Professional Documents
Culture Documents
146 Kimura Real Time PDF
146 Kimura Real Time PDF
Abstract— This paper has investigated the possibility of a real 41 deg. Fig. 2 (b) shows the voltage change when 2-line short
time symmetrical coordinate transformation. Simulation is (2LS) fault occurs. The line-to-line voltage Vab is reduced to
performed when it is applied for detection of imbalanced fault in 20% of the rated voltage. The line-to-line voltage Vab and Vca
utility power system. The power conditioner is required to are reduced to 74% of the rated voltage and the phase shift is
remain connected when the fault occurs in the utility power 24 deg.
system under certain condition. This is called as the fault ride
through (FRT) ability. The most popular fault is 1 line-to-
ground fault. This fault causes the imbalance voltages and Connection Point
currents in 3-phase power system. To optimize the output from Ld Lf Cf Lac Vac
Diode
the power conditioner of the photovoltaic system, the detection of
the imbalanced condition is important factor. In this paper, the
signal processing method by using the complex number algebra Photo- Cd
in real time system is shown at first. The fast detection of the Voltaic
imbalanced condition is verified by the computer simulations. Panel Power
System
Then the effects of the harmonic components existing in the Boost DC-DC conv. Inverter
system voltage have been investigated. The generation of the
offset output and the oscillating waveforms are indicated. (b) Photo-Voltaic generation system
remained voltage is just 20%, the power conditioner must Various control methods, such as vector current controller with
recover its output power within 1 s. feed-forward of negative sequence grid voltage (VCCF) [4],
and dual vector current controllers (DVCC) [4,5], have been
proposed.
Then the positive sequence and the negative sequence
Vca reactive current compensation control is proposed for the DGs
interface converter to support AC grid voltages during the fault
and to meet the LVRT requirement[4,5]. It proposes a new
Vbc Vab LVRT technique by taking both the positive sequence reactive
current and the negative sequence reactive current into account.
The proposed method can inject the reactive current demanded
Vdrop=52%
by the grid code and alleviate the grid voltage imbalance
Phase change =41 deg. without exceeding the peak current limit of power transistors’
of the grid-connected converter.
(a) Va drop
To realize the proper output power control in imbalanced
fault condition, the quick measurement of the negative
sequence component is very important. This paper proposes the
Vc new symmetrical coordinate calculation by using the complex
number algebra.
II. SIMULATION OF FAULT CONDITION
Vdrop= Va Fig. 4 shows the simulation results when the 1LG fault
20% occurs.
0
(a) Vbc drop
-200
Fig. 2. Phase diagrams in case of a 2LS fault with 20% residual voltage
0.12 0.14 0.16 0.18 0.2 0.22
Time (s)
[%]
100 (a) AC line-to-line system voltage
52 50
0
-50
Area-2 -100
20 0.12 0.14 0.16 0.18 0.2 0.22
Area-3 Time (s)
-10
Area-1 : Fault Ride Through with phase shift of 41 degree.
Area-2 : Fault Ride Through with no concern about the phase shift. 0.12 0.14 0.16 0.18 0.2 0.22
Time (s)
Area-3 : Fault Ride Through or Gate Block.
ª 1 3 1 3 º
Fig. 4(a) shows the voltage change at the point of «Var Vbr Vbi Vcr Vci »
connection. Phase-a voltage reduced to 0V at 0.15 sec. Then ªV pr º « 2 2 2 2 »
the line-to-line voltage Vab and Vca are reduced from 282V- «V » «V 1 V 3 V 1 V 3 V » …(4)
peak to 148V-peak (52%) of the rated voltage and the phase « nr » « ar 2 br 2 bi 2 cr 2 ci »
shift is about 40 deg. Fig. 4(b) shows the current change of the «¬V0 r »¼ « Var Vbr Vci »
inverter ac side without the FRT control. The modulation « »
factor of the inverter PWM control is kept 1 and the current
increases largely. Fig. 4(c) shows the current change of the ¬« »¼
inverter ac side with the ideal FRT control. The modulation ª 1 3 1 3 º
factor of the inverter PWM control is reduced to 0 at 0.15 sec. «Vai Vbi Vbr Vci Vcr »
and the phase-a current is decreased. The other phase currents ªV pi º « 2 2 2 2 »
are kept at the rated value. This fact shows that it is necessary «V » 2« 1 3 1 3 »
« ni » Vai Vbi Vbr Vci Vcr
to detect the fault condition as fast as possible.
