Relays and Ol SC Calculationsohiou1183141301

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 197

LSHORT-CIRCUIT CURRENT

..
CALCULATIONS
AND PROTECTIVE RELAY COORDINATION FOR
INDUSTRIAL AND COMMERCIAL POWER SYSTEMS,

A Thesis Presented to
The Faculty of the College of Engineering and Technology
Ohio University

In Partial Fulfillment
of the Requirements for the Degree
Master of Science

Houshang C. Mohammadi
s
August, 1986

OHIO UNIVERSITY
LIBRARY
ACKNOWLEDGEMENTS

I would like to offer my appreciation and thanks

to Dr. Albert J.F. Keri my advisor, and Dr. H.W. Hill for
their guidance and encouragement in the preparation of this

thesis.

I owe a great deal to my employer, E.I. Dupont


company who gave me this opportunity to continue my

education while I was working. I would also like to express


my thanks to Mr. R.L. Doughty senior project engineer at
E.I. Dupont company who checked my work through this study.
Finally, I would like to express my thanks to the
faculty and all members of staff at Ohio University who have

contributed a great deal towards this work.


TABLE OF CONTENTS

ABSTRACT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xii

CHAPTER 1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

1.1 Statement of the problem . . . . . . . . . . . . . . . . 1

1.2 Literature search . . . . . . . . . . . . . . . . . . . . . . . 4

1.3 State of the art . . . . . . . . . . . . . . . . . . . . . . . . . 5

CHAPTER 2. Sources of short circuit . . . . . . . . . . . . . . . . . 7

2.1 Generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

2.2 Synchronous motors . . . . . . . . . . . . . . . . . . . . . . . 8

2.3 Induction motors . . . . . . . . . . . . . . . . . . . . . . . . . 10

2.4 Electric utility systems . . . . . . . . . . . . . . . . . 11

2.5 Rotating machine reactance . . . . . . . . . . . . . . . 12

2.6 Symmetrical and asymmetrical currents . . . . 15

CHAPTER 3. Short-circuit-current calculation . . . . . . . . 17


3.1 Important assumptions . . . . . . . . . . . . . . . . . . . . 18
3.2 Single line diagram . . . . . . . . . . . . . . . . . . . . . . 18

3.3 Impedance diagram . . . . . . . . . . . . . . . . . . . . . . . . 19

3.4 Type and location of faults required . . . . . 22


3.5 Symmetrical short-circuit current . . . . . . . . 22

calculation

3.6 Momentary short circuit calculation . . . . . . 25

3.7 Interrupting short circuit calculation . . . 27


CHAPTER 4. General equipment used for protection . ... 31

4.1 Overcurrent relays . . . . . . . . . . . . . . . . . ....... 32


4.2 Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

4.3 Circuit breakers . . . . . . . . . . . . . . . . . . . . . . . . . 38

4.4 Generator protection .................... 40

4.5 Transformer protection . . . . . . . . . . . . . . . . . . 44

CHAPTER 5. Coordination of protective devices . . . . . . . 47

5.1 Primary considerations for coordination . . 48

5.2 Data required for a coordination . . . . . . . . . 51

5.3 Methods of coordination. . . . . . . . . . . . . . . . . . 52

5.4 Testing of protective devices . . . . . . . . . . . . 66

CHAPTER 6. Conclusion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

BIBLIOGRAPHY ....................

APPENDIX 1 . Impedance data . . . . . . . . . . . . . . . . . . . . . . . . . . 77


Al.l ANSI standard reactance values . . . . . . . . . . 77
A1.2 Transmission line impedances . . . . . . . . . . . . 78
A1.3 1 5 K V cable impedances . . . . . . . . . . . . . . . . . . . 79

A1.4 5KV cable impedances . . . . . . . . . . . . . . . . . . . . 80

A1.5 Correction factors for non magnetic ducts 81


APPENDIX 2. Belle plant short circuit study . . . . . . . . . 82
A2.1 Description of the work . . . . . . . . . . . . . . . . . 82

