Tce in 2.1

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 199

Initiative for Spreading Power System Education (ISPSE)

Faults , Stability and Protection Principles

Dr. A. Kumar

EA Training,Siemens AG
Power Transmission and Distribution ISPSE

1. DC and AC Networks

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 2
Power Transmission and Distribution ISPSE
Currents, Voltages and Power in DC Systems (1)

a ) Resistance Circuits a ) Inductive Circuits

I I

DC Voltage Source
L
R DC Current Source U
U
Example : Battery

Voltage = U = L* di = 0 (Since Current is Constant )


Current = I = U (Ohms Law)
dt
R
2 Power = U * I = 0
Power = U * I = I R

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 3
Power Transmission and Distribution ISPSE

Currents, Voltages and Power in DC Systems (2)

c ) Capacitive Circuits

I
DC Voltage Source Summary for cases (a) to (c) :
C U 1. Only in Resistive circuits, the power is non zero.
Example : Battery In Inductive and Capacitive circuits, the power is
zero.
2. Currents in inductive circuits cannot change
instantenously
3. Voltages across capacitances cannot change
instantenously
Current = I = C* dU = 0 (Since Voltage is Constant )
dt
Power = U * I = 0

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 4
Power Transmission and Distribution ISPSE

Transients in DC Systems (1)

a ) RL Circuits
U / R
U
R
Voltage Current i
I
DC Voltage Source

U L
Example : Battery
Time Time

Voltage across
Voltage = U = R * i + L* di inductance
dt
-t/T
Current = i = U ( 1 – e )
R
Time
T = L / R = Time Constant of the circuit

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 5
Power Transmission and Distribution ISPSE

Transients in DC Systems (2)

a ) RC Circuits

R
U U / R

i
Voltage
Current i
DC Voltage Source

U C
Example : Battery

Time Time

U
t
1
Voltage = U = R * i +
C ?I * dt Voltage across
0 capacitance
-t/T
Current = i = U * e
R
T = R*C = Time Constant of the circuit Time

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 6
Power Transmission and Distribution ISPSE
Transients in DC Systems (3)

a ) RLC Circuits

R
U
i
Voltage
DC Voltage Source

U C
Example : Battery
L
Time

t Time constant = 2 L / R
1
Voltage = U = R * i + L di / dt +
C ?I * dt
Current
-t/2?
0
Sin ( ? ? 2 - 1 / 4 ? )
Current = i = U * 1 * 1 2
? e t
?
R
1/4?
2
? 2
- t
TT= =2L / R == Time
R*C Time Constant
Constantof
ofthe
the circuit
circuit

?? == ?? 11/ LC
/ LC == angular
angularfrequency
frequencyofofthe
thecircuit
circuit

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 7
Power Transmission and Distribution ISPSE
Transients in DC Systems (4)

a ) LC Circuits

L
U
i
Voltage
DC Voltage Source

U C
Example : Battery

Time

t
1
Voltage = U = L di / dt +
C ?I * dt
0

Sin ?
Current = i = U *
t Current

? L/C

T = R*C = Time Constant of the circuit


t

?? == ?? 11/ LC
/ LC == angular
angularfrequency
frequencyofofthe
thecircuit
circuit

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 8
Power Transmission and Distribution ISPSE

Currents and Voltage Phasors in AC Systems (1)

u
a ) General Concepts
?

u= 2 U cos ( ? t + ? ) I

ACVoltage Source

Example : AC Generator
~ Z u
Period = T

Voltage in Time Domain

Imaginary
Note : j is an operator
U 2 which rotates the phasor
Period T = 1 / f seconds ( f = frequency in Hertz) by 90 0 in the positive direction
?
Angular velocity of the phasor = ? = 2 p f = 2 p / T radians / Second Real
Voltage as a Phasor

Example : f = 50 Hz (Hertz) J?
u = U 2 e Note : j = -1
Period T = 1 / f = 0.02 seconds = 20 milliseconds
Angular velocity ? = 2 p f = 314.16 radians per second =U 2 ( Cos ? + j Sin ? ) = u1 + j u 2

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 9
Power Transmission and Distribution ISPSE

Currents and Voltage Phasors in AC Systems (2)

b) Effective and Average Values of Voltage and Current Phasors

u= 2 U cos ( ? t + ? )
Effective (Root Mean Square) value of a Phasor

T
2
Laut definiton RMS value is =
?
1 / T u dt
0

For a sinusoidal signal u, the RMS value using the integral above is = U

Average (mean) value of a Phasor


T/2
Laut definiton Average value is = 2/T ?u dt
0

For a sinusoidal signal u, the average value using the integral above is = 2 U 2 / p

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 10
Power Transmission and Distribution ISPSE

Currents and Voltage Phasors in Resistive Circuits

Imaginary
I

u= 2 U cos ( ? t + ? )
~ R u
I

?
U

Real

Voltage and Current as Phasors

Current i u = i . R = u1 + j 0

i= u/R = 2 U cos ( ? t + ? )
R

Result : Current and Voltage are in phase

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 11
Power Transmission and Distribution ISPSE

Currents and Voltage Phasors in Inductive Circuits

Imaginary
I

u= 2 U cos ( ? t + ? )
~ X u
?
U

0
Real
90

Current i I
Voltage and Current as Phasors
0
i= 1/L
?u dt = 2 U cos ( ? t + ? - 90 ) u = L di / dt = 0 + j ? L i
?L
Note : ? L = X and is called the inductive reactance
L

Result : Voltage across the inductance leads the current through the inductance by 90 0

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 12
Power Transmission and Distribution ISPSE

Currents and Voltage Phasors in Capacitive Circuits

Imaginary
I

u= 2 U cos ( ? t + ? )
~ XC u
I
90
0

?
U

Real

Voltage and Current as Phasors


Current i
=0+ i/ j? C
0
?
u =1 / c i dt

i = C dv / dt = 2 ? C U cos ( ? t + ? + 90 )
Note : ????? ?C = X and is called the capacitive reactance
C

Result : Voltage across the capacitance lags the current through the capacitance by 90 0

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 13
Power Transmission and Distribution ISPSE

Currents and Voltage Phasors in R,L,C Circuits

Imaginary
R XL

I
iXL

u= 2 U cos ( ? t + ? )
~ XC i X L- i X
C
? i

iR Real
iXC

u= i[R + j( X - X )] Phasor diagrams of voltages and current


L C
= iZ

j?
Z is called the complex impedance and is written as Z e

Z Is the modulus of the impedance and ? is the angle of the impedance

Note : R = Z Cos ? and


( X - X ) = Z Sin ?
L C

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 14
Power Transmission and Distribution ISPSE

Resonance in AC Networks (1) : Series Resonance

ZZ==[ [RR++j j( ( XX - - XX ) )] ]
LL CC
R XL

I If X L = X C , Z If=XRL = X C , Z = R
Current
Current is
is limited
limited only
only byby the
the resistance.
resistance.
u= 2 U cos ( ? t + ? )
~ XC This
Thiscondition
conditionisiscalled Series
calledseries Resonance
Resonance

At resonance ? ?L = 1 / ? ?C
f = ( 1 / 2 ? ) * ? 1 / LC

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 15
Power Transmission and Distribution ISPSE

Resonance in AC Networks (2) : Parallel Resonance

I Z = [ R + j X L * X C / ( X L - X C) ]

R If X L = X C , ZIf=XRL = X C , Z = ?
CurrentVoltage
is limited = IZ is very
only high.
by the resistance.
i= 2 I cos ( ? t + ? )
~ XL XC This
Thiscondition
conditionisiscalled
calledseries Resonance
Parallel Resonance

At resonance ? ?L = 1 / ? ?C
f = ( 1 / 2 ? ) * ? 1 / LC

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 16
Power Transmission and Distribution ISPSE

Excercise : Calculation of various values in a RLC-Network

R = 30 O L = 95.493 mH
C = 25.385 µ F
V = 100 v 2 sin ? t ~
f = 50 Hz

Calculate :
1. RMS- Value of the current
2. Maximum value of the current
3. Angle between the source voltage and the current
4. Resonant frequency of the network
5. Time constant of the network
6. Power loss in the resistance

Also draw the phasor diagram of the current and voltages across the resistance, inductance and capacitance

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 17
Power Transmission and Distribution ISPSE

Alternating Current and Voltage on a Complex Plane

UR UX

im re
U U I
Reference : Current
I re im

im re
U U I
Reference : Voltage
re im
I

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 18
Power Transmission and Distribution ISPSE

Derivation of the Power of an Alternating-Current System

The instantaneous power p(t) of an electric system is the product of voltage u (t) and current i (t)
p(t) = u(t ) ?i(t) (Equ. 3.34)
Assume that:
? The current and voltage are sinusoidal
? There is only one frequency (no harmonics)
then following applies :
p ?t ? = u ?t ?? i ?t ? = 2 U 2 I cos ( ? t + ? u ) cos ( ? t + ? i ) (Equ. 3.35)

??cos ( ? ? ? ) ? cos ( ? ? ? ) ?
1
with cos ? ?cos ? ? (Equ. 3.36)
2
? ?
p ?t ? = U I ?cos ( ? u ? ? i ) + cos ( 2 ? t + ? u + ? i ) ? (Equ. 3.37)
?? ??konstant
? ? ?? ? ? ? ? ? ? ? ?? ?
? pulsierend mit doppelter
constant pulsating with double frequency nz ?
a networkNetzfreque

The average of this power is called effective power.


t? T
1
T ?
P? p(t)dt
(Equ. 3.38a-c)
t

? U ?I ?cos ( ? u ? ? i ) with ? u-? i = ?


? U ?I ?cos ?
Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 19
Power Transmission and Distribution ISPSE

Definition of Electrical Power

p(t) = um• sin ? t • im• sin (? t + ? )

? = 0° ? = 60° ? = 90°
u, i
u, i u, i

t t t

p(t) p(t) p(t)

t t t

Active Power Active and Reactive Power Reactive Power

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 20
Power Transmission and Distribution ISPSE

Power-Related Terms

Complex apparent power S ? U ?I* Electrical behaviour (Equ. 3.50)

Apparent power S ? U ?I Thermal design (Equ. 3.51)

Active power P ? Re? U ?I *? ? S ?cos ? (Equ. 3.52)

Reactive power Q ? Im? U ?I *? ? S ?sin ? (Equ. 3.53)

Complex alternating power S ~ ? U ?I Mechanical design (Equ. 3.54)

P
Power factor cos ? ? (Equ. 3.55)
S
P
Loss factor tan ? ? (Equ. 3.56)
Q

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 21
Power Transmission and Distribution ISPSE

Representation of Power Terms by Vectors

Reactive
current = Active current

Since
S ? U ?I *
? U ?(I w ? jI b ) (Equ. 3.57)
what applies is
Qind ? 0
Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 22
Power Transmission and Distribution ISPSE

Representation of Power p(t) in the Complex Plane

Im
S S ? U Ie j2 ? t
2?

