.0 m/s B: 1NC + 1NC 1NO + 1NC

Door Interlock Switches


Actuator HS9Z-A51: 11 mm minimum D: 1NC + 1NC 1NC + 1NC
Positive Opening Travel
Actuator HS9Z-A52/A55: 12 mm minimum
Positive Opening Force 80N minimum
Tensile Strength when Locked 1000 N minimum (GS-ET-19)
Operating Frequency 900 operations per hour
Mechanical Life 1,000,000 operations minimum (GS-ET-19)
100,000 operations minimum (operating frequency 900 operations per
Electrical Life
hour, rated load AC-12, 250V, 1A)
50A (250V) (Note: Use 250V/10A fast acting type fuse for short circuit
Conditional Short-circuit Current
protection.)

Enabling Switches
Cable UL2464, No. 21 AWG (8-core: 0.5 mm2 or equivalent/core)
Cable Diameter ø7.6 mm
Weight (approx.) 400 g (HS5E-***01)

Specifications Pilot Light


Locking Mechanism Spring Lock/Solenoid Lock Rated Voltage 24V DC
Rated Voltage 24V DC Current 10 mA
Current 266 mA Light Source LED
Coil Resistance 90Ω (at 20°C) Light Color Green
Operating Voltage Rated voltage x 85% or less (at 20°C)

Barriers
Return Voltage Rated voltage x 10% or more (at 20°C)
Maximum Continuous Applying Voltage Rated voltage x 110%
Maximum Continuous Applying Time Continuous
Insulation Class Class F

Current Ratings
AS-Interface Safety at Work

Rated Insulation Voltage (Ui) (see note 2) 250V (between LED, solenoid and grounding: 30V)
Current (Ith) 2.5A
Rated Voltage (Ue) 30V 125V 250V 1. Minimum applicable load (reference value): 3V AC/DC, 5 mA
2. UL rating: 125V
Resistive load (AC12) — 2A 1A 3. TUV, BG rating: AC-15, 0.5A/250V, DC-13, 0.22A/125V
AC UL, c-UL rating: Pilot duty AC 0.5A/125V, Pilot duty DC 0.22A/125V
Rated Inductive Load (AC15) — 1A 0.5A
Current (Ie)
(see note 3) Resistive load (DC12) 2A 0.4A 0.2A
DC
Inductive Load (DC13) 1A 0.22A 0.1A

USA: 800-262-IDEC Canada: 888-317-IDEC 379


HS5E Series Door Interlock Switches

Dimensions (mm) and Mounting Hole Layouts


Actuator Keys
Overview

HS5E-**4*G (w/pilot light)


Horizontal Mounting/Straight Actuator (HS9Z-A51)
RP RP
26.4 42.2 32.9 41 26.4
32.9
6.2 5.2 13.4 5.2 6.2 13.4

.2
.2

R2
R2

1
30

28
20

20
35

20
28

20
35
Actuator 36.2 106 Actuator 36.2 106

1
Actuator Stop 145.7 (6.3) Actuator Stop 145.7 (6.3)
4-M4 Screws 20 to 22
6 ±1
X Series E-Stops

Slot Plug
(Note)
11 ±1
61.6

61.6
106
40

40
33

33
5

5
20

20
Mounting Hole Layout

Vertical Mounting/Right-angle Actuator (HS9Z-A52)


RP RP
27.7 41.5 32.9 40.3 27.7 32.9
13.4 13.4

.2
.2
Door Interlock Switches

R2
R2

1
30

29.6

29.6
20

20
20
35

20
35
36.2 106 Actuator 36.2 106
1

1
Actuator Cover
145.7 (6.3) Actuator Cover 145.7 (6.3)
Actuator
Actuator Stop Actuator Stop
4-M4 Screws 20 to 22
Slot Plug 7.6±1
(Note)
12.6±1
61.6

61.6
106

40
40

33
33
5

5
20

20
Mounting Hole Layout
Plug the unused actuator entry slot using the slot plug supplied with the actuators.
Enabling Switches

Actuator Key Mounting Reference Position


As shown in the figure on the right, the mounting reference position of Safety Switch
Door Stop Safety Switch
the actuator when inserted in the safety switch is:
Actuator Stop
HS9Z-A51: The actuator lightly touches the actuator stop placed on the
safety switch.
HS9Z-A52: The actuator cover lightly touches the actuator stop placed on Key Stop Actuator Cover
the safety switch. HS9Z-A51 Actuator Door Stop
HS9Z-A52 Actuator
After mounting the actuator, remove the actuator stop from the safety
switch.
Barriers

Straight (HS9Z-A51) Right-angle type (HS9Z-A52)


6.2 32.4
(6) 33
5.2 0.8 2 7.2 7.2
28
20

15
26

30
28

15

20
AS-Interface Safety at Work

.4
2.
2 6.4 4.5 0.8 ø4 1.6
R 2-
4-
Actuator Stop (Note) Actuator Stop (Note)
2

2
10

• Actuator Mounting Hole Layout (Straight, L-shaped)


2-M4 Screw 20

380 www.idec.com
Door Interlock Switches HS5E Series

Dimensions and Mounting Hole Layouts, continued


Vertically/Horizontally Movable Actuator (HS9Z-A55)
Actuator Orientation
Horizontal Swing Angle Adjustment

Overview
3 (M3 Hexagon Socket Head Screw)
Orienting The orientation of the actuator operation (horizontal/vertical) can be changed with the
Actuator Stop
Insert
(Note) orientation part (white plastic part) installed on the back of the actuator.

Do not loose the orientation part, otherwise the actuator will not operate properly.
49

26
38
20°

23
(M4 R2.1
15 7 1 Hole
18.5 29 s)
3.6
Vertical Swing
Orienting Actuator Stop
The actuator stop film and actuator stop are used when adjusting the actuator position, and must be

X Series E-Stops
Insert (Note)
removed after adjustment.

0.8
vActuator Mounting Hole Layout
Angle Adjustment (horizontal/vertical swing)
(M3 Hexagon Socket Head Screw) 38
2-M4 Screw
2
20°

Door Interlock Switches


Accessory Dimensions (mm)
Actuator Type Part Number • Mounting Plate (HS9Z-SP51)

10
Mounting Plate HS9Z-SP51

6
Manual Unlocking Key (long) HS9Z-T3

2-12.8

3
2-6.6

3.
• Manual Unlocking Key • HS9Z-T3 Manual Unlocking Key 40

R
4-
(plastic, supplied with the switch, (metal, long-shaped)
non-replaceable)
3

50.7
42.2
4-M
4
ø4

21

Enabling Switches
9

ø10

15
(24)

106
170

187
4
15

130
Manual 18 6.5
Unlocking Actuator
(24.5)

6.4
4-R

22
4-
C
3

Material: Anonized A6063


Weight: approx. 180 g

HS9Z-A5P HS9Z-PH5

Barriers
2- 8
R4
Rivet: Stainless Steel Spacer: Steel ø8
2-
46 43
Handle: Aluminum
28

