Download as pdf or txt
Download as pdf or txt
You are on page 1of 21

Replay

Direct­Current Voltage Testing of Electrical
Equipment (part 1)
Search 1. Tension Testing Machine ›
< >
Home 2. Pull Testing ›
Articles 3. Tensile Testing Equipment ›
LG G5
Forum (Message 4. Compression Testing Machine ›
Board) 12V 24V 48V 2000W MAX $199
10­50V 40A DC Motor
5. Compression Testing Equipment › Speed Control PWM HHO
$6.00
with a 4G 4
Glossary
6. Practice Permit Test ›
Books  

Sitemap 
1 Introduction
Tension Testing
Sabertooth Dual 12A 6V­
Machine
This section covers direct current 24V R/C Regenerative
Motor Driver
$64.99
Pull Testing (DC) tests ordinarily performed in
the field for acceptance and
Tensile Testing maintenance of electrical equipment
Equipment and apparatus.
Compression
Testing Machine
The information provided by these 10­50V 40A PWM DC
tests will indicate whether any Motor Speed Controller
Compression CW/CCW Reversible
corrective maintenance or $18.68
Free Shipping
Testing Equipment
replacement of installed equipment
Practice Permit Test
is necessary, assess if the newly
installed equipment can be safely
Electrical Testing energized, and chart the gradual
deterioration of the equipment over
New Product Testing its service life.

Antibody Testing
The DC test methods discussed in Eaton MMX34AA9D0F0­
0 Adjustable Freq...
this section cover transformers, Eaton

insulating liquids, cables, Buy New

switchgear, motors, and generators.
It is important to have the proper Privacy Information

equipment and trained operators Electrical Engine…
when conducting these tests. Fundamentals of
Power Ele…
Robert W. Erick…

Also, if any test is to provide $133.43

optimum benefits, it is essential to Power Electronics
Daniel Hart (Har…
record all test data and $210.00

maintenance actions for further
analysis and future reference. Power
Electronics: …
Muhammad H. …
$211.40
Furthermore, the test equipment
Power
should be maintained in good Electronics: …
Ned Mohan, Tor…
condition and used by qualified $250.94

operators. When test equipment is Power
Electronics: …
used to calibrate other equipment, it Ned Mohan (Har…
$146.88
should have twice the accuracy of Electrical Motor
Contr…
Replay

the equipment under test. Gary Rockis, Gle…
$129.20
Moreover, the test equipment
should be calibrated at regular Industrial Motor
Control

intervals to assure the accuracy of Stephen Herman
$43.99

test data.
12>

The test voltage levels and Get Widget Privacy

methods, as described in this
section, are mostly in accordance
with industry standards for the types LG G5
of equipment discussed. $199
with a 4G 4
The DC voltage values correspond
to the alternating current (AC) test
volt ages as specified by the A.O. Smith BF2056D 1/2
applicable industry standards. It is hp, 1140 RPM,...
Century Electric/A...

recommended that the Buy New $249.45

manufacturer of the equipment be
consulted for specific test and test Privacy Information

voltage levels when the exact
construction of the equipment under
test is not known. Where definitive
information for a particular
equipment cannot be obtained, it is
advised that the suggested DC test
We Use... voltage be based on the rated AC
circuit voltage in order to avoid
possible damage to the insulation
system. It is also important to
observe certain additional
precautions when conducting DC
high­voltage tests; these are listed
Fluke 87­V Di…
in Sections 11.
Fluke

Electrical phenomena in insulation
when subjected to DC voltage were
Fluke 179/E…
Fluke Corporation briefly discussed in Section 1.
Before discussing various DC
voltage tests, we need to
Fluke 179 ES…
Fluke
understand better the electrical
phenomena in dielectrics when
subjected to DC voltage, which are
Fluke 117 Ele…
Fluke
discussed in the following section.

