Main Catalogue 7 Circuit Breakers ACB MCCB
Main Catalogue 7 Circuit Breakers ACB MCCB
MC ACCESSORIES
398
SELECTIVITY TABLE
410
381
KAPITEL_07_AK2 25.03.2005 11:51 Uhr Seite 382
W UNIFORM DIMENSIONS
The MO has a uniform component height and depth over it´s whole
current spectrum. Only the component width varies with the number
of poles and the frame size. Fixed and withdrawable versions have
the same width.
WTERMINATIONS
MO Air Circuit Breakers up to 5000 a come with horizontal connec-
tions, and MO 6300 A with vertikal connections, as standard. The fol-
lowing termination options are available: vertical connection, front
connections and flanged.
mo2.eps
382
mo3.eps
W SHORT-CIRCUIT CAPACITY
383
pfeilskizze 2.eps
W SELECTIVITY MO / MC
mo_over.eps
384
KAPITEL_07_AK2 25.03.2005 11:51 Uhr Seite 385
9)
1)
2) 60,5
5) 4) 8)
33,5
a
275
439,5
541,5
434
327,5
461,5
3)
275
123,5
150
a
5,5
76
270 15
300 10 45
390 150 6)
mo_dim1.eps 210 106
230 127
mo_dim2.eps
90 90 90 90
35
55 ¯ 13,5
11)
!
7)
7) 3)
¯M8
139 58
320 $ ' ' '
410 mo_dim4.eps
386
mo_dim3.eps
1250Ð1600 15 15 15
mo_leg1_4.eps
KAPITEL_07_AK2 25.03.2005 11:51 Uhr Seite 387
320 7) 8)
270 9)
5) 4)
327,5
460
3)
275
275
465,5
150
a
10)
76
220 45
123,5
367,5 58
382,5 88,5 6)
121,5
10) 13 30 140,5
210 55
300 mo_dim6.eps
mo_dim5.eps
38
55 55 55 55
¯ 13,5
!
11)
139
270 25 #
320
410 ## ' ' '
387
mo_dim7.eps mo_dim8.eps
! "
#
$ %&'
( %&'
) %&'
*+ , *+
*-+.*!++ * * *
mo_leg5_8.eps
KAPITEL_07_AK2 25.03.2005 11:51 Uhr Seite 388
1)
2)
5) 4)
a
541,5
275
451,5
327,5
435,5
3)
434
275
123,5
150
a
76
10 5,5
270 85 45
440 150 6)
570 210 106
230 127
mo_dim9.eps
mo_dim10.eps
30
11) !
7)
7)
M8
139 128
460 ' ! ! !
590
388 mo_dim11.eps mo_dim12.eps
-- -
-- - - -
mo_leg9_12.eps
KAPITEL_07_AK2 25.03.2005 11:51 Uhr Seite 389
5) 4) 7) 8)
9)
327,5
460
275
465,5
461
275
150
a
76
123,5
40,5 220 45
367,5 58
270 10) 382,5 88,5
10) 121,5
350 55 140,5
480
mo_dim14.eps
mo_dim13.eps
¯ 13,5
11)
!
139 138
270 95
460
590 ## "# ! ! !
389
mo_dim15.eps
mo_dim16.eps
! "
#
$ %&'
( %&'
) %&'
*+ , *+
-++ * * -+
-++ + + -+
mo_leg13_16.eps
KAPITEL_07_AK2 25.03.2005 11:51 Uhr Seite 390
W COMPACT STYLE
Their compact size enables the existing mounting space to be optimally utilized, saving precious equipment fitting capa-
city in the panel. The MO, up to a rated current of 1600 A for example, can be fitted into a 400 mm wide panel sec-
tion. Up to a rated current of 6300 A, a section width of 800 mm suffices.
W AUXILLIARY BUILT IN
DESCRIPTION TYPE ORDER NO.
Overcurrent relais LI ETU15 MO890150—
Overcurrent relais LSI ETU25 MO890250—
Overcurrent relais LSNIG ETU27 MO890270—
Overcurrent relais universal ETU45 MO890450—
Overcurrent relais digital ETU76 MO890760—
mc_titel.eps
w TECHNICAL DATA
• Protects systems, cables, motors & generators
• Rated uninterrupted current up to 1600A
• 3 and 4-pole design
• Switching capacity 25, 50, 100, 150 kA
• Electrical and thermo-magnetic releases
• Adjustable releases for overload and short-circuit
• Adjustable time selectivity
• Earth fault protection
w NOTE:
With main switch characteristicsin accordance with IEC/EN 60204 and isolating characteristics in accordance with
IEC/EN 60947, VDE 0660.