3« 2 2 2 2 »
III. REAL TIME SYMMETRICAL COORDINATE TRANSFORM
«¬V0i »¼ « Vai Vbi Vci »
« »
The authors propose to use memorized data at 90 degree
before to calculate the symmetrical components.
¬« ¼»
…(5)
The symmetrical coordinate calculation is performed by the where Vpr, Vnr, V0r are the real part and Vpi, Vni, V0i are the
complex number algebra. 3-phase voltages are expressed as imaginary part. And Var, V br, Vcr are the real part and Vai, V bi,
follows. Vci are the imaginary part.
ªv a º ª Va cos(Zt ) º ªVar º ª Va cos(Zt ) º
«v » «V cos(Zt 2S / 3)» «V » «V cos(Zt 2S / 3)» ǃ
« b» « b » …(1) « br » « b »
«¬vc »¼ «¬Vc cos(Zt 4S / 3) »¼ «¬Vcr »¼ «¬Vc cos(Zt 4S / 3) »¼
ªVai º ª Va sin(Zt ) º
In complex number expression, «V » «V sin(Zt 2S / 3)» …(6)
« bi » « b »
ªVa º ª Va ej (I T )
º «¬Vci »¼ «¬Vc sin(Zt 4S / 3) »¼
« » « j (I T 2S / 3) » The above equations can be replaced by
«Vb » «Vb e »
«Vc » «Vc e j (I T 4S / 3) » ª S º
¬ ¼ ¬ ¼ …(2) ªVai º « Va cos(Zt 2 ) »
Va ^cos(Zt ) j sin(Zt )` «V » « 2S S »
ª º «Vb cos(Zt )» …(7)
«V ^cos(Zt 2S / 3) j sin(Zt 2S / 3)`» « bi » « 3 2 »
« b » «¬Vci »¼ «V cos(Zt 4S S ) »
«¬Vc ^cos(Zt 4S / 3) j sin(Zt 4S / 3)`»¼ «¬ c 3 2 »¼
where Va, V b, Vc are the amplitude, and Z is angular The above equation means that the memorized data at 90
frequency. degree advance can be used for the imaginary part of the
3-phase symmetrical coordinate transformation are present voltage.
expressed as, Table I shows the parameters of simulation. Fig. 5 shows
the simulation results of the symmetrical coordinate
ªVp º ª1 e j 2S 3 e j 4S 3 º ªVa º transformation of 3-phase balanced voltage in the steady state.
« » 1« »« » Fig. 5(a) shows the 3-phase balanced voltage. Fig. 5(b) shows
«Vn » «1 e j 4S 3 e j 2S 3 » «Vb » …(3) the phase-a voltage and its 90 degree shifted data. The latter is
3
«V0 » «1 1 1 »¼ «¬Vc »¼ used as the imaginary component of the complex expression of
¬ ¼ ¬ the phase-a voltage. Fig. 5(c) shows the transformed positive
and negative sequence components. In this case, the negative
where subscript p, n and 0 denote the positive, negative and sequence component is zero since the 3-phase voltages are
zero-sequence components, respectively. balanced. The positive component depicts the peak voltage of
By dividing the real and imaginary part, each phase.
Va Vb Vc
200
TABLE I. PARAMETERS OF SIMULATION
Va Va_90
Fig. 7(b) shows the positive and negative sequence signal -200
by the previously proposed method [2]. The rising time to 20V
0.1 0.11 0.12 0.13 0.14
in the negative sequence is more than 10ms. Time (s)
Conventional w. LPF
fc=10Hz
(b) Positive and negative component outputs with LPF (10Hz)
and BRF (120Hz)
Phase of Fault (deg.)
ଶିଵ
In the above equation, the harmonic component measured has By using replacement of ൌ ଶ
, real part is as follows.
