Models V3401, V3402, V3405, V3406 40.15
Standard Spray Technical Specifications:
Upright, Pendent and Recessed Pendent
Standard and Quick Response Models: V3401, V3402, V3405, V3406
Style: Pendent, Upright or Recessed Pendent
Nominal Orifice Size: 17/ 32"/14 mm
K Factor: 8.0 Imp./11.5 S.I.1
Nominal Thread Size: 3/4" NPT/20 mm
Max. Working Pressure:
175 psi/1200 kPa
V3405/V3406 V3405/V3406 V3401/V3402
Recessed Pendent Pendent Upright Factory Hydrostatic Test: 100% @ 500 psi/3450 kPa
Min. Operating Pressure:
Approvals/Listings:
7 psi/48 kPa
0.35 bar/5 psi (VdS for upright only)
0786
Temperature Rating: See chart
See Victaulic Publication 10.01 for more details. 1 For K-Factor when pressure is measured in Bar, multiply S.I. units by 10.0.
Product Description:
Coverage
Exaggerated
Exaggeratedfor
forClarity
clarity
Job/Owner Engineer
System No. Spec Section
Location Paragraph
Contractor Approved
Submitted By Date
Date
40.15 2547 Rev. I Updated 6/2014 2014 Victaulic Company. All rights reserved.
victaulic.com 2
victaulic.com | Sprinklers | FireLock | K8.0, V34 | Publication 40.15
Approvals/Listings:
Model
APPROVALS/LISTINGS
V3401 V3405 V3405 V3402 V3406 V3406 V3406
17/32 17/32 17/32 17/32 17/32 17/32 17/32
Orifice Size (inches)
Orifice Size (mm) 14 14 14 14 14 14 14
Nominal K Factor Imperial 8.0 8.0 8.0 8.0 8.0 8.0 8.0
Nominal K Factor S.I. 5 11.5 11.5 11.5 11.5 11.5 11.5 11.5
Response Standard Standard Standard Quick Quick Quick Quick
Recessed Recessed Recessed
Deflector Type Upright Pendent Upright Pendent
Pendent Pendent Pendent
Adjustment up to up to up to
Approved Temperature Ratings F/C
135F/57C 35F/57C
135F/57C 135F/57C 135F/57C
155F/68C 155F/68C
155F/68C 155F/68C 155F/68C 135F/57C 135F/57C
175F/79C 175F/79C
cULus 175F/79C 175F/79C 175F/79C 175F/79C 175F/79C
200F/93C 200F/93C
200F/93C 200F/93C 200F/93C 200F/93C 200F/93C
286F/141C 286F/141C
286F/141C 286F/141C 286F/141C
360F/182C 360F/182C
135F/57C 135F/57C
135F/57C 135F/57C
155F/68C 155F/68C 135F/57C
155F/68C 155F/68C 135F/57C
175F/79C 175F/79C 155F/68C
FM 175F/79C 175F/79C 175F/79C None
200F/93C 200F/93C 175F/79C
200F/93C 200F/93C 200F/93C
286F/141C 286F/141C 200F/93C
286F/141C 286F/141C
360F/182C 360F/182C
135F/57C 135F/57C
135F/57C 135F/57C 135F/57C
155F/68C 155F/68C
155F/68C 155F/68C 155F/68C 135F/57C 135F/57C
175F/79C 175F/79C
NYC/MEA # 62-99-E 175F/79C 175F/79C 175F/79C 175F/79C 175F/79C
200F/93C 200F/93C
200F/93C 200F/93C 200F/93C 200F/93C 200F/93C
286F/141C 286F/141C
286F/141C 286F/141C 286F/141C
360F/182C 360F/182C
135F/57C 135F/57C
135F/57C 135F/57C 135F/57C
155F/68C 155F/68C
155F/68C 155F/68C 155F/68C 135F/57C 135F/57C
175F/79C 175F/79C
CSFM # 7690-0531:112 175F/79C 175F/79C 175F/79C 175F/79C 175F/79C
200F/93C 200F/93C
200F/93C 200F/93C 200F/93C 200F/93C 200F/93C
286F/141C 286F/141C
286F/141C 286F/141C 286F/141C
360F/182C 360F/182C
135F/57C
135F/57C
155F/68C 135F/57C
155F/68C 135F/57C
175F/79C 155F/68C
VNIIPO7 None None 175F/79C 175F/79C None
200F/93C 175F/79C
200F/93C 200F/93C
286F/141C 200F/93C
286F/141C
360F/182C
135F/57C
135F/57C
155F/68C
155F/68C
175F/79C
VdS None None 175F/79C None None None
200F/93C
200F/93C
286F/141C
286F/141C
360F/182C
135F/57C
135F/57C
155F/68C
155F/68C
175F/79C
CE None None 175F/79C None None None
200F/93C
200F/93C
286F/141C
286F/141C
360F/182C
135F/57C
135F/57C
155F/68C
155F/68C
175F/79C
LPCB None None 175F/79C None None None
200F/93C
200F/93C
286F/141C
286F/141C
360F/182C
5 For K Factor when pressure is measured in Bar, multiply S.I. units by 10.0
6 The density at S = 12m2, H = 2.5 m, shall be a minimum of: 0, 014 dm3 / m.s at P = 0,1 MPa; 0.02 dm3 / m.s at P = 0,3 MPa
40.15 2547 Rev. I Updated 6/2014 2014 Victaulic Company. All rights reserved.
