Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Technical specification

Air Coolers Blast freezers - 50 Hz


Date 10/3/2017
Customer DL-CNB
Reference 110 KW -40 deg x 1 unit

Operating Mode Unit type Model


Direct Expansion Helpman THOR-T THOR-T 488-10 R H 2H/6 400

Type of calculation Design


Required Capacity 110.00 kW Margin 0.0 %
Calculated capacity 110.04 kW

Dimensions***
Length 4520 mm Dry weight (approx. +/-5%) 862 kg
Height 1830 mm
Depth 1060 mm
Packing Pallet Shipping Volume 10.80 m

Thermal Data
Refrigerant R404A Sensible Heat Ratio 0.98
Air Temperature -40.0 C / -43.9 C
Relative Humidity 95.0% / 100.0%
Evaporation Temp -53.6 C
DT1 (Air Inlet Temp.Difference) 13.6 K
DTM (Room Temp. Difference) 11.65 K
Air Velocity m/s
Condensate 2.4 kg/h

Fan data (3)


Ziehl-Abegg Yes Fan Type AC
Air flow: 72000m/h Fans/Motor 8
Air Throw 1 x 57 m Fan diameter 560.0mm
Rotation speed 1260 rpm Voltage 230
Total Nominal Power 8400 W Phase 1ph
Total Nominal current(2) 38.4 Connection D/Y
FLC 42.9A
Sound Pressure Level(3.0 m) (1) 77 dB(A) Sound Power Level 98 dB(A)
Frequency 50 Hz

Coil data
Tube Material Copper Fin Material Aluminium
Fin Spacing 10.0 mm Number of Circuits 64
Surface 519.2 m Internal Volume 188.6 l
Connections (In-Out) 2x28mm - 2x67mm Connection Side Right - Standard
Distributor Diameter 6.0 mm

Frame and casework


Casematerial Galvanized Steel Coated
Coil Frame Material Standard

NOTES
(1) By using EN 13487 at 3 m in free field conditions
(2) Nom. current at Tair = 20C. Variations occur due to different voltage or Tair

(***) Dimension and weight are not valid for all possible options. Drawings are only preliminary and indicative.

1/2
Technical specification
Options
Defrost System Water

Insulated drip tray No


Re-Heating coil No
Hinged Fan Cowl No

Electrical
Switch on/off No Connection box No

Summary
Type Item Id
Configured Unit
Total price
Description 1 THOR-T 488-10 R H 2H/6 400
Description 2 W/GC

Program version 5.64 Data update 2017-08-24

You might also like