A2.2 12KV air circuit breaker ratings . . . . . . . . 84

A2.3 System assumptions . . . . . . . . . . . . . . . . . . . . . . 84


A2.4 Belle plant single line diagram . . . . . . . . . 85
A2.5 Belle plant impedance diagrams . . . . . . . . . . 87
A2.6 Belle plant short circuit calculation . . . 93

APPENDIX 3. System generator protection . . . . . . . . . . . . . 98


A3.1 Belle plant generator protection . . . . . . . . 98

A3.2 Belle plant bus protections . . . . . . . . . . . . . 115

APPENDIX 4. Belle plant- transformer protection . . . . . 120


A4.1 ~~~e HU-1 transformer differential relay 120

APPENDIX 5. Belle plant coordination curves . . . . . . . . 126


and detailed diagrams

"A" switch house. BANK No.1 and 12KV BUS 126

ECR No.6. 12KV BUS "A'f. . . . . . . . . . . . . . . . . . 128

ECR No.6, 12KV BUS "B" . . . . . . . . . . . . . . . . . . 130


Cogeneration generator . . . . . . . . . . . . . . . . . . 132

BANK No.7 feeder No.18. . . . . . . . . . . . . . . . . . 134


2.4KV 600HP motor river pump house . . . . . . 136

2.4KV 450HP motor boiler feeder pump No.5 138


A5.8 2.4KV 75HP motor ash pump . . . . . . . . . . . . . . . 140
A5.9 2.4KV 200HP motor recirculating pump . . . . 142
A5.10 2.4KV 200HP motor F . D . fan boilers . ..... 144
No.6 & 9
A5.11 2.4KV feeders sheet No.1 & BANK No.60 . . . 146
A5.12 2.4KV feeders sheet No.2 & BANK No.59 . .. 148
A5.13 2.4KV feeders ECR No.5 . . . . . . . . . . . . . . . . . . 150
A5.14 2.4KV 150HP motor boiler No.10 mills . . . . 152
A5.15 2.4KV 550HP motor 1 . D fan boilers . . . . . . . 154
No . 14 & 15
A5.16 2.4KV 400HP motor 1 . D fan boilers . . . . . . . 156
No.6 & 9
A5.17 480V feeders ECR No.8 sheet 1 . . . . . . . . . . . 158
A5.18 480V feeders ECR.No.8 sheet 2 . . . . . . . . . . . 160
A5.19 480V feeders ECR No.8 sheet 3 . . . . . . . . . . . 162
A5.20 2.4KV 550HP motors 1 . D fan boiler No.10. 164

APPENDIX 6. Westinghouse overcurrent relay curves . . . 166


A6.1 Type CO-7 Over Current Relay . . . . . . . . . . . . 166
A6.2 Type CO-9 Over Current Relay . . . . . . . . . . . . 167
A6.3 Type CO-11 Over Current Relay . . . . . . . . . . . 168
A6.4 Type COM-5 Over current Relay . . . . . . . . . . . 169
A6.5 Type CV-2 Under Voltage Relay . . . . . . . . . . . . 170
A6.6 Type CV-7 Under Voltage Relay . . . . . . . . . . . 171
A6.7 Westinghouse type Amptector 11-A . . . . . . . . 172
A6.8 Westinghouse type DSL-206 Limiters . . . . . . 173