Thickness: 2
36

22
40

7.5 16.5

Material: SPCC
10.5 24 Thickness: 1.6
Washer: Steel Area 5 27.5
ø4

Thickness: 2.5
56 5 Area
Coating: Orange
25
(36.2)

5 5 2.5
9

AS-Interface Safety at Work


7.5
10

(36.2)
6.5

2.5 2.5
Rivet: 27 Material: SPCC
Stainless Steel 33.5 Thickness: 2.0
43
46
(146)

R 60
10
(106)
(146)
(106)

HS5E
Interlock Switch
(6.3)

HS5E Interlock
(35) (40)
(6.3)

(35) Switch (40)

USA: 800-262-IDEC Canada: 888-317-IDEC 381


HS5E Series Door Interlock Switches

Operating Instructions

Minimum Radius of Hinged Door Actuator Angle Adjustment


Overview

• When using the safety switch for a hinged door, refer to the minimum radius • Using the angle adjustment screw, the actuator angle can be adjusted (refer
of doors as shown below. For doors with small minimum radius, use adjust- to the dimensional drawing).
able actuators (HS9Z-A55). Adjustable angle: 0 to 20°
Because deviation or dislocation of a hinged door may occur, make sure of
correct operation of the actual application before installation.
• The larger the adjusted angle of the actuator, the smaller the applicable
radius of the door opening.

HS9Z-A52 Actuator • After installing the actuator, open the door. Then adjust the actuator so that
its edge can be inserted properly into the entry slot of the safety switch.
(When the center of the hinged door is on the extension line of the actuator
mounting surface.) • After adjusting the actuator angle, apply loctite to the adjustment screw so
X Series E-Stops

that the screw will not loosen.


Min 190

Safety Switch
When using the HS9Z-A55 horizontally-movable actuator
imu mm

Mounting Holes
Mi adiu mm
R 70
nim s

m
1

Ra
um

• When the center of the hinged door is on the extension line of the contact
(161)
diu

Door Hinge Door Hinge


s

surface of actuator and safety switch: 50 mm


(36.2) (35)
• When the center of the hinged door is on the extension line of the actuator
(When the center of the hinged door is on the extension line of the contact mounting surface: 70 mm
surface of actuator and safety switch.
Door Interlock Switches

Horizontal Operation
Min 260

Safety Switch
imu mm

Mounting Holes
Mi adiu 0 mm
R 23
nim s

Mi
nim
Ra
um

um
(231)

Door
diu

Door Hinge Door Hinge R M


50 a in
s

Hinge im
mm dius u
70 m R
(41.5) (40.3) m adi
(36.2) m us
Door Hinge

(55.5)
Changing the Orientation of the Head Vertical Operation
Enabling Switches

• The head of the HS5E can be mounted in four ways by removing the four
screws from the corners of the HS5E head and reinstalling the head in the
desired orientation. Before wiring the HS5E, replace the head. Before replac-
M
Mounting Hole

ing the head, turn the manual unlock part to the UNLOCK position using the
Safety Switch

in
im

Mounting Hole
um

Safety Switch
manual unlock key. When reinstalling the head, make sure that no foreign 50 Door M
(38)

Ra in
m di
us Hinge im
m um
objects enter the safety switch. Tighten the screws, without leaving space

(58)
70 R
m adi
between the head and body, otherwise the safety switch may malfunction. (36.2) m us Door Hinge

• Recommended tightening torque: 1.0 ±0.1 N·m (55.5)

Factory Setting Head can be rotated.


Mounting Examples
Barriers

Slide Door Application

Door

HS9Z-A51
Keys

HS5E
Safety
Switches
AS-Interface Safety at Work

Latch
Door Stop

Safety Precautions
• Before manually unlocking the safety switch, make sure the machine has
come to a complete stop. Manual unlocking during operation may unlock the
switch before the machine stops, and the protection of the safety switch with
solenoid is lost. While the solenoid is energized, do not unlock the actuator
manually (solenoid lock type).

382 www.idec.com
Door Interlock Switches HS5E Series

Instructions, continued

For Manual Unlocking Cables


• Do not fasten or loosen the gland at the bot-

Overview
• Spring lock type
The HS5E allows manual unlocking of the actuator to pre-check proper door tom of the safety switch.
operation before wiring or turning power on, as well as for an emergency or a • When bending the cable during wiring, make
power failure. sure that the cable radius is kept at least Lid
• Solenoid lock type 30mm.
If the actuator is not unlocked although the solenoid is de-energized, the s
• When wiring, make sure that water or oil diu
actuator can be unlocked manually. Ra
does not enter the cable. um in
m m
.
ini
M mm
• Do not open the lid of the safety switch. Gland 30

X Series E-Stops
Otherwise the switch may become damaged.

• Solenoid has polarity. Observe the correct


polarity when wiring.
UNLOCK
Locked Unlocked Locked Unlocked
Wire Identification
LOCK

Locked Position Manual Unlocked Position


• Wires can be identified by the color and white line printed on the wire.
• To change from the locked to the manual unlocked position as shown above,
turn the actuator fully 90° using the proprietary actuator supplied with the No. Insulator Color No Insulator Color

Door Interlock Switches


switch. Colored Insulator
1 white 5 brown/white
• Using the safety switch with the actuator not fully turned (less than 90°) may Jacket
8 1 2
cause damage to the switch or errors (when manually unlocked, the switch 2 black 6 orange 7 3
will keep the main circuit disconnected and the door unlocked). 6 54
3 brown 7 blue/white
• Do not apply excessive force (0.45 N·m or more) to the manual unlock part, Dummy Insulator
otherwise the manual unlock part will be damaged. Do not leave the manual 4 blue 8 orange/white (white)
unlock key attached to the switch
during operation. This is dangerous Manual Unlocking Key
because the switch can be unlocked while (supplied with the switch)
Terminal Number Identification
the machine is in operation. • When wiring, identify the terminal number of each contact with the color of

Enabling Switches
insulator.
Recommended Tightening Torque of Mounting Screws
• The following table shows the identification of terminal numbers.
• Safety Switch: 2.0 ± 0.2 N·m (two M4 screws)
• When wiring, cut unnecessary wires such as dummy insulator (white) and/or
• Actuators unused wires to avoid incorrect wiring.
HS9Z-A51: 2.0 ± 0.2 N·m (two M4 screws)
Type Circuit Diagram
HS9Z-A52: 1.0 ± 0.2 N·m (two M4 Phillips screws)
HS9Z-A55: 1.0 ± 1.5 N·m (two M4 screws)
(+) (–)
White A2 A1 Black
• The above recommended tightening torques of the mounting screws are the
values confirmed with hex socket head bolts. When other screws are used
12 41 42 Blue/White
and tightened to a smaller torque, make sure that the screws do not become Main Circuit: Blue 11
HS5E-A Monitor Circuit: Orange 23 24 Orange/White
loose after mounting.

Barriers
Monitor Circuit: Brown 53 54 Brown/White

• Mounting bolts must be provided by the users.


