LIGHTING/POWER CIRCUIT LOAD SCHEDULE (GROUND FLOOR) LIGHTING/POWER CIRCUIT LOAD SCHEDULE (SECOND FLOOR)

CIRCUIT LIGHTING POWER C.B. CIRCUIT LIGHTING POWER C.B.


VOLT COMPUTATION WATTS REMARKS VOLT COMPUTATION WATTS REMARKS
NO. OUTLET OUTLET AMPS. NO. OUTLET OUTLET AMPS.

1 16 220 I=
15x 16 =1.09 Amps.
220
240 15 Amps. 2-2.0mm² TW CU WIRE INSIDE 15mmØ PVC 1 14 220 I=
15x14 =0.95 Amps.
220
210 15 Amps. 2-2.0mm² TW CU WIRE INSIDE 15mmØ PVC

2 16 220 I=
15 x 16
220
=1.09 Amps. 240 15 Amps. 2-2.0mm² TW CU WIRE INSIDE 15mmØ PVC 2 14 220 I=
15x14
220
=0.95 Amps. 210 15 Amps. 2-2.0mm² TW CU WIRE INSIDE 15mmØ PVC

3 16 220 I=
15 x 16 =1.09 Amps.
220
240 15 Amps. 2-2.0mm² TW CU WIRE INSIDE 15mmØ PVC 3 14 220 I=
15x14 =0.95 Amps.
220
210 15 Amps. 2-2.0mm² TW CU WIRE INSIDE 15mmØ PVC

4 08 220 I=
15 x
220
08 =0.55 Amps. 120 15 Amps. 2-2.0mm² TW CU WIRE INSIDE 15mmØ PVC 4 14 220 I=
15x14
220
=0.95 Amps. 210 15 Amps. 2-2.0mm² TW CU WIRE INSIDE 15mmØ PVC

5 04 220 I=
4 x 200 =3.64 Amps.
220
800 30 Amps. 2-3.5mm² TW CU WIRE INSIDE 15mmØ PVC 5 08 220 I=
8x 200 =7.27 Amps.
220
1600 30 Amps. 2-3.5mm² TW CU WIRE INSIDE 15mmØ PVC

6 07 220 I=
7 x 200
220
=6.36 Amps. 1400 30 Amps. 2-3.5mm² TW CU WIRE INSIDE 15mmØ PVC 6 06 220 I=
6 x 200
220
=5.45 Amps. 1200 30 Amps. 2-3.5mm² TW CU WIRE INSIDE 15mmØ PVC

7 07 220 I=
7 x 200 =6.36 Amps.
220
1400 30 Amps. 2-3.5mm² TW CU WIRE INSIDE 15mmØ PVC 7 09 220 I=
9 x 200 =8.18 Amps.
220
1800 30 Amps. 2-3.5mm² TW CU WIRE INSIDE 15mmØ PVC

8 04 220 I=
4 x
220
200 =3.64 Amps. 800 30 Amps. 2-3.5mm² TW CU WIRE INSIDE 15mmØ PVC 8 09 220 I=
9 x
220
200 =8.18 Amps. 1800 30 Amps. 2-3.5mm² TW CU WIRE INSIDE 15mmØ PVC
23.82 Amps. USING 60 Amps. TRIP BREAKER IS SAFE! 32.88 Amps. USING 60 Amps. TRIP BREAKER IS SAFE!

INDUSTRIAL LIGHTING/ACU LOAD SCHEDULE (GROUND FLOOR) ACU LOAD SCHEDULE (SECOND FLOOR)
CIRCUIT INDUST. ACU C.B. CIRCUIT ACU C.B.
VOLT COMPUTATION WATTS REMARKS VOLT COMPUTATION WATTS REMARKS
NO. LIGHTING OUTLET AMPS. NO. OUTLET AMPS.

1 04 220 I=
04x60 =1.09 Amps.
220
240 15 Amps. 2-2.0mm² TW CU WIRE INSIDE 15mmØ PVC 1 01 220 I=
1 x 1127=5.12 Amps.
220
1127 30 Amps. 2-3.5mm² TW CU WIRE INSIDE 15mmØ PVC

2 04 220 I=
04x60
220
=1.09 Amps. 240 15 Amps. 2-2.0mm² TW CU WIRE INSIDE 15mmØ PVC 2 01 220 I=
1 x 1127
220
=5.12 Amps. 1127 30 Amps. 2-3.5mm² TW CU WIRE INSIDE 15mmØ PVC

3 04 220 I=
04x60 =1.09 Amps.
220
240 15 Amps. 2-2.0mm² TW CU WIRE INSIDE 15mmØ PVC 3 01 220 I=
1 x 1127=5.12 Amps.
220
1127 30 Amps. 2-3.5mm² TW CU WIRE INSIDE 15mmØ PVC

4 04 220 I=
04x60 =1.09 Amps.
220
240 15 Amps. 2-2.0mm² TW CU WIRE INSIDE 15mmØ PVC 4 01 220 I=
1 x 1127=5.12 Amps.
220
1127 30 Amps. 2-3.5mm² TW CU WIRE INSIDE 15mmØ PVC

5 01 220 I=
1 x 1127=5.12 Amps.
220
1127 30 Amps. 2-3.5mm² TW CU WIRE INSIDE 15mmØ PVC 5 01 220 I=
1 x 1127=5.12 Amps.
220
1127 30 Amps. 2-3.5mm² TW CU WIRE INSIDE 15mmØ PVC

6 01 220 I=
1 x 1127=5.12 Amps.
220
1127 30 Amps. 2-3.5mm² TW CU WIRE INSIDE 15mmØ PVC 6 01 220 I=
1 x 1127=5.12 Amps.
220
1127 30 Amps. 2-3.5mm² TW CU WIRE INSIDE 15mmØ PVC

