Danvent DV
www.systemair.dk
Copyright: Systemair A/S
2. edition 2009
We accept no liability for
printing errors or alterations
of products made after final editing.
Welcome to Systemair
Air Handling Units
Introduction
We are delighted to present a new edition of our catalogue for air
handling units in the range 0,4-24 m3/s (1.500-86.000 m3/h). It is
the range Danvent DV, which is marketed under the group’s global
trade name Systemair.
The air handling unit range Danvent DV has been added many
improvements and new developments. The result is an extremely
flexible air handling unit, which fulfils our aim to develop products,
which are innovative in both construction and function. The
Danvent DV range compliments the existing range of air handling
units available from Systemair.
Systemair in Denmark
At the Danish Systemair factory we have manufactured air handling
units since 1977. Systemair in Denmark houses the group’s exper-
tise for major air handling units. We focus on development, manu-
facturing, sales and consultations.
Hasselager, Denmark
2009
3
Contents
Introduction .. . . . . . . . . . . . . . . . . . . . . . . 3 - 5
Product Information .. . . . . . . . . . . . . . . . . . . . . . . 8 - 9
Combination Examples . . . . . . . . . . . . . . . . . . . . . . . . 10 - 13
Functions . . . . . . . . . . . . . . . . . . . . . . . . 14 - 19
Damper DVA . . . . . . . . . . . . . . . . . . . 20 - 21
Damper DVB . . . . . . . . . . . . . . . . . . . 22 - 23
Cooler DVU . . . . . . . . . . . . . . . . . . . . . 46 - 47
4
Danvent DV
53
About the Danvent DV
Danvent DV is designed as a modular Casing
air handling unit. Each function is placed The casing protect the air handling unit
into an air handling unit casing consist- functions, and is very effective for
ing of one or more modules. The mod- thermal and sound insulation. The cas-
ular functions can be configured for ing is built to last. To ensure that the
many different applications to make up quality of the casing lives up to the high
the heart of any ventilation system. standards of its functions, we use
frames and panels which are protected
The modular construction is highly flex- against corrosion using alu-zinc of the
ible, and the possibilities often only lim- highest quality AZ 185.
ited by the imagination. The flexibility
makes it possible to combine the most Functions
optimized functions, e.g. the type of The Danvent DV features a number of
heat exchangers and fans with the well-dimensioned functions, presenting
highest efficiencies, combined with fil- a choice between different heat
ters and coils with low pressure drop. exchanger systems, a range of fans,
Combinations, which can offer the best filters, heating and cooling coils and
running- and investment costs. much more. This means the Danvent
DV can be configured for many differ-
The flexibility makes it also possible ent applications, from individual fan
to design the Danvent DV for each units to advanced air handling systems.
project.
SystemairCAD
Sizes and air volumes To ensure correct calculation and design
The Danvent DV comes in a range of of the functions, the highly advanced
14 different sizes, with air volume design program, SystemairCAD, is
capacities from 0,4-24 m3/s (1.500- developed to calculate many new
86.000 m3/h), making it possible to features. This is a very user-friendly
always find the unit optimized for any program which makes it possible to
given requirement. quickly and easily combine different
AHU functions, perform technical
calculations and document the entire
process.
1500 2000 3000 5000 10000 20000 30000 50000 90000 m3/h
240
190
150
120
100
80
60
50
40
30
25
20
15
10
0,4 0,7 1 2 3 5 10 15 20 25 m3/s
6
About the Danvent DV
SystemairCAD calculates and optimizes Disc-Lock
the energy consumption of the air An air handling unit consisting of several
handling unit, and the calculated data sections in size 10-150 can be quickly
are the basis for Eurovent certification and efficiently assembled using Disc-
and energy classification. SystemairCAD Lock, our unique assambly system. The
also calculates the Life Cycle Cost sections can be assembled externally or
(LCC calculation) of the Danvent DV. internally as required.
7
Danvent DV
Product Information
Air Handling Unit Casing Classifications
Rigid frames with sound and thermal The performance of the air handling
insulated panels. unit casing corresponds with the
following classifications according
Materials to the european standard EN 1886:
Operating temperatures
General temperatures
General temperatures of the
air in the air handling unit.
Standard design: -40/+40 ˚C
Special design: -40/+60 ˚C.
8
Product Information
Standards Eurovent Certification
The Danvent DV design is based on Danvent DV air handling units are
the demands in following CEN and Eurovent certified. This ensures the
ISO standards: conformity between the calculated
performance in SystemairCAD design
EN 305 program, and the measured perform-
Heat exchangers. Definition and test ance at independent test laboratories.
procedures.
ISO Certification
EN 308
Heat exchangers. Test procedures. Danvent DV air handling units are
developed and manufactured in
EN 779 Denmark. The Quality management
Particulate air filters for general system at the factory is certified in
ventilation. according to the standard EN ISO
9001by Bureau Veritas Certification.
EN 1751
Aerodynamic testing of dampers and Machinery Directive
valves.
Danvent DV air handling units are
EN 1886 manufactured according to the safety
Air handling units. Mechanical demands of the EU Machinery
performance. Directive.This is confirmed in the
Declaration of Conformity and the CE
EN 13053 labeling.
Ratings and performance for units and
components. Eurovent Energy Labeling
ENERG Y IJA
a duct. F
EN ISO 9001
Quality management systems.
EN ISO 12100
Safety of machinery.
EN ISO 12944.2
Corrosion protection.
Classification of environments.
9
Danvent DV
Combinations with
the DVE plug fan
To ease the process of custom-designing a unit, given the enormous range of
options, the following are examples of the most commonly applied combinations.
Choose the combination that best suit your needs and add or remove functions.
Unit size
Rotary Heat Exchanger
10 15 20 25 30 40 50 60 80 100 120 150 190 240
Standard Width 970 1120 1270 1420 1570 1720 2020 2170 2170 2370 2590 2890 3190 3490
Rotary Heat Exchanger Width - - - - - - - - 2320 2520 2890 3040 3720 4020
Single height unit Height* 520 595 670 745 820 895 1045 1120 1270 1420 1570 1720 2170 2470
Double height unit Height* 970 1120 1270 1420 1570 1720 2020 2240 2540 2840 3140 3440 4340 4940
Length 2160 2160 2460 2460 2760 3060 2910 3280 3210 3960 4260 4560 5010 5530
C1E
Weight kg 430 520 660 760 920 1100 1470 1980 2140 2630 3250 3990 6290 7610
Length 2910 2910 3210 3210 3510 3810 3660 4030 4030 4930 5230 5530 5980 6430
C2E
Weight kg 500 610 770 870 1080 1270 1690 2250 2470 3050 3890 4690 7220 8600
Length 2680 2680 3130 3130 3430 3880 4030 4400 4400 5450 5900 6200 6430 7100
C3E
Weight kg 480 580 730 810 1010 1220 1700 2230 2480 3160 3870 4660 6870 8280
Length 3430 3430 3880 3880 4180 4630 4780 5220 5220 6420 7020 7170 7400 8000
C4E
Weight kg 560 660 840 930 1180 1390 1930 2560 2830 3610 4560 5320 7790 9180
Length 2680 2680 3130 3130 3430 3880 3730 4100 4100 5080 5380 5680 6430 7100
C5E Weight kg 480 570 720 800 1010 1220 1630 2120 2330 2970 3620 4390 6860 8280
Length 3430 3430 3880 3880 4180 4630 4480 4850 4850 6050 6350 6650 7400 8000
C6E
Weight kg 550 660 840 920 1180 1380 1850 2410 2670 3370 4280 5060 7790 9170
Width 970 1120 1270 1420 1570 1720 2020 2170 2170 2370 2590 2890 - -
Single height unit Height* 520 595 670 745 820 895 1045 1120 1270 1420 1570 1720 - -
Double height unit Height* 970 1120 1270 1420 1570 1720 2020 2240 2540 2840 3140 3440 - -
Length 3210 3580 4030 4330 4780 5080 5230 5460 5230 5910 6960 7260 - -
Q1E
Weight kg 570 760 940 1130 1370 1640 2300 2550 2610 3210 4200 5130 - -
Length 3960 4330 4780 5080 5530 5830 5980 6210 5980 6880 7930 8230 - -
Q2E
Weight kg 660 850 1060 1260 1540 1810 2520 2880 2910 3660 4870 5790 - -
Length 3800 4100 4700 5000 5450 5900 6050 6280 6280 7330 8380 8680 - -
Q3E
Weight kg 650 820 1030 1140 1470 1760 2480 2720 2840 3620 4600 5550 - -
Length 4550 4850 5450 5750 6200 6650 6800 7030 6800 8000 9050 9350 - -
Q4E
Weight kg 720 900 1140 1310 1630 1930 2720 3030 3130 3980 5150 6130 - -
Length 3800 4100 4700 5000 5450 5900 6050 6280 6130 7030 8080 8680 - -
Q5E
Weight kg 640 810 1020 1170 1480 1750 2460 2700 2890 3690 4690 5840 - -
Length 4550 4850 5450 5750 6200 6650 6800 7100 6800 8000 9050 9350 - -
Q6E
Weight kg 720 900 1140 1300 1620 1920 2700 3030 3200 4120 5320 6380 - -
* DV 10-150 : Height excl. base frame DVZ. DV 190-240 : Height incl. base frame.
