Document NO.

• PH-IMS-SP08-WI1-FR03
REVISION / ISSUE:00/01

Generator Performance Report DATE:6/5/2015

Page | 1 OF 1

Model : Perkins Client: Power House Report NO.: GPR(106/2017)

Maximum LOAD : 48 KW \50 HZ Machine Code: 77 Work order NO:

Date of Inspection: 20/12/2017 Fuel type: Diesel Run hours: 23847 Hrs. Lifting Certificate NO.

Engine serial number : *U094673N* Ambient temp : 25°C Sound proof: NA CR code: NA

Oil Water Battery Boost


Duration Exhaust Temp. load Blow by Exhaust
Press Temp. Volt. P.f A1 A2 A3 Hz V KW pressure
Min °C % inch H 0 color
bar °C V 2
kpa
10 3.8 42 149 13.5 1 0 0 0 51.8 404 0 0 0.234 NA Normal

10 3.4 47 202 13.8 1 11 9 10 50.6 404 6 13 0.312 NA Normal

10 3.2 51 243 13.8 1 21 19 20 50.2 404 13 28 0.312 NA Normal

10 3.1 52 290 13.8 1 32 29 30 48.8 404 20 42 0.312 NA Normal

ENGINE INSTRUMENTS Available Check Available Check


ALTERNATOR CONTROLS
High Coolant Temperature √ √ Emergency Stop √ √

Oil /Low Oil Pressure √ √ O/U Voltage Fault

Water /Low water Level O/U Frequency Fault

High Oil Temperature Reverse Power

Exhaust Temp. 3 Start attempts

Fuel Level Overload 110%

Audible Alarm Over speed

Compression Test Records


Cylinder NO: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Pressure (Bar)

VIBRATION RECORDS (VELOCITY MM/S

POINT
X Y Z

1 40.94 28.7 24.5

2 29.91 32.36 46.11

3 33.3 22.41 27.4

4 40.6 38.55 11.8

5 10.55 26.6 11.32

6 NA NA NA

7 NA NA NA

8 36.51 41.7 50.59

Evaluation:
1- Generator test till 42 % from its full load & the frequency droped to "48.8HZ"
2- Vibration limits is out of limit.
3- Guard of generator fan is damaged.
4-Air filter is dirty.
5- Exhauster isnt fixed inplace properly.
6-No cap for exhauster.
7-No cap for radiator.
8-NO cap for fuel tank.
9-Fuel transfer pump wiring isnt connected properly.
10-Raditor fan Guard is broken.
11- No cap for air filter.
12-Generator cover isnt fixed inplace properly.
13-Generator box is full of dust and dirt.
14-Cables from Generator to control panel isolation hose is damaged.
15-Engine code is not prined on the gen set.
16-Current readings on screen (one of them isnt previewed)

Result:
Action

Inspected By QC Rep. Reviewed By QC Manager Witnessed By

Name: Mohamed Hamed Name: Mohamed Wagih Name:


Signature: Mohamed Hamed Signature: Mohamed Wagih Signature:

Date :20/12/2017 Date :20/12/2017 Date :