IDENTIFIER SET COMMENTS VALUE UNIT REV

FLUE GAS

10HBB10 CP001
>MAX1 alarm 60 mmbarG
HRSG Inlet Flue Gas Press.

10HBB10 CT001/002/003 >MAX1 alarm 625 ℃


GT exhaust fumes temperature
AP KKS >MIN1 auto opening of LP superheater inlet drain valve 100 RPM
GT#1SPD auto opening of LP live steam drain valve
auto opening of IP superheater outlet drain valve
auto opening of reheater 1 inlet drain valve
auto opening of reheater 2 inlet drain valve
auto opening of hot reheat drain valve
auto opening of HP superheater 3 inlet drain valve
auto opening of HP live steam drain valve
<MIN1 auto closing of LP superheater inlet drain valve(if level low) 100 RPM
auto closing of LP live steam drain valve(if level low)
auto closing of IP superheater outlet drain valve(if level low)
auto closing of reheater 1 inlet drain valve(if level low)
auto closing of reheater 2 inlet drain valve(if temp. high)
auto closing of hot reheat drain valve(if temp. high)
auto closing of HP superheater 3 inlet drain valve(if temp. high)
auto opening of HP live steam drain valv(if temp. high)
<MIN2 release to close weather damper 0.5 %
10HBB10 CT010/011 >MAX1 alarm 180 ℃
HRSG outlet Flue Gas Temp.
IDENTIFIER SET COMMENTS VALUE UNIT REV
LP CIRCUIT
Drum & evaporator
10HAD80 CL001/002/003 >MAX2 HRSG trip 850 mm
LP drum level(vote-dcs) >MAX1 safety closing of LP feedwater control valve isolating valve 750 mm
<MAX1 safety opening of LP feedwater control valve isolating valve 750 mm
>MAX1-50 alarm 700 mm
auto opening LP evaporator inlet drain valve
safety closing of LP feedwater control valve
<MAX1-50 auto closing LP evaporator inlet drain valve 700 mm

alarm(if LP evaporator inlet drain valve not closed )


Normal setpoint for LP drum level control during normal operation 0 mm
start-up setpoint for LP drum level control during start-up -200 mm
<MIN1 alarm -750
safety closing LP evaporator inlet drain valve mm
<MIN2 HRSG trip -1100 mm
trip of HP/IP feedwater pumps
PICA10HAD80 CP001/002/003 >MAX1 alarm 8.5 barG
LP drum press.(vote-dcs) >MIN1 auto closing of LP drum vent valve 1 barG

auto closing deaerator vent valve

<MIN2 auto opening of LP drum vent valve 0.5 barG


Steam
10HAH80 CL005 >MAX1 alarm 800 mm
LP superheater inlet drain level auto opening of LP live steam drain valve
<MIN1 auto closing of LP live steam drain valve 50 mm
release for closing LP live steam drain valve
PICZA 10LB80 CP007/008/009 >MAX2 HRSG trip 12 barG
LP live steam press. >MAX1 alarm 4.5 barG
10LB80 CF002/003/004 >MAX1 LP drum three elements level control 6.1 t/h

LP live steam flow <MAX1 LP drum one element level control 6.1 t/h
>MAX1 LP drum level setpoint at normal level 6.1 t/h
10LBA80 CL006 >MAX1 alarm 800 mm
LP live steam drain level auto opening of LP live steam drain valve
<MIN1 auto closing of LP live steam drain valve 50 mm

release for closing LP live steam drain valve


IDENTIFIER SET COMMENTS VALUE UNIT REV
IP CIRCUIT
10LAB50 CP004 >MAX1 alarm 58 barG
IP economiser inlet pressure
Drum & evaporator
LICZA10HAD50 CL001/002/003 >MAX2 HRSG trip 550 mm
IP drum level(vote-dcs) >MAX1 safety closing of IP feedwater control valve isolating valve 450 mm
<MAX1 safety opening of IP feedwater control isolating valve 450 mm
>MAX1-50 alarm 400 mm

auto opening IP evaporator inlet drain valve


safety closing of IP feedwater control valve
<MAX1-50 auto closing IP evaporator inlet drain valve 400 mm
Normal setpoint for IP drum level control during normal operation 0 mm
start-up setpoint for IP drum level control during start-up -650 mm
<MIN1 alarm -700 mm
safety closing IP evaporator inlet drain valve
<MIN2 HRSG trip -800 mm
PICZA 10HAD50 CP001/002/003 >MAX2 alarm 39 barG
IP drum press.(vote-dcs) >MIN1 auto closing of IP drum vent valve 1 barG