10
Combinations with
the DVE plug fan
Extract air Supply air
Unit size
Run-around Coil Heat Exchangers
10 15 20 25 30 40 50 60 80 100 120 150 190 240
Width 970 1120 1270 1420 1570 1720 2020 2170 2170 2370 2590 2890 3190 3490
Single height unit Height* 520 595 670 745 820 895 1045 1120 1270 1420 1570 1720 2170 2470
Double height unit Height* 1040 1190 1340 1490 1640 1790 2090 2240 2540 2840 3140 3440 4340 4940
Length 2540 2540 2690 2690 2840 2990 2990 3140 3140 3590 3890 4110 5010 5230
R1E
Weight kg 580 700 840 990 1170 1420 1980 2240 2460 2990 3800 4580 6290 7420
Length 3360 3360 3510 3510 3660 3810 3810 3960 3960 4560 4860 5010 5910 6060
R2E
Weight kg 680 820 980 1150 1360 1620 2220 2550 2790 3510 4340 5170 7050 8270
Width 970 1120 1270 1420 1570 1720 2020 2170 2170 2370 2590 2890 3190 3490
Single height unit Height* 520 595 670 745 820 895 1045 1120 1270 1420 1570 1720 2170 2470
Double height unit Height* 970 1120 1270 1420 1570 1720 2020 2240 2540 2840 3140 3440 4340 4940
Length 2240 2240 2390 2390 2540 2840 2690 2840 2990 3660 3810 3960 4410 5080
M1E
Weight kg 250 280 350 390 470 560 800 900 1000 1300 1560 1900 2320 3040
Length 3060 3060 3210 3210 3360 3660 3510 3660 3810 4410 4560 4710 5380 5980
M2E
Weight kg 330 400 480 560 640 780 1050 1180 1320 1660 2140 2460 3250 3940
M3E
Length 3580 3580 3880 3880 4180 4780 4480 4780 5080 5980 6350 6650 7550 8820
Weight kg 390 450 560 620 760 940 1270 1470 1630 2060 2660 3150 3930 5100
M4E Length 4400 4400 4700 4700 5000 5600 5300 5600 5900 6950 7250 7620 8520 9720
Weight kg 480 560 690 790 940 1150 1550 1760 1960 2530 3250 3800 4850 6000
Length 2610 2610 2910 2910 3210 3660 3360 2990 2990 3590 3810 3960 4710 5080
M5E
Weight kg 360 430 530 580 750 910 1220 1360 1520 1950 2510 2990 4190 5150
Length 3430 3430 3730 3730 4030 4480 4180 3810 3880 4630 4780 4860 5680 5980
M6E
Weight kg 460 540 670 730 930 1150 1480 1650 1880 2430 3150 3570 5110 6050
Unit size
Supply air
10 15 20 25 30 40 50 60 80 100 120 150 190 240
Width 970 1120 1270 1420 1570 1720 2020 2170 2170 2370 2590 2890 3190 3490
Single height unit Height* 520 595 670 745 820 895 1045 1120 1270 1420 1570 1720 2170 2470
Double height unit Height* 1040 1190 1340 1490 1640 1790 2090 2240 2540 2840 3140 3440 4340 4940
Length 1940 1940 2090 2090 2240 2390 2240 2390 2390 2690 2990 3140 4040 4260
S1E
Weight kg 220 260 320 370 430 510 700 800 880 1100 1400 1700 2250 2820
Length 2690 2690 2840 2840 2990 3140 2990 3140 3140 3590 3960 4110 5010 5160
S2E
Weight kg 310 370 450 520 620 730 960 1110 1230 1490 2020 2320 3170 3720
Length 1940 1940 2090 2090 2240 2390 2240 2390 2390 2690 2990 3140 4040 4260
S3E
Weight kg 340 400 500 580 690 830 1140 1320 1440 1790 2350 2800 3690 4560
Length 2690 2690 2840 2340 2990 3140 2990 3140 3140 3590 3960 4110 5010 5160
S4E
Weight kg 430 510 630 730 870 1040 1400 1630 1790 2180 2960 3410 4610 5460
* DV 10-150 : Height excl. base frame DVZ. DV 190-240 : Height incl. base frame.
11
Danvent DV
Combinations with
DVV centrifugal fan
To ease the process of custom-designing a unit, given the enormous range of
options, the following are examples of the most commonly applied combinations.
Choose the combination that best suit your needs and add or remove functions.
Unit size
Rotary Heat Exchanger
10 15 20 25 30 40 50 60 80 100 120 150 190 240
Standard Width 970 1120 1270 1420 1570 1720 2020 2170 2170 2370 2590 2890 - -
Double height unit Height* 970 1120 1270 1420 1570 1720 2020 2240 2540 2840 3140 3440 - -
Length 2090 2090 2090 2390 2390 2690 3140 3210 3510 4110 4560 4710 - -
C1V
Weight kg 450 550 640 780 900 1100 1590 2040 2330 2860 3450 4010 - -
Length 2910 2910 2910 3210 3210 3510 3960 4030 4330 4930 5530 5830 - -
C2V
Weight kg 580 700 830 970 1120 1350 1920 2350 2650 3300 4020 4670 - -
Length 2610 2610 2760 3060 3060 3510 3960 4030 4330 5230 5680 5830 - -
C3V
Weight kg 510 600 730 840 990 1230 1760 2180 2530 3210 3820 4400 - -
Length 3430 3430 3580 3880 3880 4330 4780 4850 5150 6050 6500 6950 - -
C4V
Weight kg 640 760 910 1030 1220 1480 2100 2500 2860 3680 4410 5110 - -
Length 2610 2610 2760 3060 3060 3510 3960 4030 4330 5230 5680 5980 - -
C5V Weight kg 500 600 730 850 990 1230 1760 2180 2530 3210 3820 4390 - -
Length 3430 3430 3580 3880 3880 4330 4780 4850 5150 6050 6650 6650 - -
C6V
Weight kg 630 750 910 1030 1210 1480 2100 2510 2860 3680 4410 5110 - -
Width 970 1120 1270 1420 1570 1720 2020 2170 2170 2370 2590 2890 - -
Double height unit Height* 970 1120 1270 1420 1570 1720 2020 2240 2540 2840 3140 3440 - -
Length 3210 3510 3660 4260 4410 4410 5010 5460 5460 6060 7260 7560 - -
Q1V
Weight kg 610 780 940 1160 1330 1580 2320 2640 2750 3430 4340 5110 - -
Length 4030 4330 4480 5080 5230 5230 5830 6280 6280 6880 8080 8230 - -
Q2V
Weight kg 740 940 1120 1340 1550 1790 2630 2950 3070 3830 4820 5580 - -
Length 3730 4030 4330 4930 5080 5230 5830 6280 6280 7180 8380 8680 - -
Q3V
Weight kg 670 840 1030 1220 1430 1700 2500 2820 2960 3770 4650 5460 - -
Length 4550 4850 5150 5750 5900 6050 6650 7100 7100 8000 9200 9350 - -
Q4V
Weight kg 790 990 1210 1400 1640 1910 2810 3100 3250 4170 5140 5940 - -
Length 3730 4030 4330 4930 5080 5680 6350 6800 6280 7180 8380 8680 - -
Q5V
Weight kg 660 840 1030 1220 1420 1770 2680 3000 3050 3920 4890 5730 - -
Length 4550 4850 5150 5750 5900 6500 7170 7550 7100 8000 9200 9350 - -
Q6V
Weight kg 790 990 1200 1400 1640 1980 2970 3250 3350 4320 5400 6230 - -
12
Combinations with
DVV centrifugal fan
Extract air Supply air
Unit size
Run-around Coil Heat Exchangers
10 15 20 25 30 40 50 60 80 100 120 150 190 240
Width 970 1120 1270 1420 1570 1720 2020 2170 2170 2370 2590 2890 - -
Single height unit Height* 520 595 670 745 820 895 1045 1120 1270 1420 1570 1720 - -
Double height unit Height* 1040 1190 1340 1490 1640 1790 2090 2240 2540 2840 3140 3440 - -
Length 2690 2690 2690 2840 2840 2990 3140 3140 3290 3740 4040 4190 - -
R1V
Weight kg 630 770 870 1050 1200 1460 2120 2370 2630 3200 3840 4540 - -
Length 3510 3510 3510 3660 3660 3810 3960 3960 4110 4710 5010 5160 - -
R2V
Weight kg 720 880 1020 1200 1380 1620 2360 2650 2970 3610 4390 5180 - -
Width 970 1120 1270 1420 1570 1720 2020 2170 2170 2370 2590 2890 - -
Single height unit Height* 520 595 670 745 820 895 1045 1120 1270 1420 1570 1720 - -
Double height unit Height* 970 1120 1270 1420 1570 1720 2020 2240 2540 2840 3140 3440 - -
Length 2090 2240 2240 2390 2390 2690 2840 2840 3140 3660 3810 4110 - -
M1V
Weight kg 260 300 360 410 480 590 860 940 1090 1380 1620 1880 - -
Length 3060 3060 3060 3210 3210 3510 3660 3660 3960 4410 4710 4560 - -
M2V
Weight kg 350 430 490 580 650 800 1110 1230 1400 1750 2140 2510 - -
M3V
Length 3430 3580 3580 3880 3880 4480 4780 4780 5380 6350 6800 7100 - -
Weight kg 430 490 570 660 780 990 1400 1550 1790 2420 2810 3260 - -
M4V Length 4250 4400 4400 4700 4700 5300 5600 5600 6200 7100 7700 8000 - -
Weight kg 520 610 700 820 940 1190 1660 1850 2120 2800 3330 3890 - -
Length 2310 2460 2610 2760 2910 3060 3660 3060 3210 3810 4110 4260 - -
M5V
Weight kg 380 450 540 620 740 910 1340 1460 1680 2260 2650 3090 - -
Length 3280 3280 3430 3730 3730 4180 4330 3810 3960 4630 5080 5160 - -
M6V
Weight kg 480 570 680 760 920 1150 1580 1730 2000 2670 3200 3720 - -
Unit size
Supply air
10 15 20 25 30 40 50 60 80 100 120 150 190 240
Width 970 1120 1270 1420 1570 1720 2020 2170 2170 2370 2590 2890 - -
Single height unit Height* 520 595 670 745 820 895 1045 1120 1270 1420 1570 1720 - -
Double height unit Height* 1040 1190 1340 1490 1640 1790 2090 2240 2540 2840 3140 3440 - -
Length 1940 1940 1940 2090 2090 2240 2390 2390 2540 2840 3290 3440 - -
S1V
Weight kg 240 280 320 380 440 520 750 840 960 1240 1470 1710 - -
Length 2760 2760 2760 2910 2910 3060 3210 3210 3360 3660 4260 4340 - -
S2V
Weight kg 330 390 460 540 610 720 1020 1150 1300 1630 1990 2320 - -
Length 1940 1940 1940 2090 2090 2240 2390 2390 2540 2840 3290 3440 - -
S3V
Weight kg 370 450 500 610 700 870 1240 1400 1590 2070 2480 2890 - -
Length 2610 2760 2760 2910 2910 3060 3210 3210 3360 3660 4260 4340 - -
S4V
Weight kg 460 560 640 770 880 1060 1510 1710 1930 2460 3000 3500 - -
13
Danvent DV
Functions
Dampers Mixing Damper DVP
The dampers used in Danvent DV DVP is a complete mixing damper with
comply with EN 1751 sealing class 3. three built-in dampers, which can either
They have contra-rotating aerodynami- be used as shutoff or recirculation
Damper DVA cally formed aluminium blades that dampers. DVP can be used for combi-
ensure a low pressure loss when open. nations in which supply and extract air
The blades are equipped with special are combined in two levels with hori-
rubber sealing strips between the zontal airflows. Mixing damper DVP is
blades themselves and the frame, to ideal for low-energy operation with
prevent air getting in. For very cold recirculation.
areas, the blades can also be insulated.
Damper DVB
By locating DVP after the heat
The dampers ensure a long and exchanger (supply airflow), the system
trouble-free operation, as the blades is only for 0% or 100% recirculation.
are mounted on sturdy square profile This is ideal for night-time operation in
shafts and service-free synthetic areas with no outdoor air require-
bearings with large bearing surfaces. ments, such as warehouses.
A pivoting system placed outside of the
Mixing damper DVM
airflow and which is fitted with steel Compact Filter DVG
rods and maintenance free brass bush- DVG in size 10-150 is a compact basic
es connect the blades. This all-metal EN 779 class G4 filter. It has a very
solution for the pivoting system makes short built-in length, however, DVG has
the dampers ideal for use in very cold a relatively large filter area due to the
areas. The dampers are fitted with a pleated filter construction. This gives the
position indicator. DVG filter a relatively low pressure loss
and long lifetime.