the phase shift of (kS/2) for the imaginary part. Therefore the ͳ ͵ ʹ ʹ݇
ʹܸଵ ܸ ൌ ͲǤͳܸ ଶ ൜൬ ሺെͳሻ ൰ ܿ ݏ൬߮ሺ݇ െ ͳሻ ߨ െ ߨ൰
phase of 3rd and 7th are inversed. Ͷ Ͷ ͵ ͵
ͳ ͵ ʹ ʹ݇
൬ െ ሺെͳሻ ൰
൬߮ሺ݇ ͳሻ െ ߨ െ ߨ൰
Ͷ Ͷ ͵ ͵
§ kS · ξ͵ ξ͵ ʹ ʹ݇
Vka coskZt j cos¨ kZt ¸
ቆ ሺെͳሻ ቇ ൬߮ሺ݇ ͳሻ െ ߨ െ ߨ൰
© 2 ¹ Ͷ Ͷ ͵ ͵
k 1 ξ͵ ξ͵ ʹ ʹ݇
coskZt 1 2 j sin kZt ቆ ሺെͳሻ െ ቇ ൬߮ሺ݇ െ ͳሻ ߨ െ ߨ൰
Ͷ Ͷ ͵ ͵
§ 2kS · § kS 2kS · ͳ ͵ ʹ Ͷ݇
Vkb cos¨ kZt ¸ j cos¨ kZt ¸ ൬ െ ሺെͳሻ ൰
൬߮ሺ݇ െ ͳሻ ߨ െ ߨ൰
Ͷ Ͷ ͵ ͵
© 3 ¹ © 2 3 ¹ ͳ ͵ ʹ Ͷ݇
2kS · 2kS · ൬ ሺെͳሻ ൰
൬߮ሺ݇ ͳሻ െ ߨ െ ߨ൰
§ k 1
§
¸ 1 2 j sin ¨ kZt
cos¨ kZt Ͷ Ͷ ͵ ͵
¸ ʹ Ͷ݇
© 3 ¹ © 3 ¹ ξ͵ ξ͵
ቆെ ሺെͳሻ ቇ ൬߮ሺ݇ ͳሻ െ ߨ െ ߨ൰
Ͷ Ͷ ͵ ͵
§ 4kS · § kS 4kS ·
Vkc cos¨ kZt ¸ j cos¨ kZt ¸ ξ͵ ξ͵ ʹ Ͷ݇
© 3 ¹ © 2 3 ¹ ቆെ ሺെͳሻ െ ቇ ൬߮ሺ݇ െ ͳሻ ߨ െ ߨ൰
Ͷ Ͷ ͵ ͵
§ 4kS · k 1
§ 4kS · ͳ ͵ Ͷ ʹ݇
cos¨ kZt ¸ 1 2 j sin ¨ kZt ¸
൬ െ ሺെͳሻ ൰
൬߮ሺ݇ െ ͳሻ ߨ െ ߨ൰
© 3 ¹ © 3 ¹ Ͷ Ͷ ͵ ͵
ͳ ͵ Ͷ ʹ݇
…(10) ൬ ሺെͳሻ ൰
൬߮ሺ݇ ͳሻ െ ߨ െ ߨ൰
Ͷ Ͷ ͵ ͵
ξ͵ ξ͵ Ͷ ʹ݇
By separating the real and imaginary parts, ቆ ሺെͳሻ െ ቇ ൬߮ሺ݇ ͳሻ െ ߨ െ ߨ൰
Ͷ Ͷ ͵ ͵
ξ͵ ξ͵ Ͷ ʹ݇
ܸ ൌ ܸଵ ܸ …(11) ቆ ሺെͳሻ ቇ ൬߮ሺ݇ െ ͳሻ ߨ െ ߨ൰
Ͷ Ͷ ͵ ͵
ܸ ൌ ܸଵ ܸ …(12) ͳ ͵ Ͷ
൬ ሺെͳሻ ൰
൬߮ሺ݇ െ ͳሻ ߨ െ ߨ൰
Ͷ݇
Ͷ Ͷ ͵ ͵
ଶ ͳ ͵
Ͷ Ͷ݇
൬ െ ሺെͳሻ ൰
൬߮ሺ݇ ͳሻ െ ߨ െ ߨ൰
ܸ ଶ ൌ ൫ܸଵ ܸ ൯ Ͷ Ͷ ͵ ͵
ଶ ଶ ξ͵ ξ͵ Ͷ Ͷ݇
ൌ ൫ܸଵ ܸ ൯ ൫ܸଵ ܸ ൯ ቆെ ሺെͳሻ െ ቇ ൬߮ሺ݇ ͳሻ െ ߨ െ ߨ൰
Ͷ Ͷ ͵ ͵
ൌ ܸଵ ଶ ܸ ଶ ʹܸଵ ܸ ξ͵ ξ͵ Ͷ Ͷ݇
ቆെ ሺെͳሻ ቇ ൬߮ሺ݇ െ ͳሻ ߨ െ ߨ൰ቋ
ܸଵ ଶ ܸ ଶ ʹܸଵ ܸ …(13) Ͷ Ͷ ͵ ͵
…(15)
Here, the power terms are the amplitude of the symmetrical ଶିଵ
coordinate components and they are the constants. On the By using replacement of ൌ , imaginary part is as
ଶ
other hand, the rests are the oscillating terms. Developing the follows.