A6.9 Two pole type AA12P Overload Relay ...... 174

APPENDIX 7. Buss fuses curves . . . . . . . . . . . . . . . . . . . . . . . 180

A7.1 Type LPS-RK Low Peak Dual Element fuse . . 180

A7.2 Type KRP-C HI-CAP Fuses ................ 181

APPENDIX 8. ASA Device numbers and functions . . . . . . . . 182


LIST OF FIGURES

2.1 Total short circuit current equals sum of sources 9

2.2 Symmetrical short circuit currents from . . . . . . . . . . 1 3

four surces

5.1 Typical time curves of CO-9 Relay . . . . . . . . . . . . . . . . 63

5.2 Portion of Belle plant relaying detailed diagram . 64

5.3 Portion of Belle plant co-ordination curves . . . . . . 65

A2-1 Block diagram of system setup . . . . . . . . . . . . . . . . . . . . 83

A2-2 Belle plant single line diagram . . . . . . . . . . . . . . . . . . 86

A2-3 Multiplying factors for three phase & line . . . . . . . 91

to ground faults

A2-4 Belle plant simplified impedance diagram . . . . . . . . . 92

A2-5 Equivalent circuit for fault "A" (momentary) . . . . . 93

A2-6 Simplified equivalent circu'it for fault "A". . . . . . 94

Wye-Delta transformation for fault "A". . . . . . . . . . . 94

Equivalent circuit for fault "A" (interrupting) . . 95

Wye-Delta transformation for fault "A"(interrup.) 96

Typical time curves for the 10% sensitivity . . . . . . 100

type CA generator relay

Limits for application of the CWC time curves . . . . 102

Typical time curves of the type CWC relay . . . . . . . . 103

Generator over voltage curve . . . . . . . . . . . . . . . . . . . . . 108

Generator reactive capability curve . . . . . . . . . . . . . . 109

Machine capability curve . . . . . . . . . . . . . . . . . . . . . . . . . 110


A3-7 SDF-1 tripping relay under declining frequency . . . 113

A3-8 Operating time variations with changes in . . . . . . . . 114

time-dial setting

A3-9 KAB relay voltage unit setting . . . . . . . . . . . . . . . . . . . 118


A3-10 KAB relay current unit setting . . . . . . . . . . . . . . . . . . . 119
LIST OF TABLES

Machine reactance and multiplying factors . . . . . . .

Fuse classification. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Current limiting characteristics of c-s one . . . . .

time fuse

Transformer ANSI data . . . . . . . . . . . . . . . . . . . . . . . . . . .

Rating ratios for safe co-ordinations . . . . . . . . . . .

Power air circuit breaker minimum band . . . . . . . . . .

ANSI Standard reactance values . . . . . . . . . . . . . . . . . .


Transmission line impedances. . . . . . . . . . . . . . . . . . . .

15KV cable impedances. . . . . . . . . . . . . . . . . . . . . . . . . . .


5KV cable impedances. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Correction factors for non magnetic ducts . . . . . . . . 81
Result of Belle plant short circuit study . . . . . . . 97
Limits for application of CWC relay . . . . . . . . . . . . . 101
ABSTRACT

The calculation of ac short-circuit currents,

essential to the selection of adequately rated protective

devices and equipment in industrial and commercial power


systems, is becoming increasingly important to the system

designer. Today, power systems carry larger blocks of


power, are more important to the operation of the plant and

building, and have greater safety and reliability

requirements. Meeting these requirements necessitates the


fulfillment of certain criteria, including the use of

adequately rated equipment.


This report outlines state of-the-art industrial

power system engineering practices which should be

especially valuable to industrial plant engineers and

electricians, industrial power application engineers and

others who are involved with the planning of electrical

facilities for industrial plants or commercial buildings.

The method of short-circuit-current calculation

has been selected, so that adequate ratings of all the air

circuit breakers were obtained. Fault protective devices

were selected to maintain proper relay coordination

throughout the system. These devices has been selected and

set so that only the device nearest a fault opened to clear


the fault without affecting larger devices nearer the source

of power or causing a wider outage than the minimum.

-xii-
CHAPTER ONE

INTRODUCTION

All power systems, whether they be utility,

industrial, commercial, or residential, have the common

purpose of providing electric energy to the utilization

equipment as safely and as reliably as is economically

feasible. The relative importance of economic, reliability,

and safety considerations may vary somewhat with the type of

system, but all three elements must be taken into

consideration in any good system design, and certain minimum

safety and reliability requirements must be satisfied.

1.1 STATEMENT OF THE PROBLEM

Electric power system in today's industrial plants

and large commercial establishments handle enormous

quantities of energy. A review of the trend in electric


energy usage in such establishments indicates that such

energy usage has been doubling every seven to eight years

and shows little signs of leveling off [ I ] . Many industrial

processes and commercial operations demand a high degree of

continuity of electric power supply because of the great


costs of production downtime. One of the major

considerations in the design of a power system is adequate


2

control of short circuits, or faults, as they are commonly

called. Uncontrolled short circuits can cause service

outage with accompanying production downtime and associated

inconvenience, interruption of essential facilities,

extensive equipment damage, personnel injury or fatality,

and possible fire damage.