Fluke i400 40…
Fluke

Tektronix TD…
Tektronix
Replay

Tektronix TD…
Tektronix

Tektronix TD…
Tektronix

100MHZ TWO… FIG. 1 Electrical circuit of insulation LG G5
HQRP
under DC voltage test. $199
with a 4G 4
Tektronix Pr…
2 DC Voltage Testing of
TEKTRONIX Insulation

When DC voltage is applied to an
2X 150MHz O…
Riko insulation, the electric field stress
gives rise to current conduction and
electrical polarization. Consider an
elementary circuit as shown in FIG.
Privacy
1, which shows a DC voltage
source, a switch, and an insulation
specimen. When the switch is
closed, the insulation becomes
electrified and a very high current
flows at the instant the switch is
closed. However, this current
immediately drops in value, and
then decreases at a slower rate
until it reaches a nearly constant
value. The current drawn by the
insulation may be analyzed into
several components as follows:
Capacitance charging current
Dielectric absorption current
Surface leakage current
Partial discharge current (corona)
Volumetric leakage current

Capacitance charging current: The
capacitance charging current is high
as the DC voltage is applied and
can be calculated by the formula:

where:

… ie is the capacitance charging
current E is the voltage in kilovolts
R is the resistance in megohms C is
the capacitance in microfarads t is
the time in seconds e is Napierian
logarithmic base.
The charging current is a function of Replay

time and will decrease as the time
of the application of voltage
increases. It is the initial charging
current when voltage is applied and
therefore not of any value for test
evaluation. Test readings should not
be taken until this current has
decreased to a sufficiently low
value.
LG G5
Dielectric absorption current: The $199
dielectric absorption current is also with a 4G 4
high as the test voltage is applied
and decreases as the voltage
application time increases, but at a
slower rate than the capacitance
charging current. This current is not
as high as the capacitance charging
current. The absorption current can
be divided into two currents called
reversible and irreversible charging
currents. This reversible charging
current can be calculated by the
formula:

where ia is the dielectric absorption
current V is the test voltage in
kilovolts C is the capacitance in
microfarads D is the proportionately
constant T is the time in seconds n
is a constant

The irreversible charging current is
of the same general form as the
reversible charging current, but is
much smaller in magnitude. The
irreversible charging current is lost
in the insulation and thus is not
recoverable. Again, sufficient time
should be allowed before recording
test data so that the reversible
absorption current has decreased to
a low value.

Surface leakage: The surface
leakage current is due to the
conduction on the surface of the
insulation where the conductor
emerges and points of ground
potential. This current is not desired
in the test results and should
therefore be eliminated by carefully
cleaning the surface of the
conductor to eliminate the leakage Replay

paths, or should be captured and
guarded out of the meter reading.

Partial discharge current: The
partial discharge current, also
known as corona current, is caused
by overstressing of air at sharp
corners of the conductor due to high
test voltage. This current is not
desirable and should be eliminated LG G5
by the use of stress control $199
shielding at such points during with a 4G 4
tests. This current does not occur at
lower voltages (below 4000 volts),
such as insulation resistance test
voltages.

Volumetric leakage current: The
volumetric leakage current that
flows through the insulation volume
itself is of primary importance. This
is the current that is used to
evaluate the conditions of the
insulation system under test.
Sufficient time should be allowed for
the volumetric current to stabilize
before test readings are recorded.
The total current, consisting of
various leakage currents as
described above, is shown in FIG.
2.

FIG. 2 Various leakage currents due
to the application of DC high
voltage to an insulation system.

2.1 Dielectric Phenomena and
Polarization

The dielectrics have the property of
both temporary and permanent
absorption of electrical charges and Replay

property of conduction. When a
voltage is applied to a dielectric,
forces on the positive and negative
charges inherent in the particles
which make up the dielectric tend to
orient the particles in line with the
applied field. Some dielectric
materials have molecules that have
uneven number of atoms, that is,
having asymmetrical arrangement LG G5
of charges. When such a molecule $199
is placed in an electrical field, it will with a 4G 4
migrate in an electric field, thus
become polarized with the electric
field. Such a molecule is called a
dipole. Dipoles play an important
role in the electrical characteristics
of the insulation. A dipole may be
represented by a particle having
small positive charge at one end
and a small negative charge at the
other end. When these dipoles are
subjected to DC voltage, they are
polarized and become aligned with
respect to positive and negative
polarity of the DC voltage. This
phenomenon is known as dipole
polarization. Polarization
phenomenon is influenced strongly
by the material properties, structure,
and condition of the insulation.

On the other hand, charged
particles, that is, particles with
positive and negative charges,
which are not interrupted by
interfacial barriers, and can travel
through the dielectric from one
electrode to the other, constitute the
leakage current, and are not part of
the polarization phenomenon.

After a time when the applied
voltage is removed from the
dielectric, the polarized molecules
will eventually revert to their initial
random arrangement so that the
polarization approaches zero. The
time it takes for the polarization to
drop to zero when the dielectric is
short­circuited is known as
relaxation time. It should be noted
that the large dielectrics have a
much longer relaxation time, and Replay

appropriate measures should be
taken to discharge the released
energy (voltage and current) to
ground, which is given by the
polarized molecules when they
revert to their original state.

