1- Design Criteria
Sizing table based on Velocity Limitation
Copper Water tube, type (K)
Max. Frict 2 psi/100ft, Velocity = 5 ft/s
pipe size, in pipe size, mm Flow, gpm
1/2'' 15 2.1
3/4'' 22 5.5
1'' 28 12.5
1 1/4'' 35 20.0
1 1/2'' 42 28.0
2'' 54 50.0
2 1/2'' 67 75.0
3'' 76 150.0
4'' 108 195.0
5'' 133 285.0
6'' 159 420.0
1- Maximum velocity suggested for Copper pipes is 5 ft/s (See 2006 ASPE Handbook - Volume 2 - Ch.5)
2- WSFU demand converting into gpm. (See 2003 NSPC Handbook - Table B.5.4)
3- Friction losses depend on the following data.
B- Residual Pressure:
Hr = 8 Psi (see Table 5-21 - 2006 ASPE Handbook)
= 5.41 m (Hose Bib)
Power = g x Q x H
pump h x motor h
= 2744 watt
1373.4
= 2.7 Kw
= 3.7 Hp
Selection = Grundfos
Type = Booster Pump
Model No. = Hydro 2000 ME 2 CRE15-2
Total Power = 6 kw
pump h = 70.2 %
motor h = 80.3 %