Main Circuit: Blue 11 12 41 42 Blue/White
• To avoid unauthorized or unintended removal of safety switch and the actua- HS5E-B Monitor Circuit: Orange 23 24 Orange/White

tor, it is recommended that the safety switch and the actuator are installed Monitor Circuit: Brown 51 52 Brown/White

in an unremovable manner, for example using special screws or welding the


screws. Main Circuit: Blue 11 12 41 42 Blue/White
HS5E-D Monitor Circuit: Orange 21 22 Orange/White
AS-Interface Safety at Work

Monitor Circuit Brown 51 52 Brown/White

USA: 800-262-IDEC Canada: 888-317-IDEC 383


HS1E Series Door Interlock Switches

HS1E Series Full Size Solenoid Locking Switches


HS1E features:
• Basic unit and solenoid unit in one housing
Overview

• Plastic Housing: Light weight


• Ease of Wiring: All the terminal screws are M3.5
• Available with a red or green indicator
• Choose from 4 circuit configurations
• When mounting the actuator on a movable door, and the switch on a machine body, the
door can be mechanically locked when closed
• Greater Safety: The door is unlocked by a solenoid lock-release signal from a PLC or
other source after the machine has stopped
• In the event of power failure or for machine maintenance, the door can be unlocked
X Series E-Stops

using a special tool


• Flexible Installation: The actuator can be accessed from two directions

EN1088 GS-ET-15
EN60947-5-1 BG standard
IEC60947-5-1 in Germany
Direct Opening Action Double Insulation
Certificate No.
Door Interlock Switches

20005010305145656

HS1E Series Functionality

• Conduit Port • Contact Mechanism


Use IP67 conduit or gland.

• Terminal Block
(M3.5)
• LED Indicator
(green or red)
Enabling Switches

• Straight Actuator

(Zinc Diecast)

• Angle Adjustable Actuator


(for hinged doors)
• Right-angle Actuator • Two Actuator Entry Slots

• Terminal Block for Pilot Light (M3.5)


Barriers
AS-Interface Safety at Work

384 www.idec.com
Door Interlock Switches HS1E Series

Part Numbers
Model
Actuator Lock Conduit
Contact Configuration Manual
Retention Force Mechanism Port Size Indicator Part Number

Overview
Unlock Key

1
Monitor Circuit
— — HS1E-40R
2

3
Main Circuit With — HS1E-44R-k
Main circuit: 1NC + 1NC 4
G1/2
Monitor circuit: 1NO/1NO 5
Solenoid Power — With HS1E-40KR
6
Indicator
7
Contacts are linked to
With With HS1E-44KR-k

X Series E-Stops
the solenoid mechanically. 8

1 — — HS1E-140R
Monitor Circuit
2

3
Main Circuit With — HS1E-144R-k
Main circuit: 1NC + 1NC 4
G1/2
Monitor circuit: 1NO 5
Solenoid Power — With HS1E-140KR
6 Indicator
7
Contacts are linked to
8 With With HS1E-144KR-k

Door Interlock Switches


the solenoid mechanically.
1500N
Spring Lock
(when locked)
1
— — HS1E-240R
Monitor Circuit
2

3
Main Circuit With — HS1E-244R-k
Main circuit: 1NC + 1NC 4
G1/2
Monitor circuit: 1NO + 1NC 5
+
Solenoid Power — With HS1E-240KR
6
– Indicator
Contacts are linked to 7
the solenoid mechanically. With With HS1E-244KR-k
8

1
— — HS1E-340R

Enabling Switches
Monitor Circuit
2

3
Main Circuit With — HS1E-344R-k
Main circuit: 1NC + 1NC 4
G1/2
Monitor circuit: 1NC 5
+
Solenoid Power — With HS1E-340KR
6
– Indicator
Contacts are linked to 7
the solenoid mechanically. With With HS1E-344KR-k
8

1. Key wrench for TORX screws (HS9Z-T1) is supplied with the interlock switch.
2. Specify color code in place of k in the part number. G: green, R: red
3. Actuator is not supplied with the interlock switch, and must be ordered separately.
4. TORX is a registered trademark of Camcar Textron.

Barriers
Actuator Keys & Accessories
Item Part Number Description Item Part Number Description

Straight Actuator Key Wrench (included with


HS9Z-A1 HS9Z-T1
(Mainly for sliding doors) switch)
AS-Interface Safety at Work

Right-angle Actuator
HS9Z-A2 HS9Z-P1 Conduit Opening Plug
(Mainly for rotating doors)

Replacement Manual
HS9Z-A3 Adjustable Actuator HS9Z-KEY1
Unlocking Key

USA: 800-262-IDEC Canada: 888-317-IDEC 385


HS1E Series Door Interlock Switches

Specifications
EN1088, IEC60947-5-1, EN60947-5-1(TUV), ISO14119, Part Number Key
Conforming to Standards
GS-ET-19 (BG), UL508, CSA C22.2 No. 14 (c-UL)
Applicable Use IEC60204-1, EN60204-1
HS1E - 2 4 4 K R - R
Overview

Operating Temperature –20 to +40˚C (no freezing)


Storage Temperature –40 to +80˚C
Operating Humidity 40 - 85% RH (no condensation) Indicator Color:
R (Red)
Altitude 2,000m maximum G (Green)
Rated Insulation Voltage (Ui) 300V (between LED or solenoid and ground: 60V)
Impulse Withstand Voltage (Uimp) 4 kV (between LED or solenoid and ground: 2.5 kV) Manual Unlock Key
Between live and dead metal parts: 100 MΩ minimum K (with actuator)
0 (without actuator)
X Series E-Stops

Insulation Resistance Between live metal part and ground: 100 MΩ minimum
(measured with 500V DC megger) Between live metal parts: 100 MΩ minimum
Between terminals of the same pole: 100 MΩ minimum
Indicator Rated Voltage
Electric Shock Protection Class II (according to IEC61140) 4 (24V DC)
Blank (without indicator)
Pollution Degree 3 (IEC60947-5-1)
Degree of Protection IP67 (IEC60529) Circuit Code
Main Circuit Auxiliary Circuit
Vibration Operating Extremes 10 to 55 Hz, minimum (amplitude 0.35 mm) Blank: 1NC + 1NC 1NO/1NO
1: 1NC + 1NC 1NO
Resistance Damage Limits 50 m/sec2 (approx. 5G) 2: 1NC + 1NC 1NC + 1NC
3: 1NC + 1NC 1NC
Door Interlock Switches

Shock Resistance 1,000 m/sec2 (approx. 100G)


Actuator Tensile Strength when Locked 1,500N minimum (per GS-ET-19)
Actuator Operating Speed 1 m/sec maximum
Positive Opening Travel 11 mm minimum
Positive Opening Force 20N minimum
Thermal Current (Ith) Main circuit: 10A, Auxiliary circuit: 3A
Operating Voltage (Ue) 30V 125V 250V
Resistive load (AC12) 10A 10A 6A
AC
Inductive load (AC15) 10A 5A 3A
Circuit
Main