Clearly, the fault must be quickly removed from

the power system, and this is the job of the protective

device, the circuit breakers and fusible switches. In order

to accomplish this, the protective device must have the

ability to interrupt the maximum short-circuit current which

can flow for a fault at the device location. The maximum

value of short-circuit current is frequently referred to as

the 'Iavailable'l short-circuit current.

The purpose of this report is to provide the

reader with information and procedures necessary to

calculate short-circuit currents, and also present a new

method of coordination for protective relaying by using the

typical time curves of the relay. Calculation of

short-circuit current and coordination of protective

relaying for the Belle plant, (one of the biochemical sites

of E.I.dupont de Nemours & Company) is shown for the entire

system as an example for this report.

This report defines the function of system

protection as "the detection and prompt isolation of the

affected portion of the system whenever a short circuit or


3

other abnormality occurs which might cause damage to, or

adversely affect, the operation of any portion of the system

or the load which it supplies."

This report will be limited to short-circuit

calculation and coordination of protective relaying for

low-voltage to medium-voltage industrial plants, commercial

and institutional buildings. Westinghouse protective

devices and Bussmann fuses have been used throughout the

report, which limits our selection and information about

other protective devices.

Chapter One introduces an outline of this report

and reviews some of relative methods concerning short-

circuit calculation and coordination of protective relaying.

Chapter Two explains .the major short circuit sources and

their waveforms. Chapter Three explains longhand method of

short- circuit-current calculation, which includes

impedances of all motors less than 50 hp by lumping them

together and treated as a single impedance. Chapter Four

explains different protective devices used for system

protection. Chapter Five explains several method of


coordination which will be compared with the new method

presented in this report. Chapter Six gives the conclusion


on this report. Appendix 1 provides impedance data that is

required for the Belle plant, which is used as an example

for this report. Appendix 2 provides the Belle plant


single-line diagram. Appendix 3 provides system generator
4

protection for the Belle plant. Appendix 4 provides

transformer protection of protective relaying for the Belle

plant. Appendix 5 provides the complete set of coordination

curves and detailed diagrams for the entire system.

Appendix 6 provides Westinghouse overcurrent relay curves

used throughout the study. Appendix 7 provides Bussmann

fuse curves used in this report and finally Appendix 8

provides the American Standard Association devices numbers

and functions (ASA) which are used for an automatic

switching equipment.

1.2 LITERATURE SEARCH

There are several texts available for

short-circuit-current calculation and relaying coordination

of industrial and commercial power system. Most noteworthy

is the book IEEE Recommended Practice For Protection and


Coordination of Industrial and Commertial Power Systems by

D.Dalasta [6]. Other good books are The Art and Science of

Protective Relaying by Russell C. Mason [ 3 ] , and Industrial

Power Systems Handbook by Donald Beeman [ 2 ] . These texts,

especially The Art and Science of Protective Relaying, will

provide an understanding of the function of protective

relaying and their operation for protection of industrial

and commercial power systems.


1. 3 STATE OF THE ART

Protection of power system involves short-circuit

calculation and relay coordination.

At the present there are several methods of short-

circuit-current calculation available throughout the

industries. Longhand calculation, Network Analyzer and


digital computer techniques are the most-used methods. In

general, the presence of closed loops in the impedance

network, such as might be found in a large industrial plant


high-voltage system, will favor using a network analyzer or

digital computer technique from an economic and time-saving

standpoint[l]. Radial systems, such as those used in most

low-voltage and medium-voltage systems, can be easily

resolved by longhand calculations.

There are also several methods available for

coordination of protective relaying for industrial and

commercial power systems against any abnormalities which

could reasonably be expected to occur in the course of

system operation. These methods are as follows:

1) Coordination by tables are used as a simple check for

selectivity assuming that identical or reduced fault

currents flow through the circuits in descending order,

that is, main-feeder-branch. this method is recommended


only for low-voltage branch circuits [6].