oscillating terms induces the following equations. ʹܸଵ ܸ
ͳ ͵ ʹ ʹ݇
ʹܸଵ ܸ +ʹܸଵ ܸ …(14) ൌ ͲǤͳܸ ଶ ൜൬ ሺെͳሻ ൰ ܿ ݏ൬߮ሺ݇ െ ͳሻ ߨ െ ߨ൰
Ͷ Ͷ ͵ ͵
ͳ ͵ ʹ ʹ݇
൬െ ሺെͳሻ ൰ ܿ ݏ൬߮ሺ݇ ͳሻ െ ߨ െ ߨ൰
By dividing it into the real axis component and the Ͷ Ͷ ͵ ͵
imaginary part component, the solution can be derived. Setting ξ͵ ξ͵ ʹ ʹ݇
ቆെ െ ሺെͳሻ ቇ ݊݅ݏ൬߮ሺ݇ ͳሻ െ ߨ െ ߨ൰
the voltage after the fault as V1a=0, V1b= V1c = V, Vka=0, Vkb= Ͷ Ͷ ͵ ͵
Vkc = 0.1V. Then the real axis component is as eq. (15) and the ξ͵ ξ͵ ʹ ʹ݇
ቆ െ ሺെͳሻ ቇ ݊݅ݏ൬߮ሺ݇ െ ͳሻ ߨ െ ߨ൰
imaginary axis component is as eq. (16). Ͷ Ͷ ͵ ͵
ͳ ͵ ʹ Ͷ݇
In these equations, the frequencies generated are the k+1 ൬ ሺെͳሻ െ ൰ ܿ ݏ൬߮ሺ݇ െ ͳሻ ߨ െ ߨ൰
Ͷ Ͷ ͵ ͵
order component and the k-1 order component. The amplitude ͳ ͵ ʹ Ͷ݇
is proportional to the amplitude of the harmonic component. ൬െ ሺെͳሻ െ ൰ ܿ ݏ൬߮ሺ݇ ͳሻ െ ߨ െ ߨ൰
Ͷ Ͷ ͵ ͵
ξ͵ ξ͵ ʹ Ͷ݇
ቆ െ ሺെͳሻ ቇ ݊݅ݏ൬߮ሺ݇ ͳሻ െ ߨ െ ߨ൰
Ͷ Ͷ ͵ ͵
ξ͵ ξ͵ ʹ Ͷ݇
ቆെ െ ሺെͳሻ ቇ ݊݅ݏ൬߮ሺ݇ െ ͳሻ ߨ െ ߨ൰
Ͷ Ͷ ͵ ͵
Va Vb Vc
200
200
Vp
180
100
160
0
140
120 -100
100
-200
80
0.1 0.12 0.14 0.16 0.18 0.2
60 Time (s)
40 200 [Hz]
(a) Power system voltage with 3rd harmonics
20
0
DC offset Vpf Vnf
160
50
140
120
0
Enlarged-1 Detection
on Enlarged-2
100
0.1 0.12 0.14 0.16 0.18 0.2
80 Time (s)
60
20
(b) Oscillation components when 5th harmonics exists
200
150 [Hz]
15
Vp
180
10
160
140
2 [V]
5
120
0
100
0.115 0.12 0.125 0.13 0.135 0.14 0.145
80 Time (s)
60
400 [Hz]
40 (c) Enlarged part of “(b)Enlarged-1”
20
0
DC offset Vpf Vnf
10.5 [V]
10
Fig. 8. Calculated oscillation components of positive sequence 80
40
Va Vb Vc Va Vb Vc
200 200
100 100
0 0
-100 -100
-200 -200
0.1 0.12 0.14 0.16 0.18 0.2 0.1 0.12 0.14 0.16 0.18 0.2
Time (s) Time (s)
(a) Power system voltage with 3rd harmonics (a) Power system voltage with 3rd harmonics
Vpf Vnf Vpf Vnf
200 200
150 150
100 100
50 50
0
Enlarged-1 Detection
on Enlarged-2 0
Enlarged-1 Detection
onn Enlarged-2
0.1 0.12 0.14 0.16 0.18 0.2 0.1 0.12 0.14 0.16 0.18 0.2
Time (s) Time (s)
(b) Positive and negative components with 5th harmonics (b) Positive and negative components with 7th harmonics
Vpf Vnf
25
20
15
10
15 [V] 15 [V]
5
120
120
100
100
10.2 [V]
80
11.1 [V] 200 [Hz] 80 400 [Hz]
21.5 [V] 20.1 [V]
60 60
40 40
20
20
REFERENCES
[1] Japanese Grid-interconnection Code, JEAC 9701-2010, addendum-
2011-No.1.