Mixing damper DVP
Damper DVA
DVA is a shutoff damper designed for DVG is ideal as a pre-filter, helping to
efficient closing off of the supply and prolong the lifetime and lower running
exhaust air. It can be located in both costs of the main filter. The DVG filter
lower or upper part of a double height can be slotted into the filter frame of
air handling unit. the air handling unit.
14
Functions
This system also ensures that the filter cient brush seals between the housing
cells form a tight seal with the unit and the rotor. The rotor’s drive unit is
frame to comply with EN 1886. All factory-fitted, and comes in two vari-
seals are fixed to the unit and do not ants – constant speed motor and varia-
need replacement when installing new ble speed motor. For the latter, the Compact filter DVG
filters. Filter cells from all major filter rotor is controlled by a VARIMATIC
manufacturers can be used in the DVF electronic control unit that allows con-
unit. stantly variable speed, and thus optimal
temperature control.
Rotary Heat Exchanger DVC
DVC is a rotary heat exchanger with a Plate Heat Exchanger DVQ
high level of efficiency that can also be DVQ is a plate heat exchanger with a Bag filter DVF
used to transfer moisture from warm high efficiency that comes in 2 versions.
and humid extract air. This type of heat The standard version with an efficiency
exchanger is the most efficient of the up to 65%, and the high-efficiency ver-
various heat exchanger systems and is sion with efficiency up to 75%, depend-
also the most compact, due to its short ing on operating conditions.The
length. In its standard form, efficiency is exchanger is recuperative and consists
up to 80%, and in its high-efficiency of a series of aluminium plates with a
version, up to 87%, depending on oper- double rebate and sealed so that the
ating conditions. two airflows are kept entirely separate.
Rotary Heat Exchanger DVC
Both versions are also available as DVQ is thus ideal for situations where
enthalpy or temperature heat exchang- the separation of the two airflows is a
ers. The enthalpy version can transfer necessity, to avoid the transfer of
heat and moisture from extract to unpleasant odours to the supply air for
supply air, thus increasing the example. Because humidity is not trans-
exchanger’s contribution to the systems ferred between the airflows, DVQ can
heat and moisture requirements. The also be used for dehumidifying.
temperature version transfers heat
from the extract air. At low outdoor There are two versions for use in
Plate Heat Exchanger DVQ
temperatures it can also transfer mois- different environments:
ture from the condensing extract air. • The aluminium version is used for
commercial ventilation where no
The standard version in size 10-150 is corrosive elements are present in
available as sorption heat exchanger. the air, such as schools, kindergartens,
This type is ideal for climate with high offices, airports and hotels
summer temperature and humidity. • Corrosion-resistant heat exchangers
It can save much cooling capacity and with specially-coated aluminium
energy for cooling and dehumidification plates are used in environments
of the outdoor air. where the supply air can contain
aggressive elements.
The DVC consists of a rotor made of
corrugated aluminium, built-in to a sta- The heat transfer capacity can be regu-
ble rotor housing with a large inspec- lated using the built-in by-pass damper,
tion door. The rotor is assembled on and the DVQ is always fitted with a
rails up to size 40, enabling it to be drip tray to collect condensed water
pulled out for inspection and service. from the extract air. The drip tray drain
outlet must be connected to a water
To minimize air leakage, DVC heat trap with sufficient locking height.
exchangers are fitted with highly effi-
15
Danvent DV
Functions
Run-around Coil Heat ronment the coil is to operate in. Coils
Exchangers DVR with copper tubes and aluminium fins
DVR is a heat exchanger system where are used for hot water and condensa-
a mixture of water and glycol is circu- tion. The tubes are ø10 or ø15 mm,
lated between a heating coil positioned depending on the capacity required.
in the supply airflow and a cooling coil Stainless steel tubes and aluminium fins
positioned in the extract airflow. The are used for steam heating coils.
transfer of heat takes place via a piped Electrical heating coils have heating ele-
Run-around Coil Heat Exchangers DVR circuit that must be fitted after the unit ments made of stainless steel.
is assembled.
If mildly corrosive elements are to be
DVR heat exchangers have an efficiency present in the air, the aluminium fins
of up to 55%. The effectiveness of the can be specially-coated with a protec-
system is dependant on its construction tive layer. In maritime environments, fins
and the volume and type of water/glycol on the coils must be made up of an
mixture circulating between the coils. aluminium-magnesium alloy.
Heating Coil DVH
Run-around coil heat exchangers are Coils for hot water can be supplied
used where the two airflows must be with a connection piece to fit a tem-
kept completely separate, or where perature sensor in the water circuit,
they are at a distance from each other making it possible to equip the unit
- e.g. on two different storeys of a with modulating electronic frost
building. protection.
A drip tray is fitted in the extract air The coil is fully built-in the unit as
Cooling Coil DVK coil section to collect condensation standard, but comes also in a MAX
from the extract air. The drain outlet version where the coil is wider than
must be connected to a water trap the standard unit width. This will reduce
with sufficient locking height. To elimi- the air velocity.
nate the risk of water droplets being
carried into the extract air, the DVR Cooling Coil DVK
can be supplied with a built-in droplet The DVK cooling coil is used to cool
eliminator. the supply air either with cold water, or
directly evaporation. Dimensioning a
DVR has coils made of copper tubes DVK coil is done using the design pro-
with aluminium fins. Capacity regulation gram SystemairCAD, so that design of
can be achieved using a shunt system the coil will exactly match the require-
with a motorised valve, or by regulating ments of the application.
the circulation pump.
DVK coils are made with copper tubes
Heating Coil DVH and aluminium fins. The tubes are ø10
The DVH heating coil is used to heat or ø15 mm , depending on the capacity
up the supply air, using either hot water, required. If mildly corrosive elements
condensation of a cooling medium, are to be present in the air, the alumini-
steam or electricity. Dimensioning a um fins can be specially-coated with a
DVH coil is done using the design pro- protective layer. In maritime environ-
gram SystemairCAD, so that design of ments, fins on the coils must be made
the coil will exactly match the require- up of an aluminium-magnesium alloy.
ments of the application.
Cooling coils for direct evaporation
DVH heating coils are made from a have the liquid distributor located in
range of different materials depending the unit, whilst the expansion valve can
on the heating medium and the envi-
16
Functions
be fitted on the connection pipe on shaft, and enclosed into an acoustically
the outside. insulated casing. A plug fan is a single
inlet fan, with open outlet into the air
A drip tray is fitted in the coil section handling unit. The fan has an efficiency
to collect condensation. The drain out- of up to 75% and features very low Kammerventilator DVE
let must be connected to a water trap sound levels in the lower frequencies.
with sufficient locking height. To elimi- In order to optimize the fan efficiency a
nate the risk of water droplets being number of large DVE fans are equipped
carried into the airflow, the DVK can with parallel working twin fans.
be supplied with a built-in droplet
eliminator. The coil is fully built-in the Thanks to its special construction, a
unit as standard, but comes also in a plug fan can give a low and even air Centrifugalventilator DVV
MAX version where the coil is wider speed at the outlet of the fan unit. The
than the standard unit width. This will DVE is ideal for air handling units
reduce the air velocity. where other air handling components
are to be positioned after the fan.
Cooler DVU
Cooler DVU in size 10-40 is a com- The DVE comes with a single-speed
plete cooling system, with all cooling motor regulated by a frequency con-
components and control system placed verter, necessary to control the fan
in a casing, which can be combined to speed to the actual design air volume.
the Danvent DV. This set up of the It is ideal for plants with a variable air Cooler DVU
cooling system need no external con- volume (VAV plants) as the air volume
denser for removing of heating energy is infinitely variable.
or separate space for cooling equip-
ment. It is therefore very easy to install In order to make service and inspec-
cooling in the selected Danvent DV. tion access easy, the DVE is fitted with
a large hinged inspection door. Because
The cooling capacity can be controlled the DVE has direct drive, it requires
stepless from 0 to max. capacity by the much less servicing. In order to ensure
advanced cooling control system com- trouble-free operation, all fan impellers
bined with the speed controlled are statically and dynamically balanced.
compressor. The Cooler DVU will
deliver the correct cooling capacity up Both fan and motor are assembled on
to max. in all situations, and eliminate a strong and stable frame that is in
undesirable start/stop of the compres- turn fitted on rubber vibration isolaters
sor. Hereby is durability improved for to ensure minimum vibrations to the
many years of reliable running. unit casing. The connection between
fan and unit casing at the fan inlet is
The cooling system in DVU is com- flexible, to further enhance vibration-
plete installed and factory tested. The free operation.
installation on site is very easy. Install
the Cooler DVU between the air han- Centrifugal fan DVV
dling unit sections and connect power DVV in size 10-150 is a double inlet,
supply, 0-10 V control signal and start belt-driven centrifugal fan, built into an
signal, drain for condensing water and acoustically insulated casing. Two types
eventually alarm signal. DVU is now of fans are used, each of which has its
ready for start up. own properties:
• The BK fan has backward-curved
Plug fan DVE blades with an efficiency of up to
The DVE is a plug fan, with the fan 82%, making it very economical to
impeller fitted directly to the motor run. It also provides very stable
17
Danvent DV
Functions
pressure and is best suited for air equipment. It is also ideal for use
handling units that require a very between the air handling unit and the
stable airflow, such as those in which air inlet/outlet to reduce the noise level.
the gradual build-up of dust on the
filter must not be allowed to influence For environmental reasons, the baffles
the airflow. If the speed of the BK fan are special surface treated to protect
Sound attenuator DVD
is regulated, it is also well suited to the sound-absorbing material. This treat-
plants with variable airflow. ment comes in three variants:
• The FK fan has forward curved blades 1. Standard lining, suitable for all forms
with an efficiency of up to 73%. Its of commercial ventilation purposes.
construction with multiple blades 2. Baffles with a hard-wearing lining,
means it is very quiet in operation, resistant to mechanical wear and tear.
and is best suited to small AHUs in These are used in situations where
which it can run at relatively low the baffles require dry cleaning, such
Inspection section DVI speeds. as brushing or vacuum cleaning.
3. Baffles with a synthetic lining, ideal for
The DVV fan comes with a single- or wet cleaning. Each baffle is enclosed
two-speed motor. The speed and air- in a stainless steel frame and used
flow can be infinitely variable using the where high levels of hygiene require
single-speed motor and a frequency direct washing of the baffles.
converter. Speed can be regulated in
steps using the two-speed motor. The In order to make cleaning and inspec-
Empty section DVO
standard belt drive is the highly-efficient tion access easy, variants 2 and 3 have
RE-X V-belt, with a maximum efficiency large, hinged inspection doors and the
of up to 98%, and it is also fitted with baffles are designed for easy extraction
Taper-Lock bush pulleys to make to be cleaned.
replacement and gearing simple.
Inspection Section DVI
In order to make service and inspec- The DVI inspection section is an empty
tion access easy, the DVV is fitted with section with an inspection door, for use
a large hinged inspection door. In order between components that require
to ensure trouble-free operation, all fan inspection and servicing. It can also be
impellers are statically and dynamically used if regular measurements are to be
balanced and run on ball bearings. The taken from a component. To make
bearings for smaller fans are sealed and inspection even simpler, the door can
permanently lubricated, assembled in be fitted with an inspection window,
vibration absorbing rubber bushes. and an internal light can be installed.
