Professional Documents
Culture Documents
Tce in 2.1
Tce in 2.1
Tce in 2.1
Dr. A. Kumar
EA Training,Siemens AG
Power Transmission and Distribution ISPSE
1. DC and AC Networks
I I
DC Voltage Source
L
R DC Current Source U
U
Example : Battery
c ) Capacitive Circuits
I
DC Voltage Source Summary for cases (a) to (c) :
C U 1. Only in Resistive circuits, the power is non zero.
Example : Battery In Inductive and Capacitive circuits, the power is
zero.
2. Currents in inductive circuits cannot change
instantenously
3. Voltages across capacitances cannot change
instantenously
Current = I = C* dU = 0 (Since Voltage is Constant )
dt
Power = U * I = 0
a ) RL Circuits
U / R
U
R
Voltage Current i
I
DC Voltage Source
U L
Example : Battery
Time Time
Voltage across
Voltage = U = R * i + L* di inductance
dt
-t/T
Current = i = U ( 1 – e )
R
Time
T = L / R = Time Constant of the circuit
a ) RC Circuits
R
U U / R
i
Voltage
Current i
DC Voltage Source
U C
Example : Battery
Time Time
U
t
1
Voltage = U = R * i +
C ?I * dt Voltage across
0 capacitance
-t/T
Current = i = U * e
R
T = R*C = Time Constant of the circuit Time
a ) RLC Circuits
R
U
i
Voltage
DC Voltage Source
U C
Example : Battery
L
Time
t Time constant = 2 L / R
1
Voltage = U = R * i + L di / dt +
C ?I * dt
Current
-t/2?
0
Sin ( ? ? 2 - 1 / 4 ? )
Current = i = U * 1 * 1 2
? e t
?
R
1/4?
2
? 2
- t
TT= =2L / R == Time
R*C Time Constant
Constantof
ofthe
the circuit
circuit
?? == ?? 11/ LC
/ LC == angular
angularfrequency
frequencyofofthe
thecircuit
circuit
a ) LC Circuits
L
U
i
Voltage
DC Voltage Source
U C
Example : Battery
Time
t
1
Voltage = U = L di / dt +
C ?I * dt
0
Sin ?
Current = i = U *
t Current
? L/C
?? == ?? 11/ LC
/ LC == angular
angularfrequency
frequencyofofthe
thecircuit
circuit
u
a ) General Concepts
?
u= 2 U cos ( ? t + ? ) I
ACVoltage Source
Example : AC Generator
~ Z u
Period = T
Imaginary
Note : j is an operator
U 2 which rotates the phasor
Period T = 1 / f seconds ( f = frequency in Hertz) by 90 0 in the positive direction
?
Angular velocity of the phasor = ? = 2 p f = 2 p / T radians / Second Real
Voltage as a Phasor
Example : f = 50 Hz (Hertz) J?
u = U 2 e Note : j = -1
Period T = 1 / f = 0.02 seconds = 20 milliseconds
Angular velocity ? = 2 p f = 314.16 radians per second =U 2 ( Cos ? + j Sin ? ) = u1 + j u 2
u= 2 U cos ( ? t + ? )
Effective (Root Mean Square) value of a Phasor
T
2
Laut definiton RMS value is =
?
1 / T u dt
0
For a sinusoidal signal u, the RMS value using the integral above is = U
For a sinusoidal signal u, the average value using the integral above is = 2 U 2 / p
Imaginary
I
u= 2 U cos ( ? t + ? )
~ R u
I
?
U
Real
Current i u = i . R = u1 + j 0
i= u/R = 2 U cos ( ? t + ? )
R
Imaginary
I
u= 2 U cos ( ? t + ? )
~ X u
?
U
0
Real
90
Current i I
Voltage and Current as Phasors
0
i= 1/L
?u dt = 2 U cos ( ? t + ? - 90 ) u = L di / dt = 0 + j ? L i
?L
Note : ? L = X and is called the inductive reactance
L
Result : Voltage across the inductance leads the current through the inductance by 90 0
Imaginary
I
u= 2 U cos ( ? t + ? )
~ XC u
I
90
0
?
U
Real
i = C dv / dt = 2 ? C U cos ( ? t + ? + 90 )
Note : ????? ?C = X and is called the capacitive reactance
C
Result : Voltage across the capacitance lags the current through the capacitance by 90 0
Imaginary
R XL
I
iXL
u= 2 U cos ( ? t + ? )
~ XC i X L- i X
C
? i
iR Real
iXC
j?
Z is called the complex impedance and is written as Z e
ZZ==[ [RR++j j( ( XX - - XX ) )] ]
LL CC
R XL
I If X L = X C , Z If=XRL = X C , Z = R
Current
Current is
is limited
limited only
only byby the
the resistance.
resistance.
u= 2 U cos ( ? t + ? )
~ XC This
Thiscondition
conditionisiscalled Series
calledseries Resonance
Resonance
At resonance ? ?L = 1 / ? ?C
f = ( 1 / 2 ? ) * ? 1 / LC
I Z = [ R + j X L * X C / ( X L - X C) ]
R If X L = X C , ZIf=XRL = X C , Z = ?
