Bently Nevada Vibration Probes - BYPASS procedure in SIS(PE3)

Computer Login Name = administrator


Password = admin
􀂾Open 3500 Rack Configuration software

Connect using Network


Browse the unit which you want to see

Select the unit as above and connect


Now Upload from the Rack
Verify the tag name with correct rack using channel point names, by right mouse click on
corresponding module.
From Utilities menu select software switches

Drag the mouse over the channel to see the correct tag no. and check the box and
press set button.
Removing the Bypass process is just ‘un-mark’ and click ’Set’

After Bypass Verify the tag is bypassed using this procedure.


Utilities menu, select Verification.

Change channel and see the channel bypass-Enabled/Disbaled

After completing Disconnect


Close the tab by pressing X button and press No (no need to save the config)
CAUTION:

􀂾After worked on the loop and before removing the bypass


on ‘Software Switch’, please check the vibration ‘Trend’
on System 1. You may even observe for sometime before
removing the bypass.

􀂾To bypass a spiking probe which is from pair probes


(A/B) on the same bearing, first bypass the spiking one.
Do not bypass another probe (which is not spiking) at the
same time. It can cause machine trip!

In this case, if necessary “Bypassing ONE by ONE is strongly


recommended”

􀂾Operations policy: ‘Bypassing all probes on one machine


at the same time’ is not allowed! At least one probe must
be kept ‘Live’ for machinery