FLUE GAS
10HBB10 CP001
>MAX1 alarm 60 mmbarG
HRSG Inlet Flue Gas Press.
LP live steam flow <MAX1 LP drum one element level control 6.1 t/h
>MAX1 LP drum level setpoint at normal level 6.1 t/h
10LBA80 CL006 >MAX1 alarm 800 mm
LP live steam drain level auto opening of LP live steam drain valve
<MIN1 auto closing of LP live steam drain valve 50 mm
Steam
10HAH10 CT014 >MAX1 auto closing of the HP supeheater 2 inlet drain valve Tsat+25 ℃
HP live steam flow(corr-dcs) <MAX1 IP drum three elements level control 55 t/h
>MAX1 IP drum level setpoint at normal level 55 t/h
>MIN1 release for opening of IP desuperheating isolating valve 41 t/h
10LBA10 CT019 >MAX1 auto closing of the HP live steam drain 2 valve Tsat+25 ℃
Preheater
Preheater inlet temp. CTRL setpoint for control of preheater inlet temp. 55 ℃
<MIN1 alarm 50 ℃
10LCA60 CP001 >MAX1 alarm 38 BarG
EVERY SECOND ,DCS CALCULATES THE AVERAGE PRESSURE OVER THE 15 LAST SECONDS.
PRESSURE GRADIENT (bar/min)IS CALCULATED ON THE BASIS OF THE TWO AVERAGE PRESSURES DISTANTS OF 30 SECONDS.
Inching valves maximum opening versus steam pressure
NOTE:
For the inching valves, the maximum partial openging,given as a function of the pressure,is applicable in automatic and in manual
mode of operation.
Automatic repositioning of the inching valves which are opened according to actual pressure.
1.PHILOSOPHY
Start-up level -50mm<level start <start-up level + X ,where X is given by the herebelow curve
Sketch to define the philosophy.Applicable values for drums are given herebelow.
2.LP DRUM
P X
0 50
0.8 70
2.8 175
4 200
5 200
3.IP DRUM
P X
0 50
5 140
17.7 510
25.3 650
30 650
4.HP DRUM
P X
0 50
23 130
79 420
113 530
140 530
DRUM LEVELS