Manual Installation LDM Lamp Driver Installation Sheet Rev A

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

9 Columbia Way

Baulkham Hills, NSW 2153


PH 02-9894-1444 • FAX 02-9894-4193
www.notifier.com.au

LDM Lamp Driver


Installation Sheet - Released
26/03/2015 Rev A
DOC-03-091

1 Product Overview
The LDM Lamp Driver Modules (LDM-32, LDM-E32, and LDM-R32) are used to drive lamps or LEDs in a
custom mimic connected to an addressable fire panel.

2 Installation

WARNING: Remove all power sources to the panel before installation. Leave the
external and main power OFF until installation is complete.

2.1 Mounting a LDM Module to a CHS Chassis


1. Screw two 3/4” stand-offs onto the mounting studs of a CHS chassis.
2. Place the module on the CHS chassis. Ensure the tab on the module slides into the slot on the
CHS chassis.
3. Secure the module with two 4-40 screws.

Figure 2-1 - Mounting the LDM to a CHS Chassis

2.2 Mounting a LDM Relay Expander


The LDM-R32 can either be mounted alongside a LDM module or expander in the CHS chassis (see
section 2.1 for CHS mounting), or stacked on top of a LDM module using the standoffs provided (see Figure
2-2.)
Make sure to connect the Relay Power Ribbon Cable between the LDM-R32 and the LDM Module, as
shown in Figure 2-3.

Page 1 of 4
Relay Power Ribbon Cable connection
LDM-32
(or LDM-E32) J5 J6 J7 J8

J11
LDM-R32 J10
J5 J6 J7 J8 9.;>
J10>=D2? J9
K1 K32
Standoff Standoff
K2 K31
TB4
TB1 K3 K30
1 1
2 2
3
K4 K29 3
4 4
5 K5 K28 5 J2
6 6
Chassis LDM-32 LDM-R32 7 K6 K27 7
(or LDM-E32) 8 8

Figure 2-2 – Mounting a LDM-R32 on top of Figure 2-3 - Connecting the Relay Power
a LDM Module Ribbon Cable

2.3 Connections

NOTE: When cables are not run in a conduit, shielding on cables for EIA-485
connections must be grounded outside the enclosure and fire panel. See the LDM
Series Instruction Manual for more information.

IN
OUT 120 CPU Board
OUT EOL
NC Supervision 7 Last IN
Inputs 6 LDM-32
IN 5
OUT 4
IN 3
OUT 2 IN
EGnd 1 OUT
OUT

NC Supervision 7 IN
Inputs 6
IN 5
OUT 4
IN 3 IN
OUT 2 OUT
EGnd 1
OUT
First IN
LDM-32
NC Supervision 7
Inputs 6
IN 5
OUT 4
IN 3
OUT 2
EGnd 1

Figure 2-4 – Power (TB1) and ACS Comms (TB2) connections to the CPU

Figure 2-5 - Connecting LDM-E32 expander modules with the ribbon cable

Page 2 of 4
Point Status LEDs: Point Status LEDs:
Use RED for Alarm points Use RED for Alarm points System
YELLOW for Trouble points, and System YELLOW for Trouble points, and
GREEN for Output points.
Trouble LED
GREEN for Output points. Trouble LED (Yellow)
(Yellow)

Use 680 , 1.4 W resistors Use 10K , 1.4 W resistors


for each point if using 2 mA LEDs. for each point if using 2 mA LEDs.

Custom Custom
J5 J6
Graphic Graphic
J7
J11 J8 Display Display
+5
J4 Common
J10

LAMP J9
SWITCH POWER

Figure 2-6 - Lamp/LED Wiring for 5 V DC Figure 2-7 - Lamp/LED Wiring for 24 V DC

NOTE: All LEDs must be in the same room as the LDM modules.

3 Configuration
3.1 Setting the Address and Operating Modes

Lamp Driver Address Ones


SW4
Set in the range 02-32
Tens
ALARM/TROUBLE mode
O1
F
F

DIP Switch SW3


2
3
4

SW4
5
6

Switch set to
7

OFF position
8

ALARM ONLY mode

LDM-32

Figure 3-1 - Rotary address & DIP switches on the LDM-32

NOTE: The available address range for the LDM-32 is 2-32 (inclusive.)

1. Set a unique address for the LDM-32 using the rotary address switches along the side of the
module.
2. Set the operating mode using the DIP switches on the LDM-32. See Table 1 for a description of the
switch functions.
3. Configure annunciator points via the panel’s keypad or through VeriFire Tools. Refer to the panel’s
Programming Manual for further information on programming the annunciator.

Page 3 of 4
Switch Switch Default
Description
Bank No. Setting
1 OFF Turn ‘ON’ when the lamp driver is used to control relays.
2 OFF Configures the number of expander modules.
See Table for details.
3 OFF
4 OFF Not used.
Turn ‘ON’ for Receive Only mode, to mirror another LDM at the
5 OFF
SW3 same address in a different location.
Turn ‘ON’ for Piezo Disable, to disable the buzzer from sounding
6 OFF
for any event.
Turn ‘ON’ for Switch Inhibit, to disable point control switches on
7 OFF
the annunciator.
Turn ‘ON’ for Flash Inhibit, to disable the flashing of LEDs for
8 OFF unacknowledged events. Also disables piezo.
N.B.: Flash Inhibit must be ON when using the LDM-R32.
Table 1 – DIP Switches and Default Settings

No. DIP Switch Settings


O 2 3
F
None F

O 2 3
F O 1 2
1 F F
F

O 2 3
F ON OFF
2 F
Position Position
O 2 3
F
3 F

Table 2 - Number of Expanders

4 Supplemental Documentation

For information on... Refer to... Doc No.


Operating modes LDM Series Instruction Manual 15885
Programming AFP-3030 Australian Programming Manual DOC-01-032
AFP-3030 New Zealand Programming Manual DOC-01-038
XLS-3000A Australian Programming Manual DOC-01-035
XLS-3000A New Zealand Programming Manual DOC-01-041
Notifier NCA-2 Australian Manual DOC-01-043
Notifier NCA-2 New Zealand Manual DOC-01-045
Honeywell NCA-2 Australian Manual DOC-01-044
Honeywell NCA-2 New Zealand Manual DOC-01-046

Table 3 - Supplemental Documentation

Page 4 of 4