7 01 220 I= 1 x 1127
220
=5.12 Amps. 1127 30 Amps. 2-3.5mm² TW CU WIRE INSIDE 15mmØ PVC 7 01 220 I= 1 x 1127
220
=5.12 Amps. 1127 30 Amps. 2-3.5mm² TW CU WIRE INSIDE 15mmØ PVC

8 01 220 I=
1 x 1127=5.12 Amps.
220
1127 30 Amps. 2-3.5mm² TW CU WIRE INSIDE 15mmØ PVC 8 01 220 I=
1 x 1127=5.12 Amps.
220
1127 30 Amps. 2-3.5mm² TW CU WIRE INSIDE 15mmØ PVC

9 01 220 I=
1 x 1127=5.12 Amps.
220
1127 30 Amps. 2-3.5mm² TW CU WIRE INSIDE 15mmØ PVC 9 01 220 I=
1 x 1127=5.12 Amps.
220
1127 30 Amps. 2-3.5mm² TW CU WIRE INSIDE 15mmØ PVC
29.96 Amps. USING 100 Amps. TRIP BREAKER IS SAFE!
10 01 220 I=
1 x 1127=5.12 Amps.
220
1127 30 Amps. 2-3.5mm² TW CU WIRE INSIDE 15mmØ PVC
1 x 1127
WORKBAY SERVICE PIT CIRCUIT LOAD SCHEDULE 11 01 220 I=
220
=5.12 Amps. 1127 30 Amps. 2-3.5mm² TW CU WIRE INSIDE 15mmØ PVC

12 01 220 I=
1 x 1127
220
=5.12 Amps. 1127 30 Amps. 2-3.5mm² TW CU WIRE INSIDE 15mmØ PVC
CIRCUIT C.B. 61.44 Amps. USING 100 Amps. TRIP BREAKER IS SAFE!
OUTLET VOLT COMPUTATION WATTS REMARKS
NO. AMPS.
COMPUTATION ANALYSIS:
1 12 220 I=
12x200
220
=10.91 A. 2400 30 Amps. 2-3.5mm² TW CU WIRE INSIDE 15mmØ PVC
It = 23.82+29.96+32.88+61.44+43.64
2 12 220 I=
12x200
220
=10.91 A. 2400 30 Amps. 2-3.5mm² TW CU WIRE INSIDE 15mmØ PVC =191.74 x 0.70 DF
3 12 220 I=
12x200
220
=10.91 A. 2400 30 Amps. 2-3.5mm² TW CU WIRE INSIDE 15mmØ PVC It =134.22 A.

4 12 220 I=
12x200
220
=10.91 A. 2400 30 Amps. 2-3.5mm² TW CU WIRE INSIDE 15mmØ PVC USE: 80 MM² THW. CU. WIRE AND 150 A.
43.64 Amps. USING 60 Amps. TRIP BREAKER IS SAFE! MAIN DISCONNECTING SWITCH

ELECTRICAL NOTES:
1. ALL ELECTRICAL WORKS AND INSTALLATION HEREIN SHALL CONFORM WITH THE LATEST APPROVED EDITION OF THE
ELECTRICAL CODE, RULES AND REGULATIONS OF THE LOCAL AND NATIONAL AUTHORITIES CONCERNED IN THE ENFORCEMENT OF
ELECTRICAL LAWS AND ORDINANCES.

2. ADEQUATE AND EFFECTIVE GROUNDING SHALL BE PROVIDED TO ALL METALLIC CONDUITS, CABINETS, ENCLOSURES AND
EQUIPMENTS BY MEANS OF COPPERCLAD GROUNDING RODS.

3. NO BRANCH CIRCUIT SHALL HAVE A LOAD OF MORE THAN 80% OF ITS RATING.

4. ELECTRICAL SERVICE REQUIREMENTS SHALL BE 220 VOLTS, 3-PHASE, 60 HERTZ.

5. ALL SINGLE PHASE LOADS SHALL BE SO CONNECTED TO EFFECT A BALANCED THREE PHASE SYSTEM.

6. ALL MATERIALS TO BE USED SHALL BE NEW AND APPROVED TYPE FOR BOTH PURPOSE AND LOCATION INTENDED. ALL WIRES
SHALL BE INSULATED FOR 600 VOLTS. TYPE THW. OR TW AND SHALL BE INSIDE RIGID UPVC PIPES FOR EMBEDDED PIPE.
EMT/IMC FOR EXPOSE PIPES. CIRCUIT BREAKER PANEL BOARD SHALL BE STANDARD FACTORY PRODUCTS. ALL CIRCUIT
BREAKERS SHALL BE BOLT-ON TYPE.

7. WORKMANSHIP SHALL BE EQUAL TO THE BEST STANDARD PRACTICE RECOGNIZED AND ADOPTED FOR THIS TRADE.
PROJECT LOCATION MAP
8. ALL ELECTRICAL WORKS AND INSTALLATION HEREIN SHALL BE DONE UNDER THE DIRECT SUPERVISION OF A DULY LICENSED
ELECTRICAL ENGINEER OR HIS REPRESENTATIVE. SCALE = N.D.T.S.

PREPARED BY: PROJECT NAME: CHECKED BY: APPROVED BY: SHEET NO.

V.M.JHEK BUILDERS
LICENSED CIVIL ENGINEER
REG. NO.: TIN NO.:
PROPOSED WORKSHOP AND WAREHOUSE -
DAVAO CITY
S
PTR. NO.: DATE: CIVIC MERCHANDISING INC. 33
CONTRACTOR ISSUED AT: LOCATION: DAVAO CITY OWNER

You might also like