victaulic.com 3
victaulic.com | Sprinklers | FireLock | K8.0, V34 | Publication 40.15
Dimensions:
37 mm/
1716"
45 mm/
1"
64 mm/
2"
2 38"/60 mm
Max. Hole
2"/51 mm
Min. Hole
118"/
1116"/ 58"/ 29 mm
18 mm 16 mm Typical Ceiling Tile
138"/
178"/ Finished Surface 34 mm
47 mm
MAXIMUM RECESS
2 1516"/75 mm
MAXIMUM EXTENSION
2 38"/60 mm
Max. Hole
2"/51 mm
Min. Hole
138"/
1516"/ 35 mm
24 mm 58"/
16 mm Typical Ceiling Tile
118"/
178"/ 29 mm
Finished Surface
47 mm
MAXIMUM RECESS
2 1516"/75 mm
MAXIMUM EXTENSION
40.15 2547 Rev. I Updated 6/2014 2014 Victaulic Company. All rights reserved.
victaulic.com 4
10'
3,0 m 8'
2,4 m
10'
3,0 m 8'
victaulic.com | Sprinklers | FireLock | K8.0, V34 | Publication
2,4 m 40.15 6'
1,8 m
Distribution Patterns: 8'
2,4 m 6'
1,8 m 4'
Models V3405, V3406 1,2 m
6'
K8.0 Standard Pendent and Recessed Pendent
1,8 m Patterns Trajectory
Distribution 4'
10' 1,2 m 2'
3.0m 0,6 m
4'
1,2 m 2'
8'
0,6 m 0
2.4m 2' 4' 6' 8' 10'
2' 0,6 m 1,2 m 1,8 m 2,4 m 3,0 m
0,6 m 0
6' 2' 4' 7 psi 6' 8' 10' 15 psi 12' 14' 30 p
1.8m 0,6 m 1,248
m kPa 1,8 m 2,4 m 3,0 m103 kPa3,7 m 4,3 m 207 k
0
2' 4' 7 psi 6' 8' 10' 15 psi 12' 14' 30 psi
0,6 m 1,248
mkPa 1,8 m 2,4 m 3,0 m103 kPa3,7 m 4,3 m 207 kPa
4' 10'
1.2m
7 psi 15 psi 30 psi
3,0 m
48 kPa 103 kPa 207 kPa
10'
2' 3,0 m 8'
0.6m 2,4 m
10'
3,0 m 8'
2,4 m 6'
0
1,8 m
2' 4' 6' 8' 8' 10' 12' 14' 16'
0.6m 1.2m 1.8m 2,4 m 2.4m 3.0m 3.7m
6'4.3m 4.9m
0.6m
2'
0
0.6m 1.2m 1.8m 2.4m 3.0m 3.7m 4.3m 4.9m
2' 4' 6' 8' 10' 12' 14' 16'
NOTES:
B. These graphs illustrate approximate trajectories, floor-wetting, and wall-wetting patterns for these specific Victaulic FireLock Automatic Sprinklers. They are provided as
information for guidance in avoiding obstructions to sprinklers and should not be used as minimum sprinkler spacing rules for installation. Refer to the appropriate NFPA
National Fire Code or the Authority Having Jurisdiction for specific information regarding obstructions, spacing limitations and area of coverage requirements. Failure
to follow these guidelines could adversely affect the performance of the sprinkler and will void all Listings, Approvals and Warranties.
40.15 2547 Rev. I Updated 6/2014 2014 Victaulic Company. All rights reserved.
victaulic.com 5
victaulic.com | Sprinklers | FireLock | K8.0, V34 | Publication 40.15
M Open No Bulb
WARNING
Always read and understand installation, care, and maintenance instructions, supplied with each box of sprin-
klers, before proceeding with installation of any sprinklers.
Always wear safety glasses and foot protection.
Depressurize and drain the piping system before attempting to install, remove, or adjust any Victaulic piping
products.
Installation rules, especially those governing obstruction, must be strictly followed.
Painting, plating, or any re-coating of sprinklers (other than that supplied by Victaulic) is not allowed.
Failure to follow these instructions could result in serious personal injury and/or property damage.
The owner is responsible for maintaining the fire protection system and devices in proper operating condition. For
minimum maintenance and inspection requirements, refer to the current National Fire Protection Association pam-
phlet that describes care and maintenance of sprinkler systems. In addition, the authority having jurisdiction may
have additional maintenance, testing, and inspection requirements that must be followed.
If you need additional copies of this publication, or if you have any questions about the safe installation of this
product, contact Victaulic World Headquarters: P.O. Box 31, Easton, Pennsylvania 18044-0031 USA, Telephone:
001-610-559-3300.
Installation Note
Reference should always be made to the I-40 Victaulic FireLock Automatic Sprinklers This product shall be manufactured by Victaulic or to Victaulic specifications. All products
Installation and Maintenance Sheet for the product you are installing. This installation sheet to be installed in accordance with current Victaulic installation/assembly instructions.
is included with each shipment of Victaulic products for complete installation and assembly Victaulic reserves the right to change product specifications, designs and standard
data, and is available in PDF format on our website at victaulic.com. equipment without notice and without incurring obligations.
Warranty Trademarks
Refer to the Warranty section of the current Price List or contact Victaulic for details. Victaulic is a registered trademark of Victaulic Company.
40.15 2547 Rev. I Updated 6/2014 2014 Victaulic Company. All rights reserved.
victaulic.com 6