CurrentVoltage
is limited = IZ is very
only high.
by the resistance.
i= 2 I cos ( ? t + ? )
~ XL XC This
Thiscondition
conditionisiscalled
calledseries Resonance
Parallel Resonance
At resonance ? ?L = 1 / ? ?C
f = ( 1 / 2 ? ) * ? 1 / LC
R = 30 O L = 95.493 mH
C = 25.385 µ F
V = 100 v 2 sin ? t ~
f = 50 Hz
Calculate :
1. RMS- Value of the current
2. Maximum value of the current
3. Angle between the source voltage and the current
4. Resonant frequency of the network
5. Time constant of the network
6. Power loss in the resistance
Also draw the phasor diagram of the current and voltages across the resistance, inductance and capacitance
UR UX
im re
U U I
Reference : Current
I re im
im re
U U I
Reference : Voltage
re im
I
The instantaneous power p(t) of an electric system is the product of voltage u (t) and current i (t)
p(t) = u(t ) ?i(t) (Equ. 3.34)
Assume that:
? The current and voltage are sinusoidal
? There is only one frequency (no harmonics)
then following applies :
p ?t ? = u ?t ?? i ?t ? = 2 U 2 I cos ( ? t + ? u ) cos ( ? t + ? i ) (Equ. 3.35)
??cos ( ? ? ? ) ? cos ( ? ? ? ) ?
1
with cos ? ?cos ? ? (Equ. 3.36)
2
? ?
p ?t ? = U I ?cos ( ? u ? ? i ) + cos ( 2 ? t + ? u + ? i ) ? (Equ. 3.37)
?? ??konstant
? ? ?? ? ? ? ? ? ? ? ?? ?
? pulsierend mit doppelter
constant pulsating with double frequency nz ?
a networkNetzfreque
? = 0° ? = 60° ? = 90°
u, i
u, i u, i
t t t
t t t
Power-Related Terms
P
Power factor cos ? ? (Equ. 3.55)
S
P
Loss factor tan ? ? (Equ. 3.56)
Q
Reactive
current = Active current
Since
S ? U ?I *
? U ?(I w ? jI b ) (Equ. 3.57)
what applies is
Qind ? 0
Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 22
Power Transmission and Distribution ISPSE
Im
S S ? U Ie j2 ? t
2?
S~ = U I
???
i
?u ? ?i
-? i S = U I* = P + jQ
U
Q
?
I
? ? ?u ? ?i ?u ?i
P Re
p( ? t ? 0 )
Signs of Power and Reactive Power in the 4 Quadrants of the Complex Plane
P = U • I • cos ? S
100
%
Q = U • I • sin ? 75
50 Q P
S = U•I 25
0
S = P² + Q² 0° 15° 30° 45° 60° 75° 90°
?
Q = S² - P²
P S Q
P
t t t
Abbreviations:
1 3 Note : a is an operator
a = e j120 ? = cos 120 ? + j sin 120 ? = - ? j
2 2 which rotates the phasor
by 120 0 in the positive direction
1 3
a = e j240 ? = cos 240 ? + j sin 240 ? = - ? j
2
2 2 I L3 Im
(Equ. 3.67 a-b) 240°
240°
Following is valid: 120°
1 + a + a = 1 + e j120 ? + e j240 ? = 0
2
-240°
(Equ. 3.68) I L1 Re
If abbreviations are used following results: -120°
IL1 = I
IL2 = I ?a
2
I L2
IL3 = I ?a (Equ. 3.69 a-c)
Three-Phase AC System
i
iL1
L1 iL2
L2 iL3 here: ? = 0
L3
e-j240°
- j120 2 0 0 1
e = a = cos 120 - j Sin 120 = - 0.5 – j 0.866
- j240 0 0
e = a = cos 240 - j Sin 240 = - 0.5 + j 0.866 e-j120°
iL1(t) = î ?cos ( ? t + ? ) IL1 = I
î
iL2 (t) = î ?cos ( ? t + ? - 120 ?) IL2 = I ?e - j120 ? =
2
a I with I? ?e j ?
2
iL3 (t) = î ?cos ( ? t + ? - 240 ?) IL3 = I ?e - j240 ? = a I
(Equ. 3.65a-c) IL1 ? IL2 ? IL3 = I ?(1 ? e - j120 ? + e - j240 ? )
?0
2
= 1+a + a (Equ. 3.66a-e)
Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 28
Power Transmission and Distribution ISPSE
UL1
IL1 = UL1 / ZL1 ZL1 UL1
IL1 = UL1 / ZL1 ZL1
UL2
IL2 = UL2 / ZL2 ZL2 UL2
IL2 = UL2 / ZL2 ZL2
UL3
IL3 = UL3 / ZL3 ZL3 UL3
IL3 = UL3 / ZL3 ZL3
I L3 = I ? a (Equ. 3.70a-c)
the back conductor, which has remained, can also be omitted without no need to vary
the electrical properties of the system.
UL1 IL1 = UL1 / ZL1 ZL1
A simple solution is:
UL1 = U
UL2 IL2 = UL2 / ZL2 ZL2
UL2 = U ? a
2
U L 3 = U ?a (Equ. 3.79a-c)
IL1 IL2 IL3
I L 1 = I ?e j ? i I L 1* = I ?e ? j ? i
ZL1 ZL2 ZL3
IL 2 = I ?a ?e j? i
2
IL 2 * = I ? a ? e ? j ? i
IL 3 = I ?a ?e j? i IL 3 * = I ?a ? e ? j? i
2
= 3 ?U ?I ?e -j ? i
= 3 ?(P ? jQ) = constant (Equ. 3.82a-c)
S ~ = U ?I ?e j? i + a ?a ?U ?I ?e j? i + a ?a ?U ?I ?e j ? i
2 2
= U ?I ?e j? i (1 ? a ? a )
2
= 0 ! (Equ. 3.83a-c)
Apparent power
S ? 3 ?U? ?I (Equ. 3.84)
Effective power
P ? 3 ?U? ?I ?cos ? (Equ. 3.86)
Reactive power
Q ? 3 ?U? ?I ?sin ? (Equ. 3.88)
P = 3 • U • I • cos ? S
100
%
Q = 3 • U • I • sin ? 75
50 Q P
S = 3 •U•I 25
0
S = P² + Q² 0° 15° 30° 45° 60° 75° 90°
?