S~ = U I
???
i

?u ? ?i

-? i S = U I* = P + jQ
U
Q
?
I
? ? ?u ? ?i ?u ?i
P Re

p( ? t ? 0 )

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 23
Power Transmission and Distribution ISPSE

Signs of Power and Reactive Power in the 4 Quadrants of the Complex Plane

(+) Active Power (+) Active Power


re
(-) Reactive Power (+) Reactive Power
U
im I

(-) Active Power (-) Active Power


(-) Reactive Power (+) Reactive Power

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 24
Power Transmission and Distribution ISPSE

Active-, Reactive- und Apparent Power (1)

P = U • I • cos ? S
100
%
Q = U • I • sin ? 75

50 Q P
S = U•I 25

0
S = P² + Q² 0° 15° 30° 45° 60° 75° 90°
?

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 25
Power Transmission and Distribution ISPSE

Active-, Reactive- and Apparent Power (2)

Q = S² - P²

p(t) p(t) p(t)

P S Q
P

t t t

Current and Voltage Angle 60° between Angle 90° between


Current and Voltage Voltage and Current
In Phase

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 26
Power Transmission and Distribution ISPSE

Notation for the Three-Phase AC System

Abbreviations:
1 3 Note : a is an operator
a = e j120 ? = cos 120 ? + j sin 120 ? = - ? j
2 2 which rotates the phasor
by 120 0 in the positive direction
1 3
a = e j240 ? = cos 240 ? + j sin 240 ? = - ? j
2

2 2 I L3 Im
(Equ. 3.67 a-b) 240°
240°
Following is valid: 120°

1 + a + a = 1 + e j120 ? + e j240 ? = 0
2

-240°
(Equ. 3.68) I L1 Re
If abbreviations are used following results: -120°

IL1 = I
IL2 = I ?a
2
I L2
IL3 = I ?a (Equ. 3.69 a-c)

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 27
Power Transmission and Distribution ISPSE

Three-Phase AC System

i
iL1
L1 iL2
L2 iL3 here: ? = 0
L3

e-j240°

- j120 2 0 0 1
e = a = cos 120 - j Sin 120 = - 0.5 – j 0.866
- j240 0 0
e = a = cos 240 - j Sin 240 = - 0.5 + j 0.866 e-j120°
iL1(t) = î ?cos ( ? t + ? ) IL1 = I

iL2 (t) = î ?cos ( ? t + ? - 120 ?) IL2 = I ?e - j120 ? =
2
a I with I? ?e j ?
2
iL3 (t) = î ?cos ( ? t + ? - 240 ?) IL3 = I ?e - j240 ? = a I
(Equ. 3.65a-c) IL1 ? IL2 ? IL3 = I ?(1 ? e - j120 ? + e - j240 ? )
?0
2
= 1+a + a (Equ. 3.66a-e)
Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 28
Power Transmission and Distribution ISPSE

Three Independent Single-Conductor Systems

UL1
IL1 = UL1 / ZL1 ZL1 UL1
IL1 = UL1 / ZL1 ZL1

UL2
IL2 = UL2 / ZL2 ZL2 UL2
IL2 = UL2 / ZL2 ZL2

UL3
IL3 = UL3 / ZL3 ZL3 UL3
IL3 = UL3 / ZL3 ZL3

I0 = IL1 + IL2+ IL3 = 0?


Voltage Customer
source

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 29
Power Transmission and Distribution ISPSE

Change from Single-Conductor Systems Over to a Three-Phase AC System

If it can be proved that


I L1 = I
I L2 = I ? a
2

I L3 = I ? a (Equ. 3.70a-c)
the back conductor, which has remained, can also be omitted without no need to vary
the electrical properties of the system.
UL1 IL1 = UL1 / ZL1 ZL1
A simple solution is:
UL1 = U
UL2 IL2 = UL2 / ZL2 ZL2
UL2 = U ? a
2

UL3 = U ? a (Equ. 3.71a-c)


UL3 IL3 = UL3 / ZL3 ZL3
and ZL1 = ZL2 = ZL3 (Equ. 3.72)

? Symmetric three-phase AC system


U0 = 0

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 30
Power Transmission and Distribution ISPSE

Power Types in the Three-Phase AC Network

Complex apparent power


UL1 L1 S ? U L 1 ?IL 1* ? U L 2 ?IL 2 * ? U L 3 ?IL 3 *
S ~ ? U L 1 ?IL 1 ? U L 2 ?IL 2 ? U L 3 ?IL 3
UL2 L2
Symmetry
(Equ. 3.77), (Equ. 3.78)
U L1 = U
UL3 L3 U L 2 = U ?a
2

U L 3 = U ?a (Equ. 3.79a-c)
IL1 IL2 IL3
I L 1 = I ?e j ? i I L 1* = I ?e ? j ? i
ZL1 ZL2 ZL3
IL 2 = I ?a ?e j? i
2
IL 2 * = I ? a ? e ? j ? i
IL 3 = I ?a ?e j? i IL 3 * = I ?a ? e ? j? i
2

(Equ. 3.80a-c), (Equ. 3.81a-c)


S = U ?I ?e -j ? i + a ?a ?U ?I ?e -j ? i + a ?a ?U ?I ?e -j ? i
2 2

= 3 ?U ?I ?e -j ? i
= 3 ?(P ? jQ) = constant (Equ. 3.82a-c)
S ~ = U ?I ?e j? i + a ?a ?U ?I ?e j? i + a ?a ?U ?I ?e j ? i
2 2

= U ?I ?e j? i (1 ? a ? a )
2

= 0 ! (Equ. 3.83a-c)

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 31
Power Transmission and Distribution ISPSE

Power types in Symmetric Three-phase AC System

Apparent power
S ? 3 ?U? ?I (Equ. 3.84)

? 3 ?U? ?I (Equ. 3.85)

Effective power
P ? 3 ?U? ?I ?cos ? (Equ. 3.86)

? 3 ?U? ?I ?cos ? (Equ. 3.87)

Reactive power
Q ? 3 ?U? ?I ?sin ? (Equ. 3.88)

? 3 ?U? ?I ?sin ? (Equ. 3.89)

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 32
Power Transmission and Distribution ISPSE

Active-, Reactive- und Apparent Power (1)

P = 3 • U • I • cos ? S
100
%
Q = 3 • U • I • sin ? 75

50 Q P
S = 3 •U•I 25

0
S = P² + Q² 0° 15° 30° 45° 60° 75° 90°
?

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 33
Power Transmission and Distribution ISPSE
Benefits of Three-Phase AC Systems as Compared to Single-phase or Direct Current Systems

? Savings of material

? No alternating current powers

? Revolving and no pulsating magnetic fields

? Transformation readily possible on various voltage levels


Large transmission distances at low losses

? Two voltage levels are at the customer‘s disposal

? The system can be broken up into three single-phase systems at any time

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 34
Power Transmission and Distribution ISPSE

2.Symmetrical Components and Short Circuit


Calculations

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 35
Power Transmission and Distribution ISPSE

Why Symmetrical Components ?

? A Power System is in a balanced state most of the time


i.e. the currents and voltages in all the three phases are
equal in magnitude and the angle between the phases is
equal to 1200

? During system faults (Short circuits and open circuits) and unbalance load
conditions, the magnitudes and angles may not be equal

? A mathematical tool is required to analyze the behaviour of the power


system during such disturbances. Symmetrical components are one
such tool

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 36
Power Transmission and Distribution ISPSE

What are Symmetrical Components ? (1)

Basic Approach

Any phasor of a three phase system can be represented as a linear combination


of three arbitrary phasors :

AR a1 a2 a3 A1
As ? b1 b? b? A2
AT c1 c2 c3 A3

System Phasors Arbitrary Arbitrary


coefficients Phasors

In the year 1918, C.L.Fortescue of Westinghouse presented a paper


at a AIEE-meeting and presented his symmetrical components

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 37
Power Transmission and Distribution ISPSE

Network Calculation - Symmetrical Components

U1L1

U1 1 a a2 U L1
1
U2 ? 3 1 a2 a UL2
U0 1 1 1 UL3 U1L3 U1L2
1
UL1 Positive sequence U1 = (U + a UL2+ a² UL3)
3 L1
U2 L1

U2 L2 U2 L3
UL3 1
UL2 Negative sequence U2 = (U + a² UL2+ a UL3)
3 L1
U L1 1 1 1 U1
UL2 ? a2 a 1 U2
UL3 a a2 1 U0 U0 L1
1
Zero sequence U0 = (U + UL2 + UL3)
3 L1
Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 38
Power Transmission and Distribution ISPSE

Advantages of Symmetrical components

? Positive and negative sequence networks are balanced three phase


systems and hence easy to handle

? Zero sequence network is a single phase system and hence calculations


are simple

? Calculations with sequence components can be made independently


and the results combined to get back the system phasors

Note : Symmetrical Components cannot be used if the input signals


have more than one frequency

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 39
Power Transmission and Distribution ISPSE

Display Methods for System Values

UL1 UL1
UL1(t) = ÛL1 sin? t
t
t Mathematical
equations

Time characteristic Vector(Phasor) display

Positive sequence
Negative sequence
UL1
Zero sequence

Phase-related display
Symmetrical components

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 40
Power Transmission and Distribution ISPSE

Symmetrical Component Networks

0 0
I Z
m m m g g g
U I Z U I Z
~ ~ • •
• ~ • • ~ • • •
~ ~ 0 3I
0
U ~
Positive Sequence Network Negative Sequence Network
Zero Sequence Network
m g 0
U U 0
U
m g
Z = m Z = Z = 0
g
I I I
m
Note : Only U is nonzero, since electrical generators produce only positive sequence
g 0
voltages. Hence U and U are = 0

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 41
Power Transmission and Distribution ISPSE

Equivalent Circuits for Positive, Negative and Zero Sequence Systems

Since positive and negative sequence networks are symmetrical and


zero sequence network is a single phase system, the following
equivalent circuits result

m m
I m m qm m m
qm Z U U = U - Z • I
U ~

g g g g qg g g g g
qg Z I U U = U - Z • I = - Z • I
U ~
=0

0 0 q0 0 0 0 0
q0 0 I U
0
U = U - Z • I = - Z • I
U ~ Z
=0

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 42
Power Transmission and Distribution ISPSE

Fault Current Calculations : Line to Line Faults

Positive sequence ~

Negative sequence

No Zero sequence

UN
I =
k2
Z1 ? Z 2
Note : U N is the line to line Voltage

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 43
Power Transmission and Distribution ISPSE

Fault Calculations : 3-Phase Faults

Positive sequence ~

No Negative sequence and


Zero sequence
UN
IK =
3 ?Z
Note : U N is the line to line Voltage

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 44
Power Transmission and Distribution ISPSE

Fault Current Calculations :Double Line to Ground Faults

Positive sequence ~

Negative sequence

2
-j U N [(1 + a ) Z 2 + Z 0 ]
IS =
Zero sequence
Z1 Z 2 ? Z 2 Z 0 ? Z1 Z 0

j UN [(1 + a ) Z 2 + Z 0 ]
IT =
Z1 Z 2 ? Z 2 Z 0 ? Z1 Z 0 Note : U N is the line to line Voltage

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 45
Power Transmission and Distribution ISPSE

Fault Current Calculations : Single Line to Ground Faults

Positive sequence ~

Negative sequence

Zero sequence

3 ?U N
I k1 = 3 I 0 =
Z1 ? Z 2 ? Z0
Note : U N is the line to line Voltage

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 46
Power Transmission and Distribution ISPSE

Vector Diagram for Solidly Grounded Systems

UL1

UL1 = 0

UL2 UL2

Normal operation 1-phase short circuit

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 47
Power Transmission and Distribution ISPSE

Low-Impedance Neutral Grounding

Ik1
Ik1 – 1-phase short-circuit current

Low-impedance neutral earthing

?Transient overvoltages for earthing via resistor kt ? 1.8


?Voltage rise of the fault-free phases cf ?
?Ik1 = f (Neutral impedance, fault location) 3 Ik1 ? ? Ik3
?Selective fault clearing

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 48
Power Transmission and Distribution ISPSE

Fault current calculation : Low-Impedance Neutral Grounding

Positive sequence ~

Negative sequence

Zero sequence

3 ?U N
I k1 = 3 I 0 =
Z1 ? Z 2 ? Z0
Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 49
Power Transmission and Distribution ISPSE

Examples for Zero-Sequence Impedances of Lines

Line type Voltage level Zero sequence Zero sequence


resistance R'0 reactance X'0

Overhead lines

110 kV 0.4 ... 0.2 ? /km 1.0 ... 1.5 ? /km


20 kV 0.6 ... 0.2 ? /km 1.5 ? /km
10 kV 0.6 ... 0.2 ? /km 1.6 ? /km

Cables

Oil cable 110 kV 0.8 ... 0.4 ? /km 0.4 ... 0.2 ? /km
XLPE cable 110 kV 0.6 ... 0.5 ? /km 0.3 ... 0.2 ? /km

Lead-sheath cable 20 kV 0.6 ... 0.4 ? /km 0.4 ... 0.3 ? /km
XLPE cable 20 kV 0.6 ... 0.4 ? /km 0.3 ... 0.2 ? /km

Lead-sheath cable 10 kV 2.0 ... 1.1 ? /km 0.5 ... 0.2 ? /km
XLPE cable 10 kV 3.2 ... 1.4 ? /km 0.9 ... 0.3 ? /km

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 50
Power Transmission and Distribution ISPSE

Zero Sequence Equivalent Circuits for Transformers (1)

P S
? ?
P S

?
Z PS

P S
P S
Z PS

P S
P S
Z PS

P S
?