2.2 Advantages and Disadvantages
of DC Voltage Testing
LG G5
DC voltage testing is commonly
used for testing of electrical
$199
with a 4G 4
equipment and apparatus. DC
voltage testing has advantages and
disadvantages which vary in
importance with the specific
circumstances. The advantages
and disadvantages of DC voltage
are summarized below.

2.2.1 Advantages

DC test is preferred on equipment
whose charging capacitance is very
high, such as cables.

DC voltage stress is considered
much less damaging to insulation
than AC voltages.

Time of voltage application is not as
critical with DC voltage as with AC
voltage.

Test can be stopped before
equipment failure occurs.

Measurements can be taken
concurrently.

Historical data can be compiled and
made available for evaluation.

It is not necessary to make a
separate insulation resistance test
prior to making a DC overpotential
test.

Size and weight of equipment is
significantly reduced compared to
AC voltage test.

2.2.2 Disadvantages
Stress distribution for transformers, Replay

motors, and generator winding is
different for DC voltage than is for
AC voltage.

Residual charge after a DC voltage
test must be carefully discharged.

Time required to conduct a DC
high­potential (hi­pot) test is longer
than for an AC hi­pot test. LG G5
Literature governing DC testing of $199
with a 4G 4
cables suggest possible harmful
effects hi­pot DC testing may have
on some types of cables.

Defects, undetectable with DC, can
cause failure under AC voltage test.

Voltage may not stress uniformly
the insulation system.

Temperature and voltage
dependence of resistivity.

Space charge formation­future
potential failures.

3 DC Testing Methods

After seeing how insulation behaves
when DC voltage is applied to it, let
us now take a look at the various
tests that are conducted with this
voltage. Two tests can be
conducted on solid insulation with
the application of DC voltage:
Insulation resistance testing
High­potential (Hi­pot) voltage testing

3.1 Insulation Resistance Testing

This test may be conducted at
applied voltages of 100­15,000 V.
The instrument used is a
megohmmeter, either hand
cranked, motor driven, or electronic,
which indicates the insulation
resistance in megohms. An
electronic megohmmeter is shown
in FIG. 3a. The quality of insulation
is a variable, dependent upon
temperature, humidity, and other
environmental factors.
Therefore, all readings must be Replay

corrected to the standard
temperature for the class of
equipment under test. The
temperature correction factors for
various electrical apparatus are
shown in TABLE 1. The megohm
value of insulation resistance is
inversely proportional to the volume
of insulation being tested. As an
example, a cable 100 ft. long would LG G5
have one­tenth the insulation $199
resistance of cable 1000 ft. long, with a 4G 4
provided other conditions were
identical. This test can be useful in
giving an indication of deteriorating
trends in the insulation system. The
insulation resistance values by
them selves neither indicate the
weakness of the insulation nor its
total dielectric strength. However,
they can indicate the contamination
of the insulation and trouble ahead
within the insulation system if a
downward trend continued in the
insulation resistance values.

FIG. 3 (a) Electronic megohmmeter,
5000 V and (b) 15 kV DC dielectric
test set. (Courtesy of Megger, Inc.,
Valley Forge, PA.)

Insulation resistance measurement
values can be accomplished by four
common test methods:
Short­time readings
Time­resistance readings (dielectric
absorption ratio [DAR] test)
Polarization index (PI) test
Step­voltage readings

3.1.1 Short­Time Readings

This test simply measures the
insulation resistance value for a
short duration of time, such as 30 or
60 s, through a spot reading that Replay

lies on the curve of increasing
insulation resistance values. The
reading only allows a rough check
of the insulation condition. However,
comparison of this value with
previous values is of importance. A
continued downward trend is
indicative of insulation deterioration
ahead. For interpreting the results,
the values used for comparison LG G5
should all be normalized to 20°C $199
with humidity effects considered. with a 4G 4

TABLE 1 Temperature Correction
Factors

3.1.2 Time­Resistance Readings

A good insulation system shows a
continued increase in its resistance
value over the period of time in
which voltage is applied. On the
other hand, an insulation system
that is contaminated with moisture,
dirt, and the like will show a low
resistance value. In good insulation,
the effects of absorption current
decreases as time increases. In bad
insulation, the absorption effect is
perpetuated by high leakage
current. The time­resistance
method is independent of
temperature and equipment size. It
can provide conclusive results as to
the condition of the insulation. The
ratio of time­resistance readings
can be used to indicate the
condition of the insulation system.
The ratio of a 60 s reading to a 30 s
reading is called the DAR:

Resistance reading at 60 s DAR
Resistance reading at 30s

A DAR ratio below 1.25 is cause for
investigation and possible repair of
the electrical apparatus. Usually,
the DAR readings are confined to
the hand driven megohmmeter.