Resistive load (DC12) 6A – –


Enabling Switches

DC
Rated Operating Current (Ie) Inductive load (DC13) 3A 0.9A –
Resistive load (AC12) – 3A 3A
AC
Auxiliary

Inductive load (AC15) – – 3A


Circuit

Resistive load (DC12) 3A – –


DC
Inductive load (DC13) – 0.9A –
Contact Gap Main circuit: 1.7 mm min., Auxiliary circuit: 1.2 mm min.
Operating Frequency 900 operations/hour max.
1,000,000 operations min. (at full rated load)
Mechanical Life
900 ops/hr (AC-12/250V, 6A)
Electrical Life 100,000 operations (rated load)
Conditional Short-circuit Current 100A (per IEC60947-5-1)
Barriers

Recommended Short Circuit Protection 250V, 10A fuse (Type D01 based on IEC60269-1, 60269-2)
Operating Voltage 24V DC
Current 292mA
Coil Resistance 102Ω (at 20ºC)
Solenoid
Pickup Voltage 20.5V maximum (at 20ºC)
Unit
DropOut Voltage 2.4 minimum (at 20ºC)
AS-Interface Safety at Work

Allowable Voltage 26.4V max (continuous)


Insulation Class Class F
Operating Voltage 24V DC
Current 10 mA
Indicator
Light Source LED lamp
Lens Color Red or Green (12 mm dia. Lens)
Weight Approx. 500g

386 www.idec.com
Door Interlock Switches HS1E Series

Application Examples and Circuit Diagrams


HS1E-4 (Main Circuit: 1NC-1NC, Auxiliary Circuit: 1NO/1NO)
Status 1 Status 2 Status 3 Status 4 Unlocked Manually

Overview
• Door Closed • Door Closed • Door Opened • Door Opened • Door Closed
Switch/Door
• Machine ready to operate • Machine cannot be started • Machine cannot be started • Machine cannot be started • Machine cannot be started
Status
• Solenoid de-energized • Solenoid de-energized • Solenoid energized • Solenoid de-energized • Solenoid de-energized

Door

X Series E-Stops
Monitor

Monitor

Monitor

Monitor
Monitor

Circuit

Circuit

Circuit

Circuit
Circuit

Circuit

Circuit

Circuit

Circuit
Circuit

Main

Main

Main

Main
Main

Circuit
Solenoid

Solenoid

Solenoid

Solenoid
Solenoid

Diagram
Power

Power

Power

Power
Power

Contacts are linked to Contacts are linked to Contacts are linked to Contacts are linked to Contacts are linked to

Door Interlock Switches


the solenoid mechanically the solenoid mechanically the solenoid mechanically the solenoid mechanically the solenoid mechanically

Main Circuit 3-4: Closed 3-4: Open 3-4: Open 3-4: Closed 3-4: Open
Aux. Circuit 1-2: Open 1-2: Closed 1-2: Closed 1-2: Closed 1-2: Closed
Solenoid 5-6: Power OFF 5-6: Power ON 5-6: Power ON 5-6: Power OFF 5-6: Power OFF

HS1E-14 (Main Circuit: 1NC-1NC, Auxiliary Circuit: 1NO)


Status 1 Status 2 Status 3 Status 4 Unlocked Manually
• Door Closed • Door Closed • Door Opened • Door Opened • Door Closed

Enabling Switches
Switch/Door
• Machine ready to operate • Machine cannot be started • Machine cannot be started • Machine cannot be started • Machine cannot be started
Status
• Solenoid de-energized • Solenoid energized • Solenoid energized • Solenoid de-energized • Solenoid de-energized

Door

Monitor
Monitor
Monitor
Monitor

Monitor

Circuit
Circuit
Circuit
Circuit

Circuit

Circuit
Circuit

Barriers
Circuit
Circuit

Circuit

Main
Main
Main
Main

Main

(Note)
Circuit
Solenoid
Solenoid
Solenoid
Solenoid

Solenoid

Diagram
Power
Power
Power
Power

Power

Contacts are linked to Contacts are linked to Contacts are linked to Contacts are linked to Contacts are linked to
the solenoid mechanically the solenoid mechanically the solenoid mechanically the solenoid mechanically the solenoid mechanically
AS-Interface Safety at Work

Main Circuit 3-4: Closed 3-4: Open 3-4: Open 3-4: Open 3-4: Open
Aux. Circuit 1-2: Open 1-2: Open 1-2: Closed 1-2: Closed 1-2: Open
Solenoid 5-6: Power OFF 5-6: Power ON 5-6: Power ON 5-6: Power OFF 5-6: Power OFF

1. Main Circuit: used to enable the machine to start only when the main circuit is closed.
2. Auxiliary Circuit: used to indicate whether the machine circuit or door is open or closed.
3. Terminals 7 and 8 are used for the LED indicator, and are isolated from solenoid and door status.

USA: 800-262-IDEC Canada: 888-317-IDEC 387


HS1E Series Door Interlock Switches

Application Examples and Circuit Diagrams, continued


HS1E-24 (Main Circuit: 1NC+1NC, Auxiliary Circuit: 1NC+NC)
Status 1 Status 2 Status 3 Status 4 Unlocked Manually
Overview

• Door Closed • Door Closed • Door Opened • Door Opened • Door Closed
Switch/Door
• Machine ready to operate • Machine cannot be started • Machine cannot be started • Machine cannot be started • Machine cannot be started
Status
• Solenoid de-energized • Solenoid energized • Solenoid energized • Solenoid de-energized • Solenoid de-energized

Door
X Series E-Stops

Monitor

Monitor

Monitor
Monitor

Circuit
Monitor

Circuit

Circuit
Circuit

Circuit

Circuit

Circuit

Circuit
Circuit

Circuit

Main

Main

Main
Main

Main
Circuit

Solenoid

Solenoid

Solenoid
Solenoid

Diagram
Solenoid

Power

Power

Power
Power

Power
Door Interlock Switches

Contacts are linked to the Contacts are linked to the Contacts are linked to the Contacts are linked to the Contacts are linked to the
solenoid mechanically solenoid mechanically solenoid mechanically solenoid mechanically solenoid mechanically

Main Circuit 3-4: Closed 3-4: Open 3-4: Open 3-4: Open 3-4: Open
Aux. Circuit 1-2: Closed 1-2: Open 1-2: Open 1-2: Open 1-2: Open
Solenoid 5-6: Power OFF 5-6: Power ON 5-6: Power ON 5-6: Power OFF 5-6: Power OFF

HS1E-34 (Main Circuit: 1NC+1NC, Auxiliary Circuit: 1NC)


Status 1 Status 2 Status 3 Status 4 Unlocked Manually
Enabling Switches

• Door Closed • Door Closed • Door Opened • Door Opened • Door Closed
Switch/Door
• Machine ready to operate • Machine cannot be started • Machine cannot be started • Machine cannot be started • Machine cannot be started
Status
• Solenoid de-energized • Solenoid energized • Solenoid energized • Solenoid de-energized • Solenoid de-energized