P S
Z PS

P S
P S
Z PS

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 51
Power Transmission and Distribution ISPSE

Zero Sequence Equivalent Circuits for Transformers (2)

ZP ZS
P S

? ?
?
P S ZT
T
T
ZP ZS
P S
P S ZT
T
T
ZP ZS
P S
?

P S ZT
T
T

S
P S Z PS 3ZE
ZE

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 52
Power Transmission and Distribution ISPSE

Per Cent and Per Unit Values (1)

Definition of a Per Unit and Per Cent value

The numerical per unit value of any quantity is its ratio to the chosen base quantity of the same dimensions, expressed as a

Decimal. If the same value is multiplied by 100, it becomes the Per Cent value.

Note that the per unit and per cent values are dimensionless.

For example if base voltage is chosen as 30 kilovolts(kv), voltages of 20 kv, 30 kv and 45 kv become 0.67, 1.00 and

1.5 per unit respectively. Percent wise they become 67%, 100% and 150%

Advantages of this form of representation

The performance of a whole line of apparatus (Transformers, machines etc.) regardless of its size can often be expressed

By a sigle set of constants.

Another advantage of this method, is that it permits the comparison of the performance of apparatus of different ratings.

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 53
Power Transmission and Distribution ISPSE

Per Cent and Per Unit Values (2)

Single Phase Systems

Normally voltage (kv) and kva (or mva) are chosen as the two independent base quantities.

Base power is then numerically equal to base kva(or mva). With these base quantities following

equations result :

Base current in amperes = base kva / base voltage in kv.


2 3
Base impedance in ohms = base voltage in volts / base current in amperes = (base kv) x 10 / base kva

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 54
Power Transmission and Distribution ISPSE

Per Cent and Per Unit Values (3)

Three Phase Systems

For three phase equipment, rated kva(mva) is generally given for the three phases and rated voltage

is line to line voltage.

Base kva per phase is 1/3 of the 3 phase kva and the base line to neutral voltage is base line to line

voltage divided by v 3 .

Base phase current in amperes = base kva per phase / base voltage line to neutral in kv. =

3 phase base kva / base line to line voltage x v 3


2 3
Base impedance in ohms = ( base line to line voltage in kv ) / base 3 phase kva x 10

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 55
Power Transmission and Distribution ISPSE

Per Cent and Per Unit Values (4)

Change in Base values

In Power systems, it is quite common that different components of the system have different

specified base quantities.

For short circuit calculations, it is necessary to use one common base system.

The following equations permit the conversion from one base to another.

Per unit impedance on new kva base =

per unit impedance on given kva base x new kva base / given kva base

Per unit impedance on new kv base =


2
per unit impedance on given kv base x ( given kv base / new kv base)

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 56
Power Transmission and Distribution ISPSE

Example for a Fault Calculation using Symmetrical components and per unit values (1)

Find the per unit values of the symmetrical components of current and voltage, the line currents and the line to ground

and the line to line voltages for a zero impedance fault on phase a of a generator with following data :

Generator ratings : 15000 kva, 13.8 kv

Positive sequence impedance : 0.007 + j 0.35 per unit

Negative sequence impedance : 0.05 + j 0.45 per unit

Zero sequence impedance : 0.007 + j 0.06 per unit

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 57
Power Transmission and Distribution ISPSE

Example for a Fault Calculation using Symmetrical components and per unit values (2)

Solution :

The given conditions are

Ea = 1.0; Z1 = 0.007 + j 0.35 ; Z2 = 0.05 + j 0.45 0.007 + j 0.35

and Z0 = 0.007 + j 0.06 V a1


I a1
Positive sequence Ea ~
Ia1 = Ia2 = Ia0 = 1.0 / (Z1 + Z2 + Z0)
0
= 1.160 85.7 = 0.086 – j 1.156
0.05 + j 0.45
Va0 = - Ia0 x Z0 = -0.070 + j0.003
Negative sequence V a2
I a2
Va2 = - Ia2 x Z2 = -0.524 - j0.022

Va1 = Ia1 x ( Z2 + Z0 ) = 0.594 - j0.022 0.007 + j 0.06

Line Currents : Zero sequence V a0


I a0
Current in phase a Ia = Ia1 + ia2 +ia0 = 3 x Ia1

= 0.258 – j3.468

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 58
Power Transmission and Distribution ISPSE

Example for a Fault Calculation using Symmetrical components and per unit values (3)

Line Currents ( contd) : 0.007 + j 0.35

Current in phase b V a1
I a1
Ib = ( a 2x Ia1 +a x ia2 + ia0 ) = Positive sequence ~ Ea

2
= Ia1 x ( 1 + a + a ) = 0

Current in phase c
0.05 + j 0.45
2
Ib = ( a x Ia1 +a x ia2 + ia0 ) = V a2
Negative sequence
2 I a2
= Ia1 x ( 1 + a + a ) = 0

Voltage of phase a
0.007 + j 0.06
Va = ( Va1 + va2 + va0 ) = 0 ( Faulted phase)
Zero sequence I a0
V a0
Voltage of phase b
2
Vb = ( a x Va1 +a x Va2 + Va0 ) =

= - 0.140 – j 0.964

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 59
Power Transmission and Distribution ISPSE

Example for a Fault Calculation using Symmetrical components and per unit values (4)

Voltages (contd)
0.007 + j 0.35
Voltage of phase c
V a1
2 I a1
Vc = ( a x Va1 +a x Va2 + Va0 ) =
Positive sequence ~ Ea

= - 0.070 + j 0.973

Line to line Voltages


0.05 + j 0.45
Vab = Vb – Va = - 0.140 – j 0.964
Negative sequence V a2
Vbc = Vc – Vb = 0.070 + 1.937 I a2

Vca = Va – Vc = 0.070 – j 0.973


0.007 + j 0.06

Zero sequence I a0
V a0

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 60
Power Transmission and Distribution ISPSE

Short Circuit –Current Waveforms for different Fault Locations and Fault Instants

Fault at voltage maximum Fault at voltage zero

Minimum DC Transient Maximum DC Transient

t t

Network Faults

Fault at generator
terminals

Very high fault


current t

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 61
Power Transmission and Distribution ISPSE

Short Circuit Current and Short Circuit Power

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 62
Power Transmission and Distribution ISPSE

Short Circuit levels at Different Voltage Levels

350 MVA 30 MVA 400 kVA

380 kV 110 kV 20 kV 400 V

SK“ = 32 GVA SK“ = 4.6 GVA SK“ = 350 MVA SK“ = 10 MVA
IK“ = 45 kA IK“ = 24 kA IK“ = 10 kA IK“ = 15 kA

bei 10 kV

SK“ = 350 MVA I K“ = 20 kA

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 63
Power Transmission and Distribution ISPSE

Short Circuit Calculations

Dahlem 20 kV SS Schmitz
WEA Reetz
Nato
~

Hallschlag SS1
UN = 20 kV
Dahlem 110 kV SS IK = 3,97 kA WEA
? K = 79,1° Collas
SK = 137,64 MVA
~

110 kV Netz
SK = 2,8 GVA 3,5 km NA2XSY
Kyllerberg
1x150mm²
Backes

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 64
Power Transmission and Distribution ISPSE

Formula for Simplified Calcualtions in % / MVA

Transformer
Network
Sk‘‘ • SN, uK Line
Z, l, UN
• •
Synchrongenerator
SN, xd‘‘ • „
S K in MVA
1,1 • 100 xd“ in %
XNetwork =
SK“
SN in MVA
xd“ „ 1,1 • 100
XSynchron. = SK = uK in %
SN ? X
Z in ? / km
uK „
XTransfor.. = „ SK l in km
SN IK =
3 • UN UN in kV
Z • l • 100
XLine = X in % / MVA
U²N
Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 65
Power Transmission and Distribution T PoweISPSE
r
s Example for Simplified Calculations in % / MVA
raini
Cent g
n
er

110 kV 20 kV

• •
Network Transformer Line
3 GVA 110/20 kV NA2XS2Y, 1x150mm2
30 MVA, uk=12% 3 km, Z=0,227 ? /km

1,1 • 100
Xnetwork = = 0,037 % / MVA
3000
„ 1,1 • 100
12 SK = = 181,2 MVA
XTrafo = = 0,400 % / MVA 0,607
30

0,227 • 3 • 100 „ 181,2


XLine = = 0,170 % / MVA IK = = 5,3 kA
20² 3 • 20
? X = 0,607 % / MVA
Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 66
Power Transmission and Distribution T PoweISPSE
r
s Short Circuit Voltage of Transformers
raini
Cent g
n
er


IN .

SN.
100 100
Ik max = S k max =
u k [%] u k [%]

Example
Ratio Capacity uk I k max S k max
20 / 0,4 kV 400 kVA 4% 25 • I N 10 MVA
110 / 20 kV 30 MVA 12 % 8,33 • I N 250 MVA
380 / 110 kV 350 MVA 21 % 4,76 • I N 1670 MVA

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 67
Power Transmission and Distribution T PoweISPSE
r
s Short Circuit Currents in 3. Ph Networks (1)
raini
Cent g
n
er

L1
ZL IK IK
L1
U L2
L3
L3 L2 1 2
IL1

U
1 3 Ph. Fault IK = (100%)
3 • ZL IL3 IL2

U
2 2 Ph. Fault IK = (85%) IL2 IL1
2 • ZL

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 68
Power Transmission and Distribution ISPSE
Short Circuit Currents in 3. Ph Networks (2)

L1
ZL
L1
U L2
IK
L3
L3 L2 ZE
N

U
1. Ph Fault Four wire network I K = (50% assuming ZL = ZE)
3 • (ZL + ZE)

3•U
1. Ph Fault Three wire network IK =
(Zm + Zg + Z0)

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 69
Power Transmission and Distribution ISPSE

Damping of Short Circuit Currents

30 MVA NA2XSY 3x1x150 mm² Z = 0,227 ? / km


110 / 20 kV
uK 12 %
5 10 15 20 km

kA
10
?„
Ik
5

5 10 15 20 km
Line length ?

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 70
Power Transmission and Distribution ISPSE

Short Circuit Power with Parallel Operation of Transformers

110 kV

40 MVA 40 MVA
uK 12% uK 12%

333 MVA 333 MVA

20 kV

666 MVA

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 71
Power Transmission and Distribution ISPSE

1.Phase Fault

IK
ZL
L1
U1
L2
L3 ? K
ZN IK
N

L1 In general :

U
IK =
3 • ? ZL + ZN ?
L3 L2

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 72
Power Transmission and Distribution ISPSE

2.Phase Fault without Ground

ZL
L1 U 23
L2 ? K
L3
IK
IK

L1
In general :

U
IK =
2 • ZL
L3 L2

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 73
Power Transmission and Distribution ISPSE

Two Phase to Ground Fault

ZL

L1
L2
L3
IK
ZE
L1 L1

L3 (L3) (L2) L2 L3 (L3) (L2) L2


2 ph. Fault without ground 2.Ph fault with ground

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 74
Power Transmission and Distribution ISPSE

3.Phase Fault

IK
ZL U1
L1
L2 ?K IK
L3

L1
In general :

U
IK =
3 • ZL
L3 L2

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 75
Power Transmission and Distribution ISPSE

Simultaneous Fault (1)

ZL
L1
L2
L3
IK

ZE

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 76
Power Transmission and Distribution ISPSE

Simultaneous Fault (2)

L1
L2
L3
IL2 , IM
1. Fault point

IL2 , IL3 L1
L2
L3
IL3 , IM

2. Fault point

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 77
Power Transmission and Distribution ISPSE

Short Circuit Current Waveform for different Fault Locations

Far from Generator Close to Generator


IK'' = Anfangs-Kurzschlußwechselstrom
Strom obere Einhüllende Strom
ip = Stoßkurzschlußstrom
IK = Dauerkurzschlußstrom obere Einhüllende
abklingende DC-Komponente
iDC = abklingende DC-Komponente des abklingende DC-Komponente
2 2 I k ? 2 2 I k' ' Kurzschlußstromes
2 2 Ik ' ' A = Anfangswert der abklingenden 2 2 Ik ' '
ip

ip
DC-Komponente 2 2 Ik
A

A
Zeit
Zeit
untere Einhüllende
untere Einhüllende

Constant AC Component 50 / 60 Hz Constant AC Component 50 / 60 Hz


Decaying DC Component Decaying DC Component
Time Constants Time Constants
Medium Voltage 10 ms ... 50 ms Medium Voltage 10 ms ... 100 ms
High Voltage 50 ms ... 100 ms High Voltage 50 ms ... 250 ms
EHV 80 ms ... 150 ms EHV 80 ms ... 250 m
Generator level bis zu 500 ms