<MIN2 auto opening of IP drum vent valve 0.5 barG


PICZA10HAD50 CP001/002/003GR >MAX1 alarm 3 bar/min
IP drum pessure GR HRSG trip
CTRL setpoint for positive IP drum press. gradient control 2 bar/min
<MIN1 alarm
setpoint for negative IP drum press. gradient control -2 bar/min
steam

10LBA50 CF005/006/007 >MAX1 IP drum three elements level control 9 t/h


IP superheater outlet steam flow <MAX1 IP drum one element level control 9 t/h
>MAX1 IP drum level setpoint at normal level 9 t/h
10LBA50 CL005 >MAX1 alarm 800 mm
IP live steam drain pipe level auto opening of IP superheater outlet steam drain valve
<MIN1 auto closing of IP superheater outlet steam drain valve 50 mm
release for closing of IP superheater outlet steam drain valve
IDENTIFIER SET COMMENTS VALUE UNIT REV
IP CIRCUIT
Steam
10LBC10 CT014 >MAX1 GT RUNBACK(time delay 30 minutes) 377 ℃
Cold reheat temp. alarm 377 ℃
<MIN1 alarm Tsat+25 ℃
10LBC10 CL006 >MAX1 alarm 800 mm
Reheater inlet drain pipe level auto opening of reheater inlet drain valve
<MIN1 auto closing of reheater inlet drain valve 50 mm

release for opening reheater inlet drain valve


10HAJ10 CT017/023 >MIN1 Safety limitation of the desuperheating control valve opening Tsat+50 ℃
Reheater 2 inlet temp. <MIN2 Safety closing of the desuperheating control valve Tsat+25 ℃
Saftety closing of the desuperheating control valve isolating valve
10LBC10 CT015 >MAX1 GT RUNBACK(time delay 30 minutes) 505 ℃
Reheater 1 outlet temp. alarm 505 ℃
10HAJ10 CT018 >MAX1 auto closing of the reheater 2 inlet drain valve Tsat+25 ℃

Reheater 2 inlet drain temp.


<MIN1 alarm Tsat ℃
auto opening of the reheater 2 inlet drain valve
10LBB10 CP012/013/014 >MAX2 HRSG trip 30 barG
Hot reheat steam pressure >MAX1 alarm 24 barG
10LBB10 CT020/021/022 >MAX1 GT RUNBACK(time delay 30 minutes) 573 ℃
Hot reheat steam temp. alarm
CTRL setpoint for control of hot reheat steam temp. 568 ℃
10LBB10 CT019 >MAX1 auto closing of the hot reheat steam drain valve Tsat+25 ℃

Hot reheat steam drain temp.


<MIN1 alarm Tsat ℃
auto opening of the hot reheat steam drain valve
IDENTIFIER SET COMMENTS VALUE UNIT REV
HP CIRCUIT
Economiser
11LAB75 CP101 >MAX1 Alarm 173 barG
HP economiser inlet temp.
Drum & evaporator
LICZA 10HAD10 CL001/002/003 >MAX2 HRSG trip 700 mm
IP drum level(vote-dcs) >MAX1 safety closing of HP feedwater control valve isolating valve 600 mm

<MAX1 safety opening of HP feedwater control valve isolating valve 600 mm

>MAX1-50 Alarm 550 mm


auto opening HP evaporator inlet drain valve
safety closing of HP feedwater control valve

<MAX1-50 auto closing HP evaporator inlet drain valve 550 mm


Normal setpoint for HP drum level control during normal operation 0 mm
start-up setpoint for HP drum level control during normal operation -530 mm
<MIN1 Alarm -580 mm
safety closing IP evaporator inlet drain valve
<MIN2 HRSG trip -1000 mm

PIA 10HAD10 CP001/002/003 >MAX1 Alarm 144 barG

HP drum press.(vote-dcs) >MIN1 auto closing HP drum vent valve 2 barG


<MIN2 auto opening HP drum vent valve 0.5 barG

PIA 10HAD10 CP001/002/003 GR. >MAX2 Alarm curve +3 bar/min

IP drum pessure GR HRSG trip


>MAX1 alarm curve +1 bar/min
CTRL setpoint for positive HP drum press. gradient control curve bar/min
<MIN1 Alarm -2 bar/min
setpoint for negative HP drum press. gradient control