18
Functions
Air Distributor DVL The unit is available with components,
The DVL air distributor is used when which protect the air intake and
even distribution of the airflow across exhaust against rain and snow. Outdoor
the entire cross-section of the AHU is air section DVY feature outlet of
required, immediately after the DVV exhaust air behind the DV unit.
fan outlet.
Control system E28
Air distributor DVL
It is ideal for positioning before the Danvent DV is available with factory
DVD sound attenuator if this is located installed and fully integrated Systemair
only a short distance from the outlet of E28 control system.
the DVV fan.
It is an advanced user-friendly system,
Roof Units DV with an external remote control panel
DV air handling unit in size 10-150 is for all settings. The panel also shows
available as roof unit, designed for out- the status for a number of actual
door installation. In this version is the parameters and alarms. The remote
unit assembled on a base frame and control panel can be placed freely in
feature a roof construction which the building.
together with the double sealing of the
panels provides protection against the E28 is the perfect control system for all
effects of the weather. DV air handling units. From the simple
solution for supply air, to the advanced
DV Roof Units can be delivered with 2 control system for heat recovery,
different types of roofing: cooling, variable air flow with air quality
sensors, free night cooling and cooling
Bitumen roof: recovery.
Manufactured of polyester reinforced
bitumen material, fitted to the unit by a E28 control system is prepared for
heating process. The bitumen roof is a communication to a BMS system in the Bitumen roof
very tighten and robust roofing com- building. Communication by Modbus,
plete factory finished. TCP/IP or LON is standard for E28.
Steel profile roof: The main board with the E28 control-
Manufactured of alu-zink protected ler is installed in- or outside the DV
corrugated steel sheets, and profiles for unit. It is connected to the remote
fastening and finishing the roofing. control panel together with sensors
This type of roofing is supplied for local and actuators mostly placed in the air
assembling on the DV air handling unit. handling unit. After connection of
The steel profile roof is a robust power supply, and a few external
roofing of which the surface matches components the E28 control system Steel profile roof
the DV panels. is ready for starting the unit.
Controller E28
19
Danvent DV
Damper DVA
Function: Shafts:
Supply or exhaust damper. 14,3 mm.
10
240
100
120
150
190
20
25
80
30
40
50
60
10
15
2
0,3 0,5 1 2 3 5 10 15 20 25 m3/s
20
Damper DVA
DVA 10-150
35
H2
DVA 190-240
L DVA 190-240
Dimensions
21
Danvent DV
Damper DVB
Function: Blade pivoting system:
Exhaust damper. Steel rods with maintenance free brass
bushes.
Sealing:
Rubber sealing strips between the
damper blades. Special sealing between
the unit frame and damper blades.
20
240
100
120
190
150
20
25
80
30
40
50
60
10
15
10
5
0,3 0,5 1 2 3 5 10 15 20 25 m3/s
22
Damper DVB
DVA 10-150
DVB 10-150
DVA 190-240
DVB 190-240
Dimensions
23
Danvent DV
Mixing Damper DVM
Function: Blade pivoting system:
Supply and mixing dampers. Steel rods with maintenance free brass
bushes.
Air tightness classification:
Class 3 according to EN 1751. Blade position indicator:
Arrow for indication of the blade posi-
Damper blades: tions.
Aerodynamically formed aluminium
profiles. Can be supplied insulated. Motor bracket:
Bracket for fixing of a damper motor
Bearings: for each damper.
Synthetic material with large bearing
surfaces. Damper motor:
The dampers are activated by a motor
Shafts: for each damper.
14,3 mm. DV 10-150: 2 damper motors.
DV 190-240: 4 damper motors.
Sealing:
Rubber sealing strips between the
damper blades. Special sealing between
the unit frame and damper blades.
20
240
190
100
120
150
20
25
80
30
40
50
60
10
15
10
5
0,3 0,5 1 2 3 5 10 15 20 25 m3/s
24
Mixing Damper DVM
DVM 10-150
DVM 10-150
DVM 190-240
DVM 190-240
Dimensions
Size 10 15 20 25 30 40 50 60 80 100 120 150 190 240
B 970 1120 1270 1420 1570 1720 2020 2170 2170 2370 2590 2890 3190 3490
H 520 595 670 745 820 895 1045 1120 1270 1420 1570 1720 2170 2470
L 520 520 520 520 520 670 670 670 820 970 970 970 1120 1570
D 500 600 800 900 1100 1200 1500 1600 1700 1800 2000 2300 2600 2800
E 200 200 300 300 300 400 400 500 600 700 700 700 1000 1200
F 235 260 235 260 235 260 260 285 235 285 295 295 295 345
G 100 100 100 100 100 100 100 100 100 100 100 100 660 710
K 160 160 110 110 110 135 135 85 110 135 135 135 60 185
25
Danvent DV
Mixing Damper DVP
Function: Blade pivoting system:
Supply, exhaust and mixing dampers. Steel rods with maintenance free brass
bushes.
Air tightness classification:
Class 3 according to EN 1751. Blade position indicator:
Arrow for indication of the blade posi-
Damper blades: tions.
Aerodynamically formed aluminium
profiles. Can be supplied insulated. Motor bracket:
Bracket for fixing of a damper motor
Bearings: for each damper.
Synthetic material with large bearing
surfaces. Damper motor:
The dampers are activated by a motor
Shafts: for each damper.
14,3 mm. DV 10-150: 3 damper motors.
DV 190-240: 6 damper motors.
Sealing:
Rubber sealing strips between the
damper blades. Special sealing between
the unit frame and damper blades.
10
240
100
120
150
190
20
25
80
30
40
50
60
10
15
2
0,3 0,5 1 2 3 5 10 15 20 25 m3/s
26
Mixing Damper DVP
35
35
DVP 10-150
35
35
35 DVP 10-150
DVP 190-240
H
2
DVP 190-240
Dimensions
Size 10 15 20 25 30 40 50 60 80 100 120 150 190 240
B 970 1120 1270 1420 1570 1720 2020 2170 2170 2370 2590 2890 3190 3490
H 970 1120 1270 1420 1570 1720 2020 2240 2540 2840 3140 3440 4340 4940
L 520 520 670 670 670 820 820 820 820 1120 1120 1120 1420 1570
D 900 1050 1200 1350 1500 1650 1950 2100 2100 2300 2520 2820 2600 2800
E 350 450 500 600 650 750 900 1000 1150 1300 1450 1600 1500 1800
F - - - - - - - - - - - - 295 345
G - - - - - - - - - - - - 410 410
27
Danvent DV
Compact Filter DVG
Function: Filter surface area:
Pre and main filter. Large surface area due to the pleated
DVG 10-150. filter form.
100
0
0
0
25
20
30
50
80
40
60
10
10
12
15
15
70
50
0,3 0,5 1 2 3 5 10 15 m3/s
28
Compact Filter DVG
Dimensions
Size 10 15 20 25 30 40 50 60 80 100 120 150
B 970 1120 1270 1420 1570 1720 2020 2170 2170 2370 2590 2890
H1 520 595 670 745 820 895 1045 1120 1270 1420 1570 1720
H2 970 1120 1270 1420 1570 1720 2020 - - - - -
L 150 150 150 150 150 150 150 150 150 150 150 150
29
Danvent DV
Bag Filter DVF
Function: Fitting the filter cells:
Main filter. DVF 10-150: The filter cells are pressed
against the sealing strips and locked
Filter classification: into place using a sliding bar system.
G3, F5, F6, F7, F9 according to EN 779. This system is easy to operate by using
a large handle.
Filter material: DVF 190-240: The filter cells are pres-
G3: Synthetic material. sed against the sealing strips in the filter
F5, F6, F7, F9: Glass fibre material. bank frames with effective fasteners.
Sealing: Accessories:
Rubber sealing strips are fixed to the U-tube and inclined tube manometers.
filter cabinet. Air tightness according to Stainless steel sheet below filter.
EN 1886.
120
150
190
G3
20
25
80
30
40
50
60
F5
F6
15
F7
F9
10
30
Bag Filter DVF
DVF 10-150
DVF 190-240
DVF 190-240
Dimensions
Size 10 15 20 25 30 40 50 60 80 100 120 150 190 240
B 970 1120 1270 1420 1570 1720 2020 2170 2170 2370 2590 2890 3190 3490
H1 520 595 670 745 820 895 1045 1120 1270 1420 1570 1720 2170 2470
H2 970 1120 1270 1420 1570 1720 2020 - - - - - - -
L 600 600 600 600 600 600 600 600 600 600 600 600 1350 1350
31
Danvent DV
Rotary Heat Exchanger DVC
Function: Rotor:
Regenerative heat exchanger with high Made up of corrugated aluminium in an
efficiency. extremely sturdy construction.
Types: Sealing:
S – Standard heat exchanger. In order to safeguard against leakage
Efficiency up to 80%. between the airflows the heat exchang-
H – High efficiency heat exchanger. er is fitted with highly effective brush
Efficiency up to 87%. type seals against the rotor.
32
Rotary Heat Exchanger DVC
Constant speed Air directions
Accessories:
Function: Rotary alarm switch.
A gear motor that is connected to
three-phase mains voltage drives the Constant speed – motor data
exchanger. This drive system gives full
DVC Motor power Voltage Current
recovery when the exchanger is run- Size W V A
ning. When connecting the motor it 10-20 90 3 x 230 0,7
must be ensured that the electrical 3 x 400 0,4
installation is fitted with an overcurrent 25-100 180 3 x 230 1,2
protection. 3 x 400 0,7
120-240 550 3 x 230 2,8
3 x 400 1,6
Alarm connections:
Built-in relay which can be connected
to an alarm system.
33
Danvent DV
Rotary Heat Exchanger DVC
DVC 60-240 Variant A and B
Heat exchanger supplied in divided version
Transport protection
HT
Transport height HT
Size 60 80 100 120 150 190 240
HT 1640 1790 1940 2090 2240 2765 3065
150
19
10
240
190
100
120
150
20
25
80
30
40
50
60
15
0-
-1
10
24
50
0
100
80
supply air
= 1,0
extract air
60
60 70 80 90% 0,3 0,5 1 2 3 5 10 15 20 25 m3/s
Efficiency qv supply air
200
19
10
150
0
240
15
-2
100
120
150
190
20
25
80
30
40
50
60
15
10
40
100
supply air
= 1,0
extract air
70
60 70 80 90% 0,3 0,5 1 2 3 5 10 15 20 25 m3/s
Efficiency qv supply air
34
Rotary Heat Exchanger DVC
DVC 10-50
DVC 60-150
DVC 190-240
L
C B C
Dimensions
Size 10 15 20 25 30 40 50 60 80 100 120 150 190 240
B 970 1120 1270 1420 1570 1720 2020 2170 2170 2370 2590 2890 3190 3490
H 970 1120 1270 1420 1570 1720 2020 2240 2540 2840 3140 3440 4340 4940
L 300 300 300 300 300 300 450 520 520 520 520 520 670 670
F - - - - - - - 2170 2320 2520 2890 3040 3720 4020
C - - - - - - - 0 75 75 150 75 265 265
35
Danvent DV
Plate Heat Exchanger DVQ
Function: By-pass:
Recuperative plate heat exchanger with The heat exchanger is supplied with a
high efficiency. DVQ 10-150. built-in by-pass that enables the heat
recuperation to be regulated from
Application: 0 - 100%. The by-pass function is com-
The plate heat exchanger is used prised of a damper for the exchanger
where it is a requirement that the sup- and a damper for a by-pass airway.
ply and exhaust air are kept separated, The by-pass function is located in the
e.g. in order to ensure that unwanted middle of models DVQ 100-150. The
odours in the exhaust air are not trans- heat exchanger is therefore in 2 sec-
ferred to the supply air. tions.