392 For 4-pole version and additional technical details, refer to the Special Catalogue K-LEISTMC-3.
Operating instructions and additional measured diagrams are available on our homepage: www.schrack.com
KAPITEL_07_AK2 25.03.2005 11:51 Uhr Seite 393
w TECHNICAL DATA
• Adjustable overload release Ir:
0.8 – 1 x In (ex-factory 0.8 x In)
• Adjustable short-circuit release Ir:
6 – 10 x In (ex-factory 6 x In) MC.-A40: 8 - 10 x In
• Lift terminals as standard for MC1, screw terminals as accessories
mc2-a160.eps mc110231.eps • Screw terminals as standard for MC2, lift terminals as accessories
• Switching capacity 25 / 50 / 100 kA at 415 V 50/60 Hz
w CERTIFICATIONS
IEC/EN 60947-2
w TECHNICAL DATA
• RMS value and “thermal memory”
• Adjustable overload release Ir: 0.5 – 1 x In (ex-factory 0.8 x In)
• Adjustable short-circuit release Ir: 2 – 12 x In (ex-factory 6 x In)
• for MC3...-AE250/400: 2 – 11 x In (ex-factory 6 x In)
• for MC3....-AE630: 2 – 8 x In (ex-factory 6 x In)
mc3-ae250.eps • Switching capacity 25 / 50 / 100 kA at 415 V 50/60 Hz
• Screw terminals as standard, lift terminals as accessories for MC2/MC3
w CERTIFICATIONS
IEC/EN 60947-2
w TECHNICAL DATA
• Adjustable overload release Ir: 0.8 – 1 x In (ex-factory 0.8 x In)
• Adjustable short-circuit release Ir: 6 – 10 x In (ex-factory 6 x In); MC..-4-A40 8 - 10 x In
• Lift terminals as standard for MC1, screw terminals as accessories
• Screw terminals as standard for MC2, lift terminals as accessories
• Switching capacity 25 / 50 / 100 kA at 415 V 50/60 Hz
w CERTIFICATIONS
IEC/EN 60947-2
w TECHNICAL DATA
• RMS value and “thermal memory”
• Adjustable overload releases Ir: 0.5 – 1 x In (ex-factory 0.8 x In)
• Adjustable short-circuit releases li: 2 – 12 x In (ex-factory 6 x In)
• For MC3...-AE250/400: 2 – 11 x In (ex-factory 6 x In)
• For MC3....-AE630: 2 – 8 x In (ex-factory 6 x In)
• Switching capacity 25 / 50 / 100 kA at 415 V 50/60 Hz
• Screw terminals as standard, lift terminals as accessories for MC2/MC3
w CERTIFICATIONS
IEC/EN 60947-2
396
W 4-POLE, ELECTRONIC DELAYED RELEASES
w TECHNICAL DATA
• RMS value and “thermal memory”
• Adjustable overload release Ir: 0.5 – 1 x In (ex-factory 0.8 x In)
• Adjustable time delay setting to overcome current peaks tr: 2 – 20 s at 6 x Ir as well as infinity (without overload
release; ex-factory 10 s)
• Adjustable delayed short-circuit release Isd: 2 – 10 x Ir (ex-factory 6 x Ir)
• MC3...-4-VE630: 2 – 7 x Ir (ex-factory 6 x Ir)
• Adjustable delay time tsd: Steps: 0, 20, 60, 100, 200, 300, 500, 750, 1000 ms (ex-factory 0)
• Adjustable non-delayed short-circuit release Ii: 2 – 12 x In (ex-factory 12 x In)
• MC2 fixed 12 xIn
• MC3...-4-VE400: 2 – 11 x In (ex-factory 6 x In)
• MC3...-4-VE630: 2 – 8x In (ex-factory 6 x In)
• Switchable i2t-constant function (ex-factory: OFF) MC3/MC4
• Screw terminals as standard, lift terminals as accessories for MC2/MC3
w CERTIFICATIONS
IEC/EN 60947-2
w TECHNICAL DATA
• Rated uninterrupted current up to 1600A
• Switch disconnectors MC1-PN, two switch positions 0/1, cannot be tripped remotely
• Switch disconnector MC1-N, with trip setting, can be tripped remotely with U/A voltage
release
• 3 and 4-pole design
mc1-pn.eps • Main switch characteristics including positive drive to IEC/EN 60204 and VDE 0113
• Isolating characteristics according to IEC/EN 60947-3 and VDE 0660 protection against
accidental contact according to VDE 0160 part 100
• U/A voltage releases and trip-indicating auxillary contacts can also be used with MC...-N
switch disconnectors.
