Princess Noura Bint Abdulrahman University for Women Project Joint venture

Riyadh, Kingdom of Saudi Arabia El Seif/CCC


part / package: package 3 - Utillity area references: time: date:
department: ENGINEERING 1:58 PM 1/16/2018
calcs by: Aleksandar Jankovic sr.str.eng

BRACKET 700-2
Building / area: Irrigation water tank rev: THE IRRIGATION WATER TANK Sheet:
issued for: APPROVAL 0 pipe support 0 5 5

Princess Noura Bint Abdulrahman University for Women Project Joint venture
Riyadh, Kingdom of Saudi Arabia El Seif/CCC
part / package: package 3 - Utillity area references: time: date:
department: ENGINEERING 1:58 PM 1/16/2018
calcs by: Aleksandar Jankovic sr.str.eng

1.0 THE INPUT DATA


The wieght of fluid……….………………………………………………… 10 kN/m3
The weight of pipe 700 mm dia……….………………………………….. 218 kg/m
Adopted steel grade……………..… ASTM A36 yield stren..Py= 245 N/mm2
The strength of the weld (Fexx=60% of Py)…….…………….…..Pyw= 147 N/mm2
The distance between two supports horizontaly….……………L= 2 m
The pipe center line offset from the ceiling……….……………………… NA m
The compressive strength of concrete after 28 days……….…...... fc'= 35 MPa
The density of the steel...……….………………………….………...γs= 7860 kg/m3
The earthquake zone, as per consultant instruction………....…..zone 0
The pipe diameter………………………………………………………..D= 700 mm
The height of the structure (roof elevation)………………………………. 5 m
The bracket elevation (the highest)………………………………………. 4 m
Adopted bolts are steel grade… 8.8 GR, diameter………. 20 mm

2. LOADS ANALYSES
2.1 Dead load
The wieght of the pipe………………………………………………. 436 kg
The weight of the fluid……………………………………………….. 384.65 kg
The weight of the clamp...………………………………………….. 30 kg
total= 850.65 kg
Total weight without water including stiffeners, bolts, nuts……… 512.6 kg
total dead load G=…………….. 5.126 kN
Total weight including water weight (for seismic force required)… 897.25 kg
total dead load Gs=…………… 8.9725 kN

2.2 Seismic load


Seismic force as per UBC 1997 vol 2, section 1632-lateral seismic force for non structural

3.2.1 coefficients
Component amplification factor, Ap
Ap=…….. 1 as per table 16-O, for category 3B

Component response modification factor, Rp


Rp=…….. 3 as per table 16-O, for category 3B

Seismic importance factor, Ip


Ip=……… 1 as per table 16-K, for category 3

Seismic coefficient, Ca
Ca=…….. 0.19 as per table 16-Q, assuming soft soil (Se), and alternative for zone 1,

3.2.2 TOTAL SEISMIC LATERAL FORCE


Fp=(((Ap*Ca*Ip)/Rp)*(1+3(Hx/Hr))) * Gs=….……………………………… 1.9320783 kN
Total force... E= 1.9320783 kN

2.3 Live load


Assumed pressure variation……………….……………………………p= 0.1 bar
Dynamic force created by water surge: Fw=A*P=…………….…...Fw= 3.8465 kN
Building / area: Irrigation water tank rev: THE IRRIGATION WATER TANK Sheet:
issued for: APPROVAL 0 pipe support 0 5 6

Princess Noura Bint Abdulrahman University for Women Project Joint venture
Riyadh, Kingdom of Saudi Arabia El Seif/CCC
part / package: package 3 - Utillity area references: time: date:
department: ENGINEERING 1:58 PM 1/16/2018
calcs by: Aleksandar Jankovic sr.str.eng

5. THE LOAD DISTRIBUTION ON THE CLAMP/STEEL BRACKET LOCATION


Forces are:
dead load:
vertical force…………….8.9725 kN
bending moment……… 0 kNm
live load:
horizontal force………… 3.8465 kN
bending moment……… 1.346275 kNm
seismic load horizontal
horizontal force…………. 1.932078 kN
bending moment……… 0.676227 kNm

6. THE CHECK OF THE STEEL BRACKET


Is calculated in softwear STAAD PRO 2006 and input/output files are shown on following
pages.
The deisgn criteria AISC ASD included, and the bracket is checked on the torsion stress.
Building / area: Potable tabk rev: POTABLE TANK Sheet:
issued for: APPROVAL 0 the pipe support 0 5 7

Princess Noura Bint Abdulrahman University for Women Project Joint venture
Riyadh, Kingdom of Saudi Arabia El Seif/CCC
part / package: package 3 - Utillity area references: time: date:
department: ENGINEERING 1:58 PM 1/16/2018
calcs by: Aleksandar Jankovic sr.str.eng

7.0 THE CHECK OF THE ANCHORING SYSTEM

The adopted is post drilled HILTI anchored system using galvanized HILTI bolts prior to
water's environment.
Due to water's environment the designed anchored system is not using grouting, the plate
will be directly tighten to the concrete wall. All other steel items, susch as beam, clamp and
connection bolts will be hot deep galvanized.

The calculations are based on maximum reaction forces assuming all types of loads:
dead load:
live load,
seismic load horizontal perpendicular,
seismic load horizontal longitudinal

Fx= 3.89 kN Mx= 9.92 kNm


Fy= 9.664 kN My= 3.893 kNm
Fz= 1.93 kN Mz= 1.357 kNm

Assuming safety factor of ……. 2

Fx= 7.78 kN Mx= 19.84 kNm


Fy= 19.328 kN My= 7.786 kNm
Fz= 3.86 kN Mz= 2.714 kNm
Building / area: Irrigation water tank rev: THE IRRIGATION WATER TANK Sheet:
issued for: APPROVAL 0 the pipe support 0 7 9