Variants: De-icing:
The plate heat exchanger is available in In situations where the outdoor air is
2 variants: extremely cold there is a risk of the
exchanger icing up. De-icing can take
A – Aluminium heat exchanger. place either by regulating the by-pass
Is used in ventilation plant where damper or by reducing the supply air
the air does not contain corrosive flow.
elements, e.g. ventilation plant for
commercial purposes. Aluminium is, Drip tray:
however, resistant to many chemi- A drip tray is fitted beneath the heat
cal elements. This exchanger variant exchanger for collection of the water
can therefore be applied in ventila- that can condense in the extract air.
tion plant where such elements are The drip tray drain outlet must be fit-
present. These conditions should ted with a water trap that is designed
be evaluated for each plant. for the actual pressure difference.
Refer to the assembly instructions.
K – Corrosion-resistant heat exchanger.
The heat exchanger plates are
coated with corrosion resistant
synthetic material. This exchanger
variant can be applied in ventilation
plant where the air contains ele-
ments which are corrosive to alu-
minium.
36
Plate Heat Exchanger DVQ
Pressure difference between
the exchanger air flows
150
100
120
150
1,4
1,0
20
25
0,6
80
30
40
50
60
10
15
100
70
50
50 60 70 80% 0,3 0,5 0,7 1 1,5 2 3 5 7 10 15 m3/s
Efficiency qv supply air
Conditions: outdoor air: - 15 ˚C,
extract air: + 22 ˚C 40% RH
150
100
120
150
1,4
1,0
20
25
0,6
80
30
40
50
60
10
15
100
70
supply air
extract air
50
50 60 70 80% 0,3 0,5 0,7 1 1,5 2 3 5 7 10 15 m3/s
Efficiency qv supply air
37
Danvent DV
Plate Heat Exchanger DVQ
Air directions DVQ-S 10-50
Extract air, diagonal down-flow
Extract air
Supply air
Supply air
DVQ-H 10-50
Extract air
Air directions
Extract air, diagonal up-flow *
Supply air
DVQ-H 60
Extract air
Extract air
* Air directions with diagonal up-flow the extract air, before the heat
extract air (3 and 4) should only be exchanger, is less than the following
Supply air used when the moisture content of values:
38
Plate Heat Exchanger DVQ
DVQ-S 60-80 DVQ-H 80
1. By-pass damper
2. Heat exchanger damper
3. Shaft for damper motor
4. Plate heat exchanger
5. Drip tray drain outlet
6. Drip tray
DVQ-S 100-150 DVQ-H 100-150
Dimensions
Size 10 15 20 25 30 40 50 60 80 100 120 150
B 970 1120 1270 1420 1570 1720 2020 2170 2170 2370 2590 2890
H 970 1120 1270 1420 1570 1720 2020 2240 2540 2840 3140 3440
L type S 1050 1200 1200 1500 1500 1650 1650 2020 2020 2320 2620 3070
L type H 1420 1720 1820 2170 2320 2320 2840 3290 2470 2470 3220 3220
RG 1” 1” 1” 1” 1” 1½” 1½” 1½” 1½” 1½” 1½” 1½”
39
Danvent DV
Run-around Coil Heat Exchanger DVR
Function: Fins:
Heat exchanger system with a heating Al – Standard aluminium.
coil built into the supply airside and a
cooling coil built into the extract air- Alup – Aluminium with a synthetic
side. The coils must be connected with coating. Used where the air
a piped circuit in which a water/glycol is mildly corrosive.
mixture is circulated.
AlMg3 – Aluminium magnesium alloy.
Application: Used where the air can
The run-around coil heat exchangers come into contact with sea-
are used where it is a requirement that water.
the two airflows must be kept com-
pletely separated, or where they are at Drip tray:
a distance from each other, e.g. on two The extract air section is fitted with a
different storeys of a building. drip tray for collection of condensed
water. The drip tray drain outlet must
Variants: be fitted with a water trap that is
Standard – Coil which has the same designed for the actual pressure differ-
width as the unit. ence. Refer to the assembly instruc-
MAX – Coil which is wider than tions.
the unit. DVR 10-150.
Droplet eliminator:
Construction: DVR is available with a droplet elimina-
The heat exchanger coils consists of tor in the extract air section.
copper tubes with aluminium fins.
Regulation:
Copper tubes: A motorised valve built into the pipe
Z – Copper tubes ø10 mm. circuit regulates the heat exchanger
Used for lower capacity heat capacity.
exchangers.
Extract air
1. Air vent
2. Manometer
3. Safety valve
4. Feed valve
5. Pressure expansion
6. Thermometer
7. Motorised valve
8. Flow measuring valve
9. Pump
Supply air
40
Run-around Coil Heat Exchanger DVR
Inlet
Outlet
Standard
Standard
DVR 10-150
DVR 10-150
RG – Drain connection,
extract air
MAX
DVRMAX
10-150
DVR 10-150
Drain connection,
extract air
Standard
DVR 190-240
RG – Drain connection,
extract air
Dimensions
Size 10 15 20 25 30 40 50 60 80 100 120 150 190 240
B 970 1120 1270 1420 1570 1720 2020 2170 2170 2370 2590 2890 3190 3490
H 520 595 670 745 820 895 1045 1120 1270 1420 1570 1720 2170 2470
300 300 300 300 300 300 300 300 300 300 300 300 300 300
Supply L* 450 450 450 450 450 450 450 450 450 450 450 450 450 450
600 600 600 600 600 600 600 600 600 600 600 600 600 600
450 450 450 450 450 450 450 450 450 450 450 450 600 600
Extract L* 600 600 600 600 600 600 600 600 600 600 600 600 750 750
750 750 750 750 750 750 750 750 750 750 750 750 900 900
41
Danvent DV
Heating Coil DVH
Function: Copper tubes:
Air heater. Z – Copper tubes ø10 mm.
Used for lower capacity heating
Heating mediums: coils.
W – Hot water.
Max. temperature 100 ˚C, Y – Copper tubes ø15 mm.
max. working pressure 10 Bar. Used for higher capacity heating
Also available for temperatures coils.
up to 130 ˚C.
Fins:
C – Condensation Al – Standard aluminium.
Max. working pressure depending
on the type of refrigerant. Alup – Aluminium with a synthetic
coating. Used where the air
S – Steam. is mildly corrosive.
Max. temperature 170 ˚C.
Max. working pressure 7 Bar. AlMg3 – Aluminium magnesium alloy.
Used where the air can
E – Electrical heating. come into contact. with
DVH 10-150. seawater.
Variants: Assembly:
Standard – Coil which has the same The heating coil is assembled on guide
width as the unit. rails, which enables easy removal for
inspection purposes.
MAX – Coil which is wider than
the unit. Hot water and Frost protection:
condensation coils only. Heating coils for hot water are available
DVH 10-150. with a connection piece for the fitting
of a temperature sensor in the water
Construction: circuit.
Finned coils for hot water and conden-
sation consists of copper tubes with Electrical heating:
aluminium fins. Finned coils for steam The inspection door, which can be
consists of stainless steel tubes with opened only by using a key, gives access
aluminium fins. Coils for electrical heat- to a terminal box for the electrical con-
ing consists of stainless steel tube heat- nections. The coil has a built-in safety
ing elements. thermostat with an automatic reset
function and an overheating thermostat
with manually resetting.
42
Heating Coil DVH
Standard
DVH 10-150
Standard
DVH 10-150
MAX
DVH 10-150
MAX
DVH 10-150
Standard
DVH 190-240
Dimensions
Size 10 15 20 25 30 40 50 60 80 100 120 150 190 240
B 970 1120 1270 1420 1570 1720 2020 2170 2170 2370 2590 2890 3190 3490
H1 520 595 670 745 820 895 1045 1120 1270 1420 1570 1720 2170 2470
H2 970 1120 1270 1420 1570 1720 2020 - - - - - - -
L* 150 150 150 150 150 150 150 150 150 - - - - -
- 300 300 300 300 300 300 300 300 300 300 300 300 300 300
- 450 450 450 450 450 450 450 450 450 450 450 450 450 450
- 600 600 600 600 600 600 600 600 600 600 600 600 600 600
L** 300 300 300 300 300 300 300 300 300 300 300 300 300 300
43
Danvent DV
Cooling Coil DVK
Function: Fins:
Air cooler. Al – Standard aluminium.
Droplet eliminator:
DVK is available with a droplet elimina-
tor that prevents condensed water
droplets from being carried into the
airflow.
44
Cooling Coil DVK
Standard
DVK 10-150
RG – Drain connection
MAX
DVK 10-150
Drain connection
Standard
DVK 190-240
RG – Drain connection
Dimensions
Size 10 15 20 25 30 40 50 60 80 100 120 150 190 240
B 970 1120 1270 1420 1570 1720 2020 2170 2170 2370 2590 2890 3190 3490
H1 520 595 670 745 820 895 1045 1120 1270 1420 1570 1720 2170 2470
H2 970 1120 1270 1420 1570 1720 2020 - - - - - - -
L* 450 450 450 450 450 450 450 450 450 450 450 450 600 600
- 600 600 600 600 600 600 600 600 600 600 600 600 750 750
- 750 750 750 750 750 750 750 750 750 750 750 750 900 900
RG 1” 1” 1” 1” 1” 1½” 1½” 1½” 1½” 1½” 1½” 1½” 1½” 1½”
45
Danvent DV
Cooler DVU
Function: Compressor:
Cooler DVU in size 10-40 is a com- Stepless speed controlled compressor
plete cooling system, with all cooling combined with a frequency converter,
components and control system which is designed special for this appli-
placed in a DV casing, which can be cation. The construction ensure the
combined to the DV air handling unit. lowest energy consumption, because
This set up of the cooling system the cooling capacity is always adapted
need no external condenser for the current need. This eliminates also
removing of heating energy or sepa- undesirable start/stop of the compres-
rate space for cooling equipment. It is sor. Hereby is durability improved for
therefore very easy to install cooling many years of reliable running.
in the selected DV unit.
Refrigerant:
Ready for operation upon delivery: Type R 407 C.