Door

Monitor
Monitor

Monitor
Monitor

Monitor

Circuit
Circuit

Circuit
Circuit

Circuit
Barriers

Circuit
Circuit

Circuit
Circuit

Circuit

Main
Main

Main
Main

Main

(Note)
Circuit
Solenoid
Solenoid

Solenoid
Solenoid

Solenoid

Diagram
Power
Power

Power
Power

Power

Contacts are linked to the Contacts are linked to the Contacts are linked to the Contacts are linked to the Contacts are linked to the
solenoid mechanically solenoid mechanically solenoid mechanically solenoid mechanically solenoid mechanically
AS-Interface Safety at Work

Main Circuit 3-4: Closed 3-4: Open 3-4: Open 3-4: Open 3-4: Open
Aux. Circuit 1-2: Closed 1-2: Closed 1-2: Open 1-2: Open 1-2: Closed
Solenoid 5-6: Power OFF 5-6: Power ON 5-6: Power ON 5-6: Power OFF 5-6: Power OFF

1. Main Circuit: used to enable the machine to start only when the main circuit is closed.
2. Auxiliary Circuit: used to indicate whether the machine circuit or door is open or closed.
3. Terminals 7 and 8 are used for the LED indicator, and are isolated from solenoid or door status.

388 www.idec.com
Door Interlock Switches HS1E Series

Dimensions (mm)
HS1E with indicator - using 1500N operating force
Horizontal Mounting Vertical Mounting

Overview
104 Right-angle Actuator HS9Z-A2
Straight Actuator HS9Z-A1 4 88
33

23.5 26
45.4
39.2

129
121
10

19.5 ±1
10
8.5 ±1

61 (RP)
12.3
2
68.8 (RP)
49.5

X Series E-Stops
7.5

11.0 Actuator Cover


HS9Z-A2 Actuator
6.5 ±1 22 17.5 ±1
54.3 (RP) Actuator Cover
31.2
HS9Z-A1 Actuator
21 46.5 (RP)
2-M6 Actuator Mounting Holes 61
5 89
RP: Actuator Mounting 89
Reference Position

26
63

Slot Plug

23.5
3-M5 Screw
45

(supplied)
40

4
35

(Note)

Door Interlock Switches


Mounting Hole Layout
5.5

Note: Plug the unused atuator entry slot using the slot plug supplied with the interlock switch.

Enabling Switches
Barriers
AS-Interface Safety at Work

USA: 800-262-IDEC Canada: 888-317-IDEC 389


HS1E Series Door Interlock Switches

Accessories
Straight Actuator (mainly for sliding doors) HS9Z-A1
9 49.3
19.3
Overview

2-M6 R3
.2 1
Screws

29.2
22

40
22

43
Actuator 7.4 Actuator Cover
Mounting (red)
Holes

4.1
2
X Series E-Stops

Right-angle Actuator (mainly for hinged doors) HS9Z-A2


20 41.5
11 11.5
7.4 1
2-M6 Screws

29.2
22

40

43
22

*After installing the actuator, .2


remove the actuator cover. Actuator R3
Door Interlock Switches

Mounting Actuator Cover


(red)
Holes

2
4.1
90
°

Adjustable Actuator
• The actuator angle is adjustable (0˚ to 20˚) for hinged doors.
Enabling Switches

• The minimum radius of the door opening can be as small as 100mm.

For HS1/HS2 Series (HS9Z-A3)


(Note) 18
Actuator Stop
Film (attached)
29.2

58
44
58
72
Barriers

.2 2-M6 Screws
5 R3 2
20 Door hinge Actuator
Angle Adjustment Screw Mounting Holes
(M3 hexagon socket head screw)

30
(21)
33 max.

20°
12
AS-Interface Safety at Work

All dimensions in mm.

390 www.idec.com
Door Interlock Switches HS1E Series

Accessories, continued

Actuator Angle Adjustment

Overview
• Using the screw (M3 hex socket head screw), the actuator angle can be • After installing the actuator, open the door. Then adjust the actuator so that
adjusted (refer to the dimensional drawing). Adjustable angle: its edge can be inserted properly into the entry slot of the safety switch.
(0˚) to 20˚
• Recommended tightening torque: 0.8 N-m (approx. 8.0 kgf-cm)
• The larger the adjusted angle of the actuator, the smaller the applicable
radius of the door opening. • After adjusting the actuator angle, apply loctite or the like to the adjustment
screw so as to prevent its loosening.

Minimum Radius of Hinged Door

X Series E-Stops
• When using the interlock switch for a hinged door, refer to the minimum When using the HS9Z-A3 Angle Adjustable (vertical) Actuator
radius of doors shown below. For the doors with small minimum radius, use
angle adjustable actuators (HS9ZA3 or HS9Z-A3S). • When the door hinge is on the extension line of the interlock switch surface:

Note: Because deviation or dislocation of hinged door may occur in actual applications, make sure
of the correct operation before installation.

HS9Z-A2 Actuator M
ini
m
u
• When the door hinge is on the extension line of the interlock switch surface: 50 m
m Rad
m

Door Interlock Switches


ius
Min mm

Min mm
230

• When the door hinge is on the extension line of the actuator mounting
130
imu

imu
mR

mR

surface:
adiu

adiu
s

Door Hinge HS9Z-A3/A3S


Actuator

• When the door hinge is on the extension line of the actuator mounting
surface:
HS9Z-A2 M

Enabling Switches
Actuator ini
m
80 um
m Ra
m di
us
Min mm
Min 0 mm

400
imu
24
imu

mR
mR

adiu
adiu

s
s

Door Hinge

Barriers
AS-Interface Safety at Work

USA: 800-262-IDEC Canada: 888-317-IDEC 391


HS1C Series Door Interlock Switches

HS1C Series Full Size Solenoid Locking Switches


HS1C features:
• Rugged Aluminum Die-cast Housing
Overview

• With the actuator mounted on a movable door, and the switch on a machine, the door
can be mechanically locked when closed.
• Greater Safety: The door is unlocked by a solenoid lock-release signal from a PLC or
another source after the machine has stopped.
• In the event of power failure or for machine maintenance, the door can be unlocked
using a special tool.
• Flexible Installation: The actuator can be accessed from two directions.
• Select from four different circuit configurations.
• IP67 Protection
X Series E-Stops

EN1088 GS-ET-15
EN60947-5-1 BG standard in Germany
IEC60947-5-1

Certificate No. Direct Opening Action


20005010305145652
Door Interlock Switches

HS1C Series Functionality

Two Conduit Ports (G1/2)


Use IP67 conduit or
gland

Contact Mechanism
(Direct Opening Action)
Enabling Switches

LED Indicator
(green or red) Tubular Clamp
Terminal Block (M3)

Two Actuator
Entry Slots
Straight Actuator
(SUS304)
Barriers

Ground Terminal (M4)

Manual Unlocking Entry (M4 hole) Indicator Terminal Block (M3.5)


Right-angle Actuator Accessible using a small screwdriver
(SUS304) after removing a TORX screw on the
AS-Interface Safety at Work

unlocking entry

Angle Adjustable Actuator


for hinged doors

TORX is a registered trademark of Camcar Textron.

