Kelani Cu Cables
Kelani Cu Cables
Kelani Cu Cables
BS 6004/BS 6346
(Method F)
In free air or on a perforated cable tray
(Method A) (Method B) horizontal or vertical
Enclosed in conduit Enclosed in conduit (Method C)
In thermally on a wall, Clipped direct
insulating wall etc. .. or in trunking etc. .. Touching Spaced
Conduct by one diameter
or cross
sectional
area 2 Cables 3 or 4 2 Cables 3 or 4 2 Ca[,les 3 or 4 2 Cables 3 Cables 3 Cables 2 Cables
single cables single cables single cables single three three single phase ac or de
phase ac three phase ac three phase ac three phase ac
phase ac phase ac or 3 cables three
or de phase ac ordc phase ac or de flat phase ac or de
and flat and flat trefoi I phase ac flat
flat
touching touching
(mm 2) or trefoil. Horizontal Vertical
(A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A)
1 11 1.() .5 13.5 12 15.5 14 - - - - -
1.5 14.5 13.5 17.5 15.5 20 18 - - - - -
2.5 20 18 24 21 27 25 - - - - -
.4 26 24 32 28 37 33 - - - - -
6 34 31 41 36 47 43 - - - - -
10 46 42 57 50 65 59 - - - - -
16 61 56 76 68 87 79 - - - - -
25 80 73 101 89 114 104 131 114 110 146 130
35 99 89 125 110 141 129 162 143 137 181 162
50 119 108 151 134 182 167 196 174 167 219 ·197
70 151 136 192 171 234 214 251 225 216 281 254
95 182 164 232 207 284 261 304 275 264 341 311
120 210 188 269 239 330 303 352 321 308 396 362
150 240 216 300 262 381 349 406 372 356 456 419
185 273 245 341 296 436 400 463 427 409 521 480
240 321 286 400 346 515 472 546 507 485 615 569
300 367 328 458 394 594 545 629 587 56 '1 709 659
400 - - 546 467 694 634 754 689 656 852 795
500 - - 626 533 792 723 868 789 749 982 920
630 - - 720 611 904 826 1005 905 855 1138 1070
800 - - - - 1030 943 1086 1020 971 1265 1188
1000 - - - - 1154 1058 1216 1149 1079 1420 1337
Note - For rating factors-VCJri tion in ambient air temperature ref~r ta.hie Y-01
The data i tak n from BS 7( 71: 2008, Requirement ior Ele tri ill lnstllllation. IEE Wiring
Regu lations-Seventeenth Edition.
- See Table A2 for Voltage Drop.
L. I
BS 6004/BS 6346
Not -Ref r 1 ble /-0 I for ma irnum value of vollage drop in omumer in tallcition
-The cl, ta i · taken from B 7671: 008, Requirements for El 'ctri al In t, llation , IEE Wiring
R ·gulation -_ evente( nth Editi n
21
BS 7889/BS 7211
Not .. - For rating Iactor. -Vari.Hi on in .imhienl , 11 tc1 ip ·'rdtur ref ·rt, bi"' Y-01
Th data i. taken fr m lL 7 >71: _()08, Require ment f ir El tri I In tallation , IEE\ 'irin
R gulcl ions-S venteenth dition.
- Se Table 132 for Volt, ge Dr )p.
LI
BS 7889/BS 7211
'ot -R er table X-01 fr r n irnum vdlUL' >f \Oltage dr pin con umcr in tallation
-Th data ic; lilk n fn m l3 ~671: _008 R quirem nt or El tri al Install tion , IEE Wiring
Reguldtion -S v ntP •nth Fditton.
21
BS 6346
Ambient air temperature 30°C
Standard ground temperature 15°C
Conductor operating temperature 70°C
Coduct- Clipped direct In free air or on a perforated cable tray, horizontal or vertical
or cross Laid direct (Method C) (Method F)
setional in ground
area
For re ting fa !ors-Vari tion in ambi nt air t mp ralure r fer tabl Y-01
Note: The data ar" taken from l3 7671: 2008, Requir •m "nt for fie lrical In. tallations,
I -E Wiring R gulations- ev nteenth Edition ER 69- 'O erie 0 r ubli cltion tFor L.1hles l..rnl dired 111 ground nwtho !).
Sec Table C-2 for Voltage Drop
.L I
BS 6346
Ambient air temperature 30°C
Standard ground temperature 15°C
Conductor operating temperature 70°C
Nole : -Refer table · -0 I for maximum valu of voltage drop in consum r in tallation
-The datJ is taken from BS 7671: 2008, Requirements for Ele tri al Installations, IEE Wiring
Regulations-Sevenleenlh Edition.