• MC2/3/4-N... can be combined with the MC-XR... remote operator.
• Lift terminals as standard for MC1, screw terminals as accessories
• Screw terminals are standard for MC2/MC3/MC4,
lift terminals are accessories for MC2/MC3
w NOTE:
Operating instructions and measured diagrams are available on our homepage:
www.schrack.com
RATED CURRENT/MAX. FUSE AGL DIM. (WxHxD) PU TYPE WEIGHT ORDER NO.
63 A/125 A 90x145x84,5 1 MC1-PN-63 1,046 MC163034—
100 A/125 A 90x145x84,5 1 MC1-PN-100 1,046 MC110034—
125 A/125 A 90x145x84,5 1 MC1-PN-125 1,046 MC112034—
160 A/250 A 105x84x149 1 MC2-PN-160 2,345 MC216034—
200 A/250 A 105x84x149 1 MC2-PN-200 2,345 MC220034—
397
250 A/250 A 105x84x149 1 MC2-PN-250 2,345 MC225034—
400 A/630 A 140x275x166 1 MC3-PN-400 6,34 MC340034—
630 A/630 A 140x275x166 1 MC3-PN-630 6,34 MC363034—
with remote trip
63 A/125 A 90x145x84,5 1 MC1-N-63 1,046 MC163035—
100 A/125 A 90x145x84,5 1 MC1-N-100 1,046 MC110035—
125 A/125 A 90x145x84,5 1 MC1-N-125 1,046 MC112035—
160 A/250 A 105x84x149 1 MC2-N-160 2,345 MC216035—
200 A/250 A 105x84x149 1 MC2-N-200 2,345 MC220035—
250 A/250 A 105x84x149 1 MC2-N-250 2,345 MC225035—
400 A/630 A 140x275x166 1 MC3-N-400 6,34 MC340035—
630 A/630 A 140x275x166 1 MC3-N-630 6,34 MC363035—
800 A/1600 A 210x401x207 1 MC4-N-800 21 MC480035—
1000 A/1600 A 210x401x207 1 MC4-N-1000 21 MC410035—
1250 A/1600 A 210x401x207 1 MC4-N-1250 21 MC412035—
1600 A/1600 A 210x401x207 1 MC4-N-1600 21 MC416035—
MC ACCESSORIES
w TECHNICAL DATA
• Breaking capacity: AC15, 230 V 4A
DC13, 24 V 3A
w MAXIMUM PERMISSIBLE
mm216378.eps
MC 1 MC 2 MC 3 MC 4
Normal auxiliary contact
1 2 3 3
1 NO oder 1 NC
Trip-indicating contact
1 1 1 2
1 NO oder 1 NC
Early make
1 1 1 1
auxiliary contact 2 NO
w TECHNICAL DATA
Can be clipped onto the main switch:
• MC1 - one standard auxiliary contact
• MC2 - up to 2 standard auxiliary contacts M22-(C)K...
• MC3,4 - up to 3 standard auxiliary contacts M22-(C)K...
w RANGE OF APPLICATION
Switches with the main contacts. Used for signalling and interlocking circuits.
w TECHNICAL DATA
Can be clipped onto the main switch:
• MC1 - one trip-indicating auxiliary contact
• MC2 - one trip-indicating auxiliary contact M22-(C)K...
• MC3 - one trip-indicating auxiliary contact M22-(C)K...
