Professional Documents
Culture Documents
Ts Condensing Technology
Ts Condensing Technology
Ts Condensing Technology
Condensing Technology
2
Index
1 Basics Page 4
5
3 Condensing technology in Page 9
existing buildings
7 Selection guide
5 Vitocrossal 300
Gas fired condensing boiler
6 Vitodens 300
Gas fired wall mounted
condensing boiler
7 Vitoplex 300
Low temperature oil fired boiler
with Vitotrans 333 flue gas/water
heat exchanger
8 Vitotrans 333 3
Flue gas/water heat exchanger
1 Basics
For natural gas (methane CH4), the Fig. 2: Condensing boilers achieve a standard Fig. 3: Energy gain from hot gases (natural gas)
efficiency of up to 109% by gaining additional
following simplified combustion energy from flue gas (natural gas)
equation applies:
4
Basics
5
2 Significant variables for the
utilisation of condensing technology
Fuel oil EL Nat. gas Town gas Coking gas LPG and
LPG-air mixtures
6
Significant variables for the utilisation
of condensing technology
90 90
Sizing the rated output
Operating datum
80 80
Heating system temperature [°C]
Flow temperature
The boiler design should ensure
that at the lowest likely outside 70 70
temperature, the heat demand can 60 60
be fully covered. For Germany,
these design temperatures are 50 50
-10 to -16 °C. However, such low Return temperature
40 40
Heating load [%]
7
Significant variables for the utilisation
of condensing technology
90
90
D
Standard efficiency [%]
85
80
84
E
75
10 20 30 40 50 60 70 80 90 100
Specific combustion load [%]
15 10 5 0 -5 -10 -15
Outside temperature [°C]
8
3 Condensing technology in existing
buildings
9
Condensing technology in existing
buildings
1.1 0.9
1.2
0.8
1.3
1.4 6 0.7
1.5
1.6 0.6
1.7
1.8 0.5
2.0 4
2.5 0.4 3
3.0
Oversizing factor
0.3
4.0
0.2
0.1
7 2 1 5
-15 -10 -5 0 5 10 15 20 30 40 50 60 70 80 90
-12.5
Outside temperature [°C] Heating water temperature [°C]
Fig. 12: Calculating the oversizing of the heating surfaces (system 90/70 °C)
In winter, and at cold outside temperature to the intersection of the hot gases and thereby to
temperatures, open all radiator results in (3). Proceeding horizontally achieve the condensing benefit.
valves in the evening and read off from (3) to the intersection with the
the flow and return temperatures the vertical of (2), the so-called In the example shown, which
following afternoon. Preconditions oversizing factor (6) results at the indicates oversizing by a factor of
are that the boiler and mixer are set intersection with the outside 1.4 (6), the actual temperature falls
so that room temperatures reach the temperature (4) (in this example 1.4). below this return temperature at
desired range (20 to 23 °C) when the In other words, the heating surfaces outside temperatures as low as
radiator valves are fully opened. are 40% oversized. This means that -12.5 °C (7).
with the lowest expected outside
The average value, comprising the temperature (e.g. -15 °C), the average The utilisation of condensing
flow and return temperatures heating water temperature would not technology in the illustrated example
(mean heating water temperature, have to be 80 °C, as intended, but will not be fully achieved/not
e.g. (54 + 46) / 2 = 50 °C) is the input only 65 °C. achieved at all only on days where
size (1) for the diagram. At the same the outside temperature falls below
time, the current outside The condensation limit for hot gases -12.5 °C. However, on such days, a
temperature should be known created by the combustion of natural condensing boiler will still be more
(in this example: 0 °C) (2). gas is approx. 57 °C (5). The return efficient than a low temperature
temperature must fall below this boiler because of its substantially
Bringing the vertical of (1) with the value to achieve partial condensation lower flue gas temperatures.
curve of the average heating water
10
4 Significant variables and criteria for
optimum gain
Return
Flow paths
Flue
In conventional low temperature outlet
boilers, the heating surfaces are Low temperature boiler Condensing boiler
designed to prevent condensation
of hot gases inside the boiler.
