TRANSFORMER WINDING RESISTANCE (WR) TEST REPORT

Test Certificate

Customer YAMAHA, BQIP Test performed on 10/12/2017


Plant Landhi

Plant section / Identification: Transformer Room -1250 KVA

Transformer type : TSUN6141


LPK No. : 21400874
Test Instrument Type : Winding Resistance Tester Rated power : 1250KVA
Vector Group : Dyn11 Prim/Sec Current : 65.60/1739 A
Cooling : ONAN
Frequency : 50Hz
Prim/Sec Voltage : 11000/415 V

Test Results:

Primary Windings()

Tap Positions 1 2 3 4 5 6

R-Y 1.29 1.24 1.20 1.17 1.14 1.12

Y-B 1.26 1.25 1.20 1.17 1.14 1.13

B-R 1.27 1.23 1.19 1.18 1.15 1.13


Secondary Winding ()
R-N 0.03 -- -- -- --
Y-N 0.03 -- -- -- --
B-N 0.03 -- -- -- --

Remarks:

Siemens Representative Client Representative


........................................... ..............................................
Name ................................... Name .........................................
Date Date ..