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 78
Power Transmission and Distribution ISPSE

Short Circuit Current Waveform for Faults at Generator Terminals

?
N [ ( 1 / X d – 1 / X d ) exp(- t / T
? ?
Ik= ?2 U d)

+ ( 1 / X?d – 1 / X d) exp (- t / T ?d) + 1 / X d cos ? t [


+ ?2 U
?
N / X d exp ( - t / Tg)

Subtransient Time Constant T ?d


Transient Time Constant T ?d
Steady State Time Constant Td

Note : Resistance of generator stator neglected

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 79
Power Transmission and Distribution ISPSE

Characteristic Values for 3.Phase Synchronous Generators

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 80
Power Transmission and Distribution ISPSE

2.Planning of Transmission and


Distribution Networks
Design Criteria

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 81
Power Transmission and Distribution ISPSE

Topics

? Basics

? Medium Voltage Networks

? Low Voltage Networks

? Transmission Tasks

? Planning of Urban Networks

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 82
Power Transmission and Distribution ISPSE

Tasks of Electrical Networks

? Transmission

? Distribution

? Reliability of Supply

? Compensation

? Synchronisation

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 83
Power Transmission and Distribution ISPSE

Demands on Electrical Networks

? High Availability

? Low Losses

? Less Space Requirements

? Environmental friendly

? Low Costs

? Flexible

? High Quality of Supply

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 84
Power Transmission and Distribution ISPSE
Users of High Voltage Networks

? Public Power Supply Companies


Power Grids, National Netwotks, Regional Networks, Urban Networks
? Industrial users
Steel, Cement. Chemical Industries, Automobile Industry
? Generating Systems

? Traction Networks
Remote Trains, Local Trains
? Special Networks
Airports, Hospitals, Laboratries, yards

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 85
Power Transmission and Distribution ISPSE
Voltage Levels

Extra High Voltage 1200 kV


Transmission 765 kV
380/ 400 kV
275 kV
High Voltages
220 kV
150 kV
110 kV
60 kV
Medium Voltages
30 kV
20 kV
10 kV
6 kV Distribution
Low Voltages
600 V
400 V

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 86
Power Transmission and Distribution ISPSE

From Generation to Consumer

380 kV

110 kV

10 kV
20 kV

0,4 kV

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 87
Power Transmission and Distribution ISPSE

Reasons for Network Planning

? State analysis
?New Structuring
? Retrofit oder Strenghthening
? Choice of Voltage level
? Switchgear Concept
? Comparison of alternatives
? Determination of Investment costs
? Layout of Protection Concepts
? Network calculations
? reduction of losses
? Training
? Solution of operational Problems

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 88
Power Transmission and Distribution ISPSE

Planning Criteria

? Imax Load Current

??U Voltage drop

? Ik min, Ik max Short Circuit Currents

? n-1 Reliability

?€ Costs

? Availability of Trenches

? Network Dynamics

? Future Developments

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 89
Power Transmission and Distribution ISPSE

Quality of Supply with Electric Energy

? Power
? Sufficient

? Voltage
? Amount Umin < U < Umax
? Frequency fmin < f < fmax
? Symmetry U0 < U0,max Zero-sequence voltage
U2 < U2,max Negative-sequence voltage
? Harmonics Uh < Uh,max Harmonic voltages
Ih < Ih,max

? Reliability
Hu < Hu,max Frequency of breaks
Tu < Tu,max Duration of breaks
? Price
? Price to be as low as possible

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 90
Power Transmission and Distribution ISPSE

Methods of Neutral Earthing of Power Transformers

Neutral point connection (see VDE 0141)


Designation Schematic circuit diagram Notes
Small MV networks for
Insulated neutral
power plant internal use
point
Distribution networks

10 kV to 110 kV networks
Ground-fault
having a large open-wire
compensation
portion
using a Petersen
coil

Low-resistance 110 kV to 380 kV networks


neutral point
(with short interruptions)
grounding
Transmission networks
(immediate direct
grounding) Interconnected networks

Low-resistance
neutral point 10 kV to 110 kV networks
grounding having a large cable
(curren- limiting Distribution networks
grounding)

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 91
Power Transmission and Distribution ISPSE

3. Power System Stability

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 92
Power Transmission and Distribution ISPSE

Power Transmission – The basic Equation

P
V1 , ? 1 V2 , ? 2

G~ G~
X
V1 V2
P = ( 1 - ? 2)
sin (?
X

Power-Flow Control

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 93
Power Transmission and Distribution ISPSE

Power Transmission – Types of Stability


Generator Operation Motor Operation

Power Pe
Stable Operation Unstable Operation

Mechanical Power Input Pm


Power Angle (? 1 - ? 2)

Steady State ( Dynamic) Stability

The capability of synchronous machines to remain stable under the condition of small load changes

is referred to as steady state(dynamic) stability.

Since modern power systems do not just have one machine but many machines supplying a network,

the steady state(dynamic) stability refers to the network of machines.


Transient Stability

The capability of synchronous machines or systems to remain stable under large impacts for example

Faults or loss of a major generating unit is called „Transient Stability“

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 94
Power Transmission and Distribution ISPSE

Power Transmission – Power Swing Equation


Power Swing

The dynamic state of a synchronous machine is governed by the power swing

equation : Pa = M d2 ? / dt 2

For single synchronous machines, ? is called torque or rotor angle.

For a network of machines, ? could be referred to as power angle.

M = angular Momentum of the machine (network)

Pa = Accelerating power of the rotor = Mechanical Power Input Pm – Electrical Power Output Pe

Unstable power swing

Stable power swing


d
Rotor angle

Time in sec
Example of a typical swing curve
Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 95
Power Transmission and Distribution ISPSE

System Stability – Equal Area Criterion

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 96
Power Transmission and Distribution ISPSE

System Stability – Equal Area Criterion with Faults

A2

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 97
Power Transmission and Distribution ISPSE

4. Protection Principles

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 98
Power Transmission and Distribution ISPSE

Tasks of Power System Protection


The protection device can not prevent
a power system fault • but:
?Minimize the consequences
• by:
• Fast and selective tripping of
devices effected by the fault
• automatic reclosure in case of
transient failures
• Providing all necessary
information for failure clarification
That will not happen with the right and rapid restoration of the power
protection system!
system

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 99
Power Transmission and Distribution ISPSE

Cosequences of Power System Faults

? Danger to Operating Personnel

? Damage to Power Equipment

? Loss of System Stability and


Power Interruption

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 100
Power Transmission and Distribution ISPSE

Typical Reasons for Faults

Faults on OHL
Atmospheric impact (lighting, ice,wind)
fast plant growth (trees, bush fires)
mechanical impact (cranes, planes)
Faults on cables
Isolation-flashover (i.e water in cable joints)
Thermical overload
Mechanical damage (i.e. shovel excavator)
Faults on transformers, CTs/VTs and Motors
Break down of the insulation (ageing, transient overvoltages)
Thermal overload
Faults on busbars
Short circuit caused by external elements (isolators falling down, exploded
CTs/VTs)
(in MV by animals)
Switching Errors (i.e. switch onto earth or switching off of the sectionalizers
under load)

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 101
Power Transmission and Distribution ISPSE

Fault-Statistics
(VDEW fault- and damage statistics 1986)

20 kV: 110 kV: 380kV

18042 2385 357 faults


(13 per 100 km) (4,9 per 100 km) (3,4 per 100 km)
of which: of which: of which:

60 % 31 % 51 % atmospheric impact

11 % 4% 4% external impact

2% 5% 8% internal impact

23 % 40 % 11 % no defined reason

4% 20 % 26 % feedback from other power systems

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 102
Power Transmission and Distribution ISPSE

Types of Faults

• 3-pol. short circuit 3-pol. interruption

HV EHV
5% 1%

2-pol. short circuit 2-pol. interruption

25 % 6%

1-pol. short circuit 1-pol. interruption

70 % 93 %

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 103
Power Transmission and Distribution ISPSE

Basic Requirements of Protection Systems (1)


Speed : Clear the fault
as fast as necessary, (Time grading !) Se
e.g. short-circuits should be cleared within the ivity ns
itiv
ct ity
le
critical tripping time (i. e. <100 ms in power Se
transmission systems)
to reduce damage and to ensure stability of the
power system.

Reliability : Function correctly when required


1. Must operate during faults which are within its
Sp ity
ee il
d
liab
zone of protection (Dependability).
Re
2. Should not operate for faults outside its protective
zone or no operation during unfaulty condittions
(Security).

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 104
Power Transmission and Distribution ISPSE

Basic Requirements of Protection Systems (2)


Selectivity : Selective isolation
of the faulty component of the power system Se
ivity ns
itiv
network.
lect ity
Se
Realised through grading of a protective device
threshold, timing or operating characteristics.

Sensitivity : Ability of the device to initiate


protective action, when the sensed quantities Sp
ee ility
exceed the threshold (Pick-up or set value). d
liab
Re

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 105
Power Transmission and Distribution ISPSE

Protection Zones

Protection Zones

1. Generator

2. Transformer

3. Busbar

4. Feeder

5. Motors

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 106
Power Transmission and Distribution ISPSE

Definition of Basic Terms used in System Protection (1)


Primary Protection :

are protective relays within a given protection zone that should operate for
prescribed abnormalities within that zone.

Sometimes such relays are referred to as „ main protection „.

Pickup Value 1) :

The minimum input that will cause a device to complete contact operation or
similar designated action.

This value is also sometimes called „ threshold value „ or „ set value „

Dropout 1) :

A term for contact operation (opening or closing) as a relay just departs


from pickup. Also identifies the maximum value of input quantity which will
allow the relay to dropout. 1) IEEE Standard Dictionary of Electrical and Electronics Terms

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 107
Power Transmission and Distribution ISPSE

Definition of Basic Terms used in System Protection (2)


Local Relay Backup protection 1) :

A form of protection that operates independently of specified components


in the primary protective system and that is intended to operate if the
primary protection fails or is temporarily out of service

Local Breaker Backup protection :

A form of protection that is triggered by the local protection and detects


breaker fail conditions. If such a condition is identified, this protection gives
a trip command to all the breakers necessary to clear the fault.

Remote Backup protection 1) :

A form of backup protection in which the protection is at a station or


stations other than that which has the primary protection

1) IEEE Standard Dictionary of Electrical and Electronics

Terms Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 108
Power Transmission and Distribution ISPSE
Measuring Signals and Criteria for Fault Detection and Clearence

Current I I> I I>> ? I SI dI


dt
Voltage V V> V< dV
dt
Impedance Z Z< dZ
dt

Frequency f f> f< ?f df


dt
Phase angle f ?f df
dt

Power S P Q S(t)
Note : In numerical systems, only the
currents and voltages are the input signals.
Temperature ? ?> ? ? d?
Other measuring quantities are derived
dt
(calculated) from these two inputs

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 109
Power Transmission and Distribution ISPSE
General Block Diagram of a Protective Relay

Bus Bar

Bus isolator Trip Command to


Circuit Breaker Trip Coil
Breaker
Currents +
CT
Protective
Voltages Relay
VT
Line isolator

+ -
DC Power Supply
from Station Battery

Note : Earthing Switches not shown Note : Other Binary Inputs and Outputs not shown

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 110
Power Transmission and Distribution ISPSE

Measuring Principle of Overcurrent Protection (1)


Tripping characteristics of a two-step definite-time protection (DMTL)

t [sec]
2.0

1.5 Tripping area

1.0

0.5

0.5 1.0 1.5 2.0 2.5 x IN


I> I>>

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 111
Power Transmission and Distribution ISPSE

Measuring Principle of Overcurrent Protection (2)

Tripping characteristics of an inverse-time protection (IDMTL)

I Inverse
t [sec] D definite
2.0 M Minimum
T Time
1.5
L Lag
Characteristical curves:
?IEC
1.0 ?ANSI
?British Standard

0.5

0.5 1.0 1.5 2.0 2.5 x IN

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 112
Power Transmission and Distribution ISPSE

Measuring Circuit of Overcurrent Protection

L1
Definite Time
IL1
Tripping area

L2
IL2 OR - Inverse
- Very Inverse
L3 Inverse Time
IL3 - Extremely Inverse
- Long inverse
N