? Savings of material
? The system can be broken up into three single-phase systems at any time
? During system faults (Short circuits and open circuits) and unbalance load
conditions, the magnitudes and angles may not be equal
Basic Approach
AR a1 a2 a3 A1
As ? b1 b? b? A2
AT c1 c2 c3 A3
U1L1
U1 1 a a2 U L1
1
U2 ? 3 1 a2 a UL2
U0 1 1 1 UL3 U1L3 U1L2
1
UL1 Positive sequence U1 = (U + a UL2+ a² UL3)
3 L1
U2 L1
U2 L2 U2 L3
UL3 1
UL2 Negative sequence U2 = (U + a² UL2+ a UL3)
3 L1
U L1 1 1 1 U1
UL2 ? a2 a 1 U2
UL3 a a2 1 U0 U0 L1
1
Zero sequence U0 = (U + UL2 + UL3)
3 L1
Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 38
Power Transmission and Distribution ISPSE
UL1 UL1
UL1(t) = ÛL1 sin? t
t
t Mathematical
equations
Positive sequence
Negative sequence
UL1
Zero sequence
Phase-related display
Symmetrical components
0 0
I Z
m m m g g g
U I Z U I Z
~ ~ • •
• ~ • • ~ • • •
~ ~ 0 3I
0
U ~
Positive Sequence Network Negative Sequence Network
Zero Sequence Network
m g 0
U U 0
U
m g
Z = m Z = Z = 0
g
I I I
m
Note : Only U is nonzero, since electrical generators produce only positive sequence
g 0
voltages. Hence U and U are = 0
m m
I m m qm m m
qm Z U U = U - Z • I
U ~
g g g g qg g g g g
qg Z I U U = U - Z • I = - Z • I
U ~
=0
0 0 q0 0 0 0 0
q0 0 I U
0
U = U - Z • I = - Z • I
U ~ Z
=0
Positive sequence ~
Negative sequence
No Zero sequence
UN
I =
k2
Z1 ? Z 2
Note : U N is the line to line Voltage
Positive sequence ~
Positive sequence ~
Negative sequence
2
-j U N [(1 + a ) Z 2 + Z 0 ]
IS =
Zero sequence
Z1 Z 2 ? Z 2 Z 0 ? Z1 Z 0
j UN [(1 + a ) Z 2 + Z 0 ]
IT =
Z1 Z 2 ? Z 2 Z 0 ? Z1 Z 0 Note : U N is the line to line Voltage
Positive sequence ~
Negative sequence
Zero sequence
3 ?U N
I k1 = 3 I 0 =
Z1 ? Z 2 ? Z0
Note : U N is the line to line Voltage
UL1
UL1 = 0
UL2 UL2
Ik1
Ik1 – 1-phase short-circuit current
Positive sequence ~
Negative sequence
Zero sequence
3 ?U N
I k1 = 3 I 0 =
Z1 ? Z 2 ? Z0
Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 49
Power Transmission and Distribution ISPSE
Overhead lines
Cables
Oil cable 110 kV 0.8 ... 0.4 ? /km 0.4 ... 0.2 ? /km
XLPE cable 110 kV 0.6 ... 0.5 ? /km 0.3 ... 0.2 ? /km
Lead-sheath cable 20 kV 0.6 ... 0.4 ? /km 0.4 ... 0.3 ? /km
XLPE cable 20 kV 0.6 ... 0.4 ? /km 0.3 ... 0.2 ? /km
Lead-sheath cable 10 kV 2.0 ... 1.1 ? /km 0.5 ... 0.2 ? /km
XLPE cable 10 kV 3.2 ... 1.4 ? /km 0.9 ... 0.3 ? /km
P S
? ?
P S
?
Z PS
P S
P S
Z PS
P S
P S
Z PS
P S
?
P S
Z PS
P S
P S
Z PS
ZP ZS
P S
? ?
?
P S ZT
T
T
ZP ZS
P S
P S ZT
T
T
ZP ZS
P S
?
P S ZT
T
T
S
P S Z PS 3ZE
ZE
The numerical per unit value of any quantity is its ratio to the chosen base quantity of the same dimensions, expressed as a
Decimal. If the same value is multiplied by 100, it becomes the Per Cent value.
Note that the per unit and per cent values are dimensionless.
For example if base voltage is chosen as 30 kilovolts(kv), voltages of 20 kv, 30 kv and 45 kv become 0.67, 1.00 and
1.5 per unit respectively. Percent wise they become 67%, 100% and 150%
The performance of a whole line of apparatus (Transformers, machines etc.) regardless of its size can often be expressed
Another advantage of this method, is that it permits the comparison of the performance of apparatus of different ratings.
Normally voltage (kv) and kva (or mva) are chosen as the two independent base quantities.
Base power is then numerically equal to base kva(or mva). With these base quantities following
equations result :
For three phase equipment, rated kva(mva) is generally given for the three phases and rated voltage
Base kva per phase is 1/3 of the 3 phase kva and the base line to neutral voltage is base line to line
voltage divided by v 3 .