Cooler DVU is configured and tested
from the factory, and will be delivered Electrical connection:
complete finished and ready for start 3 x 400 V + N + PE.
up after installation, which is very 0-10 V DC for control of capacity.
easy. Install the Cooler DVU between Start/stop signal.
the air handling unit sections and Possibility for alarm at operating error.
connect power supply, control signals
and drain for condensing water. DVU Service friendly:
can be connected to almost all types Cooler DVU is equipped very service
of control systems for air handling friendly and has a large inspection door
units. that gives easy access for inspection
and service of the cooling components.
Construction:
DVU is designed with an evaporative Drip tray:
cooling coil for cooling the supply air The cooling coil is fitted with a drip
in the lower part of the unit, and a tray for collection of condensed water.
condensing coil in the extract air in The drip tray outlet must be fitted with
the upper part of unit. Both coils a water trap that is designed for the
consist of copper tubes and alumini- actual pressure difference. Refer to the
um fins. assembly instructions.
46
Cooler DVU
Energy saving with stepless capacity regulation
Absorbed power
Traditionel 3-step
cooling
DV Cooler stepless
Cooling capacity
Power saved with Cooler DVU
Airflow – Capacity
1000 2000 3000 5000 10000 15000 m 3/h
40
30
25
20
15
10
Dimensions
Size 10 15 20 25 30 40
B 970 1120 1270 1420 1570 1720
H 970 1120 1270 1420 1570 1720
L 970 1120 1120 1270 1270 1270
47
Danvent DV
Plug Fan DVE
Function: Regulation of air flow:
Plug fan built into an acoustically insu- The frequency converter can continu-
lated air handling unit. ously control the fan speed and airflow.
Power consumption can be greatly
Construction: reduced by operating the fan at lower
Single inlet plug fan with open outlet speed.
into the air handling unit.
The fan impeller is fitted directly to the Operating temperatures:
motor shaft. Standard design: -10/+40 ˚C
This fan type has low sound power lev- Special design: -30/+60 ˚C.
els in the lower frequencies.
Efficiency up to 75%. Service friendly:
Fan and motor are assembled on vibra- The DVE fan section is equipped with a
tion isolators. large inspection door giving easy access
for service. The DVE in sizes 10-30 has
S – Standard plug fan the fan and motor assembled on guide
DVE 10-240 rails allowing easy extraction from the
unit.
H – High efficiency plug fan
DVE 10-150 Balancing:
All fans are fully balanced both statically
Positioning in the air handling unit: and dynamically.
A plug fan supplies air at the fan sec-
tion outlet with a low and even air Vibration isolators:
speed. In certain situations it can, there- The fan and motor are built on a stable
fore, be an advantage to position air base frame that is connected to the
handling components on the outlet unit casing with rubber vibration isola-
side of the fan. tors. These are designed for high levels
of vibration absorption.
Motor:
DVE is supplied with a 1-speed motor. Flexible coupling:
In order to regulate the fan speed to The fan inlet is flexible connected to
its actual operating point the motor the unit casing. This ensures a good
must be fitted with a frequency con- vibration absorption.
verter.
Sound data:
Twin fans: The design program SystemairCAD
For optimizing the fan efficiency in the calculates the fan sound power level
operating point, are following types Lw (ref. 1 pW). The calculations are
equipped with Twin fans: based on measurements carried out
DVE-S 190-240 according to the following standards:
DVE-H 50-150
• EN ISO 5136, determination of
Twin fans are 2 separate plug fans, each sound power level in a duct.
powered by a motor. The parallel oper- • EN ISO 3741, determination of
ation of the Twin fans is optimized by a sound power level in reverberation
common frequency converter. rooms.
48
Plug Fan DVE
DVE 10-150
DVE 190-240
DVE 190-240
Dimensions
Size 10 15 20 25 30 40 50 60 80 100 120 150 190 240
B 970 1120 1270 1420 1570 1720 2020 2170 2170 2370 2590 2890 3190 3490
H1 520 595 670 745 820 895 1045 1120 1270 1420 1570 1720 2770 2470
H2 970 1120 1270 1420 1570 1720 2020 - - - - - - -
L, DVE-S 750 750 750 900 900 1050 1200 1200 1350 1650 1800 1950 1950 2100
L, DVE-H 750 750 900 900 1050 1200 1050 1200 1200 1500 1650 1800 - -
A* 750 750 750 900 900 900 1000 1000 1100 1200 1300 1400 1300 1400
* Space needed for extracting the fan from the unit housing.
49
Danvent DV
Plug Fan DVE
DVE 10-150 duct connections
185
Dimensions
Size 10 15 20 25 30 40 50 60 80 100 120 150 190 240
D 900 1050 1200 1350 1500 1650 1950 2100 2100 2300 2520 2820 3120 3420
E 350 450 500 600 650 750 900 1000 1150 1300 1450 1600 1950 2250
F 350 450 500 600 650 750 900 1000 1150 1300 1450 1600 1500 1500
50
Plug Fan DVE 10-15
Ps Ps
Pa 1100 1500 2000 2500 3000 4000 m3/h Pa 1100 1500 2000 2500 3000 4000 m3/h
2500 2500
64
DVE-10-S DVE-10-H
in -1
69
nm
70
2,0
72
%
2000 1,5 2000
72
in -1
1,5 45
74
kW kW 00
nm
74
s=
s=49
1,1 1,1
00
40
1500 46 1500 00
72
00
72
0,7 0,7
5 5 35
41 00
00
65
0,5 1000 0,5
1000 5 5
31
65
00
36
00
0,3 0,3
54
7 7
32 27
700 00 700 00
24
54
28 00
00
500 500
25
00 21
00
400 400
19
22 00
00
300 300
200 200
0,3 0,4 0,5 0,7 1,0 1,2 m3/s 0,3 0,4 0,5 0,7 1,0 1,2 m3/s
Ps Ps
Pa 1500 2000 2500 3000 4000 5000 6000 m3/h Pa 1500 2000 2500 3000 4000 5000 6000 m3/h
2500 2500
67
67
DVE-15-S DVE-15-H
72
72
%
2,2 2,2
in -1
in -1
2000 kW 2000
74
kW
74
nm
nm
s=
s=
41
41
00
00
1,5 1,5
1500 1500
72
72
1,1 1,1
36
36
00
00
65
65
32
32
00
5 5
0,5 0,5
5 5
28
28
00
00
700 700
54
54
0,3 0,3
25
25
7 7
00
00
500 500
22
22
00
00
400 400
19
19
50
50
300 300
17
17
00
00
200 200
0,4 0,5 0,7 1,0 1,5 1,7 m3/s 0,4 0,5 0,7 1,0 1,5 1,7 m3/s
51
Danvent DV
Plug Fan DVE 20-25
Ps Ps
Pa 2500 3000 4000 5000 6000 7000 8000 m3/h Pa 2500 3000 4000 5000 6000 7000 8000 m3/h
2500 2500
64
in -1
DVE-20-S DVE-20-H
69
nm
4,0
70
72
%
2000 3,0 2000 32
72
00
74
kW
%
3,0
s=
in -1
kW
74
nm
s=
2,2
2,2 28
35
1500 1500 00
00
72
72
1,5 25
1,5 00
31
00
1000 1,1 65
1000 1,1
22
00
27
65
00
0,7
5 0,7
5
54
19
50
24
700 700
00
0,5
5 0,5
5
17
00
21
54
00
500 500
15
00
18
50
400 400
13
50
17
00
300 300
200 200
0,6 0,7 1,0 1,5 2,0 2,4 m3/s 0,6 0,7 1,0 1,5 2,0 2,4 m3/s
ER 45C
Ps Ps
Pa 2500 3000 4000 5000 7000 10000 m3/h Pa 2500 3000 4000 5000 7000 10000 m3/h
2500 2500
64
in -1
69
DVE-25-S DVE-25-H
70
nm
72
%
5,5
72
4,0 28
%
74
2000 2000 4,0 50
74
in -1
s=
s=
nm
3,0
kW 3,0
32
kW 25
00
00
1500 1500
72
2,2
2,2
28
22
00
72
00
65
1,5
1,5
1000
25
1000 19
00
50
1,1
1,1
22
65
00
17
54
700 00
700 0,7
5 0,7
5
19
50
15
0,5 00
5 0,5
5
500 500
17
00
13
00
54
400 400