• MC4 - up to 2 trip-indicating auxiliary contacts M22-(C)K...
w RANGE OF APPLICATION
Indicates trip “+” through voltage release, overload- or short-circuit release
MC ACCESSORIES
w TECHNICAL DATA
• Cannot be used in conjunction with XR-MC remote release unit or undervoltage units or shunt trips
w RANGE OF APPLICATION
For interlocking and load-shredding circuits
W UNDERVOLTAGE RELEASES
w TECHNICAL DATA
• W/o auxiliary contacts
• Non-delayed disconnection of MCCBs or MC-N switch disconnectors when the control
voltage drops below 35 % - 70% Us.
• For use in Emergency Stop units in conjunction with Emergency Stop button
• Built into switch
mc199471.eps
MC ACCESSORIES
W UNDERVOLTAGE RELEASES
WITH TWO EARLY MAKE AUXILIARY CONTACTS
w TECHNICAL DATA
• With 2 early make auxiliary contacts
• For early make of undervoltage release when using main switches and
for interlocking and load-shredding circuits
• Built into switch
• Other voltages and variants available to order
W SHUNT TRIPS
w RANGE OF APPLICATION
• W/o auxiliary contacts
• Switches are tripped by voltage pulse or switch-on of uninterrupted voltage
w NOTE
When the undervoltage release is in a de-energized state, accidental contact with the main
contacts of the switch during attempts to switch on is safely prevented. Shunt trip cannot
400 mc199744.eps
MC ACCESSORIES
mc2-xdv.eps mc3-xdv.eps
w TECHNICAL DATA
• Complete with rotary drive
• Sizes 1 and 2 can also be combined with insulating surround
• Rotary handle can be rotated up to 90° for switches in lying position
• Available in the following variants:
Main switch, black/grey:
• Standard MC.-XD
• MC.-XDV switch is lockable in Off position (up to 3 padlocks)
• With door interlock, lockable in Off or On position. MC.-XDTV (up to 3 padlocks)
In the ON position, can be defeated using a 1mm pin, door cannot be defeated in the locked ON and OFF positions.
In the Off position when the door is closed, can be switched on with red/yellow emergency stop switch:
• MC.-XDVR switch is lockable in Off position (up to 3 padlocks)
• With door interlock, lockable in Off or On position. MC.-XDTVR
In the ON position, can be defeated using a 1mm pin, door cannot be defeated in the locked ON and OFF positions.
Can be switched on when door is closed
MC ACCESSORIES
w TECHNICAL DATA
• Complete with rotary drive and interlocking device
• Degree of protection IP66
• MC.-XTD
Standard, non lockable, black/grey
• MC.-XTVD, MC.-XTVDV, MC.-XTVDVR
• Cannot be defeated in locked OFF and ON positions.
• Can be modified such that it can be defeated from the outside using a screwdriver when in the unlocked ON position
• Door can only be opened in OFF position
MC.-XTVD: Can be locked in Off posiiton on handle, can also be modified in On position, black/grey
MC.-XTVDV : Can also be locked on switch in Off position, black/grey
MC.-XTVDVR: Can also be lockable on switch in Off position, emergency stop red/yellow
• Rotary handle can be rotated up to 90° for switches in lying position
• Order extension shafts separately.
w TECHNICAL DATA
• Can be cut to required length
• For maximum enclosure depths of 400 or 600 mm
MC ACCESSORIES
w TECHNICAL DATA
rotary handle on switch or
additional door interlocking
rotary handle required.
403
mc_xmv_i2.eps
MC ACCESSORIES
mc299832.eps
mc_fern_m.eps
w TECHNICAL DATA
• On/off switching and resetting by constant or impulse voltage
• Switching can be synchronised
• Local switching by hand possible
• Switching time On ≤ 60 ms
Switching must not be simultaneous via remote operator and tripped via undervoltage release/shunt trip. Remote
operators can be combined with MC switches and MC-N disconnectors but not with MC-PN disconnectors.
Operating instructions and measured diagrams are available on our homepage: www.schrack.com
w SPACERS:
Enables fast and economic mounting of switches of various sizes, with or without rotary handle
• Or remote drive on same grid depth
• Each set contains 4 spacers
• Grid depth increases by 17,5 mm for each spacer set
w CLIP PLATES:
• For mounting MC1/MC2 switches on DIN rail
MC ACCESSORIES
w TECHNICAL DATA
• Standard equipment with all MC1, MC1-PN and MC1-N switches
• Conversion kit for switches with screw connections
• Type includes parts for 3 or 4-pole switches respectively
• 3/4-pole
• Fitted inside switch housing
mc190015.eps • Use MC.-XSKA cover
w TECHNICAL DATA
• Type includes parts for one side of switch, top or bottom
3 or 4-pole respectively.