Base phase current in amperes = base kva per phase / base voltage line to neutral in kv. =
In Power systems, it is quite common that different components of the system have different
For short circuit calculations, it is necessary to use one common base system.
The following equations permit the conversion from one base to another.
per unit impedance on given kva base x new kva base / given kva base
Example for a Fault Calculation using Symmetrical components and per unit values (1)
Find the per unit values of the symmetrical components of current and voltage, the line currents and the line to ground
and the line to line voltages for a zero impedance fault on phase a of a generator with following data :
Example for a Fault Calculation using Symmetrical components and per unit values (2)
Solution :
= 0.258 – j3.468
Example for a Fault Calculation using Symmetrical components and per unit values (3)
Current in phase b V a1
I a1
Ib = ( a 2x Ia1 +a x ia2 + ia0 ) = Positive sequence ~ Ea
2
= Ia1 x ( 1 + a + a ) = 0
Current in phase c
0.05 + j 0.45
2
Ib = ( a x Ia1 +a x ia2 + ia0 ) = V a2
Negative sequence
2 I a2
= Ia1 x ( 1 + a + a ) = 0
Voltage of phase a
0.007 + j 0.06
Va = ( Va1 + va2 + va0 ) = 0 ( Faulted phase)
Zero sequence I a0
V a0
Voltage of phase b
2
Vb = ( a x Va1 +a x Va2 + Va0 ) =
= - 0.140 – j 0.964
Example for a Fault Calculation using Symmetrical components and per unit values (4)
Voltages (contd)
0.007 + j 0.35
Voltage of phase c
V a1
2 I a1
Vc = ( a x Va1 +a x Va2 + Va0 ) =
Positive sequence ~ Ea
= - 0.070 + j 0.973
Zero sequence I a0
V a0
Short Circuit –Current Waveforms for different Fault Locations and Fault Instants
t t
Network Faults
Fault at generator
terminals
SK“ = 32 GVA SK“ = 4.6 GVA SK“ = 350 MVA SK“ = 10 MVA
IK“ = 45 kA IK“ = 24 kA IK“ = 10 kA IK“ = 15 kA
bei 10 kV
Dahlem 20 kV SS Schmitz
WEA Reetz
Nato
~
Hallschlag SS1
UN = 20 kV
Dahlem 110 kV SS IK = 3,97 kA WEA
? K = 79,1° Collas
SK = 137,64 MVA
~
110 kV Netz
SK = 2,8 GVA 3,5 km NA2XSY
Kyllerberg
1x150mm²
Backes
Transformer
Network
Sk‘‘ • SN, uK Line
Z, l, UN
• •
Synchrongenerator
SN, xd‘‘ • „
S K in MVA
1,1 • 100 xd“ in %
XNetwork =
SK“
SN in MVA
xd“ „ 1,1 • 100
XSynchron. = SK = uK in %
SN ? X
Z in ? / km
uK „
XTransfor.. = „ SK l in km
SN IK =
3 • UN UN in kV
Z • l • 100
XLine = X in % / MVA
U²N
Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 65
Power Transmission and Distribution T PoweISPSE
r
s Example for Simplified Calculations in % / MVA
raini
Cent g
n
er
110 kV 20 kV
• •
Network Transformer Line
3 GVA 110/20 kV NA2XS2Y, 1x150mm2
30 MVA, uk=12% 3 km, Z=0,227 ? /km
1,1 • 100
Xnetwork = = 0,037 % / MVA
3000
„ 1,1 • 100
12 SK = = 181,2 MVA
XTrafo = = 0,400 % / MVA 0,607
30
„
IN .
„
SN.
100 100
Ik max = S k max =
u k [%] u k [%]
Example
Ratio Capacity uk I k max S k max
20 / 0,4 kV 400 kVA 4% 25 • I N 10 MVA
110 / 20 kV 30 MVA 12 % 8,33 • I N 250 MVA
380 / 110 kV 350 MVA 21 % 4,76 • I N 1670 MVA
L1
ZL IK IK
L1
U L2
L3
L3 L2 1 2
IL1
U
1 3 Ph. Fault IK = (100%)
3 • ZL IL3 IL2
U
2 2 Ph. Fault IK = (85%) IL2 IL1
2 • ZL
L1
ZL
L1
U L2
IK
L3
L3 L2 ZE
N
U
1. Ph Fault Four wire network I K = (50% assuming ZL = ZE)
3 • (ZL + ZE)
3•U
1. Ph Fault Three wire network IK =
(Zm + Zg + Z0)
kA
10
?„
Ik
5
5 10 15 20 km
Line length ?
110 kV
40 MVA 40 MVA
uK 12% uK 12%
20 kV
666 MVA
1.Phase Fault
IK
ZL
L1
U1
L2
L3 ? K
ZN IK
N
L1 In general :
U
IK =
3 • ? ZL + ZN ?
L3 L2
ZL
L1 U 23
L2 ? K
L3
IK
IK
L1
In general :
U
IK =
2 • ZL
L3 L2
ZL
L1
L2
L3
IK
ZE
L1 L1
3.Phase Fault
IK
ZL U1
L1
L2 ?K IK
L3
L1
In general :
U
IK =
3 • ZL
L3 L2
ZL
L1
L2
L3
IK
ZE
L1
L2
L3
IL2 , IM
1. Fault point
IL2 , IL3 L1
L2
L3
IL3 , IM
2. Fault point
ip
DC-Komponente 2 2 Ik
A
A
Zeit
Zeit
untere Einhüllende
untere Einhüllende
?