15
00
11
50
300 300
13
50
200 200
0,7 1,0 1,5 2,0 2,5 2,8 m3/s 0,7 1,0 1,5 2,0 2,5 2,8 m3/s
52
Plug Fan DVE 30-40
Ps Ps
Pa 4000 5000 7000 10000 12000 m3/h Pa 4000 5000 7000 10000 12000 m3/h
2500 2500
in -1
in -1
64
DVE-30-S DVE-30-H
70
72
nm
69
7,5
nm
5,5 26
72
%
28 00
5,5
74
2000 50 2000
s=
4,0
%
kW 4,0
74
kW 23
00
s=
25
00
72
1500 3,0 1500
3,0
20
2,2 22 00
00 2,2
72
65
1000 1000 17
1,5 19 50
50
1,5
1,1
17 1,1
700 00 700 15
00
54
65
0,7 15
5 00 0,7
5
13
00
500 500
13
50
54
400 400
110
12 0
00
300 300
200 200
0,9 1,0 1,5 2,0 2,5 3,0 3,4 m3/s 0,9 1,0 1,5 2,0 2,5 3,0 3,4 m3/s
Ps Ps
Pa 4000 5000 7000 10000 15000 m3/h Pa 4000 5000 7000 10000 15000 m3/h
2500 2500
70
64
DVE-40-S DVE-40-H
in -1
72
69
%
7,5 nm
74
7,5
72
%
2000 2000
in -1
s=
22 74
50
nm
5,5 5,5
s=
kW kW
26
00
20
72
72
3,0 18
3,0 00
65
20
2,2 2,2
1000 1000 16
00
00
17
1,5 1,5 14
50
65
00
54
700 700
1,1 1,1
12
50
15
00
00
13
00
400 400
95
0
11
00
300 300
200 200
1,0 1,5 2,0 2,5 3,0 4,0 4,5 m3/s 1,0 1,5 2,0 2,5 3,0 4,0 4,5 m3/s
53
Danvent DV
Plug Fan DVE 50-60
Ps Ps
Pa 5000 7000 10000 15000 19000 m3/h Pa 5000 7000 10000 15000 19000 m3/h
2500 2500
in -1
DVE-50-S DVE-50-H
64
69
70
nm
72
%
72
2000 7,5 2000 2x
4,0 28
74
74
kW
in -1
00
s=
s=
nm
2x
5,5 3,0
22
kW 25
00
50
1500 1500
72
2x
4,0 20 2,2
00
22
00
72
65
3,0
2x
18
1000 1,5
1000
00
19
50
2,2
2x
1,1
16
00
17
54
00
700 1,5 700
65
2x
0,7
14
5
00
1,1 15
00
2x
0,5
5
12
500 500
50
13
54
00
400 400
11
00
11
50
300 300
95
0
200 200
1,5 2,0 2,5 3,0 4,0 5,0 5,5 m3/s 1,5 2,0 2,5 3,0 4,0 5,0 5,5 m3/s
Ps Ps
Pa 7000 10000 15000 20000 25000 m3/h Pa 7000 10000 15000 20000 25000 m3/h
2500 2500
in -1
64
DVE-60-S DVE-60-H
69
nm
70
2x
5,5
72
%
72
2000 2000
%
25
00 74
74
s=
in -1
s=
nm
7,5 2x
4,0
kW 22
20
50
00
1500 1500
2x
72
5,5 3,0
kW
18
20
00
00
2x
4,0 2,2
65
72
16
1000 1000 17
00
3,0 50
2x
1,5
14
2,2
00
2x
1,1
54
15
65
700 700 00
12
50
1,5
2x
0,7
5 13
00
500 500
11
1,1
00
54
400 400
10
11
00
00
90
0
300 300
200 200
1,8 2,0 2,5 3,0 4,0 5,0 6,0 7,0 m3/s 1,8 2,0 2,5 3,0 4,0 5,0 6,0 7,0 m3/s
54
Plug Fan DVE 80-100
Ps Ps
Pa 8000 10000 15000 20000 30000 m3/h Pa 8000 10000 15000 20000 30000 m3/h
2500 2500
DVE-80-S DVE-80-H
in -1
70
64
nm
69
72
%
2000
in -1
2000
74
11
nm
72
,0 2x
s=
%
kW 5,5 21
50
74
kW
s=
18
00
20
1500 1500 2x 00
7,5
72
4,0
72
16
00 18
2x 00
5,5 3,0
65
1000 1000 2x 16
14
4,0 2,2 00
00
3,0
12
2x 14
65
50
1,5 00
54
700 700
2,2 2x
1,1 12
11
50
00
1,5
500 500
98
2x 11
0
0,7 00
54
5
400
88
400
0
95
0
80
0
300 300
200 200
2,2 2,5 3,0 4,0 5,0 7,0 9,0 m3/s 2,2 2,5 3,0 4,0 5,0 7,0 9,0 m3/s
Ps Ps
Pa 10000 15000 20000 30000 40000 m3/h Pa 10000 15000 20000 30000 40000 m3/h
2500 2500
DVE-100-S DVE-100-H
70
64
in -1
69
72
nm
%
2000 15 2000
in -1
2x
74
,0
72
7,5
%
19
nm
s=
50
74
s=
16
11 2x 18
00
,0 5,5 00
kW
1500 1500 kW
72
14
50
2x
7,5 4,0 16
72
00
65
13
2x
00
5,5 3,0
1000 1000 14
00
11
2x
80
2,2
4,0
65
12
50
10
54
2x
1,5
11
00
95
2,2
0
2x
1,1
500 500 10
00
85
54
0
400 400 90
0
75
0
300 300
200 200
3,0 4,0 5,0 7,0 10,0 m3/s 3,0 4,0 5,0 7,0 10,0 m3/s
55
Danvent DV
Plug Fan DVE 120-150
Ps Ps
Pa 15000 20000 30000 40000 50000 m3/h Pa 15000 20000 30000 40000 50000 m3/h
2500 2500
DVE-120-S DVE-120-H
70
in -1
64
69
nm
72
%
2000 22 2000
,0
74
18 2x
72
%
in -1
,5 11 17
s=
74
,0 50
nm
s=
15 14
,0 20 2x
kW 7,5
kW
1500 1500 15
72
50
13
11 00 2x
,0 5,5
72
14
00
11
65
50 2x
7,5 4,0
1000 1000 12
50
10 2x
5,5 20 3,0
2x 11
2,2 00
700 4,0 700
54
90
65
0
98
3,0 2x 0
1,5
80
0
500 500
88
0
2,2
72
0
54
400 400 80
0
64
0
300 300
200 200
3,5 4,0 5,0 7,0 10,0 14,0 m3/s 3,5 4,0 5,0 7,0 10,0 14,0 m3/s
Ps Ps
Pa 16000 20000 30000 40000 50000 60000 m3/h Pa 16000 20000 30000 40000 50000 60000 m3/h
2500 2500
DVE-150-S DVE-150-H
70
in -1
64
72
69
%
2000
nm
2000
in -1
74
72
22
%
s=
nm
,0 2x 1
2 x 520
74
11,
12 0k 15
W
s=
18 40 ,0
,5
kW
14
1500 1500 00
72
15
,0 2x
7,5
11
12
00
11 50
72
,0 2x
5,5
65
10
1000 1000
00
11
20
7,5 2x
4,0
90
0
2x 10
3,0 00
65
5,5
54
700 700
80
0
2x 90
4,0 2,2 0
70
500 500 80
0
3,0 0
54
400 400
62
0
70
0
55
300
0
300
200 200
4,4 5,0 7,0 10,0 15,0 18,0 m3/s 4,4 5,0 7,0 10,0 15,0 18,0 m3/s
56
Plug Fan DVE 190-240
Ps Ps
Pa 20000 30000 40000 50000 80000 m3/h Pa 25000 30000 40000 50000 70000 100000 m3/h
2500 2500
64
DVE-190-S DVE-240-S
in -1
69
2x
nm
in -1
64
18,
69
72
5
nm
2000 2000
%
14
00 2x
74
72
2x 2x 22
%
15, 18, 12
s=
,0 00
74
0k 5k
W W
13
s=
00 2x
15,
2x 0 11
1500 11, 1500 00
0
11 2x
50 11,
72
0 10
2x 00
7,5
72
10 2x
20 90
1000 2x
1000 7,5 0
5,5
2x
90 5,5 80
2x 0 0
65
4,0
700 700
65
2x
2x 4,0
3,0 80
0 70
0
2x
2x 72 3,0
2,2 0
500 500 62
0
54
54
64
400 0 400
55
0
300 300
200 200
5,5 7,0 10,0 15,0 20,0 23,0 m3/s 7,0 10,0 15,0 20,0 25,0 28,0 m3/s
57
Danvent DV
Centrifugal Fan DVV
Function: Service friendly:
Centrifugal fan built into an acoustically The DVV is equipped with a large
insulated air handling unit. DVV 10-150. inspection door giving easy access for
service. The sizes 10-30 have the fan
Construction: and motor assembled on guide rails
Double inlet centrifugal fan with belt allowing easy extraction from the unit.
drive.
Fan, motor and base frame is assem- Bearings:
bled on vibration isolators. Smaller fans are fitted with fully
encased bearings, that are lubricated
BK – Centrifugal fan with backward during manufacture. The bearings are
curved blades. assembled in vibration absorbing rub-
This fan type has efficiency up to ber bushes.
82%, and is therefore extremely Larger fans are fitted with bearings
cost-effective to run. provided with lubricating nipples. These
The BK fan can deliver high pres- bearings must be lubricated at regular
sure, and is suitable for plants that intervals according to the operating
operate with pressure variations. conditions.
58
Centrifugal Fan DVV
Connection variants
Dimensions
Size 10 15 20 25 30 40 50 60 80 100 120 150
B 970 1120 1270 1420 1570 1720 2020 2170 2170 2370 2590 2890
H1 520 595 670 745 820 895 1045 1120 1270 1420 1570 1720
H2 970 1120 1270 1420 1570 1720 2020 - - - - -
L 785 785 785 935 935 1085 1235 1235 1385 1685 1835 1985
A* 750 750 750 900 900 900 900 900 1100 1200 1400 1500
* Space needed for extracting the fan from the unit housing.
59
Danvent DV
Centrifugal Fan DVV
Duct connections
Dimensions
Size 10 15 20 25 30 40 50 60 80 100 120 150
D* 300 350 450 500 600 650 700 800 900 1000 1100 1200
F 530 530 600 600 700 850 900 950 850 950 1000 1050
G 75 75 75 75 75 75 75 75 75 75 75 75
G 145 170 145 170 145 170 270 230 280 330 380 430
K 145 170 145 170 145 170 270 245 295 345 395 445
K 75 75 75 75 75 75 75 90 90 90 90 90
M 145 170 145 170 145 170 270 245 295 315 350 460
M 75 75 145 170 145 170 75 90 90 80 80 80
* Dimensions of the duct connection part DVT – A, see page 79.