• Fitted outside switch housing
• Standard equipment with sizes MC2, MC3 and MC4
• Use MC.-XSKA cover
mc190019.eps
w TECHNICAL DATA
• for Cu- and Al cable
• Includes cover
• Includes parts for one side of the switch, top or bottom
for 3-pole switches
• Comes with terminal for control circuit cabling
mc196730.eps mc496836.eps for 2 x 2,5 mm2 Cu cable
• Fitted outside switch housing
• Round cross-section or section cross-section cables
• For 4-pole model, see Special Catalogue K-MCCBMCE4
MC ACCESSORIES
w TECHNICAL DATA
• Special cable lugs with narrow profile
mc299776.eps mc299775.eps
w TECHNICAL DATA
• Includes parts for one side of switch, top or bottom for 3-pole switch
w TECHNICAL DATA
• Use MC.-XSKA cover or phase separator
MC ACCESSORIES
w TECHNICAL DATA
• Includes parts for two terminals, top or bottom for 3-pole or 4-pole switch
• Supplied as standard with tunnel terminals
mc196739.eps
w TECHNICAL DATA
• Protection against accidental contact when using cable lugs, rails or
tunnel terminals
• Type includes parts for one side of switch, top or bottom
for 3 or 4-pole switch respectively.
• IP4X degree of protection front, side and rear on the connection side when using
mc290038.eps insulated conductor material IP1X
• Cover already included for tunnel terminals
w TECHNICAL DATA
Includes auxiliary plug-in adaptor
• Mounting position: vertical
• 3 positions: Connected, test, disconnected as well as removed. The 3 positions are indicated mechanically.
• The auxiliary contacts can also be used for remote signalling. Either an NC M22-K01 or NO M22-K10 depending on
the position
MC ACCESSORIES
w TECHNICAL DATA
• For switches with standard box terminal connection
• Connection to system through connection cable supplied above
• in conjunction with IP2X finger protection
• Increase in protection against accidental contact is possible on output side of switch
w TECHNICAL DATA
• Connection to system possible top or bottom
• A cover is required for adaptor elements and switches with rear connection
408
W MC 3 TO 630 A PGR 4962
w TECHNICAL DATA
• Top connection to system
• A cover is required for adaptor elements and switches with rear connection
MC ACCESSORIES
w TECHNICAL DATA
• For 4-pole MCCCbs MC2-4 and switch disconnectors MC2-N-4
• Independent of mains and auxiliary power Ue = 200 V – 690 V 50/60 Hz
• Auxillary switches: 1 N/O, 1 N/C
• XFI30: Rated fault current ln = 0,03 A, suitable for personnel protection according to IEC/EN 60947-2 Annex B
and VDE 664 parts 2 and 3
• XFI: Rated fault current ln = 0,1-0,3-1-3 A, delay time tv = 60-150-300-450 ms,
Core-balance principle with pulse current sensitivity and peak withstand current
For technical data and ordering information, please refer to our Special Catalogue K-MCCBMCE4.
w TECHNICAL DATA
• Independent of mains and auxiliary supply
• Ig = 0,3 x 1,0 x Iu
• tg = 0 – 20 – 60 –100 – 200 – 500 – 750 – 1000 ms
• Can only be used in conjunction with MCCBs with electronic releases
• Earth fault can be displayed in optional DMI communicaiton module
For technical data and ordering information, please refer to our Special Catalogue K-MCCBMCE4.