N [ ( 1 / X d – 1 / X d ) exp(- t / T
? ?
Ik= ?2 U d)
Topics
? Basics
? Transmission Tasks
? Transmission
? Distribution
? Reliability of Supply
? Compensation
? Synchronisation
? High Availability
? Low Losses
? Environmental friendly
? Low Costs
? Flexible
? Traction Networks
Remote Trains, Local Trains
? Special Networks
Airports, Hospitals, Laboratries, yards
380 kV
110 kV
10 kV
20 kV
0,4 kV
? State analysis
?New Structuring
? Retrofit oder Strenghthening
? Choice of Voltage level
? Switchgear Concept
? Comparison of alternatives
? Determination of Investment costs
? Layout of Protection Concepts
? Network calculations
? reduction of losses
? Training
? Solution of operational Problems
Planning Criteria
? n-1 Reliability
?€ Costs
? Availability of Trenches
? Network Dynamics
? Future Developments
? Power
? Sufficient
? Voltage
? Amount Umin < U < Umax
? Frequency fmin < f < fmax
? Symmetry U0 < U0,max Zero-sequence voltage
U2 < U2,max Negative-sequence voltage
? Harmonics Uh < Uh,max Harmonic voltages
Ih < Ih,max
? Reliability
Hu < Hu,max Frequency of breaks
Tu < Tu,max Duration of breaks
? Price
? Price to be as low as possible
10 kV to 110 kV networks
Ground-fault
having a large open-wire
compensation
portion
using a Petersen
coil
Low-resistance
neutral point 10 kV to 110 kV networks
grounding having a large cable
(curren- limiting Distribution networks
grounding)
P
V1 , ? 1 V2 , ? 2
G~ G~
X
V1 V2
P = ( 1 - ? 2)
sin (?
X
Power-Flow Control
Power Pe
Stable Operation Unstable Operation
The capability of synchronous machines to remain stable under the condition of small load changes
Since modern power systems do not just have one machine but many machines supplying a network,
The capability of synchronous machines or systems to remain stable under large impacts for example
equation : Pa = M d2 ? / dt 2
Pa = Accelerating power of the rotor = Mechanical Power Input Pm – Electrical Power Output Pe
Time in sec
Example of a typical swing curve
Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 95
Power Transmission and Distribution ISPSE
A2
4. Protection Principles
Faults on OHL
Atmospheric impact (lighting, ice,wind)
fast plant growth (trees, bush fires)
mechanical impact (cranes, planes)
Faults on cables
Isolation-flashover (i.e water in cable joints)
Thermical overload
Mechanical damage (i.e. shovel excavator)
Faults on transformers, CTs/VTs and Motors
Break down of the insulation (ageing, transient overvoltages)
Thermal overload
Faults on busbars
Short circuit caused by external elements (isolators falling down, exploded
CTs/VTs)
(in MV by animals)
Switching Errors (i.e. switch onto earth or switching off of the sectionalizers
under load)
Fault-Statistics
(VDEW fault- and damage statistics 1986)
60 % 31 % 51 % atmospheric impact
11 % 4% 4% external impact
2% 5% 8% internal impact
23 % 40 % 11 % no defined reason
Types of Faults
HV EHV
5% 1%
25 % 6%
70 % 93 %
Protection Zones
Protection Zones
1. Generator
2. Transformer
3. Busbar
4. Feeder
5. Motors
are protective relays within a given protection zone that should operate for
prescribed abnormalities within that zone.
Pickup Value 1) :
The minimum input that will cause a device to complete contact operation or
similar designated action.
Dropout 1) :
Power S P Q S(t)
Note : In numerical systems, only the
currents and voltages are the input signals.
Temperature ? ?> ? ? d?
Other measuring quantities are derived
dt
(calculated) from these two inputs
Bus Bar
+ -
DC Power Supply
from Station Battery
Note : Earthing Switches not shown Note : Other Binary Inputs and Outputs not shown
t [sec]
2.0
1.0
0.5
I Inverse
t [sec] D definite
2.0 M Minimum
T Time
1.5
L Lag
Characteristical curves:
?IEC
1.0 ?ANSI
?British Standard
0.5
L1
Definite Time
IL1
Tripping area
L2
IL2 OR - Inverse
- Very Inverse
L3 Inverse Time
IL3 - Extremely Inverse
- Long inverse
N
IN
0.14 .Tp
Inverse : t =
( I / I p ) 0.02 - 1
13.5 .Tp
Very Inverse : t =
( I/Ip)- 1
120 .Tp
Long Inverse : t =
( I/Ip)- 1
80 .Tp
Extremely Inverse : t =
( I/Ip)2- 1
8.9341
Inverse : t = ( 2.0938
+ 0.17966 ).D
( I/Ip) - 1
3.922
Very Inverse : t = ( 2
+ 0.0982 ).D
( I/Ip) - 1
5.6143
Long Inverse : t = ( 2.0938
+ 2.18592 ).D
( I/Ip) - 1
5.64
Extremely Inverse : t = ( 2-
+ 0.02434 ).D
( I/Ip) 1
Current
Current
I>> t
IL1
I> t
Direction
& TRIP
UL1
Currents
Calculation of Impedances
and
Voltages Comparison with the settings
U Load
L3
Positive sequence ~ U1 U F1
I2
Zs2 Z1
Zs1 : Positive sequence impedance of the infeed
Negative sequence U F2
U2
Zs2 : Negative sequence impedance of the infeed
I0
Zs0 : Zero sequence impedance of the infeed Zs0 Z0
Zero sequence U0 U F0
Z1 und Z0 : Positive (negative) and zero sequence
impedance of the line upto fault respy
I2
Zs2 Z1
Zs1 : Positive sequence impedance of the infeed