392 www.idec.com
Door Interlock Switches HS1C Series

Part Numbers

Contact Configuration Indicator LED Part Number Actuator Keys & Accessories
Main Circuit: 1NC+1NC Item Part Number Description

Overview
Auxiliary Circuit: 1NO/1NO
Green HS1C-R44R-G Straight Actuator
Auxiliary

1
HS9Z-A1
Circuit

2
(Mainly for sliding doors)
3
Circuit
Main

4 Right-angle Actuator
HS9Z-A2
5
+ (Mainly for rotating doors)
Solenoid
Power

6 Indicator Red HS1C-R44R-R


– 7 +
Contacts are linked
to the solenoid 8 –
mechanically HS9Z-A3 Adjustable Actuator

X Series E-Stops
Main Circuit: 1NC+1NC
Auxiliary Circuit: 1NO
Auxiliary

1 Green HS1C-R144R-G HS9Z-T1 Key Wrench (included with switch)


Circuit

3
Circuit
Main

4
+
Solenoid

5
Power

6 Indicator Red HS1C-R144R-R


– 7 +

Door Interlock Switches


Contacts are linked
to the solenoid 8 –
mechanically

Main Circuit: 1NC+1NC


Auxiliary Circuit: 1NC+1NC
Auxiliary

1 Green HS1C-R244R-G
Circuit

3
Circuit
Main

4
+
Solenoid

5
Power

6

Indicator Red HS1C-R244R-R
7 +
Contacts are linked
to the solenoid 8 –

Enabling Switches
mechanically

Main Circuit: 1NC+1NC


Auxiliary Circuit: 1NC
Green HS1C-R344R-G
Auxiliary

1
Circuit

3
Circuit
Main

4
+
5
Solenoid
Power

6

Indicator Red HS1C-R344R-R
7 +
Contacts are linked
to the solenoid 8 –
mechanically

Barriers
AS-Interface Safety at Work

USA: 800-262-IDEC Canada: 888-317-IDEC 393


HS1C Series Door Interlock Switches

Specifications
Conforming to Standards EN1088, IEC60947-5-1, EN60947-5-1, GS-ET-19, UL508 Part Number Key
Operating Temperature –20 to +40˚C (no freezing)
HS1C - R 1 4 4 R - R
Overview

Storage Temperature –40 to +80˚C


Operating Humidity 85% RH maximum (no condensation)
Altitude 2,000m maximum
Indicator Color
Rated Insulation Voltage (Ui) 300V (between LED or solenoid and ground: 60V) R (Red)
Impulse Withstand Voltage (Uimp) 4 kV (between LED or solenoid and ground: 2.5 kV) G (Green)
Between live and dead metal parts: 100 MΩ minimum
Between live metal part and ground: 100 MΩ minimum
Insulation Resistance Housing Color
Between live metal parts: 100 MΩ minimum
Between terminals of the same pole: 100 MΩ minimum R (Red)
X Series E-Stops

Electric Shock Protection Class Class 1 (IEC61140)


Pollution Degree 3 (IEC60947-5-1)
Solenoid and LED Voltage
Degree of Protection IP67 (IEC60529) 4 (24V DC)
Vibration Operating Extremes 10 to 55 Hz, amplitude 0.5 mm
Resistance Damage Limits 60 m/sec2 (approx. 6G) Circuit Code
Main Circuit Auxiliary Circuit
Shock Resistance 1,000 m/s (approx. 100G)
2 Blank:
1:
1NC + 1NC
1NC + 1NC
1NO/1NO
1NO
2: 1NC + 1NC 1NC + 1NC
Actuator Tensile Strength when Locked 1,500N minimum 3: 1NC + 1NC 1NC
Door Interlock Switches

Operating Speed 1 m/sec maximum


Positive Opening Travel 11 mm minimum
Positive Opening Force 20N minimum
Thermal Current (Ith) Main circuit: 10A, Auxiliary circuit: 3A
Operating Voltage (Ue) 30V 125V 250V
Resistive load (AC12) 10A 10A 6A
AC
Inductive load (AC15) 10A 5A 3A
Circuit
Main

Resistive load (DC12) 6A – –


DC
Rated Operating Current (Ie) Inductive load (DC13) 3A 0.9A –
Resistive load (AC12) – 3A 3A
Enabling Switches

AC
Auxiliary

Inductive load (AC15) – – 3A


Circuit

Resistive load (DC12) 3A – –


DC
Inductive load (DC13) – 0.9A –
Contact Opening Distance Main circuit: 1.7 mm max., Auxiliary circuit: 1.2 mm min.
Operating Frequency 900 operations/hour max.
Mechanical Life 1,000,000 operations
Electrical Life 100,000 operations (rated load)
Conditional Short-circuit Current 100A (IEC60947-5-1)
Recommended Short Circuit Protection 250V, 10A fuse (Type D01 based on IEC60269-1, 60269-2)
Operating Voltage 24V DC
Barriers

Current 415 mA
Coil Resistance 58Ω (at 20ºC)
Solenoid Energizing Voltage Rated voltage x 85% maximum (at 20ºC)
Unit De-energizing Voltage Rated voltage x 10% minimum (at 20ºC)
Continuous Applicable Voltage Rated voltage x 110%
Continuous Applicable Duration Not specifically limited
AS-Interface Safety at Work

Insulation Class Class B


Operating Voltage 24V DC
Current 10 mA
Indicator
Light Source LED lamp
Lens Color Red or Green (12 mm dia. Lens)
Weight Approx. 660g

394 www.idec.com
Door Interlock Switches HS1C Series

Dimensions (mm)
HS1C-R44R-* - using the straight actuator (HS9Z-A1)
RP RP

Overview
30 68.8 36.5 54.3 30 125
9 13.8 13.8 9 49.5 36.5 Conduit
2 10 Conduit 2 10 Port G1/2
R Port G1/2 R2
2.

. 4
7 .7

ø5
.4
ø5
43
40

42

42
40
43
22

22
106

106
Actuator Actuator

74

74
47

47
Actuator Cover Actuator Cover

X Series E-Stops
1.5

ø5
49.5 23.5 26 ø5 23.5 26

.2
.2 8.5 ±1.0

42
1.5 125
6.5 ±1.0

39.7
39.7
Slot Plug

35
47
35
(Note) 4 4-M5 Screws

4
23.5 26

Mounting Hole Layout

Door Interlock Switches


HS1C-R44R-* - using the Right-angle actuator (HS9Z-A2)
RP 125
30 61 36.5 Conduit RP 49.5 36.5 Conduit
6 2 10 Port G1/2 46.5 30 2 10 Port G1/2
6
R R2 .4
.4

2. .7 ø5
ø5

7
43
40

42

42
22
22

40
43
106

106

Enabling Switches
Actuator
74

74
Actuator
47

47

Actuator Cover Actuator Cover

1.5

ø5
49.5 23.5 26 ø5 23.5 26

.2
42

1.5 125 .2
19.5 ±1.0
11
17.5 ±1.0

47

4-M5 Screw
11

39.7

39.7
35

Slot Plug 35
(Note) 23.5 26
4

Mounting Hole Layout


4

Barriers
AS-Interface Safety at Work

USA: 800-262-IDEC Canada: 888-317-IDEC 395


HS1C Series Door Interlock Switches

Accessories
Straight Actuator (mainly for sliding doors)
HS9Z-A1
Overview

9 49.3
19.3
2-M6 R3
.2 1
Screws

29.2
22

40
22

43
Actuator 7.4 Actuator Cover
Mounting (red)
Holes

4.1
2
X Series E-Stops

Right-angle Actuator (mainly for hinged doors)


HS9Z-A2
20 41.5
11 11.5
7.4 1
2-M6 Screws
Door Interlock Switches

29.2
22

40

43
22

.2
Actuator R3
*After installing the actuator, Mounting Actuator Cover
remove the actuator cover. (red)
Holes

2
4.1
90
°
Enabling Switches

Adjustable Actuator
• The actuator angle is adjustable (0˚ to 20˚) for hinged doors.