3.1.3 PI Test

The PI test is a specialized
application of the dielectric
absorption test. The PI is the ratio Replay

of the insulation resistance at 10
min to the insulation resistance at 1
min. A PI of less than 1 indicates
equipment deterioration and the
need for immediate maintenance.
This test is used for dry insulation
systems such as dry type
transformers, cables, rotating
machines, etc.
LG G5
3.1.4 Step­Voltage Readings (DC $199
Voltage Tip­Up Test) with a 4G 4

In this method, voltage is applied in
steps to the insulation under test by
a way of a controlled voltage
method. As voltage is increased,
the weak insulation will show lower
resistance that was not obvious at
lower voltage levels. Moisture, dirt,
and other contaminants can be
detected at lower voltage levels,
that is, below operating voltages,
whereas aging and physical
damage in clean, dry insulation
systems can only be revealed at
higher voltages. The step­voltage
test is very valuable when
conducted on a regular periodic
basis.

3.2 High­Potential Voltage Test

A DC hi­pot voltage test is a voltage
applied across the insulation at or
above the DC equivalent of the 60
Hz operating crest voltage (i.e., DC
value = 1.41 times RMS value).
This test can be applied as a step­
voltage test. When the high
potential voltage is applied as a
dielectric absorption test, the
maximum voltage is applied
gradually over a period of 60­90s.
The maximum voltage is then held
for 5 min with leakage current
readings taken each minute. When
this test is applied as a step­voltage
test, the maximum voltage is
applied in a number of equal
increments, usually not less than
eight, with each voltage step being
held for an equal interval of time.
The time interval between each Replay

step should be 1­4 min. At the end
of each interval, a leakage current
or insulation resistance reading is
taken before proceeding to the next
step. A plot of test voltage versus
leakage current or insulation
resistance can then be drawn to
indicate the condition of the
insulation system. Routine
maintenance tests are conducted LG G5
with a maximum voltage at or below $199
75% of the maximum test voltage with a 4G 4
per mitted for acceptance tests, or
at 60% of the factory test voltage. A
15 kV DC dielectric test set is
shown in FIG. 3b.

Dielectric absorption test: The
dielectric absorption test is
conducted at volt ages much higher
than the usual insulation resistance
test values and can exceed 100 kV.
This test is an extension of the hi­
pot test. Under this test, the voltage
is applied for an extended period of
time, from 5 to 15 min. Periodic
readings are taken of the insulation
resistance or leakage current. The
test is evaluated on the basis of
insulation resistance. If insulation is
in good condition, the apparent
insulation resistance will increase
as the test progresses.

The dielectric absorption tests are
independent of the volume and the
temperature of the insulation under
test.

4 Transformers

The DC testing of transformers
involves testing of the solid winding
insulation and the insulating fluids
used in transformers. The testing of
insulating fluids is covered in
Section 4. The testing of solid
winding insulation complements
other transformer testing. The solid
winding insulation tests are not
conclusive in themselves, but
provide valuable information on
winding conditions, such as
moisture content, and Replay

carbonization. The DC tests are
considered nondestructive even
though at times they may cause a
winding failure. It should be pointed
out that a winding failure results
from an incipient failure that the test
was supposed to detect. If it had
gone undetected, it might have
occurred at an unplanned time. The
DC tests conducted for transformer LG G5
winding insulation are discussed in $199
the following section. with a 4G 4

TABLE 2 Typical Insulation
Resistance Values for Power and
Distribution Transformers

4.1 Insulation Resistance
Measurement

This test is performed at or above
rated voltage to determine if there
are low resistance paths to ground
or between winding to winding as a
result of winding insulation
deterioration. The test
measurement values are affected
by variables such as temperature,
humidity, test voltage, and size of
transformer. This test should be
conducted before and after repair or
when maintenance is per formed.
The test data should be recorded
for future comparative purposes.
The test values should be
normalized to 20°C for comparison
purposes. The general rule of
thumb that is used for acceptable
values for safe energization is 1 MO
per 1000 V of applied test voltage
plus 1 M­ohm. Sample resistance
values of good insulation systems
are shown in TABLE 2. The test
procedures are as follows:

1. Do not disconnect the ground
connection to the transformer tank
and core. Make sure that the
transformer tank and core are
grounded.