60
Centrifugal Fan DVV 10-15
DVV-10-BK
56
in -1
%
67
%
72
nm
59
1,6
t=
t=
2, 62
0 00
67
1,0 k 56
W 00
50
56
00
0,63
45
00
0,40
40
00
35
00
0,25
30
00
25
00
DVV-10-BK: Max. motor: IEC 112 M, J = 0,010 kgm2 DVV-10-FK: Max. motor: IEC 112 M, J = 0,018 kgm2
DVV-15-BK
63
in -1
%
70
74
2,5
n
%
t=
60
t=
58
00
1,6
kW
69
52
00
1,0
46
00
56
0,6 40
3 00
35
00
0,4
31
00
27
0 0
23
50
DVV-15-BK: Max. motor: IEC 112 M, J = 0,014 kgm2 DVV-15-FK: Max. motor: IEC 112 M, J = 0,028 kgm2
61
Danvent DV
Centrifugal Fan DVV 20-25
DVV-20-BK
62
in -1
4,0
72
%
76
nm
t=
%
46
64
00
t=
2,5 k
W
71
40
00
1,6
34
61
00
1,0
29
00
0,6
3
25
00
0,4
21
00
17
50
DVV-20-BK: Max. motor: IEC 132 M, J = 0,034 kgm2 DVV-20-FK: Max. motor: IEC 132 M, J = 0,06 kgm2
DVV-25-BK
in -1
nm
61
%
72
77
4,0
%
t=
65
t=
2,5 k 37
W 00
71
32
1,6 00
60
27
1,0 00
23
0,6 00
3
20
00
0,4
17
00
14
50
DVV-25-BK: Max. motor: IEC 132 M, J = 0,05 kgm2 DVV-25-FK: Max. motor: IEC 132 M, J = 0,11 kgm2
62
Centrifugal Fan DVV 30
DVV-30-BK
65
in -1
76
nm
%
5,5
80
t=
4,0
kW
34
%
00
66
t=
75
2,5
29
00
64
1,6
25
00
1,0
21
00
0,6 18
3 00
15
50
13
00
DVV-30-BK: Max. motor: IEC 132 M, J = 0,10 kgm2 DVV-30-FK: Max. motor: IEC 132 M, J = 0,15 kgm2
63
Danvent DV
Centrifugal Fan DVV 40
%
DVV-40-BK1 DVV-40-BK2
in -1
74
66
79
nm
t=
10
,0
6,3 30
kW 00
75
in -1
65
nm
76
%
4,0 k 26
4,0 00
80
W t=
5,0
27
00
2,5 22
75 2,5 00
23
62
00
1,6 19
1,6
64
00
20
00
1,0 16
1,0 00
17
00
13
50
0,6 14
3 50 0,6
3
11
12 50
50
DVV-40-BK1: Max. motor: IEC 160 L, J = 0,15 kgm2 DVV-40-BK2: Max. motor: IEC 160 L, J = 0,53 kgm2
%
67
t=
64
Centrifugal Fan DVV 50
DVV-50-BK1 DVV-50-BK2
%
in -1
75
80
69
10,
nm
12
t=
0 ,5
27
00
in -1
6,3
kW
nm
67
%
77
81
6,3
75
23
t= 00
4,0 k 23
W
00 4,0
20
77 00
2,5 20
00
2,5
67
17
63
00
17
1,6 50
1,6
14
50
15
00
1,0
1,0
12
13 50
00
11 10
00 50
DVV-50-BK1: Max. motor: IEC 160 L, J = 0,33 kgm2 DVV-50-BK2: Max. motor: IEC 160 L, J = 0,83 kgm2
%
68
t=
65
Danvent DV
Centrifugal Fan DVV 60
DVV-60-BK1 DVV-60-BK2
in -1
%
nm
81
75
70
t=
10, 12
0 ,5 23
00
76
in -1
% 6,3
kW
nm
81
75
t=
70
6,3 19
kW 19 50
00
4,0 4,0
76
65
16 16
50 50
2,5 2,5
65
14 14
50 50
1,6 1,6
12 12
50 50
11 11
00 00
95 95
0 0
DVV-60-BK1: Max. motor: IEC 180 L, J = 0,90 kgm2 DVV-60-BK2: Max. motor: IEC 180 L, J = 1,23 kgm2
%
68
t=
66
Centrifugal Fan DVV 80
DVV-80-BK1 DVV-80-BK2
in -1
76
81
70
t=
16
nm
,0
21
in -1
50
nm
81
76
70
t=
10,0 10,0
kW kW
19 19
00 00
76
76
6,3 6,3
16 16
50 50
4,0 4,0
14 14
00 62 00
62
2,5 2,5
11 11
50 50
1,6 1,6
95 95
0 0
80 80
0 0
DVV-80-BK1: Max. motor: IEC 180 L, J =1,55 kgm2 DVV-80-BK2: Max. motor: IEC 180 L, J = 2,29 kgm2
%
69
t=
67
Danvent DV
Centrifugal Fan DVV 100
DVV-100-BK1 DVV-100-BK2
in -1
81
76
nm
70
t=
22
,0
in -1
19
00
nm
15,0
76
81
76
t=
70
10, 15 16 10, 16
0k ,0 00 0k 00
W W
6,3 13 76 6,3 13
50 50
64
64
4,0 11 4,0 11
70 70
2,5 10 2,5 10
00 00
87 87
0 0
75 75
0 0
DVV-100-BK1: Max. motor: IEC 200 L, J = 2,56 kgm2 DVV-100-BK2: Max. motor: IEC 200 L, J = 3,61 kgm2
%
70
t=
68
Centrifugal Fan DVV 120
DVV-120-BK1 DVV-120-BK2
in -1
77
82
70
nm
t=
30
22,0 ,0 17
00
in -1
nm
77
15,0
%
kW
82
77
70
t= 14
15 50
,0
kW 14
10,0 00
10,0
12 77
12
50 50
6,3
64
6,3
64
10 10
70 70
4,0
4,0
90 90
0 0
2,5
2,5
77 77
0 0
65 65
0 0
DVV-120-BK1: Max. motor: IEC 200 L, J = 4,61 kgm2 DVV-120-BK2 Max. motor: IEC 200 L, J = 6,37 kgm2
%
72
t=
69
Danvent DV
Centrifugal Fan DVV 150
DVV-150-BK1 DVV-150-BK2
in -1
%
nm
85
80
72
t=
22,0 30
,0 14
50
80
15,0
in -1
kW
nm
%
12
77
50
82
71
t=
16
,0
10,0 11 10,0
kW 50
10
70
69
77
6,3 10 6,3
00
90
0
64
4,0 85 4,0
0
75
75 0
0
65 65
0
0
57 57
0
0
DVV-150-BK1: Max. motor: IEC 225 L, J = 7,72 kgm2 DVV-150-BK2: Max. motor: IEC 225 L, J = 9,20 kgm2
70
Air Distributor DVL
Function: Construction:
DVL 10-150. DVL consists of a distributor plate fit-
Used where an even distribution of the ted to the fans air outlet. The air dis-
airflow is required after the DVV fan tributor is built into the air handling
outlet. Can be necessary in cases unit.
where an air handling component such
us a sound attenuator is fitted after the
DVV fan.
Dimensions
Size 10 15 20 25 30 40 50 60 80 100 120 150
B 970 1120 1270 1420 1570 1720 2020 2170 2170 2370 2590 2890
H1 520 595 670 745 820 895 1045 1120 1270 1420 1570 1720
H2 970 1120 1270 1420 1570 1720 2020 - - - - -
L 335 335 335 335 335 335 335 335 335 335 485 485
A 120 120 130 160 160 180 180 220 220 220 320 320
71
Danvent DV
Sound Attenuator DVD
Function: Variants:
Sound attenuator DVD is used to 1 – Baffles with standard lining. Can be
reduce the sound output levels from used in all types of commercial
the air handling unit to its inlets and ventilation plant.
outlets.
2 – Baffles with a hard-wearing lining
Construction: which is resistant to abrasions from
The sound attenuator is an absorption dry cleaning. The DVD has large
attenuator with baffles. The baffles are inspection doors enabling the baf-
surface treated in order to prevent the fles to be easily extracted for
absorption material fibres from being cleaning.
carried into the airflow.
3 – Baffles with a synthetic lining which
is suitable for wet cleaning. Each
baffle is encased in a stainless steel
frame.The DVD has large inspec-
tion doors enabling the baffles to
be easily extracted for cleaning.
Sound attenuation
Attenuation dB Mid-Frequency Hz
63 125 250 500 1000 2000 4000 8000
DVD - 900 5 11 17 25 36 39 36 28
DVD - 1200 7 15 23 32 43 46 43 36
72
Sound Attenuator DVD
DVD 10-150
DVD 190-240
Dimensions
Size 10 15 20 25 30 40 50 60 80 100 120 150 190 240
B 970 1120 1270 1420 1570 1720 2020 2170 2170 2370 2590 2890 3170 3490
H1 520 595 670 745 820 895 1045 1120 1270 1420 1570 1720 2170 2470
H2 970 1120 1270 1420 1570 1720 2020 - - - - - - -
L 900 900 900 900 900 900 900 900 900 900 900 900 900 900
L 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200
73
Danvent DV
Inspection Section DVI
Function: Construction:
DVI is used where the possibility of Inspection section DVI consists of an
service, inspection or measuring is empty unit casing with an inspection
required, before or after an air handling door.
function.
Accessories:
Inspection window fitted into the
access door.
DVI 10-150
DVI 190-240
Dimensions
Size 10 15 20 25 30 40 50 60 80 100 120 150 190 240
B 970 1120 1270 1420 1570 1720 2020 2170 2170 2370 2590 2890 3190 3490
H1 520 595 670 745 820 895 1045 1120 1270 1420 1570 1720 2170 2470
H2 970 1120 1270 1420 1570 1720 2020 - - - - - - -
L DVI 10-150: 300 - 450 - 600 - 750 - 900 - 1050 - 1200 - 1350 - 1500
L DVI 190-240: 300 - 450 - 600 - 750
74
Empty Section DVO
Function: Construction:
Used in units where space is required Empty section DVO consists of an
to fit a component, such as a tempera- empty unit casing, where the side
ture sensor, or if it is required to have panels are assembled with screws.
the possibility of applying an extra air
handling function at a later date. Accessories:
Inspection window fitted into the side
panel.
DVO 10-150
DVO 190-240
Dimensions
Size 10 15 20 25 30 40 50 60 80 100 120 150 190 240
B 970 1120 1270 1420 1570 1720 2020 2170 2170 2370 2590 2890 3190 3490
H1 520 595 670 745 820 895 1045 1120 1270 1420 1570 1720 2170 2470
H2 970 1120 1270 1420 1570 1720 2020 - - - - - - -
L 150 - 300 - 450 - 600 - 750 - 900 - 1050 - 1200 - 1350 - 1500
Inspection window cannot be fitted to the DVO when L = 150.
75
Danvent DV
Outdoor Air Section DVY
Function: Construction:
Outdoor air section DVY is used for air Outdoor air section DVY consists of an
intake and outlet in roof units for com- air handling unit casing with inspection
binations of Danvent DV 10-50. DVY door. The openings for air intake and
has air intake through the end of the outlet has louvers for effective protec-
unit, and outlet of exhaust air behind tion against rain and snow.
the unit, opposite the inspection side.
Type 1
Type 2
Dimensions
Size 10 15 20 25 30 40 50 60 80 100 120 150
B 970 1120 1270 1420 1570 1720 2020 2170 2170 2370 2590 2890
H 970 1120 1270 1420 1570 1720 2020 2240 2540 2840 3140 3440
L 520 670 820 820 970 1120 1120 1420 1420 1570 1720 1720
76
Base Frame DVZ
Function: Construction:
To ensure that the Danvent DV is The base frame consists of strong, rigid
assembled on an even and stable sup- galvanised steel profiles. Equipped with
port, the base frame DVZ is used. adjustable supporting feet for indoor
units.
L
B
B L
Unit width Unit length
H
Indoor unit 150 og 250
Roof unit 250
Supporting Legs
Function: Construction:
Danvent DV in sizes 10-40 will be sup- The supporting legs are made of sturdy
plied with supporting legs.Therefore it galvanized steel, and have adjustable
is possible to assemble the air handling supporting feet.
unit on an even and stable base with-
out an additional base frame. The air
100
handling unit can also be supplied with
base frame DVZ if necessary.
ø 50
77
Danvent DV
Double height unit
DV 10-150
Dimensions for Ducts
Dimensions on the following unit functions
Damper DVA 190-240 See page 21 Mixing damper DVP 190-240 See page 27
Damper DVB - - 23 Fan DVE, outlet on top, 190-240 - - 50
Mixing damper DVM - - 25 Fan DVV, outlet - - 60
DV 10-50 DV 60-150
DV 10-50 DV 60-150
185 185
78
Duct Connection Part DVT
Type 1 Type 3
DVT 10-150 DVT 10-240
Type 2 Type 4
DVT 10-150 DVT 10-240
Function: Variant:
Duct Connection Part DVT is used when con- A – Fan DVV, outlet
necting ductwork to the DV air handling unit. B – Damper DVA, mixing damper DVP
C – Damper DVB, mixing damper DVM
D – Others
Dimensions
Size 10 15 20 25 30 40 50 60 80 100 120 150 190 240
Variant A D 300 350 450 500 600 650 700 800 900 1000 1100 1200 - -
E 300 350 450 500 600 650 700 800 900 1000 1100 1200 - -
Variant B D - - - - - - - - - - - - 2600 2800
E - - - - - - - - - - - - 1500 1800
Variant C D 500 600 800 900 1100 1200 1500 1600 1700 1800 2000 2300 2600 2800
E 200 200 300 300 300 400 400 500 600 700 700 700 1000 1200
Variant D D 900 1050 1200 1350 1500 1650 1950 2100 2100 2300 2520 2820 3120 3420
E 350 450 500 600 650 750 900 1000 1150 1300 1450 1600 1950 2250
79
DV_Catalogue.uk.10.2009-V2