• The minimum radius of the door opening can be as small as 100mm.

For HS1/HS2 Series (HS9Z-A3) (Note) 18


Actuator Stop
Film (attached)
29.2

58
44
58
72
Barriers

.2 2-M6 Screws
5 R3 2
20 Door hinge Actuator
Angle Adjustment Screw Mounting Holes
(M3 hexagon socket head screw)

30
(21)
33 max.
AS-Interface Safety at Work

20°
12

All dimensions in mm.

396 www.idec.com
Door Interlock Switches Precautions

Safety Precautions

• In order to avoid electric shock or a fire, turn the power off before installation, • Do not place a PLC in the circuit between the safety switch and the load. The
removal, wire connection, maintenance, or inspection of the switch. safety security can be endangered in the event of a malfunction of the PLC.

Overview
• If relays are used in the circuit between the safety switch and the load, • Do not disassemble or modify the switch. It may cause a breakdown or an
consider degrees of the danger and use safety relays, since welded or sticking accident.
contacts of standard relays may invalidate the functions of the safety switch.

Operation Precautions - for all series


• Regardless of door types, do not use the safety switch as a door stop. Install • Prevent foreign objects such as dust and liquids from entering the switch
a mechanical door stop at the end of the door to protect the safety switch while connecting conduit or wiring.
against excessive force.

X Series E-Stops
• If the operating atmosphere is contaminated, use a protective cover to
• Do not apply excessive shock to the switch when opening or closing the door. prevent the entry of foreign objects into the switch through the actuator entry
slots.
• A shock to the door exceeding 1,000 m/sec2 (approx. 100G) may cause the
contacts of the switch to chatter, and a malfunction of the switch may occur. • Entry of a considerable amount of foreign objects into the switch may affect
the mechanism of the switch and cause a breakdown.
• For connection of wires, unscrew the cover. Unnecessary loosening of other
screws may cause a malfunction of the switch. • Do not store the switches in a dusty, humid, or organic-gas atmosphere.

HS5E/HS5B Precautions

Door Interlock Switches


For Rotating Head Directions Note: Because deviation or dislocation of hinged doors may occur in actual
applications, make sure of the correct operation before installation.
• The heads of the HS5E/HS5B can be rotated in 90° increments after removing
the 4 screws on the corners of the head. Prevent entry of foreign objects into When using the HS9Z-A52 Actuator
the switch during removal of the head. Tighten these screws with torque
designated in the instruction sheet. Improper torque may cause errors. • When the door hinge is on the extension line of the interlock switch surface:

Factory Setting Head can be rotated.


Min
190 um R
im
Mi

mm adiu
nim
17 m R
0 m ad

Enabling Switches
u

Door Hinge Door Hinge


m ius

• When door hinge is on the extension line of the actuator mounting surface:
Min
Mi

260 m Ra
23 m R
nim

imu
0 m ad

mm dius
u

Door Hinge
Door Hinge
ius

Minimum Radius of Hinged Doors

Barriers
• When using the interlock switch on hinged doors, refer to the minimum radius
of doors shown below. When using on doors with small minimum radius, use
the angle adjustable actuator (HS9Z-A55).

HS2B Precautions
Wire Connection • Cracks or burrs on the conduit entry may deteriorate the housing protection
against water.
AS-Interface Safety at Work

• The HS2B has 3 conduit ports, which are closed as a part of the molded
switch housing. • When changing to another conduit port, close the unused opening with an
optional plug (Part No. HS9Z-P1).
• Make an opening for wire connection by breaking one of the conduit-port
knockouts on the switch housing using a screwdriver.

• When breaking the conduit port, take care not to damage the contact block or
other parts inside the switch.

USA: 800-262-IDEC Canada: 888-317-IDEC 397


Precautions Door Interlock Switches

HS1E Precautions

Wire Connection 1. This unlocking method is intended for an escape from a machine when a person is
locked in. For access to the unlocking entry, an access hole should be opened on the
Overview

• Make an opening for wire connection by breaking one of the conduit-port mounting panel. When opening the hole, apply proper protection against water or other
foreign objects.
knockouts on the switch housing using a screwdriver. 2. Caution: After the unlocking operation, put the screw back into the unlocking entry
for safety.
• Before breaking the knockout, temporarily remove the connector-fixing lock
nut from the switch.
• When breaking the knockout, take care not to damage the contact block or
other parts inside the switch.
• Cracks or burrs on the conduit entry may deteriorate the housing protection.
X Series E-Stops

• When changing to the other conduit port, close the unused opening with an
optional plug (accessory).
Unlock Unlock

Plug
Type No. HS9Z-P1 Screwdriver Normal Position Manual Unlocking Position

89

26
Manual Unlocking
Door Interlock Switches

M5
• Remove the screw located on the unlocking entry at the side of the switch us-

23.5
ing the key wrench included with the switch. Then insert a small screwdriver
into the switch to push the lever inside of the switch toward the indicator
until the actuator is unlocked (refer to the diagram on the right).

• Insert a small screwdriver into the elliptical hole on the back of the switch,
then push the lever inside of the switch toward the indicator until the actuator
is unlocked (refer to the diagram on the right).

HS1C Precautions
Enabling Switches

• Regardless of door type, do not use the safety switch as a locking device.
Install a locking device independently, for example, using a metal latch (also
applicable to HS1E).

• The safety switch cover can be only removed with the special key wrench
supplied with the switch or with the optional screwdriver (also applicable to
HS1B and HS1E).
• Remove the screw located on the unlocking entry at the side of the switch us-
ing the key wrench included with the switch. Then insert a small screwdriver
into the switch to push the lever inside of the switch toward the indicator
Screwdriver
until the actuator is unlocked (refer to the diagram on the right).
Barriers

Caution: After the unlocking operation, put the screw back into the unlocking
entry for safety.
AS-Interface Safety at Work

398 www.idec.com
Door Interlock Switches Precautions

Operation Precautions

Applicable Crimping Terminals Applicable Connectors (As shown below)

Overview
• (Refer to the Crimping Terminal 1 or 2 shown in the drawing below.) • Use connectors which maintain the IP67 protection.

