Directional Region For Oc and Ef

You might also like

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 3

Over Current Relay Operating Angle for R, Y & B phase (Leading)

Va^+Vb^+Vc^ = 0
Make :
characteristic Angle : 45
R operating angle : 225 To 45
Y operating angle : 105 To 285
B operating angle : 345 To 165

Earth Fault Current Relay Operating Angle for R, Y & B phase (Lagging)
Va^+Vb^+Vc^ = 3Vo
Make :
Characteristic Angle : -45
R operating angle : 45 To 225
Y operating angle : 285 To 105
B operating angle : 165 To 345
Leading)

phase (Lagging)
Transformer MVA 35 MVA
Primary Voltage 132 KV
Secondary Voltage 110 V
HV SIDE
Primary Current 200 A
Secondary Current 1 A
Primary Voltage 33 KV
Secondary Voltage 110 V
LV SIDE
Primary Current 800 A
Secondary Current 1 A
Transformer TAP Changer Ratio 1
Full load current in HV side 153.085 A
Full load current in LV side 612.341 A
ICT for HV Side 1.306
ICT for LV Side 1.306

ID> 0.2
ID>> 7
IR1 1
IR2 4
S1 0.2
S2 0.3
S3 0.7

ID 1
Ires 1
Iop 1.2

You might also like