Steam

>MIN1 Safety limitation of the desuperheating control valve opening Tsat+50 ℃


10HAH10 CT012/013
HP superheater 2 inlet temp. <MIN2 Safety closing of the desuperheating control valve Tsat+25 ℃
Saftety closing of the desuperheating control valve isolating valve
IDENTIFIER SET COMMENTS VALUE UNIT REV
10HAH10 CT011 >MAX1 GT RUNBACK(time delay 30 minutes) 543 ℃

HP superheater 1 outlet temp. alarm


10LBA10 CP007/008/009 >MAX2 HRSG trip 123 barG
HP live steam press.(vote-dcs) >MAX1 alarm 112 barG

10LBA10 CT015/016/017 >MAX1 GT RUNBACK(time delay 30 minutes) 573 ℃


HP live steam temp.(vote-dcs) >MAX1 alarm 573 ℃
CTRL setpoint for control of hot reheat steam temp. 568 ℃
10LBA10 CT018 >MAX1 auto closing of the HP live steam drain valve Tsat+25 ℃
HP live steam drain temp.
<MIN1 alram Tsat ℃
auto opening of the HP live steam drain valve

10HAH10 CT014 >MAX1 auto closing of the HP supeheater 2 inlet drain valve Tsat+25 ℃

HP superheater 2 inlet drain


temp. <MIN1 alram Tsat ℃

auto opening of the HP superheater 2 inlet drain valve

10LBA10 CF006/007/0008 >MAX1 HP drum three elements level control 55 t/h

HP live steam flow(corr-dcs) <MAX1 IP drum three elements level control 55 t/h
>MAX1 IP drum level setpoint at normal level 55 t/h
>MIN1 release for opening of IP desuperheating isolating valve 41 t/h

release for closing of HP desuperheating isolating valve


<MIN1 safety closing of IP desuperheating control valve 41 t/h

safety closing of HP desuperheating control valve


auto closing of IP desuperheating control valve
auto closing of HP desuperheating control valve

10LBA10 CT019 >MAX1 auto closing of the HP live steam drain 2 valve Tsat+25 ℃

HP live steam drain 2 temp. <MIN1 alram


auto opening of the HP live steam drain 2 valve Tsat ℃
IDENTIFIER SET COMMENTS VALUE UNIT REV

Preheater
Preheater inlet temp. CTRL setpoint for control of preheater inlet temp. 55 ℃
<MIN1 alarm 50 ℃
10LCA60 CP001 >MAX1 alarm 38 BarG

Preheater inlet press.


Curve
setpoint for positive HP drum press. gradient control

EVERY SECOND ,DCS CALCULATES THE AVERAGE PRESSURE OVER THE 15 LAST SECONDS.
PRESSURE GRADIENT (bar/min)IS CALCULATED ON THE BASIS OF THE TWO AVERAGE PRESSURES DISTANTS OF 30 SECONDS.
Inching valves maximum opening versus steam pressure
NOTE:
For the inching valves, the maximum partial openging,given as a function of the pressure,is applicable in automatic and in manual
mode of operation.
Automatic repositioning of the inching valves which are opened according to actual pressure.

1.inching drain valve


2.Hot reheat and HP start-up valve
Inching valves maximum opening versus drum pressure
NOTE:
For the inching valves, the maximum partial openging,given as a function of the pressure,is applicable in automatic and in manual
mode of operation.
Automatic repositioning of the inching valves which are opened according to actual pressure.
Allowed drum level for GT start-up

1.PHILOSOPHY

Start-up level -50mm<level start <start-up level + X ,where X is given by the herebelow curve

Sketch to define the philosophy.Applicable values for drums are given herebelow.
2.LP DRUM

REFERENCE FOR DRUM LEVELS =DRUM NORMAL LEVEL

Start-up level(mm) -200


Normal level(mm) 0
Nominal pressure(barG) 4

P X
0 50
0.8 70
2.8 175
4 200
5 200
3.IP DRUM

REFERENCE FOR DRUM LEVELS =DRUM NORMAL LEVEL

Start-up level(mm) -650


Normal level(mm) 0
Nominal pressure(barG) 25.3

P X
0 50
5 140
17.7 510
25.3 650
30 650
4.HP DRUM

REFERENCE FOR DRUM LEVELS =DRUM NORMAL LEVEL

Start-up level(mm) -530


Normal level(mm) 0
Nominal pressure(barG) 113

P X
0 50
23 130
79 420
113 530
140 530
DRUM LEVELS

EFERENCE FOR DRUM LEVELS =DRUM NORMAL LEVEL


`