Fig. 13: Boiler design features
Condensing boiler design is quite
different: the Inox-Crossal heating
surface was designed so that hot
gases and condensate flow in the
same direction, i.e. down. This Condensate from Domestic
creates a permanent self-cleaning condensing boilers waste water
effect, which also prevents
Oil(EL) Gas
condensate concentrations.
0 1 2 3 4 5 6 7 8 9 10 11 12
Hot gas and heating water inside the pH value
heat exchanger should flow in a acidic alkaline
countercurrent pattern to utilise the
low temperature of the return water
0 1 2 3 4 5 6 7 8 9 10 11 12
influx, in order to provide maximum
cooling of the outflowing hot gases.
Domestic Clean Tap water
At the same time, modulating Battery acid
vinegar rain water
Stomach acid
burners with suitably intelligent
Ammonia
controls should be utilised, to enable
Lemon juice Sea water
automatic matching of the output to Rain water Distilled
the current heating demand. water
(neutral)
11
Significant variables and criteria for
optimum gain
To prevent concentration of
condensate and its return into the
combustion chamber, hot gas and
condensate should flow in the same
direction, i.e. down. This allows
condensate droplets to flow
downward, supported by gravity and Fig. 16: Hot gas and condensate flow
following hot gases. Therefore, the
hot gas exit of heat exchangers is
generally arranged at the bottom.
12
Significant variables and criteria for
optimum gain
Constant
gap width = 0.8 mm Hot gases
900 °C
Gap height = 36 mm
Flue gas
40 °C
Fig. 19: Laminar heat transfer of the Inox-Radial heating surfaces: individual windings are 0.8 mm
apart
13
Significant variables and criteria for
optimum gain
14
Significant variables and criteria for
optimum gain
15
Significant variables and criteria for
optimum gain
Its practical usefulness is further Fig. 21: Oil fired wall mounted condensing boiler Vitoplus 300
enhanced by the ease with which it
can be cleaned. The adjustable spiral
of the Inox-Radial heating surface
makes annual maintenance very easy
– indeed it can be relaxed to provide
an 8 mm cleaning gap –. This enables
unavoidable combustion residues
produced by fuel oil to be quickly
and thoroughly removed. (Fig. 23).
Fig. 22: Vitoplus 300 with Vitocell-W 100 Fig. 23: Adjustable Inox-Radial spiral heat
exchanger
16
Significant variables and criteria for
optimum gain
Fig. 25: Vitoflame 300 in maintenance position Fig. 26: Downstream Inox-Radial heat exchanger
Vitolaplus 300 can be operated with
all commercially available types of
fuel oil. According to the [German]
ATV-DVWK Code of Practice A 251,
a neutralising system is superfluous
when using low sulphur fuel oil (up
to 50 ppm).
17
Significant variables and criteria for
optimum gain
18
Significant variables and criteria for
optimum gain
condensing technology it is 50
Fuel oil EL
30
The water vapour dew point should
be kept as high as possible, to allow 25
19
Significant variables and criteria for
optimum gain
20
Significant variables and criteria for
optimum gain
The achievable gross calorific value Fig. 35: Hydraulic requirements for condensing
technology
is also influenced by the sizing of the
pump capacity or spread. Fig. 35
illustrates this influence: halving, in
·
an existing system (Q = const.), the
capacity (V) increases the spread
(∆ϑ). However, the average radiator Capacity
100 %
temperature will initially drop.
· ·
V = Q / ∆ϑ ϑin = 50 °C
50 °C
If the flow is raised so that, when VL ϑave. = 45 °C
heat is transferred to the room, the RL 40 °C
original temperature conditions are ϑout = 40 °C
reinstated, the spread doubles if the
average temperature is identical; the
return temperature drops Capacity
correspondingly. This significantly 50 %
improves the condensing effect.