SELECTIVITY TABLE MC TO MO
Typ MO1-. upstream device with standard trip unit ETU15 MO1-. upstream device with selective trip unit ETU25
In = Iu [A] 630 800 1000 1250 1600 630 800 1000 1250 1600
Ii [A] 5040 6400 8000 10000 12800 12600 16000 20000 25000 32000
Icu [kA] 50 65 50 65 50 65 50 65 50 65 50 65 50 65 50 65 50 65 50 65
SELECTIVITY TABLE MC TO MO
Typ MO1-. upstream device with universal trip unit ETU45 MO1-. upstream device with digital trip unit ETU76
In = Iu [A] 630 800 1000 1250 1600 630 800 1000 1250 1600
Ii[kA] 40 52 40 52 40 52 40 52 40 52 40 52 40 52 40 52 40 52 40 52
Icu [kA] 50 65 50 65 50 65 50 65 50 65 50 65 50 65 50 65 50 65 50 65
OFF/ON OFF/ON OFF/ON OFF/ON OFF/ON
down stream device selectivity limit (kA)
Iu Icu [kA] B N B N B N B N B N B N B N B N B N B N
[A]
MC1-A.. . 40 25(50) T T T T T T T T T T T T T T T T T T T T
50 25(50) T T T T T T T T T T T T T T T T T T T T
63 25(50) T T T T T T T T T T T T T T T T T T T T
80 25(50) T T T T T T T T T T T T T T T T T T T T
100 25(50) T T T T T T T T T T T T T T T T T T T T
125 25(50) T T T T T T T T T T T T T T T T T T T T
MC2-A.. . 40 100(150) T T T T T T T T T T T T T T T T T T T T
50 100(150) T T T T T T T T T T T T T T T T T T T T
63 100(150) T T T T T T T T T T T T T T T T T T T T
80 100(150) T T T T T T T T T T T T T T T T T T T T
100 100(150) T T T T T T T T T T T T T T T T T T T T
125 25...100 T T T T T T T T T T T T T T T T T T T T
160 25...100 T T T T T T T T T T T T T T T T T T T T
200 25...100 T T T T T T T T T T T T T T T T T T T T
250 25...100 T T T T T T T T T T T T T T T T T T T T
MC1-M.. . 40 25(50) T T T T T T T T T T T T T T T T T T T T
50 25(50) T T T T T T T T T T T T T T T T T T T T
63 25(50) T T T T T T T T T T T T T T T T T T T T
80 25(50) T T T T T T T T T T T T T T T T T T T T
100 25(50) T T T T T T T T T T T T T T T T T T T T
MC2-M.. . 125 25...100 T T T T T T T T T T T T T T T T T T T T
160 25...100 T T T T T T T T T T T T T T T T T T T T
200 25...100 T T T T T T T T T T T T T T T T T T T T 411
MC2-VE.. . 100 50...150 T T T T T T T T T T T T T T T T T T T T
160 50...150 T T T T T T T T T T T T T T T T T T T T
250 50...150 T T T T T T T T T T T T T T T T T T T T
MC3-.E . 250 50...150 T T T T T T T T T T T T T T T T T T T T
400 50...150 T T T T T T T T T T T T T T T T T T T T
630 50...150 T T T T T T T T T T T T T T T T T T T T
MC4-.E . 630 50(100) T/40T/52 T/40T/52 T/40T/52 T/40T/52 T/40T/52 T/40T/52 T/40T/52 T/40T/52 T/40T/52 T/40T/52
800 50(100) T/40T/52 T/40T/52 T/40T/52 T/40T/52 T/40T/52 T/40T/52 T/40T/52 T/40T/52 T/40T/52 T/40T/52
1000 50(100) T/40T/52 T/40T/52 T/40T/52 T/40T/52 T/40T/52 T/40T/52 T/40T/52 T/40T/52 T/40T/52 T/40T/52
1250 50(100) T/40T/52 T/40T/52 T/40T/52 T/40T/52 T/40T/52 T/40T/52 T/40T/52 T/40T/52 T/40T/52 T/40T/52
1600 50(100) T/40T/52 T/40T/52 T/40T/52 T/40T/52 T/40T/52 T/40T/52 T/40T/52 T/40T/52 T/40T/52 T/40T/52
notice T: full selectivity
mo_sel2.eps
KAPITEL_07_AK2 25.03.2005 11:51 Uhr Seite 412
SELECTIVITY TABLE MC TO MO
SELECTIVITY TABLE MC TO MO
SELECTIVITY TABLE MC TO MO
SELECTIVITY TABLE MC TO MO
SELECTIVITY TABLE MC TO MO
SELECTIVITY TABLE BM TO MC
BM
MC1- A... MC 2- A...
Icu = 25 (50) kA Icu = 25 (50)(100)(150) kA
BM
MC1- A... MC 2- A...
Icu = 25 (50) kA Icu = 25 (50)(100)(150) kA
mc_seltab2.eps
NOTES
418