• HS1C • Applicable Connector Dimensions


Terminals No. 1 to 6: Use solid or stranded wires only (crimping terminals
not applicable). • Flex Conduit: VF03 (Japan Flex) www.nipolex.co.jp
Terminals No. 7 and 8: Crimping Terminal 1 • Steel Connector (G1/2): ALC-103
Ground Terminal: Crimping Terminal 2 (PF13.5): RBC-103PG13.5
• HS1B

30 mm
G1/2

max.
Ground Terminal: Crimping Terminal 2
Other Terminals: Crimping Terminal 1

X Series E-Stops
HS2B, HS5B, and HS1E
Crimping Terminal 1 9 mm max.

3.6 min. 3.5 max. 3.5 min. 3.8 max.


Recommended Screw Tightening Torque
• HS1C: 5.0±0.5 N-m (approx. 50±5 kgf-cm)
(4 or 6 pcs of M5 hex socket head cap screws)
7.6 max.
6.9 max.

ø3.6 min. ø4.1 min.

• HS1B: 5.0±0.5 N-m (approx. 50±5 kgf-cm)


Crimping Terminal 1 Crimping Terminal 2 (2 or 4 pcs. of M5 hex socket head cap screws)

Door Interlock Switches


Use an insulation tube on the crimping terminal. • HS2B: 5.0±0.5 N-m (approx. 50±5 kgf-cm)
(2 pcs of M5 hex socket head cap screws)
Wire Approx. 4mm Crimping Terminal
• HS5B: 4.0±0.4 N-m (approx. 40±4 kgf-cm)
(2 pcs of M4 hex socket head cap screws)

• HS1E: 5.0±0.5 N-m (approx. 50±5 kgf-cm)


Insulation Tube (4 or 6 pcs of M5 hex socket head cap screws)

• Actuator (HS9Z-A1/A2)
Installation Examples (see the diagrams below) 5.0±0.5 N-m (approx. 50±5 kgf·cm)
Mounting on Sliding Doors

Enabling Switches
• (2 pcs. of M6 hex socket head cap screws)
Door Actuator (HS9Z-A51/A52)
• 2.0±0.2 N-m (approx. 20±2 kgf·cm)
HS9Z-A1 Actuator (2 pcs of M4 hex socket head cap screws)

• 1.0±0.2 N-m (approx. 10±2 kgf·cm)


Door Stop
(2 pcs of M4 Phillips screws)
Mounting on Hinged Doors The screws are supplied by the user.

Latch

Applicable Wire Size

Barriers
• HS1C: 0.5 to 0.75 mm2 (Terminals No.1, 2, 5 to 8)
1.0 to 1.25 mm2 (Terminals No.3, 4, and grounding terminal)

• HS5B: 0.5 to 1.25 mm2

• HS1E: 0.5 to 1.25 mm2


HS9Z-A1 Actuator
HS9Z-A2 Actuator
AS-Interface Safety at Work

USA: 800-262-IDEC Canada: 888-317-IDEC 399


Precautions Door Interlock Switches

Actuator Angle Adjustment • After installing the actuator, open the door. Then adjust the actuator so that
• Using the screw (M3 hex socket head screw), the actuator angle can be its edge can be inserted properly into the entry slot of the safety switch.
adjusted (refer to the dimensional drawing). Adjustable angle: (0˚) to 20˚
• Recommended tightening torque: 0.8 N-m (approx. 8.0 kgf-cm)
• The larger the adjusted angle of the actuator, the smaller the applicable
Overview

radius of the door opening. • After adjusting the actuator angle, apply loctite or the like to the adjustment
screw so as to prevent its loosening.

Minimum Radius of Hinged Door Horizontal Swing


• When using the interlock switch on hinged doors, refer to the minimum radius
of doors shown below. When using on doors with small minimum radius, use
the angle adjustable actuator (HS9Z-A55).
Note: Because deviation or dislocation of hinged doors may occur in actual applications, make sure
of the correct operation before installation. M
in 50
X Series E-Stops

im m
um m
Ra Door Hinge M
When using the HS9Z-A52 Actuator di
us
in 70
im m
um m
• When the door hinge is on the extension line of the interlock switch surface: Ra
di Door Hinge
us

Vertical Swing
Min
190 um R
im
Mi

mm adiu
nim
17 m R
0 m ad
u

Door Hinge Door Hinge


m ius
Door Interlock Switches

M
s

in
im 50 m
um m
Ra Door Hinge M 7
in
di
us im 0 m
• When door hinge is on the extension line of the actuator mounting surface: um m
Ra
di Door Hinge
us

Actuator Angle Adjustment for the HS9Z-A55


Min
Mi

260 m Ra
23 m R
nim

imu

• Using the angle adjustment screw, the actuator angle can be adjusted (see
0 m ad

mm dius
u

Door Hinge
Door Hinge
figures on page 370. Adjustable angle: 0 to 20°
ius

• The larger the adjusted angle of the actuator, the smaller the applicable
Enabling Switches

radius of the door opening.


When using the HS9Z-A55 Angle Adjustable Actuator • After installing the actuator, open the door. Then adjust the actuator so that
• When door hinge is on the extension line of the interlock switch surface: its edge can be inserted properly into the actuator entry slot of the interlock
50 mm switch.
• When door hinge is on the extension line of the actuator mounting surface: • After adjusting the actuator angle, apply Loctite to the adjustment screw so
70 mm that the screw will not loosen.

Applicable Cable Glands


Use a cable gland with a degree of protection IP67 When Using Multi-core Cables (Example)
Barriers

30 max.

G1/2, PG13.5, M20 Conduit Port Size Plastic Cable Gland Metal Cable Gland
G1/2 SCS-10* ALS-16**
(Seiwa Electric) (Nihon Flex)
9 max.
PG13.5 ST13.5 ABS-**PG13.5
all dimensions in mm (K-MECS) (Nihon Flex)
When Using Flexible Conduits (Example) M20 ST-M20X1.5 ALS-**EC20
Flexible conduit example: VF-03 (Nihon Flex) (K-MECS) (Nihon Flex)
AS-Interface Safety at Work

Conduit Port Size Plastic Cable Gland Metal Cable Gland


• Different cable glands are used depending on the cable sheath outside diameter. When
G1/2 — RLC-103 (Nihon Flex)
purchasing a cable gland, confirm that the cable gland is applicable to the cable sheath
PG13.5 — RBC-103PG13.5 (Nihon Flex) outside diameter.
• When using a 1/2-14NPT cable gland, use the HS5B interlock switch with M20 conduit
M20 — RLC-103EC20 (Nihon Flex)
port (Part No.: HS5B-***BM) together with an adapter (Part No.: MA-M/NPT 20X1.5
5402-0110, K-MECS) and a gasket (Part No.: GP M20, K-MECS). Install a gasket between
the interlock switch and the adapter. Apply sealing tape between the cable gland and
the adapter to make sure of IP67 protection for the enclosure.

400 www.idec.com