IN

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 113
Power Transmission and Distribution ISPSE

Time – Current Characteristic acc. IEC 60255-3 / BS

0.14 .Tp
Inverse : t =
( I / I p ) 0.02 - 1
13.5 .Tp
Very Inverse : t =
( I/Ip)- 1

120 .Tp
Long Inverse : t =
( I/Ip)- 1

80 .Tp
Extremely Inverse : t =
( I/Ip)2- 1

T p = Time multiplier Setting


I p = Current Setting
I = Short Circuit (Fault) Current
Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 114
Power Transmission and Distribution ISPSE

Time – Current Characteristic acc. IEEEE / ANSI

8.9341
Inverse : t = ( 2.0938
+ 0.17966 ).D
( I/Ip) - 1
3.922
Very Inverse : t = ( 2
+ 0.0982 ).D
( I/Ip) - 1

5.6143
Long Inverse : t = ( 2.0938
+ 2.18592 ).D
( I/Ip) - 1

5.64
Extremely Inverse : t = ( 2-
+ 0.02434 ).D
( I/Ip) 1

D = Time Dial Setting


I p = Current Setting
I = Short Circuit (Fault) Current
Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 115
Power Transmission and Distribution ISPSE

Principle of Directional Measurement (1)

Notes : 1. For directional measurement, a reference measuring signal is required


2. Only in the faulty section, currents at both line ends are in the forward direction

Current

Short circuit angle (> 90 0 )


Voltage as reference
Voltage as reference
Short circuit angle (< 90 0 )

Current

Forward Fault Reverse Fault


Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 116
Power Transmission and Distribution ISPSE

Measuring Circuit of Directional Overcurrent Protection

I>> t
IL1

I> t

Direction
& TRIP

UL1

Fast stage (I>>): directional

Back-up stage (I>): non-directional

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 117
Power Transmission and Distribution ISPSE
Fundamentals of Distance Protection

Why Distance Protection ???


1. Transmission circuits are invariably multi-source loop systems, which
transmit huge blocks of power from the generating sources to the the distribution
centres. Fault levels are generally high, and if faults are not cleared rapidly, they
can cause system instability , extensive damage and hazards to personnel.
Faults on transmission line must be cleared as soon as possible (Fault clearing
time < 100 ms for EHV-systems). Since they carry huge blocks of power, system
restoration demands a rapid automatic reclosing.

2. Simple overcurrent relays (directional or non-directional ) cannot be used, since


they are too slow and their performance is dependent on infeed conditions at the
time of fault. Further, the fault current must be much higher than the maximum load
current, which is not always true for transmission line faults.

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 118
Power Transmission and Distribution ISPSE
Basic Measuring Principle

Currents
Calculation of Impedances
and
Voltages Comparison with the settings

Distance Relay –Block Diagram


I
U
?Z
U Load
Load
I
I
U
U Load
?Z Fault
I
Since Impedance is proportional to Distance to fault,

this protection is called Distance Protection


Z Fault
?? Z Load

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 119
Power Transmission and Distribution ISPSE

Representation of Impedance on a Complex Impedance Plane


X
Example : 380 kV line loaded with 600 MW,
Unity Power Factor. Line Z = l ? Z'
Fault Line
The line is 200 Kms long and has
following line data :
Z = 0.26 ohms / Km at an angle of 80 0.
X (4.51 + j 25.6 ) O
UN
2

Fault at the middle of the line


Z Load =
80 0 S Load
X
I R 241 O
U Load
Load
2
UN
Z Load = = 241 Ohms = R
S Load

U Load

Z = 0.26 x 100 = 26 O 80 0. = (4.51 + j 25.6) O


Fault
Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 120
Power Transmission and Distribution ISPSE

Mathematical Basis for Impedance Calculations (1)


L1 Note : Voltages , currents and impedances I1
Zs1 Z1
L2 are complex

L3
Positive sequence ~ U1 U F1

I2
Zs2 Z1
Zs1 : Positive sequence impedance of the infeed
Negative sequence U F2
U2
Zs2 : Negative sequence impedance of the infeed
I0
Zs0 : Zero sequence impedance of the infeed Zs0 Z0

Zero sequence U0 U F0
Z1 und Z0 : Positive (negative) and zero sequence
impedance of the line upto fault respy

UL1 = U1 + U2 + U0 = UF1 + I1 x Z1 + UF2 + I2 x Z1 + UF0 + I0 x Z0 Relay Location


= (UF1 + UF2 + UF0) + Z1 x (I1 + I2 + I0) + I0 x (Z0 – Z1)
= Z1 x IL1 + IE x (Z0 – Z1 ) / 3 = Z1 x IL1 + IE x ZE
Phase to ground Fault
= Z1 x ( IL1 + IE x ZE / Z1 )

UL1 / ( IL1 + IE x ZE / Z1 ) = Z1 Impedance measured by the relay

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 121
Power Transmission and Distribution ISPSE

Mathematical Basis for Impedance Calculations (2)


L1
Note : Voltages , currents and impedances I1
L2 Zs1 Z1
are complex
L3
Positive sequence ~ U1 U F1

I2
Zs2 Z1
Zs1 : Positive sequence impedance of the infeed
Negative sequence U F2
U2
Zs2 : Negative sequence impedance of the infeed
Relay Location
Z1 : Positive (negative) sequence
impedance of the line upto fault
Phase to Phase Fault
2 2
UL2 = a x U1 + a x U2 = a x (UF1 + I1 x Z1) + a x (UF2 + I2 x Z1)
UL3 = a x U1 + a 2 x U2 = a x (UF1 + I1 x Z1) + a 2 x (UF2 + I2 x Z1)
UL2 - UL3 = (a 2 – a ) x [ (UF1 - UF2) + Z1 x ( I1 - I2 ) ]= (a 2 – a ) x [ Z1 x ( I1 - I2 ) ]
IL2 - IL3 = (a 2 – a ) x ( I1 - I2 )

UL2 - UL3
= Z1 Impedance measured by the relay
IL2 - IL3

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 122
Power Transmission and Distribution ISPSE

Mathematical Basis for Impedance Calculations (3a)


L1
Note : Voltages , currents and impedances I1
L2 Zs1 Z1
are complex
L3
Positive sequence ~ U1 U F1

I2
Zs2 Z1
Zs1 : Positive sequence impedance of the infeed
Negative sequence U F2
U2
Zs2 : Negative sequence impedance of the infeed
I0
Z1 : Positive (negative) sequence Zs0 Z0

impedance of the line upto fault Zero sequence U0 U F0

UL2 = a 2 x U1 + a x U2 + Uo = a 2 x (UF1 + I1 x Z1) + a x (UF2 + I2 x Z1) +( UF0 + I0 x Z0)


UL3 = a x U1 + a 2 x U2 + U0 = a x (UF1 + I1 x Z1) + a 2 x (UF2 + I2 x Z1) +( UF0 + I0 x Z0)
UL2 - UL3 = (a 2 – a ) x [ (UF1 - UF2) + Z1 x ( I1 - I2 ) ]= (a 2 – a ) x [ Z1 x ( I1 - I2 ) ] Relay Location
IL2 - IL3 = (a 2 – a ) x ( I1 - I2 )

UL2 - UL3 2 Phase to ground Fault


= Z1 Impedance measured by the relay
IL2 - IL3

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 123
Power Transmission and Distribution ISPSE

Mathematical Basis for Impedance Calculations (3b)


L1
Note : Voltages , currents and impedances I1
L2 Zs1 Z1
are complex
L3
Positive sequence ~ U1 U F1

I2
Zs2 Z1

It can also be shown, for this fault type, : Negative sequence U F2


U2

I0
UL2 / ( IL2 + IE x ZE / Z1 ) = Z1
Zs0 Z0
and
Zero sequence U0 U F0
UL3 / ( IL3 + IE x ZE / Z1 ) = Z1

Summarizing :
Relay Location
For a 2 phase to ground fault, the phase to phase loop of the faulty phases
as well as the phase to ground loops of the faulty phases measure the same
Impedance. 2 Phase to ground Fault

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 124
Power Transmission and Distribution ISPSE

Mathematical Basis for Impedance Calculations (4)


L1
Note : Voltages , currents and impedances I1
L2 Zs1 Z1
are complex
L3
Positive sequence ~ U1 U F1

UL1 = U1 + U2 + Uo = (UF1 + I1 x Z1) = I1 x Z1


IL1 = ( I1 + I2 + I0 ) = I1 Relay Location
UL2 = a 2 x U1 + a x U2 + Uo = a 2 x (UF1 + I1 x Z1) = a 2 x I1 x Z1
3 Phase (to ground) Fault
IL2 = a 2 x I1 + a x I2 + Io = a 2 x I1
UL3 = a x U1 + a 2 x U2 + U0 = a x (UF1 + I1 x Z1) = a x I1 x Z1
IL3 = a x I1 + a 2 x I2 + Io = a x I1
Hence the impedances measured by the 6 loops are :
UL1 / IL1 = Z1

UL2 / IL2 = Z1 1. The Currents and Voltages are symmetrical

UL3 / IL3 = Z1 2. All the 6 loops measure the same Impedance


(UL1 – UL2) / (IL1-IL2) = Z1
(UL2 – UL3) / (IL2-IL3) = Z1
(UL3 – UL1) / (IL3-IL1) = Z1

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 125
Power Transmission and Distribution ISPSE

Measured Impedance with Resistance Faults (1)


L1 Note : Voltages , currents and impedances
I1
L2 are complex Zs1 Z1

L3

Fault Resistance RF Positive sequence ~ U1 U F1

I2 3RF
Zs2 Z1

Negative sequence U F2
U2

Impedance measured by the relay : I0


Zs0 Z0
UL1 / ( IL1 + IE x ZE / Z1 ) = Z1 + 3 RF Zero sequence U0 U F0

Relay Location

Phase to ground Fault with fault Resistance

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 126
Power Transmission and Distribution ISPSE

Measured Impedance with Resistance Faults (2)


L1 Note : Voltages , currents and impedances I1
Zs1 Z1
L2 are complex

L3
Positive sequence ~ U1 U F1
Fault Resistance RF RF

I2
Zs2 Z1

Negative sequence U F2
U2

Relay Location
Impedance measured by the relay :

UL2 - UL3 Phase to Phase Fault with Fault Resistance


= Z1 + R F
IL2 - IL3

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 127
Power Transmission and Distribution ISPSE

Measured Impedance with Resistance Faults (3)


L1
Note : Voltages , currents and impedances I1
L2 Zs1 Z1
are complex
L3
Positive sequence ~ U1 U F1
Fault Resistance RF

I2
Zs2 Z1
Impedance measured by the relay : Negative sequence
U2 U F2
3RF
UL2 - UL3 I0
= Z1
IL2 - IL3 Zs0 Z0

UL2 / ( IL2 + IE x ZE / Z1 ) = Z1 + 3 RF Zero sequence U0 U F0

and
UL3 / ( IL3 + IE x ZE / Z1 ) = Z1 + 3 RF
Relay Location

Phase to Phase Fault with Fault Resistance

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 128
Power Transmission and Distribution ISPSE

Fundamental Equations for Impedance (Distance) Calculations (1)

IL1 ZL
ZL = RL + j XL
IL2
IL3
ZE = RE +j XE
IE ZE

UL1 UL2 UL3


6 loops: 3 phase- phase loops and
3 phase- ground loops

phase- phase -loop: UL1-L2 = ZL ( IL1 - IL2)

Measured current
measured voltage

The same applies to the other phases

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 129
Power Transmission and Distribution ISPSE

Fundamental Equations for Impedance (Distance) Calculations (2)

IL1 ZL
ZL = RL + j XL
IL2
IL3
ZE = RE +j XE
IE ZE

UL1 UL2 UL3

phase-ground-loop: UL1 = ?L1 · ( RL + j XL )- ?E · ( RE +j XE)

?L1, ?E measured current


measured voltage

The same applies to the other phases


Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 130
Power Transmission and Distribution ISPSE

Directional Measurement with Distance Relays


Current I Current I

A B C
Z< Z< Z< Z<

Summary : 1 2 3 4
1. Both relays 2 and 3 measure the same
X Line C Line
impedance magnitude but different X
angles.

e
Voltag
2. In this example, the relay 3, which sees
the fault in the forward direction, measures

Fault
X
an impedance angle of 80 0 and relay 2 80 0
0.
80 0
measures an angle of - 100
B
e
R B
Voltag

R
Current as
3. Distance Relay 3 gives a trip command Current as reference
X
Fault

reference
to ist breaker, since fault in the forward 00 Z=U 00
Z=U
direction and relay 2 does not, since fault - 80 0
I 100 0 I
in reverse direction
Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 131
Power Transmission and Distribution ISPSE

Measuring Signals for Directional Measurement (1)


The measuring signals for the six measuring loops for distance measurements
are :
Phase to ground Loops Phase to Phase Loops

UL1 and ( IL1 + IE x ZE / Z1 ) ( UL1 – UL2 ) and ( IL1 – IL2 )

UL2 and ( IL2 + IE x ZE / Z1 ) ( UL2 – UL3 ) and ( IL2 – IL3 )

UL3 and ( IL3 + IE x ZE / Z1 )


( UL3 – UL1 ) and ( IL3 – IL1 )

Can we use the same signals for the six directional measuring loops ?