Negative sequence U F2
U2
Zs2 : Negative sequence impedance of the infeed
Relay Location
Z1 : Positive (negative) sequence
impedance of the line upto fault
Phase to Phase Fault
2 2
UL2 = a x U1 + a x U2 = a x (UF1 + I1 x Z1) + a x (UF2 + I2 x Z1)
UL3 = a x U1 + a 2 x U2 = a x (UF1 + I1 x Z1) + a 2 x (UF2 + I2 x Z1)
UL2 - UL3 = (a 2 – a ) x [ (UF1 - UF2) + Z1 x ( I1 - I2 ) ]= (a 2 – a ) x [ Z1 x ( I1 - I2 ) ]
IL2 - IL3 = (a 2 – a ) x ( I1 - I2 )
UL2 - UL3
= Z1 Impedance measured by the relay
IL2 - IL3
I2
Zs2 Z1
Zs1 : Positive sequence impedance of the infeed
Negative sequence U F2
U2
Zs2 : Negative sequence impedance of the infeed
I0
Z1 : Positive (negative) sequence Zs0 Z0
I2
Zs2 Z1
I0
UL2 / ( IL2 + IE x ZE / Z1 ) = Z1
Zs0 Z0
and
Zero sequence U0 U F0
UL3 / ( IL3 + IE x ZE / Z1 ) = Z1
Summarizing :
Relay Location
For a 2 phase to ground fault, the phase to phase loop of the faulty phases
as well as the phase to ground loops of the faulty phases measure the same
Impedance. 2 Phase to ground Fault
L3
I2 3RF
Zs2 Z1
Negative sequence U F2
U2
Relay Location
L3
Positive sequence ~ U1 U F1
Fault Resistance RF RF
I2
Zs2 Z1
Negative sequence U F2
U2
Relay Location
Impedance measured by the relay :
I2
Zs2 Z1
Impedance measured by the relay : Negative sequence
U2 U F2
3RF
UL2 - UL3 I0
= Z1
IL2 - IL3 Zs0 Z0
and
UL3 / ( IL3 + IE x ZE / Z1 ) = Z1 + 3 RF
Relay Location
IL1 ZL
ZL = RL + j XL
IL2
IL3
ZE = RE +j XE
IE ZE
Measured current
measured voltage
IL1 ZL
ZL = RL + j XL
IL2
IL3
ZE = RE +j XE
IE ZE
A B C
Z< Z< Z< Z<
Summary : 1 2 3 4
1. Both relays 2 and 3 measure the same
X Line C Line
impedance magnitude but different X
angles.
e
Voltag
2. In this example, the relay 3, which sees
the fault in the forward direction, measures
Fault
X
an impedance angle of 80 0 and relay 2 80 0
0.
80 0
measures an angle of - 100
B
e
R B
Voltag
R
Current as
3. Distance Relay 3 gives a trip command Current as reference
X
Fault
reference
to ist breaker, since fault in the forward 00 Z=U 00
Z=U
direction and relay 2 does not, since fault - 80 0
I 100 0 I
in reverse direction
Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 131
Power Transmission and Distribution ISPSE
Can we use the same signals for the six directional measuring loops ?
Can we use the same distance measuring signals for the six directional measuring loops ?
Current I Current I
F2 F1
A B C
Z< Z< Z< Z<
1 2 3 4
For a close in fault (Fault at the beginning of the line section ahead (F1) and behind the
relay location (F2) ) the voltage is almost zero.
Measurement of direction with the faulty voltage will not give a unique result.
Dis
tan
X1
ce
Ch
ara
cte
ris
tic
R1
R1E
Di
R
re
ct
io
na
l
Ch
ar
ac
te
ris
tic
grading time
(s)
0.6
0.3
X X X X X X X
X Circuit Breaker
Teleprotection Schemes
1 2
I o > Setting
Earth fault in
& Forward direction
Forward direction
Two Issues !
1. How to measure the direction ?
2. All the faults in the forward direction (beyond the line section) are measured without
selectivity
Current I Current I
F2 F1
A B C
Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 139
Power Transmission and Distribution ISPSE
Measure the angle between Io of the line and a reference (polarising) quantity.
The polarising signals are either the zero sequence voltage (from an open delta) or
the zero sequence current in the transformer neutral connected to the bus.
_ _ ?
F2 F2
A B A B
_
OR ? _
Zig-Zag Transformer Delta-Star Transformer
Note : In numerical relays, this open delta voltage can be calculated Source of polarizing current
Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 140
Power Transmission and Distribution ISPSE
Current I Current I
F2 F1
A B C
Transmit a signal to remote end
I o > Setting Earth fault in Phase selection and hence single pole
& Forward direction breaker opening not possible
using this method
Forward direction
Fault at F2 Fault at F1
-A sends a signal to B, indicating a forward fault
-Relay at end A sends a signal to B, indicating a forward fault
-Relay at end B sends a signal to A, indicating a forward fault -B sees a reverse fault and does not send any signal to A
- Relay C in the line BC sends a signal to B indicating a forward fault - C in the line BC sends a signal to B indicating a forward fault
- Relay B in line BC meaures a reverse fault and does not send a signal to C - B in line BC also sends a signal to C indicating a forward fault
- Line BC remains in service - Both the breakers in line BC trip
Trip
1st 2nd
t1 dead time t2 dead time tgrading
IC
IC
-I CX L
I CX VS VR
L
A VS VR B V S= V R + I CX L
Under light (no) load conditions or if the breaker at the remote end is open, the voltage at the remote end
is higher than the sending end voltage. Longer the line higher is this voltage .