21
BS 5467
Ambient air temperature 30°C
Standard ground temperature 1 5°C
Conductor operating temperature 90°C
PVC Aluminium XLPE Copper 0.6/1 kV
Laid
direct in Clipped direct In free air or on a perforated cable tray, horizontal or vertical
ground (Method C) (Method F)
'
Spaced by one cable dia meter
Touching Touching
2 Cab I · s single 3 or 4 cables
pha e ac three pha e ac
Conductor 2 Cables 3 cables 2 Cables 3 or 4 2 Cables 3 cables 3 cables Horizontal Vertical Horizontal Vertical
cross single three single cables single three three
sectional phase ac pha. e cc phase ac three phase ac phase ac pahase
area touching touching or de phase ac or de flat ac trefoil
flat flat flat
(mm 2 ) A A A A A A A A A A A
50 274 231 237 220 253 232 222 282 266 288 266
•.: 70 337 283 303 277 322 293 285 357 33 7 358 331
95 403 337 367 333 33 g 352 346 436 412 425 393
120 458 381 425 383 449 405 402 504 477 485 449
150 510 424 488 437 516 462 463 566 539 549 510
185 574 474 557 496 587 524 529 643 614 6 '18 574
240 661 542 656 579 689 612 625 749 714 715 666
300 739 601 755 662 792 700 720 842 805 810 755
400 820 657 853 717 899 767 815 929 889 848 797
500 910 720 962 791 1016 851 918 1032 989 923 871
630 1001 781 1082 861 1146 935 1027 1139 1092 992 940
800 1055 8'16 1170 904 1246 987 1 ·119 1204 1155 1042 978
1000 1155 860 1261 961 1345 1055 '1214 1289 1238 1110 1041
Not : Thes data are taken from BS 7671: 2008, Requirements for Electri <I lnstall<ltions,
IEE Wiring Regulation -Seventeenth [dition & ERA 69-30 eries of publications For uhl ·s kiid direc.t in Liround m thi d).
See Table 02 for Voll age drop
21. Current Carrying Capacity and Voltage Drop
BS 5467
Ambient air temperature 30°C
Standard ground temperature 15 °C
Conductor operating temperature 90°C
PVC Aluminium XLPE Copper 0.6/1 kV
Conductor
2 cables, single phase a.c. 3 or 4 cables, three phase a.c.
cross
sectional
area
,
(mm 2 ) (mV/A/m) (mV/A/m) (mV/A/m) (mV/A/m) (mV/A/m) (mV/A/m)
Note: -Refer table /-01 ior ma.·irnum value of vollage drop in consumer in tallation
-The data is taken from 85 7671: 2008, Requirements ior Electrical Installations, IEE Wiring
RegulJtions- ·eventeenth Edition.
21
BS 6004/BS 6346
TABLE - E
Enclosed in conduit Enclosed in conduit Clipped direct In free air or on a Voltage drop
in thermally on a wall or in perforated cable
insulating wall etc. trunking etc. tray etc., horizontal
or vertical
Conductor (Method A) (Method B) (Method C) (Method El (mV/Nm)
cross
sectional
1 Two 1Three or 1 Two 1Three or 1 Two 1Three or 1 Two 1Three or 2 core 2 core 3 or 4
area core cable 4 core core cable 4 core core 4 core core 4 core cable de cable core
single cable, single cable, cable cable, cable cable, single cable
phase ac three phase ac three single three single three phase three
or de phase ac or de phase ac phase ac phase ac phase ac phase ac ac phase
or de or de ac
(mm 2) (A) (A) (A) (A) (A) (A) (A) (A)
1 11 10 13 11.5 15 1.1.5 17 14.5 44 44 38
1.5 14 13 16.5 15 19.5 17.5 22 18.5 29 29 25
2.5 18.5 17.5 23 20 27 24 30 25 18 18 15
4 25 23 30 27 36 32 40 34 11 n 9.5
6 32 29 38 34 46 41 51 43 7.3 7.3 6.4
10 43 39 52 46 63 57 70 60 4.4 4.4 3.8
16 57 52 69 62 85 76 94 80 2.8 2.8 2.4
25 75 68 90 80 112 96 119 101 ·1.75 1 .75 LS
35 92 83 111 99 138 1"19 148 126 1.25 1.25 1 .1
50 110 99 133 118 168 144 180 153 0.93 0.94 0.81
70 139 125 168 149 213 184 232 196 0.63 0.65 0.57
95 167 150 201 179 258 223 282 238 0.46 0.50 0.43
120 192 172 232 206 299 259 328 276 0.36 0.41 0.35
150 219 196 258 225 344 299 379 319 0.29 0.34 0 .29
185 248 223 294 255 392 341 434 364 0.23 0.29 0.25
240 291 261 344 297 461 403 514 430 0.18 0.24 0.21
300 334 298 394 339 530 464 593 497 0.145 0.21 0.185
400 - - 470 402 634 557 715 597 0.105 0.185 0.160
For rating fa tars - Variation in ambient air temperature refer table Y-0 J
Note: -Ref r table X-o-1 for maximum valu of voltag, drop in consumer in tallation
-The data is taken from BS 7 71: 2008, Requiremen ior Ele trical In. tc II tion , IEE Wiring
Regulation -Seventeenth Edition.