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 132
Power Transmission and Distribution ISPSE

Measuring Signals for Directional Measurement (2)

Can we use the same distance measuring signals for the six directional measuring loops ?

Current I Current I
F2 F1

A B C
Z< Z< Z< Z<
1 2 3 4

For a close in fault (Fault at the beginning of the line section ahead (F1) and behind the
relay location (F2) ) the voltage is almost zero.
Measurement of direction with the faulty voltage will not give a unique result.

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 133
Power Transmission and Distribution ISPSE

Measuring Signals for Directional Measurement (3)


~ ~ ~
~ ~ ~
fault L1-E
~ ~ ~
VL1 Zgrid Relay Zline
Vf
VN
If
VL3 VL2 VL3
fault-free VL2
faulty phase voltage VL1
Vf
VN
If
If
VL3 VL2 VL3 VL2
Vdir
sound-phase voltages voltage memory

for single and two phase For

faults 3-phase faults

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 134
Power Transmission and Distribution ISPSE

Example of Pickup Characteristics of Distance Protection (1)


X
Line Characteristic

Dis
tan
X1

ce
Ch
ara
cte
ris
tic
R1

R1E
Di

R
re
ct
io
na
l
Ch
ar
ac
te
ris
tic

Quadrilateral Pickup Characteristic ( Electronic and Numerical)

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 135
Power Transmission and Distribution ISPSE

Example of Pickup Characteristics of Distance Protection (2)

Mho Pickup Characteristic Quadrilateral Pickup Characteristic


( Electromechanical,Electronic ( Electronic and Numerical)
and Numerical)

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 136
Power Transmission and Distribution ISPSE

Grading (Remote Backup) with Distance Protection

grading time
(s)
0.6

0.3

X X X X X X X

X Circuit Breaker

Grading with Infeed from two ends

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 137
Power Transmission and Distribution ISPSE

Teleprotection Schemes

Why use tele-protection?

1 2

Faults in this area Faults in this area Faults in this area


are cleared after t2 are cleared without additional are cleared after t2
at line end 2 time delay at both line ends at line end 1
Faults on approximately 75% of the line length are cleared
without delay at both line ends

Faults in the remaining 25% of the line length


are cleared with a time delay (Not acceptable in HV and EHV Systems) .

Solution: Exchange of information between the two line ends

Required: Communication channel (PLC, microwave radio, fibre optic, etc.)


Teleprotection logic (dedicated device or internal
function in numerical protection devices)
Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 138
Power Transmission and Distribution ISPSE

High Resistance Ground Fault Protection (1)


Why necessary?
Many clients do not accept distance relays for detecting and clearing high resistance earth faults,
due to the difficulty in setting.
A common practice is to use directional overcurrent relay . A block diagram is shown below.

I o > Setting
Earth fault in
& Forward direction
Forward direction

Two Issues !
1. How to measure the direction ?

2. All the faults in the forward direction (beyond the line section) are measured without
selectivity
Current I Current I
F2 F1

A B C
Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 139
Power Transmission and Distribution ISPSE

High Resistance Ground Fault Protection (2)


Method for Directional Measurement

Measure the angle between Io of the line and a reference (polarising) quantity.

The polarising signals are either the zero sequence voltage (from an open delta) or

the zero sequence current in the transformer neutral connected to the bus.

_ _ ?
F2 F2

A B A B

3 x Uo ( Open delta voltage )

_
OR ? _
Zig-Zag Transformer Delta-Star Transformer
Note : In numerical relays, this open delta voltage can be calculated Source of polarizing current
Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 140
Power Transmission and Distribution ISPSE

High Resistance Ground Fault Protection (3)


Method to ensure selectivity

Current I Current I
F2 F1

A B C
Transmit a signal to remote end

I o > Setting Earth fault in Phase selection and hence single pole
& Forward direction breaker opening not possible
using this method
Forward direction

Received signal from remote end


& Trip command to breaker

Fault at F2 Fault at F1
-A sends a signal to B, indicating a forward fault
-Relay at end A sends a signal to B, indicating a forward fault
-Relay at end B sends a signal to A, indicating a forward fault -B sees a reverse fault and does not send any signal to A

- Both the breakers in line AB trip - Line AB remains in service

- Relay C in the line BC sends a signal to B indicating a forward fault - C in the line BC sends a signal to B indicating a forward fault

- Relay B in line BC meaures a reverse fault and does not send a signal to C - B in line BC also sends a signal to C indicating a forward fault
- Line BC remains in service - Both the breakers in line BC trip

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 141
Power Transmission and Distribution ISPSE

Logically dependent Supplementary Functions to Distance Relay (1)

1. Single and three pole autoreclosing


For faults within the proteced zone (line section) the distance relay trips without
intentional time delay. In cases where single pole breakers are used, single phase faults
result in the opening of the faulty phase. Once the breaker opens at both line ends,
the fault current gets interrupted and the arc at the fault location extinguishes. After a
certain delay (around 1 s for single phase faults and is called the dead time), a reclosing
command is given to the closing coil of the circuit breaker. If the fault still hangs on
(permanent fault), in most of the cases the breakers at both line ends open out in all the
three phases and the breakers lockout.
In the case of a mutiphase fault, all three poles of the breaker open at both line ends.
Depending upon the network, a fast reclosing after a dead time of around 0.3-0.5 s may
follow. If the fault is permanent, the breakers at both line ends open out and are locked.
Note : Single pole breaker opening and reclosing is not practiced with cable networks,
since, cable faults are generally permanent.

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 142
Power Transmission and Distribution ISPSE

SIPROTEC 4 - 7SA Automatic reclosure (ARC)

Trip Close Trip Close Final


1-pole Trip
3-pole
*
Close

Trip
1st 2nd
t1 dead time t2 dead time tgrading

ADT = close after successful ARC at remote end


* DLC = reclose only when line is dead
RDT = reduced dead time after non-selective trip
Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 143
Power Transmission and Distribution ISPSE

Logically dependent Supplementary Functions to Distance Relay (2)

2. Dead line check and Check-Synchronizing


When breakers get locked out after unsuccesful reclosure, or if the line has to be chraged,
it is necessary to ensure that the bus voltages and the line voltages are synchronous, before
the breaker is closed.
When the breakers at both line ends are open, normally at one line end, a dead line check is
made and if the line is dead, the breaker is closed. After charging the line at one end,
the voltages of the line and the bus must be synchronous, before closing the breaker.
For the voltages to be synchronous, following conditions must be satisfied :
1. The voltage difference | ? U | < set value
2. AND the difference in frequency of the voltages | ? f | < set value
3. AND the difference in the phase angle of the voltages| ? f | < set value
If required, these tests can be carried out for all the three phases and also can be ensured
that the phase sequence of the line and bus voltages are the same.

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 144
Power Transmission and Distribution ISPSE

Logically dependent Supplementary Functions to Distance Relay (3)

3. Distance to Fault Location


If distance relays trip and open the breakers due to faults, it is very useful to know,
the distance of the fault from the line end. Using this data, the maintenance staff can
carry out the necessary repairs and ensure fast restoration. The result of distance
measurement is an indication of the location of the fault. The reactance measured by the
distance relay is a more accurate indication of the fault location than the impedance, since
the fault resistance can influence the accuracy of fault location based on impedance
calculations.
In numerical relays, the fault calculation can be done very accurately, since the fault data
(currents and voltages) is stored.
A fast distance estimation is used for breaker tripping and a slow and accurate distance
determination is done using the stored fault data.

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 145
Power Transmission and Distribution ISPSE

Logically dependent Supplementary Functions to Distance Relay (4)


4. Overvoltage Protection (Ferranti effect)

Transmission line model using distributed parameters

IC
IC
-I CX L

I CX VS VR
L

A VS VR B V S= V R + I CX L

Under light (no) load conditions or if the breaker at the remote end is open, the voltage at the remote end
is higher than the sending end voltage. Longer the line higher is this voltage .
The voltage has to be monitored and if it increases beyond a certain value, the breaker has to be opened.

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 146
Power Transmission and Distribution ISPSE

Current Differential Protection (1)


Principles of differential protection
Determination of a current difference ( Based on Kirchoff‘s law)

A hole is in
the bucket! ?

I1 I2 I1 I2
Protected unit Protected unit
i1 i1
i2 i2

i1
? I> ? I=I1 - I2 ? I> ? I=I1 + I2
=0 i2

External fault, Internal fault


or load
Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 147
Power Transmission and Distribution ISPSE

Current Differential Protection (2)


IP1 IP2 IP1 IP2
I1F I2F IF
Protected Protected
object object
IS1 IS2 IS1 IS2
IS1 IS2
?I IDiff =¦ I1 + I2¦ ?I IDiff =¦ I1 + I2¦

internal fault external fault or load

Assumption: CT- ratio: 1/1 Assumption: CT- ratio: 1/1


IP1 = I1F IP1 = IF
IP2 = I2F IP2 = -IF
IDiff = ¦ IP1 + IP2 ¦ = ¦ I1F + I2F ¦ IDiff = ¦ IP1 + IP2 ¦ = IF - IF = 0
? Trip ? no Trip

Used for Protecting :


Requirements for Differential Protection:
?Lines / Cables
Internal faults ( between CT-sets ) ? Trip ?Generators / Motors (> 1MVA)
External faults ? no Trip ?Transformers (> 1MVA)
?Busbars
Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 148
Power Transmission and Distribution ISPSE

Transformer Differential Protection


Basic Measuring Principle

CT 1:
CT 2:
e1= - 5%
I P1 e2 = + 5% I P2 = -I P1
IF
Protected
object

IRest I Rest =¦ I S1¦ +¦ I S2¦


I Rest = 2·I P1

I S2=
I S1= 1.05·I P2
0.95·I P1
I Diff= ¦ I S1+ I S2¦
IDiff
I Diff = 0.1·I P1

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 149
Power Transmission and Distribution ISPSE

Busbar Differential Protection

Fault detecting Principle

Uses Kirchoff‘s law


?I
0 which states :

Vectorial sum of a current at a node is zero

G M

Grid-
infeed Load

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 150
Power Transmission and Distribution ISPSE

IEEE Std C37.2.1996 Device Numbers (1)

3.1.21 Device number 21—distance relay


A device that functions when the circuit admittance, impedance, or
reactance increases or decreases beyond a predetermined value.

3.1.25 Device number 25—synchronizing or synchronism-check relay


A synchronizing device produces an output that causes closure at zero-phase angle difference between
two circuits. It may or may not include voltage and speed control. A synchronism-check relay permits
the paralleling of two circuits that are within prescribed limits of voltage magnitude, phase angle,
and frequency.

3.1.27 Device number 27—undervoltage relay


A device that operates when its input voltage is less than a
predetermined value.

3.1.30 Device number 30—annunciator relay


A nonautomatically reset device that gives a number of separate visual indications upon the
functioning of protective devices and that may also be arranged to perform a lockout function.

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 151
Power Transmission and Distribution ISPSE

IEEE Std C37.2.1996 Device Numbers (2)


3.1.49 Device number 49—machine or transformer thermal relay
A device that functions when the temperature of a machine armature winding or other load-carrying
winding or element of a machine or power transformer exceeds a predetermined value.

3.1.50 Device number 50—instantaneous overcurrent relay


A device that operates with no intentional time delay when the current exceeds a preset value.