The voltage has to be monitored and if it increases beyond a certain value, the breaker has to be opened.
A hole is in
the bucket! ?
I1 I2 I1 I2
Protected unit Protected unit
i1 i1
i2 i2
i1
? I> ? I=I1 - I2 ? I> ? I=I1 + I2
=0 i2
CT 1:
CT 2:
e1= - 5%
I P1 e2 = + 5% I P2 = -I P1
IF
Protected
object
I S2=
I S1= 1.05·I P2
0.95·I P1
I Diff= ¦ I S1+ I S2¦
IDiff
I Diff = 0.1·I P1
G M
Grid-
infeed Load
B1
A B C
Z< Z< Z< Z<
1 2 3 4
For a fault at F2, distance relays 1 and 2 give a trip command to the respective breakers.
If one of the breakers fails to open, all the breakers connected to the same bus section as the
faulty breaker have to be opened out to interrupt the fault current.
This breaker fail detection is done by breaker fail protection which is initiated by trip commands
of all the relays which trip the breaker.
Task of Breaker Failure Protection
I> :
CT current
50BF
To trip only the bus section,
& to which the bay with the faulty
Start BFP t2
breaker is connected!
ON
OFF
+ –
59 Overvoltage
59 25 79 ST = 25 Check synchronism
= 79 Autoreclosure
ST Control
21 Distance protection
21 FO M FR 49 FO Fault locator
FR Fault recorder
M Measurement
Back-up 85 67N 49 Overload
Protection 67N Earthfault determination
85 Teleprotection
Modem
opp.
line end
52 TC 52 TC
87 BB
B2
50 BF + - B2
B1
B1
+ -
87 L
21
VT Protection Group B
Protection Group A (Main 2 )
( Main 1 )
52 TC
87 BB
50 BF
B1
B1
+ -
21
VT
Protection Group A
( Main 1 )
? Rotating Machines
Generators (synchronous / asynchronous)
Motors (synchronous / asynchronous)
? Static Units
Transformers
Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 161
Power Transmission and Distribution ISPSE
G
Protection device has to be :
Internal Faults:
Stator: Rotor, Excitation circuit:
? Earth Faults ? Earth Fault
? Short Circuits (2- and 3 phases) (single, double)
? Interturn faults ? Underexcitation
(with split stator winding) (partly respec. complete)
? Overload ? Over voltage
? Over excitation (U/f)
External Faults:
Grid/Transformer: Turbine, Regulator:
? Earth Faults ? Loss of Prime mover
? Short Circuits (Reverse Power)
? Overload (Stator, Rotor) ? Over- and Under voltage
? Negative Phase Sequence ? Over- and Under Frequency
? Asynchronous operation ? Over Excitation (U/f)
(cap.Load, long fault duration) (Influenced by regulator)
? Torsionalstress
? Under frequency (PG < PU)
Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 164
Power Transmission and Distribution ISPSE
Short Circuits
A) Internal Faults
1) Isolated neutral 2) Low resistance
(or high resistance grounding) (or solidly grounded neutral)
L1
3phase short circuit
L2
L3
Single phase short
Interturn fault circuit
Phase to phase short circuit (Resistor limits the
fault current)
- t
2 ?? ' '
k ? k k
?
2 ? ?' - ? ?e T' d
2 ??
k
- t
2 ??' 'k ?e Tg
Driving Voltages U??p < U?p < Up
Short circuit current Subtransient part transient part Steady state DC - current
short circuit current
? t t t ?
? ? ? ?
? - - - ?
ik ? 2 ? I ' ' ? I ' ?e T' ' d sin?? t - ? ?? I ' - I ?e T' d sin?? t - ? ?? I sin?? t - ? ?? I' ' ?e Tg sin? ?
k k k k k k
? ?
? ?
Stator
Rotor +
Earth (ground) fault Excitation
in the rotor system
-
RE CE
? in case of an earth fault, only small currents flow due to non earthing
Problem:
Double earth faults and interturn faults as a consequence of an earth fault cause:
• magnetic unbalance
• high currents at the fault location
+ Coupling Voltage
Measuring Source
Unit
Excitation
system
-
„Earthing brush “
Methods:
- Coupling of an AC voltage (50 Hz or 60 Hz)
- Measuring of the earth fault current Higher
- Measuring of the earth fault resistance Sensitivity
- Coupling of low frequency square wave voltage
L1 L2 L3
Connection
to the earthing
brush
>40V
105? 4? F
IE,Stray IE
coordinated Relay
resonant circuit to fN
7XR6004
RV
Controlling device
IE (7XT71)
+
RV
-
UH Ucontrol
Excitation
Digital
CE RE Protection (7UM62)
RM Umeas.
RE Fault resistance
RV Coupling resistor
UH Auxiliary supply ( ? 50V) Measuring transducer
RM Measuring shunt resistor
CE Rotor capacitance
UH - 50V
CE RE
UM
RM UM
1,88V
? ?
RV
?CE
2 ? UM ? 0 RE ? ?
iE t
UM ? RM ?i E
RV - 1,88V
? 20k?
