GPR (19-2015) Code 81
GPR (19-2015) Code 81
• PH-IMS-SP-08-1-FR02
REVISION / ISSUE:00/01
DATE:1/12/2014
Generator Performance Report
Page | 1 OF 1
10 55 78 350-375 24.7 1 336 332 290 60.4 481 266 28 0.7 NA Normal
10 55 78 437-454 24.7 1 538 555 586 60.4 481 466 49 0.7 NA Normal
10 55 79 522-529 24.7 1 832 792 861 60.4 486 697 73 1.2 NA Normal
15 54 79 572-583 24.5 1 992 947 985 60.4 484 817 85 1.8 NA Normal
POINT X Y Z
1 16 12 6.5
2 6.5 12 6.5
3 5.8 9.9 8
4 3 7.6 4.3
5 4.7 6.7 5
6 11.3 10.3 26.5
7 4.3 7.3 4.7
8 5 8.2 6.2
Evaluation:
1- Generator tested till 85 % from its full load
2- All parameter readings were in acceptance range at 85% from full load except battery volt.
3- gen.have not spark arrestor and protection cap.
Result:
Action
Name: Mohamed Wageh Said Mahmoud Name: Mohamed Wageh Name: Sabe Salah,Ramadan,Ahmed Khedr