3.1.51 Device number 51—ac time overcurrent relay


A device that functions when the ac input current exceeds a predetermined value, and in which the input
current and operating time are inversely related through a substantial portion of the performance range.

3.1.52 Device number 52—ac circuit breaker


A device that is used to close and interrupt an ac power circuit under normal conditions or to interrupt this
circuit under fault or emergency conditions.

3.1.59 Device number 59—overvoltage relay


A device that operates when its input voltage exceeds a predetermined value

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 152
Power Transmission and Distribution ISPSE

IEEE Std C37.2.1996 Device Numbers (3)


3.1.62 Device number 62—time-delay stopping or opening relay
A device that imposes a time delay in conjunction with the device that initiates the shutdown, stopping,
or opening operation in an automatic sequence or protective relay system.

3.1.63 Device number 63—pressure switch


A device that operates at a given pressure value or at a given rate of change of pressure.

3.1.67 Device number 67—ac directional overcurrent relay


A device that functions at a desired value of ac overcurrent flowing in a predetermined direction.

3.1.68 Device number 68—blocking or “out-of-step” relay


A device that initiates a pilot signal for blocking of tripping on external faults in a transmission line or
in other apparatus under predetermined conditions, or cooperates with other devices to block
tripping or reclosing on an out-of-step condition or on power swings.

3.1.74 Device number 74—alarm relay


A device other than an annunciator, as covered under device function 30, that is used to operate,
or that operates in connection with, a visual or audible alarm
Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 153
Power Transmission and Distribution ISPSE

IEEE Std C37.2.1996 Device Numbers (4)


3.1.79 Device number 79—reclosing relay
A device that controls the automatic reclosing and locking out of an ac circuit interrupter.

3.1.81 Device number 81—frequency relay


A device that responds to the frequency of an electrical quantity, operating when the frequency or
rate of change of frequency exceeds or is less than a predetermined value.

3.1.85 Device number 85—carrier or pilot-wire relay


A device that is operated or restrained by a signal transmitted or received via any communications
media used for relaying.

3.1.86 Device number 86—lockout relay


A device that trips and maintains the associated equipment or devices inoperative until it is reset
by an operator, either locally or remotely.

3.1.87 Device number 87—differential protective relay


A device that operates on a percentage, phase angle, or other quantitative difference of two or
more currents or other electrical quantities.
Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 154
Power Transmission and Distribution ISPSE

IEEE Std C37.2.1996 Device Numbers (5)


3.1.94 Device number 94—tripping or trip-free relay
A device that functions to trip a circuit breaker, contactor, or equipment; to permit immediate
tripping by other devices; or to prevent immediate reclosing of a circuit interrupter if it should
open automatically, even though its closing circuit is maintained closed.

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 155
Power Transmission and Distribution ISPSE

Local Breaker Back up Protection


B2
B3
Current I Current I
F2

B1
A B C
Z< Z< Z< Z<
1 2 3 4

For a fault at F2, distance relays 1 and 2 give a trip command to the respective breakers.
If one of the breakers fails to open, all the breakers connected to the same bus section as the
faulty breaker have to be opened out to interrupt the fault current.
This breaker fail detection is done by breaker fail protection which is initiated by trip commands
of all the relays which trip the breaker.
Task of Breaker Failure Protection
I> :
CT current
50BF
To trip only the bus section,
& to which the bay with the faulty
Start BFP t2
breaker is connected!

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 156
Power Transmission and Distribution ISPSE

Example of a Protection System using IEEE-Device numbers

ON

OFF
+ –

59 Overvoltage
59 25 79 ST = 25 Check synchronism
= 79 Autoreclosure
ST Control
21 Distance protection
21 FO M FR 49 FO Fault locator
FR Fault recorder
M Measurement
Back-up 85 67N 49 Overload
Protection 67N Earthfault determination
85 Teleprotection

Modem
opp.
line end

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 157
Power Transmission and Distribution ISPSE

Redundancy Concept for EHV Lines : 2 Main Relays

52 TC 52 TC

87 BB

B2
50 BF + - B2
B1
B1
+ -
87 L

21

VT Protection Group B
Protection Group A (Main 2 )
( Main 1 )

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 158
Power Transmission and Distribution ISPSE

Redundancy Concept for HV Lines : 1 Main Relay

52 TC

87 BB

50 BF
B1
B1
+ -

21

VT
Protection Group A
( Main 1 )

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 159
Power Transmission and Distribution ISPSE

5. Basics of Generator Protection

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 160
Power Transmission and Distribution ISPSE

Machine Protection - What Does it Mean ?

Machine Protection includes


all devices which are able to detect faults
and abnormal operation situation in machines
and react to this.

? Rotating Machines
Generators (synchronous / asynchronous)
Motors (synchronous / asynchronous)
? Static Units
Transformers
Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 161
Power Transmission and Distribution ISPSE

Special Features of Generator Protection

? Multitude of different Protection Functions

? Several trip circuits with different voltage levels

? Phase sequence switch-over (Pump Storage PP)

? Individual Power Plant Control System

G
Protection device has to be :

Sensitive Fast Selective Reliable

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 162
Power Transmission and Distribution ISPSE

Faults in Synchronous Generators 1

Internal Faults:
Stator: Rotor, Excitation circuit:
? Earth Faults ? Earth Fault
? Short Circuits (2- and 3 phases) (single, double)
? Interturn faults ? Underexcitation
(with split stator winding) (partly respec. complete)
? Overload ? Over voltage
? Over excitation (U/f)

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 163
Power Transmission and Distribution ISPSE

Faults in Synchronous Generators 2

External Faults:
Grid/Transformer: Turbine, Regulator:
? Earth Faults ? Loss of Prime mover
? Short Circuits (Reverse Power)
? Overload (Stator, Rotor) ? Over- and Under voltage
? Negative Phase Sequence ? Over- and Under Frequency
? Asynchronous operation ? Over Excitation (U/f)
(cap.Load, long fault duration) (Influenced by regulator)
? Torsionalstress
? Under frequency (PG < PU)
Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 164
Power Transmission and Distribution ISPSE

Short Circuits

A) Internal Faults
1) Isolated neutral 2) Low resistance
(or high resistance grounding) (or solidly grounded neutral)

L1
3phase short circuit
L2
L3
Single phase short
Interturn fault circuit
Phase to phase short circuit (Resistor limits the
fault current)

B) External Faults In 1) earth faults are also possible

Generator is the e.m.f. for the short circuit


Transformer currents and becomes to stress
? Back-up protection
Grid

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 165
Power Transmission and Distribution ISPSE

Main Components of Machine Protection (Part 1)

Generator - Differential Protection; 87G


Transformer - Differential Protection; 87T
Overcurrent Time Protection; 50, 51V
Impedance Protection; 21
Stator Earth Fault Protection for:
Generators directly connected to the busbar; 67N
Generators connected to the busbar via unit transformer
Protection Range 90 % ; 64
Protection Range 100 %; 64 100%
Rotor Earth Fault Protection; 64R
Unbalanced Load (Negative Sequence) Protection; 46
Reverse Power Protection; 32R

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 166
Power Transmission and Distribution ISPSE

Main Components of Machine Protection (Part 2)

Overvoltage Protection (Undervoltage); 59, (27)


Over and Underfrequency Protection; 81
Underexcitation (Loss of field) Protection; 40
Stator Overload Protection; 49
Overexctation (U/f) Protection; 24
Out of Step Protection; 78
Breaker Failure Protection; 50BF
Rotor Overload Protection; 49R
(Overcurrent at excitation transformer)
Interturn Fault Protection
(separate Stator windings - hydro generators)
Tripping matrix (Software matrix)

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 167
Power Transmission and Distribution ISPSE

Typical Short Circuit Current Waveforms

I??SC= Subtransient short-circuit current


I?SC = Transient short-circuit current
- t
? ?
2 ? ?' ' - ?' ?e T' 'd
k k
ISC = Steady state short-circuit current

- t
2 ?? ' '
k ? k k
?
2 ? ?' - ? ?e T' d
2 ??
k

- t
2 ??' 'k ?e Tg
Driving Voltages U??p < U?p < Up

Actual reactances X??d < X?d < Xd

Time Constants T??d < T?d < Td

Short circuit current Subtransient part transient part Steady state DC - current
short circuit current
? t t t ?
? ? ? ?
? - - - ?
ik ? 2 ? I ' ' ? I ' ?e T' ' d sin?? t - ? ?? I ' - I ?e T' d sin?? t - ? ?? I sin?? t - ? ?? I' ' ?e Tg sin? ?
k k k k k k
? ?
? ?

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 168
Power Transmission and Distribution ISPSE

Example of a Short-Circuit Current Waveform

Data: SN = 200 MVA (Synchronous generator)


xd = 1,78 x´d = 0,24 x´´d = 0,16
TG = 0,097s T´d = 1,125s T´´d = 0,05s

Rotor (e.m.f) voltages Short circuit currents


2,25 1,11
Up Up´ Up´´ IK ? ? I N ? 1,26I N I ´K ? ? I N ? 4,6 IN
.U Xd X?d
Turbo generator 2,25 1,11 1,07 N
.U 1,07
Salient pole generator 1,8 1,2 1,13 N I ´´K ? ? I N ? 6,7 I N
X?d?
Fully asymmetrical DC component Without Dc offset

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 169
Power Transmission and Distribution ISPSE

Requirement for Rotor Earth Fault Protection

Stator
Rotor +
Earth (ground) fault Excitation
in the rotor system
-

RE CE

? in case of an earth fault, only small currents flow due to non earthing

Problem:
Double earth faults and interturn faults as a consequence of an earth fault cause:
• magnetic unbalance
• high currents at the fault location

? Destruction of the Rotor


Task: Detect an earth fault immediately when it starts to build up

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 170
Power Transmission and Distribution ISPSE

Protection Principle for Rotor Earth Fault Detection

+ Coupling Voltage
Measuring Source
Unit
Excitation
system
-
„Earthing brush “

Methods:
- Coupling of an AC voltage (50 Hz or 60 Hz)
- Measuring of the earth fault current Higher
- Measuring of the earth fault resistance Sensitivity
- Coupling of low frequency square wave voltage

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 171
Power Transmission and Distribution ISPSE

Connection Block Diagram (50 Hz/60Hz - Injection)

L1 L2 L3
Connection
to the earthing
brush
>40V

105? 4? F
IE,Stray IE

If stray current is too high


Pick-up limit:
IE,Fault > IE,Stray...
IE,Fault 0,75H

coordinated Relay
resonant circuit to fN

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 172
Power Transmission and Distribution ISPSE
Basic Diagram: Injection of Low Frequency (1- 3 Hz) Square Wave Voltage

7XR6004

RV
Controlling device
IE (7XT71)
+
RV
-
UH Ucontrol
Excitation
Digital
CE RE Protection (7UM62)
RM Umeas.

RE Fault resistance
RV Coupling resistor
UH Auxiliary supply ( ? 50V) Measuring transducer
RM Measuring shunt resistor
CE Rotor capacitance

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 173
Power Transmission and Distribution ISPSE
Basic Principle: Injection of Low Frequency Square Wave Voltage

Equivalent circuit: 50V


UH
RV
2 t

UH - 50V
CE RE
UM
RM UM
1,88V
? ?
RV
?CE
2 ? UM ? 0 RE ? ?
iE t
UM ? RM ?i E
RV - 1,88V
? 20k?
2 UM
RM ? 375 ?
? UM ~
1 RE ? 5k?
U H ? ? 50V 0,75V RE
t

- 0,75V

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 174
Power Transmission and Distribution ISPSE

Need for Reverse Power Protection

Turbine

Active power Situations:

G Network • Steam loss of the turbine


(e. g. valve leakage)
iL1,iL2,iL3 uL1,uL2,uL3
• Normal shutdown of the unit
Protection Device (opening of the valves)

• In both cases an active power is flowing from the network to the generator,
generator runs as a motor and drives the turbine

• This condition leads to overheating of the turbine blades

• The network circuit breaker must be interrupted in a short time

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 175
Power Transmission and Distribution ISPSE

Ranges of Reverse Power

Turbine

Active power

P mach
steam turbine: (1 ? 3)%
Network
S N ,mach
G
P mach
gas turbine: (3 ? 5)%
iL1,iL2,iL3 uL1,uL2,uL3 S N ,mach

diesel drive: P mach


Protection Device ? 5%
S N , mach

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 176
Power Transmission and Distribution ISPSE

Unbalanced Load (or Negative Sequence) Protection

Negative Overheating
Physics:
sequence of the rotor

Results:
1. The negative sequence heats the rotor
2. This heating is the reason for using a thermal model
(differential equation first order)
3. The transient behaviour of such a thermal model is an exponential function
(For a step negative sequence, the temperature increases exponentially)
4. The curve, given by generator manufacturer, takes only into consideration
the heating but not the cooling. The simplest form of this curve is
(I2/IN)2 t = C.
5. It's necessary to calculate the parameters (k-factor and time constant)
from the generator manufacturer data

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 177
Power Transmission and Distribution ISPSE

Negative Sequence Curve of a Generator (supplied by Generator Manufacturer)

Formula 1: Formula 2:
[(I2/IN)2 - (K2)2] t = K1 [(I2/IN)2] t = K1

with: I2/IN actual negative sequence


K2 constant permissible negative sequence (0,02 -0.2)
K1 constant depends on the generator design (5 - 30s)
Permissible time [sec.]