In reverse it follows that high ϑin = 55 °C
capacities reduce the spread and can 55 °C
therefore potentially reduce the VL ϑave. = 45 °C
condensing effect (Fig. 36).
RL 35 °C
ϑout = 35 °C
21
5 Condensate treatment
Condensate created in the boiler Heating system 75/60 ˚C Heating system 40/30 ˚C
and in the flue pipe during heating 100 1
α modulating
must be discharged. With a gas burner
α modulating
consumption of 3000 m3/p.a. for the 80 burner 0.8
Condensate value α
may be created (Fig. 37).
40 0.4
80
if the total theoretical condensate
ϑV
volume (Table 1) is created (complete
60
condensation). As the pH value has
ϑR
been shifted towards ”acidic”, and the
ϑV
condensate may contain substances, 40
the Abwassertechnische Vereinigung
ϑR
[Germany] has published their Code
20
of Practice ATV-DVWK-A 251, on 0 0.2 0.4 0.6 0.8 1 0 0.2 0.4 0.6 0.8 1
Load ϕ Load ϕ
which the waste water regulations of
most water authorities [in Germany]
are based. Fig. 37: Condensate
22
Condensate treatment
23
6 Emissions and flue gas system
6.1 Emissions
200
NOx
The particularly clean combustion 180
CO
achieved by modern MatriX radiant 160
burners ensures that Viessmann
condensing boilers realise 140
substantially better results than the Emission limits in mg/kWh 120
limits prescribed by all known
100
regulations (Fig. 41). In some cases
emissions already fall below 80
technically verifiable levels.
60
The extremely low emissions
achieved by the MatriX radiant 40
burner are the result of the complete 20
premixing of gas and air, as well as
the low combustion temperature, 0
DIN 4702, Swiss Blue Angel Hamburg Vitodens 300/333
which results from the large semi- pt 6 values RAL-UZ 61 values Vitocrossal 300
circular reaction surface. (type CU3 and CM3)
A high proportion of the released
energy is dissipated through infrared
Fig. 41: Emissions characteristics of Vitodens 300/333 and Vitocrossal 300 gas fired condensing
radiation from the reaction zone. This boilers (type CU3 and CM3) compared to various regulations and designations
significantly reduces NOx formation.
Blue flame burners should be used
for oil fired condensing boilers, since Prior to work on the flue gas system, Rated output above 50 kW
these offer particularly clean the heating contractor should confer (e.g.Vitodens 300, 66.0 kW or multi-
combustion. with the responsible flue gas boiler systems):
inspector [where applicable]. 150 cm2 and an additional 2 cm2 for
each kW output above 50 kW.
6.2 Flue gas system Basically, a differentiation is drawn
depending on whether the If an open-flue boiler (boiler type B)
The low flue gas temperature condensing boiler is to be installed is selected, the combustion air will
(< 85 °C) and the risk of residual – inside the living space (where be drawn from the room where the
humidity condensing in the flue gas people congregate) or boiler is installed. Special measures
system, make a conventional – outside the living space (boiler need to be taken so that the living
chimney unsuitable for the room). space can make adequate volumes
installation of condensing boilers. of air available for combustion
The low flue gas temperature is not Installation inside the living space is without sacrificing the ambient
always adequate to ensure a thermal only permitted up to 50 kW. The climate (interconnected room air
current within the flue gas system. system may also be installed inside supply). The flue pipe should be
Therefore, condensing boilers are the living space if the flue pipe, coaxial until it enters the duct, thus
frequently equipped with a fan and inside the area where people the combustion air supply is effected
are operated with positive pressure. congregate, is run inside a protective via the outer pipe casing. Any
Compared to conventional chimneys, pipe and is surrounded by air (fan- escaping flue gas is, therefore,
these conditions lead to quite assisted system, balanced flue directly piped back to the boiler
different requirements: operation). Using a connector, which (Fig. 42).