2. Disconnect all high­voltage, low­
voltage, and neutral connections,
lightning arresters, fan systems,
meters, or any low­voltage control Replay

systems that are connected to the
transformer winding.

3. Before beginning the test, jumper
together all high­voltage bushings,
making sure that the jumpers are
clear of all metal and grounded
parts. Also jumper together all low­
voltage and neutral bushings,
making sure jumpers are clear of all LG G5
metal and grounded parts. $199
with a 4G 4
4. Use a megohmmeter with a
minimum scale of 20,000 M­Ohm.

5. Resistance measurements are
then made between each set of
windings and ground. The windings
that are to be measured must have
its ground removed in order to
measure its insulation resistance.

6. Megohmmeter reading should be
maintained for a period of 1 min.

Make the following readings for two­
winding transformers:

a. High­voltage winding to low­
voltage winding and to ground

b. High­voltage winding to ground

c. Low­voltage winding to high­
voltage winding and to ground

d. Low­voltage winding to ground

e. High­voltage winding to low­
voltage winding

The connections for these tests are
shown in Figures 2.4a through e
and 2.5a through e for single­phase
and three­phase transformers,
respectively.

Megohmmeter readings should be
recorded along with the test
temperature (°C). The readings
should be corrected to 20°C by the
correction factors shown in TABLE
1. If the corrected field test values
are one­half or more of the factory
insulation readings or 1000 M­Ohm,
whichever is less, the transformer Replay

insulation system is considered safe
for a hi­pot test.

LG G5
$199
with a 4G 4

FIG. 4 Test connections for
insulation resistance of a single­
phase transformer. Note: In figure
(e) reverse the L and E leads to
measure from high­winding to low­
winding.

For three­winding transformers, test
should be made as follows:

• High to low, tertiary and ground
(H­LTG)

• Tertiary to high, low and ground
(T­HLG)

• Low to high, tertiary and ground
(L­HTG)

• High, low, and tertiary to ground
(HLT­G)

• High and tertiary to low and
ground (HT­LG)

• Low and tertiary to high and
ground (LT­HG)

• High and low to tertiary and
ground (HL­TG)

Do not make the megohm test of
the transformer winding without the
transformer liquid because the
values of insulation resistance in air
will be much less than in the liquid.
Also, do not make the insulation
resistance test of the transformer
when it is under vacuum because of
the possibility of flashover to Replay

ground.

The test connections shown in FIG.
5a, c, and e are most frequently
used. The test connections in FIG.
5b and d give more precise results.

The readings obtained in the
connections in FIG. 5a and b are
practically equal to readings in test LG G5
connections in FIG. 5c and d,
respectively.
$199
with a 4G 4

FIG. 5 Test connections for
insulation resistance of a three­
phase transformer: (a) connection
for high winding to low winding to
ground; (b) connection for high
winding to ground and low winding
guarded; (c) connection for low
winding to high winding to ground;
(d) connection for low winding to
ground and high winding guarded;
and (e) connection for high winding
to low winding.

Acceptable insulation resistance
values for dry and compound­filled
transformers should be comparable
to those for Class A rotating Replay

machinery, although no standard
minimum values are available.

Oil­filled transformers or voltage
regulators present a special
problem in that the condition of the
oil has a marked influence on the
insulation resistance of the
windings.
LG G5
In the absence of more reliable data
the following formula is suggested:
$199
with a 4G 4

v IR kVA CE

...where...

IR is the minimum 1 min 500 V DC
insulation resistance in megohms
from winding to ground, with other
winding or windings guarded, or
from winding to winding with core
guarded C is a constant for 20°C
measurements E is the voltage
rating of winding under test kVA is
the rated capacity of winding under
test

Values of C at 20°C 60 Hz 25 Hz

Tanked oil­filled type 1.5 1.0

Untanked oil­filled type 30.0 20.0

Dry or compound­filled type 30.0
20.0

This formula is intended for single­
phase transformers. If the
transformers under test is one of
the three­phase type, and the three
individual windings are being tested
as one, then E is the voltage rating
of one of the single­phase windings
(phase to phase for delta connected
units and phase to neutral or star
connected units) kVA is the rated
capacity of the completed three­
phase winding under test

4.2 Dielectric Absorption Test
The dielectric absorption test is an Replay

extension of the transformer
winding insulation resistance
measurement test. The test
consists of applying voltage for 10
min and taking readings of
resistance measurements at 1 min
intervals.