2 UM
RM ? 375 ?
? UM ~
1 RE ? 5k?
U H ? ? 50V 0,75V RE
t
- 0,75V
Turbine
• In both cases an active power is flowing from the network to the generator,
generator runs as a motor and drives the turbine
Turbine
Active power
P mach
steam turbine: (1 ? 3)%
Network
S N ,mach
G
P mach
gas turbine: (3 ? 5)%
iL1,iL2,iL3 uL1,uL2,uL3 S N ,mach
Negative Overheating
Physics:
sequence of the rotor
Results:
1. The negative sequence heats the rotor
2. This heating is the reason for using a thermal model
(differential equation first order)
3. The transient behaviour of such a thermal model is an exponential function
(For a step negative sequence, the temperature increases exponentially)
4. The curve, given by generator manufacturer, takes only into consideration
the heating but not the cooling. The simplest form of this curve is
(I2/IN)2 t = C.
5. It's necessary to calculate the parameters (k-factor and time constant)
from the generator manufacturer data
Formula 1: Formula 2:
[(I2/IN)2 - (K2)2] t = K1 [(I2/IN)2] t = K1
10000
Example:
1000 K1 = 10 s
Formula 1 K2 = 0.1
Formula 2
100
10
0 0.1 0.2 0.3 0.4 0.5 0.6
Unbalanced load
alarm stage I2>
t
T WARN
Tripping area
Thermal
tripping stage
Unbalanced load
tripping stage I2>>
Thermal
alarm stage
T >>TRIP
I2perm I2>> I2
GS excitation
3~ device
- Countermeasure:
Underexcitation Protection
0,975
0,975
0,95
0,95
0,85
0,9
0,8
0,9
MW
type of generator: TLRI 108/46
0,85 220
nominal apparent power SN = 200 MVA
nominal voltage VN = 15.750 kV
200 nominal current IN = 7.331 kA
nominal frequency fN = 50.0 Hz
power factor cos? N = 0.8
180 cold-air temperature Tx = 40.00 °C
0,7
0,8
160
140
0,7 0,6
120
0,6 100
80
0,4
60
0,4
40
0,2
cosphi
cosphi
0,2
Q
MVAr 140 120 100 80 60 40 20 0 20 40 60 80 100 120 140 160 180 MVAr
underexcited overexcited
turbine limit
steady P
state stator limit
dynamic stability
stability limit
limit
theoretically
limit VP If
SN rotor limit
?N
?N
Q
2
VN
VN
2 Xd
? ; ? SN Xd: synchronous reactance
X 'd
X‘d: transient reactance
underexcited overexcited
P [p.u]
1 U=1; I=1;
0.85
U=0.9; I= 1.11
Stability
limit
overexcited
under-excited
Q [p.u]
0.81/xd
1/xd
Definitions for Converting the Generator Diagram into the Admittance Diagram
Conversion:
?
I ?V S* P - jQ P Q
Y? ?
? ? ? - j
V ?V V2 V2 V2 V2
In the per unit
+ P + G
representation
P
G? the diagrams are
V2 the same, only
Q there is a phase
B? - 2
Q V B shift in the reactive
+ +
part of 180°
Note: in the per unit calculation is VN = 1
1 1 1 ? 0.9 ? 1
x d1 ? x
1 2
? 1 = 80° x
d2
x
d1
? 2 = 90° x d3 ? 1 or ? x d ? 3 = 100° or 110°
d
Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 185
Power Transmission and Distribution ISPSE
13472 A
0.748 A
18000/1A CT Setting: 30000A
Impedance Protection
tNetz +? t
I>
Z 1 ? 0,7X T
Z<
0,1s
Z1
G
XG XT
Z<
ZG ZT
ZL
I > (ZG)
t ZT (backward)
ZG
ZL
Z
2. Stage (ZT) ZT
1. Overvoltage
The result of a overvoltage is
LM a higher magnetizing current
2. Underfrequency
A low frequency increases
the magnetizing losses
1 U
Induction: B=
4.44 w A f
w - windings
A - cross section Thermal overheating of iron
BS U/UN
~
BN f/f N A thermal model is required
Tripping area
Thermal
tripping stage
Definite time
tripping stage U/f>
Thermal
warning stage
TU/f>
Xd XTr
Stiff system
XN U= const.
Tm ?
Protection
1. If generator feeds into the short circuit too long, the rotor accelerates
and the permissible angle ? perm.exceeds the limit
2. Active power swings appears after the clearing of the short circuit,
because the generator had fallen out of step
Measuring point
X’d Protection X
T XN
R
'
UN U 'N - jd
Z ? ZG ? ZT ? Z N '
? ' e
ZG Generator UP UP
impedance
ZT Transformer- ? Z
impedance ZR ? '
- ZG
U ZR = f(?)
ZN Network 1 ? N' e - jd
impedance UP
ns
Protection
io
at
tu
Si
Measuring Principle of Inadvertent Energization Protection (ANSI 50/27 - IEC I> and U<)
? Generator Breaker
? Excitation Breaker
Breakers
? Turbine Rapid Shut Down
Protection Functions
? HV Network Breaker
? Auxiliary Supply Breaker 1
? Auxiliary Supply Breaker 2
? Aux. Supply Changeover
? SEE/SFC, Unit-trafo
? SEE/SFC, Aux.-Trafo
? Reserve
? Special Trips at Hydro
Stations (e.g. braking)
7UM6 7UM6
7UM62
7UM62
7UM61
G
G