– During operation, there is no provides secondary ventilation up to Generally, the following conditions
requirement for resistance against the duct (operation with apply:
soot combustion, etc. interconnected room air supply), a
– The chimney will be subjected to condensing boiler may, in
only minor temperature loads. exceptional cases, also be installed Permissible:
– The system may operate with inside the living space, when it is
positive or negative pressure. operated as open flue system. – Gas fired boilers may be installed
– Corrosive condensate must be on the same floor
expected. Outside the living space, the flue – Occupied rooms with
pipe may also be installed inside the interconnected air supply
These conditions can be met by boiler room without secondary – Adjoining rooms with
simple flue pipes which are made ventilation. In that case, however, the interconnected air supply
from plastic, stainless steel, ceramics boiler room would require an – Adjoining rooms with
or glass. adequately sized ventilation aperture interconnected air supply (larders,
to the outside (acc. to TGI ’86/96). basements, utility rooms, etc.)
Rated output up to 50 kW:
24 150 cm2 or 2 x 75 cm2
Emissions and flue gas system
Not permissible:
3 2
– Stairwells and common hallways.
Exception: detached houses and
two-family homes of low height
(top edge of the floor in the top
floor < 7 m above ground level) Fig. 42: Flue gas systems for Vitodens 200 and 300 for open flue operation
– Bathrooms and toilets without
outside windows with duct
ventilation
– Rooms in which explosive or
flammable materials are stored
– Rooms ventilated mechanically or
via individual duct systems to DIN
Balanced flue operation:
18117-1.
4 Vertical roof terminal
Balanced flue boilers (boiler type C) 10 5 Outside wall terminal
draw combustion air from outside 4 6 Sealed balanced flue
the building shell. For this purpose, (multiple connections)
either the available cross-section of 7 Outside wall terminal
8 Vertical roof terminal (flat roof)
the duct will be used, inside of which
4 9 6 7 9 Existing sealed
the flue pipe is installed, or a coaxial balanced flue
pipe, through the inside of which the 10 Horizontal roof terminal
flue gas flow is exhausted, whilst 11 Separate air supply
combustion air is drawn in through and flue pipe
the outer pipe casing. In either case, 11 6 8 5
25
7 Selection guide
Vitoplus 300
27
Selection guide
Vitocrossal 300
Vitotrans 333
7.6 Selection table for wall mounted associated connection sets make
combination/conventional boilers installation quick and easy.
with focus on DHW heating
Table 6 provides some assistance in
The operation of Viessmann wall selecting either a wall mounted
mounted boilers is particularly user- combination boiler (incl. standby
friendly, both through uncomplicated instantaneous water heater) or a
controls and convenient DHW boiler with separate DHW cylinder
loading, utilising the integral Quick with special focus on DHW heating.
DHW heating system. Plate heat
exchangers provide hot water in Condensing technology offers
combination boilers – without particular advantages for building
wasting unnecessary energy or water renovation, as simple and cost-
consumption. effective solutions can be found for
the flue gas side of the system.
The extensive Vitocell range of Extensive chimney work involving
cylinders covers higher water brickwork is not required; instead the
demands, i.e. from 80 to 300 litres. simple insertion of plastic flue pipes
Whether DHW cylinders are installed into existing ducts will normally
as wall mounted devices, or suffice. Alternatively direct access to
below/adjacent to the boiler, their outside air will be created through
shape or colour always matches small wall apertures.
Viessmann wall mounted boilers. The
+ = recommended
0 = qualified recommendation
– = not recommended
30
7.7 Modular design from Viessmann
31
The Viessmann Group
Viessmann UK Office:
Viessmann Limited
Hortonwood 30,Telford
Shropshire,TF1 7YP, GB
Tel: + 44 1952 675000
Fax: + 44 1952 675040
E-Mail: info-uk@viessmann.com
Wall mounted
oil and gas fired
condensing boilers