The resistance values measured
during this test are plotted on log­ LG G5
log paper with coordinates of $199
resistance versus time. The slope of with a 4G 4
the curve for a good insulation
system is a straight line increasing
with respect to time, whereas a
poor insulation system will have a
curve that flattens out with respect
to time.

There are two tests that are
conducted under dielectric
absorption test. These are PI and
DAR tests, which are discussed in
Sections 3.

TABLE 3 Dielectric Test Values for
Routine Maintenance of Liquid­
Filled Transformers

4.3 DC High­Potential Test

The DC hi­pot test is applied at
above the rated voltage of a
transformer to evaluate the
condition of winding insulation. The
DC high­voltage test is not
recommended on power
transformers above 34.5 kV;
instead the AC hi­pot test should be
used. Generally, for routine
maintenance of transformers, this
test is not employed because of the
possibility of damage to the winding
insulation. However, this test is
made for acceptance and after
repair of transformers. If the hi­pot
test is to be conducted for routine
maintenance, the AC test values
should not exceed 65% of factory
AC test value. The routine
maintenance AC voltage value
should be converted to an
equivalent DC voltage value by
multiplying it by 1.6, that is, 1.6
times the AC value for periodic Replay

testing (i.e., 1.6 × 65 = 104% of AC
factory test value). The DC hi­pot
test can be applied as a step­
voltage test where readings of
leakage current are taken for each
step. If excessive leakage current is
noticed, voltage can be backed off
before further damage takes place.
For this reason, the DC hi­pot test is
considered to be a nondestructive LG G5
test. Some companies conduct the $199
AC hi­pot test at rated voltage for 3 with a 4G 4
min for periodic testing instead of
the 65% of factory test voltage. The
hi­pot test values for DC voltages
are shown in TABLE 3.

The procedure for conducting this
test is as follows (refer to FIG. 6a
and b for test connections):

Transformer must have passed the
insulation resistance test
immediately prior to starting this
test.

Make sure transformer case and
core are grounded.

Disconnect all high­voltage, low­
voltage, and neutral connections,
low­voltage control systems, fan
systems, and meters connected to
the transformer winding and core.

Short­circuit with jumpers together
all high­voltage bushings and all
low­voltage bushings to ground as
discussed under "Insulation
resistance measurements."

Connect hi­pot test set between
high­voltage winding and ground.

Gradually increase test voltage to
the desired value. Allow test voltage
duration of 1 min, after which
gradually decrease voltage to zero.

Remove low­voltage to ground
jumper and connect hi­pot test set
between low­voltage winding and
ground. Also connect the short
circuited high­voltage winding to
ground. Gradually increase test Replay

voltage to desired value. Allow the
test voltage duration of 1 min, after
which gradually decrease voltage to
zero.

If the preceding two tests do not
produce breakdowns or failures, the
transformer is considered
satisfactory and can be energized.
LG G5
Remove all jumpers and reconnect
primary and secondary connections
$199
with a 4G 4
and other system equipment that
may have been disconnected.

FIG. 6 Transformer high voltage (hi­
pot) test connection: (a) high
winding hi­pot test connection and
(b) low winding hi­pot test
connections.

The following are some cautions
and considerations in performing hi­
pot tests:

In liquid­filled transformers two
insulation systems are in series,
that is, solid insulation with oil or
synthetic fluid. When AC or DC hi­
pot test voltage is applied, the
voltage drops are distributed as
follows:

=====

Test Voltage | Winding Insulation
(Paper­Cellulose) (% Stress
Distribution) | Oil Insulation (%
Stress Distribution)

AC 25 75

DC 75 25
===== Replay

When using DC hi­pot test voltage
on liquid­filled transformers, the
solid insulation may be
overstressed.

Insulation that may be weakened
near the neutral may remain in
service due to lower stress under
operating conditions. However, LG G5
when subjected to hi­pot test
voltage, it may break down and
$199
with a 4G 4
require immediate repair. The
weakened insulation may usually be
detected by the measurement at
lower voltages.

If a hi­pot test is to be conducted for
routine maintenance, consider the
following in advance: (1) assume
that a breakdown will occur, (2)
have replacement or parts on hand,
(3) have personnel available to
perform work, and (4) is the loss of
the transformer until repairs are
made beyond the original routine
outage?

===
Top of Page PREV.   NEXT Related articles HOME

You might also like