Beam Deflection Check (Span-Depth Ratio) EC2

You might also like

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 3

PROJECT: -

SUBJECT: Span-Effective Depth Ratio


EC2: 1-1:2004
Beam detail
The beam is S beam
S: Simply supported, one/two way sapnning simply supported slab
E: End span of continuous beam, one/two-way continuous slab
I: Interior span of bea, one/two -way spanning slab
C: Cantilever
F: Flat slab
Section detail Section type 3
Flange Section : 1
Flat Slab: 2
Slab and Beam: 3

Concrete strength fck = 30 N/mm2, MPa


Rebar yield strength fy = 500 N/mm2
beam span L,Leff = 8 m
beam width b = 1000 mm
beam height h = 275 mm
beam cover = 25 mm
ultimated bending mom M = 140.17 kN-m
Tension reinforcement, As,req 1357 mm2
Compression reinforcement, As',req 0 mm2
Tension reinforcement
Compression reinforcement
Effective depth d = 250 mm
Factor for structural system, K = 1 Reference reinforcement ratio, r0 0.005
tension reinforcement As prov = 2826 mm2 Tension reinforcement ratio, r 0.006
compression reinforcemAs' prov = 0 mm2
Compression reinforcement ratio, r' 0.000
Modification factors
Steel Tensile stress factor
310/s = 2.08
For flange section For flat slab
flange breadth, b = mm Long span factor,
= 8.5/l 1.0
rib breadth, bw = mm
b/bw = ### For slab and beam
Wide flange factor = ### Long span factor,
= 7.5/l 0.9

Limit span/depth ratio

Basic Limit span/depth ratio, l/d = 18.5


Modified Limit span/depth ratio, l/d = 38.5
Actual span/depth ratio, l/d = 32.0
Satisfactory OK!
Clause 7.4.2

Table 7.4N

Expression 7.17

Expression 7.16a

Expression 7.16b