10000
Example:

1000 K1 = 10 s
Formula 1 K2 = 0.1
Formula 2
100

10
0 0.1 0.2 0.3 0.4 0.5 0.6

Negative Sequence [p.u.]

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 178
Power Transmission and Distribution ISPSE

Trip Characteristic of the Negative Sequence Function (Unbalanced Load Protection)

Unbalanced load
alarm stage I2>
t

T WARN
Tripping area
Thermal
tripping stage

Unbalanced load
tripping stage I2>>

Thermal
alarm stage
T >>TRIP

I2perm I2>> I2

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 179
Power Transmission and Distribution ISPSE

Reasons for Underexcitation


- Failure of the excitation device
• short circuit in the excitation circuit
ZLoad
• interruption in the excitation circuit
- Maloperation of the automatic voltage regulator
- Incorrect handling of the voltage regulator
(generator, transformer)
- Generator running with capacitive load

GS excitation
3~ device
- Countermeasure:
Underexcitation Protection

Note: This protection is also called


Loss of Field Protection

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 180
Power Transmission and Distribution ISPSE

Capability Curve of a Turbo Generator

0,975
0,975
0,95

0,95

0,85
0,9

0,8
0,9
MW
type of generator: TLRI 108/46
0,85 220
nominal apparent power SN = 200 MVA
nominal voltage VN = 15.750 kV
200 nominal current IN = 7.331 kA
nominal frequency fN = 50.0 Hz
power factor cos? N = 0.8
180 cold-air temperature Tx = 40.00 °C
0,7
0,8
160

140
0,7 0,6
120

0,6 100

80
0,4
60
0,4
40
0,2

cosphi
cosphi

0,2

Q
MVAr 140 120 100 80 60 40 20 0 20 40 60 80 100 120 140 160 180 MVAr

underexcited overexcited

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 181
Power Transmission and Distribution ISPSE

Load Diagram of a Synchronous Machine (Cylindrical-rotor Machine)

turbine limit
steady P
state stator limit
dynamic stability
stability limit
limit
theoretically
limit VP If

SN rotor limit

?N

?N
Q
2
VN
VN
2 Xd
? ; ? SN Xd: synchronous reactance
X 'd
X‘d: transient reactance

underexcited overexcited

The generator capability curve describes


the stability limits of the generator

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 182
in the Case of ISPSE
Power Transmission and Distribution
Per Unit Capability Diagram of a Synchronous Generator
Undervoltage (90% VN)

P [p.u]

1 U=1; I=1;
0.85
U=0.9; I= 1.11
Stability
limit
overexcited
under-excited

Q [p.u]
0.81/xd

1/xd

In the case of an under-voltage the generator capability curve


moves to right and reduces the stability limits of the generator

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 183
Power Transmission and Distribution ISPSE

Definitions for Converting the Generator Diagram into the Admittance Diagram

Complex Power: Admittance:


G: Conductance
? I
S ? V ?I S? P ? jQ Y? Y ? G ? jB
V B: Susceptance

Conversion:
?
I ?V S* P - jQ P Q
Y? ?
? ? ? - j
V ?V V2 V2 V2 V2
In the per unit
+ P + G
representation
P
G? the diagrams are
V2 the same, only
Q there is a phase
B? - 2
Q V B shift in the reactive
+ +
part of 180°
Note: in the per unit calculation is VN = 1

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 184
Power Transmission and Distribution ISPSE
Underexcitation Protection with the Criterion Admittance Y>

? Admittance calculation guarantees a right


char.3 char.2 char.1 behaviour, if the voltages decreases
G[p.u.]
? 3 independent characteristics
and 3 timer

? characteristic 1,2 is adaptated on the


steady state curve;
? additional inquiry of the field voltage
(release a short trip time)
?1
? characteristic 3 is adaptated on the
B[p.u.] ?3 ?2 dynamic stability limit curve
1 1 1
x d3 x d1 x d2
? blocking of the protection at U<25% UN

Settings: Can direct read out from the generator diagram

1 1 1 ? 0.9 ? 1
x d1 ? x
1 2
? 1 = 80° x
d2
x
d1
? 2 = 90° x d3 ? 1 or ? x d ? 3 = 100° or 110°
d
Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 185
Power Transmission and Distribution ISPSE

Differential Interturn Protection – Connection and Settings

Generator Differential Protection


22454 A -F11 7UM622 (87G-A)
0.748 A
30000/1A CT Setting: 30000A Differential S1

2?0.748 A CT Setting: 15000A Differential S2


Loss of Field
Neg. Seq.
777.8 MVA Loss of Synchr.
20 kV Gen Overload
22454 A Gen-Tfr Backup
Generator Interturn Protection
(Transverse Differential Protection)
-F12 7UT612 (87GUP-A)
8981 A
0.748 A CT Setting: 30000A
12000/1A

13472 A
0.748 A
18000/1A CT Setting: 30000A

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 186
Power Transmission and Distribution ISPSE

Impedance Protection

tNetz +? t
I>

Z 1 ? 0,7X T
Z<
0,1s

Z1

G
XG XT
Z<

? Correct measuring of the transformer reactance


? Measuring of a fictitious generator reactance (short circuit at the generator
terminals: U ? 0, I =ISC,G ? Z ? 0)

? Settings value of the protection is the unit transformer reactance


(Requirement: Z1 ? 0,7 · XT)

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 187
Power Transmission and Distribution ISPSE

Scheme with an Impedance or Distance Protection

ZG ZT

ZL

I > (ZG)
t ZT (backward)
ZG
ZL

Z
2. Stage (ZT) ZT

ZG: Generator ZT: Transformer ZL: Line


Transformer Line
Line

? Fast back-up protection for the whole system.


Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 188
Power Transmission and Distribution ISPSE

Basics of the Overexcitation

Protected objects: Transformer and generators

Equivalent network for a transformer

1. Overvoltage
The result of a overvoltage is
LM a higher magnetizing current

2. Underfrequency
A low frequency increases
the magnetizing losses
1 U
Induction: B=
4.44 w A f
w - windings
A - cross section Thermal overheating of iron

BS U/UN
~
BN f/f N A thermal model is required

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 189
Power Transmission and Distribution ISPSE

Basic Idea of Algorithm Design

1. The manufactors give a curve U/f = f (t) U/f

?t isn't possible to describe this with one ln-function.


It's must be a polynom n-th order.

2. A good model to describe a thermal process t


is the differential equation first order
Calculation of the
d ? (t) thermal losses Q
Q= ? + ? (t)
dt
? thermal time constant transformation
U
(tx)
? actual temperature f 1
Q
Q=
Q thermal losses curve (1 - exp(-tx/ ?)

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 190
Power Transmission and Distribution ISPSE
Trip Characteristic of the Overexcitation Function

Tripping area

Thermal
tripping stage

Definite time
tripping stage U/f>

Thermal
warning stage
TU/f>

U/f (1) U/f> U/f


(1st setting value of (Setting value of
thermal characteristic) definite time stage)

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 191
Power Transmission and Distribution ISPSE

Why Out of Step Protection is necessary ?

Xd XTr
Stiff system
XN U= const.
Tm ?

Protection

1. If generator feeds into the short circuit too long, the rotor accelerates
and the permissible angle ? perm.exceeds the limit

2. Active power swings appears after the clearing of the short circuit,
because the generator had fallen out of step

3. If the out of step condition persists for a long time, inadmissible


mechanical (torsional vibration) and thermal stress of the system
(generator, turbine) appears

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 192
Power Transmission and Distribution ISPSE

Equivalent Circuit for the Out of step condition

Measuring point
X’d Protection X
T XN
R

ZG ZT ZN U‘N Measured Impedance:


U’p UR
U 'P Z
ZR ? ' - ZG
UP ? UN '

'
UN U 'N - jd
Z ? ZG ? ZT ? Z N '
? ' e
ZG Generator UP UP
impedance
ZT Transformer- ? Z
impedance ZR ? '
- ZG
U ZR = f(?)
ZN Network 1 ? N' e - jd
impedance UP

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 193
Power Transmission and Distribution ISPSE

Why Inadvertent Energization Protection?

ns

Protection
io
at
tu
Si

1. The generator stands still or rotates but it is not energized (or is


being energized). The circuit breaker is closed through a
maloperation (e.g. in 1 1/2 CB-schemes).

2. Arc flashover on the circuit breaker before synchronisation or


during shut down of the generator.

Damage of Generator due to the high current stress


(Generator starts to run as a asynchronous motor or
situation is similar to a wrong synchronisation).
Damage of turbine is also possible.
(Protection mainly used in USA)
Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 194
Power Transmission and Distribution ISPSE

Measuring Principle of Inadvertent Energization Protection (ANSI 50/27 - IEC I> and U<)

1. For a fast reaction, an instantaneous current measuring


principle is used. In that case a trip delay of approx. 25 ms is
possible.

2. The positive sequence voltage and the detected changing


into the operational condition 1 (valid measured quantities
are available; conditions: U> 0.1 Un or I > 0.1In and f > 10Hz)
blocks the overcurrent function.

3. A timer with a pick-up and drop out delay controls the


reaction of the protection function.

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 195
Power Transmission and Distribution ISPSE

Recommendations for Protection Functions


Protection ANSI /IEEE) Generator – Rated Power (MVA)
<5 5 - 50 50 - 200 > 200
Stator earth fault 90 % 64, 59N, 67N X X X X
Stator earth fault 100 % 64(100%) X X
Differential 87G, 87T o X X X
Overcurrent time 50, 51V X X o o
Impedance 21 X X
Interturn fault X
Rotor earth fault 64R o X X X
Unbalanced load 46 X X X
Underexcitation 40 o X X X
Out of step 78 X
Stator overload 49 X X X X
Rotor overload 49R X
Overvoltage 59 X X X X
Frequency f > 81 X X X X
Frequency f < 81 X X X
Reverse power 32 X X X X
Undervoltage 27 Y Y Y Y
Overexcitation (U/f) 24 o X X
Y: Pump storage stations (motor /phase shift operation
o option
Copyright © SIEMENS AG PTD EA 2007. All rights reserved.
Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 196
Power Transmission and Distribution ISPSE

Tripping Concept (Matrix)


The number of breakers, the generator protection has to trip
depends on the fault type, the plant design and plant operation,
generator operation and general operation philosophy of the client .

? Generator Breaker
? Excitation Breaker
Breakers
? Turbine Rapid Shut Down

Protection Functions
? HV Network Breaker
? Auxiliary Supply Breaker 1
? Auxiliary Supply Breaker 2
? Aux. Supply Changeover
? SEE/SFC, Unit-trafo
? SEE/SFC, Aux.-Trafo
? Reserve
? Special Trips at Hydro
Stations (e.g. braking)

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 197
Power Transmission and Distribution ISPSE

Redundancy Concepts (Large Units) : Each Object Protected by 2 Devices

Protection Group A Protection Group B

7UM6 7UM6

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 198
Power Transmission and Distribution ISPSE

Alternatives to Full Redundancy

Without Redundancy Partly Redundant


(also limitations of the Ct’s and Vt’s
and trip circuits)

7UM62

7UM62
7UM61
G
G

Investment cost optimisation


System/-cost optimisation

Copyright © SIEMENS AG PTD EA 2007. All rights reserved.


Energy Automation : Faults , Stability and Protection Principles
PTD-EA/TCE_IN_2.1/STAB / 199

You might also like