21
BS 5467
TABLE - F
Enclosed in conduit Enclosed in conduit Clipped direct In free air or on a Voltage drop
in thermally on a wall or in perforated cable
insulating wall etc. trunking etc. tray etc., horizontal
or vertical
Conductor (Method A) (Method 8) (Method Cl (Method E) (mV/A/m)
cross
sectional
area 1 Two 1Three or 1 Two 1Three or 1 Two 1Three or 1 Two 1Three or 2 core 2 core 3 or 4
core cable 4 core core cable 4 core core 4 core core 4 core cable cable core
single cable, single cable, cable cable, cable cable, de single cable
phase ac three phase ac three single three single three phase three
or de phase ac or de phase ac phase ac phase ac phase ac phase ac ac phase
(mm 2 ) ordc or de ac
(A) (A) (A) (A) (A) (A) (A) (A)
1 14.5 13 17 15 19 17 21 18 46 46 40
1.5 18.5 16.5 22 19.5 24 22 26 23 31 31 27
2.5 25 22 30 26 33 30 36 32 19 19 16
4 33 30 40 35 45 40 49 42 12 12 10
6 42 38 51 44 .58 52 63 54 7.9 7.9 6.8
10 57 51 69 60 80 71 86 75 4.7 4.7 4
16 76 68 91 80 107 96 11 5 100 2.9 2.9 2.5
25 99 89 119 105 138 119 149 127 1.85 1.9 1.65
35 121 109 146 128 1 71 147 185 158 1.35 1.35 1.15
50 145 no 175 154 209 179 225 192 0.98 1.00 0.87
70 183 164 221 194 269 229 289 246 0.67 0.69 0.60
95 220 197 265 233 328 278 352 298 0.49 0.52 0.45
120 253 227 305 268 382 322 410 346 0.39 0.42 0.37
150 290 259 334 300 441 3 71 473 399 0.31 0.35 0.30
185 329 295 384 340 506 424 542 456 0.25 0.29 0.26
240 386 346 459 398 599 500 641 538 0.195 0.24 0.21
300 442 396 532 455 693 576 741 621 0.155 0.21 0.185
400 - - 625 536 803 667 865 741 0.12 0.19 0.165
For rating factor - Variation in ambient air t rnperc tur refer t. ble Y-0 I
Note: -R"fer tnhle X-01 for ma, imum value of 1oltage drop in onsumer inst,1llcllion
-The data is taken from B 7671: 2008, Requir menL ior Electri Ji Installations, JEE Wiring
Regulations-Seventeenth Edi ! ion.
21
BS 6346
Ambient air temperature 30°C
Standard ground temperature 15°C
Conductor operating temperature 70°C
TABLE - G
1 three or four 1 two core 1 three or 1 two core 1 three or Two core 2 core cable 3 or 4 core ,
core cable three cable, single four core cable, single four core cable de single phase cable three !
phase phase ac or cable three phase ac or cable three ac phase ac :
ac de phase de phase
ac ac
(mm 2 ) (A) (A) (A) (A) (A)
1.5 27 21 18 22 19 29 29 25
2.5 y=-.) 28 2c
.) 31 26 18 18 15
4 47 38 33 41 35 11 n 9.5
. 6 59 49 42 53 45 7.3 7.3 6.4
10 78 67 58 72 62 4.4 4.4 3.8
16 101 89 77 97 83 2.8 2.8 2.4
25 132 118 102 128 110 1 .75 1 .75 1.5
35 159 145 125 15 7 135 1.25 1.25 1.1
50 188 175 151 190 163 0.93 0.94 0.81
70 233 222 192 241 207 0.63 0.65 0.57
95 279 269 231 291 251 0.46 0.50 0.43
120 317 310 267 336 290 0.36 0.41 0.35
150 355 356 306 386 332 0.29 0.34 0.29
185 401 405 348 439 378 0.23 0.29 0.25
240 462 476 409 516 445 0.18 0.24 0.21
300 517 547 469 592 510 0.145 0.21 0.185
400 580 621 540 683 590 0.105 ().185 0.16
For rating factor.-Variation in ambi =-nt Jir t mperatur ref r table Y-01
Nol<: : -Refer tabl X-01 ior maximum value oi voltag drop in consumer installation
-The data i taken from BS 7671: 2008, Requir m nts for Etectrical Installations, IEE Wiring
Regula lion -S ·venteenth Edition & ERA 69- ' 0 s ries of publications (I ot ohlC's laid din•ct in ground methorl1.
21
BS 5467
Ambient air temperature 30°C
Standard ground temperature 15°C
Conductor operating temperature 90 °C
TABLE - H
1 three or four 1 two core 1 three or 1 two core 1 three or Two core 2 core cable 3 or 4 core
core cable three cable, single four core cable, single four core cable de single phase cable three
phase ac phase ac or cable three phase ac or cable three ac phase ac
de phase ac de phase ac
Not : -Refer table /-01 for maximu~ value of volttige drop 111 con umer instzilhtion
-The datJ i tak n from HS 7671: ?008, Requir m m for El ctrical In ·ttillations, IEE Wiring
Regulations-Seventeenth Edition & ERA 69-30 series of publi ~atiom (for cclbl 'S 1.)1(1 din·l t in ground nwtho