2) Coordination by using the device characteristic curve can


6

be used for any size system. The sheet of log-log paper

on which the study is being made is placed on top of the

device characteristic curve. Proper curve then can be

selected and traced. Human error is very high in this

method which makes it undesirable to use.

Coordination by using the typical time curves is a new

method presented in this report. This method is

recommended, since relay curve is drawn by finding

several points from typical time curve. These points are

then ploted and traced on log-log paper. calculation of

these points require knowing the relay type, current

transformer (c.t.) ratio, available taps, ampere range of

the relay, circuit voltage level and available

short-circuit current. These requirements will ensure

correct data point transformation from typical time curve

of the relay to the log-log paper, which practically

eleminates human error.


CHAPTER TWO

SOURCES OF SHORT CIRCUIT

If adequate protection is to be provided for a

plant electric system, the size of the electric power system

must be considered to determine how much short-circuit

current it will deliver. This is done so that circuit

breakers or fuses may be selected with adequate interrupting

capacity. This interrupting capacity should be high enough

to open safely the maximum short-circuit current which the

power system can cause to flow through a circuit breaker if

a short circuit occurs in the feeder or equipment which it

protects.

When determining the magnitude of short-circuit

currents, it is extremely important that all sources of

short circuit be considered and that the impedance

characteristics of these sources be known. There are four

basic sources of short-circuit current:

1. Generators
2. Synchronous motors
3. Induction motors
4. Electric utility systems
All these can feed short-circuit current into a

short circuit as shown in figure 2.1.


2.1 GENERATORS

Generators are driven by turbines, diesel engines,

water wheels, or other types of prime movers. When a short

circuit occurs on the circuit fed by a generator, the

generator continues to produce voltage because the field

excitation is maintained and the prime mover drives the

generator at normal speed. The generated voltage produces a

short circuit current of a large magnitude that flows from

the generator to the short circuit. This flow of short-

circuit current is limited only by the impedance of the

generator and the short circuit. For a .short circuit at the

terminals -of the generator,. the current from the generat0.r

is limited only by its own impedance.

2.2 SYNCHRONOUS MOTORS

Synchronous motors are constructed much like

generators; that is, they have a field excited by direct

current and a stator winding in which alternating current

flows. Normally, synchronous motors draw A.C. power from

the line and convert electric energy to mechanical energy.

During a system short circuit, the voltage on the

system is reduced to a very low value. Consequently, the


motor stops delivering energy to the mechanical load and

starts slowing down. However, as the prime mover drives a

generator, the inertia of the load and motor rotor drives

the synchronous motor. The synchronous motor then becomes a

generator and delivers short-circuit current for many cycles

after the short circuit has occurred. The amount of short-

circuit current produced by the motor depends upon the

impedance of the synchronous motor and impedance of the

system to the point of short circuit.


FROM E L ECTRIC

I
UTILITY SYSTEM

SHORT- CIRCUIT
CURRENT FROM
E L E C T R I C UTlUTT
TURBINE GENERATOR
I METAL CLAD
SWITCHGEAR
SYSTEM

CURRENT
FROM
GENERATOR

SYNCHRONOUS
MOTOR
I TOTAL SHORT
CIRCUIT
1 CURRENT
-?OM ALL

I
FGUR
SHORTURCUlT

SYN MOTOR
INDUCTION
SHORT-CIRCUIT /1 "
CURRENT FROM '
lNWCTlCE(

Figure 2.1 Total short-circuit current equals sum of source


contributions [I] .
2.3 INDUCTION MOTORS

The inertia of the load and rotor of an induction

motor have the same effect on an induction motor as on a

synchronous motor; that is, they drive the motor after the

system short circuit occurs. There is one major difference.

The induction motor has no DC field winding, but there is a

flux in the induction motor during normal operation. This

acts like flux produced by the dc field winding in the

synchronous motor.

The field of the induction motor is produced by

induction from the stator rather than from the DC winding.

The rotor flux remains normal as long as voltage is applied

to the stator from an external source. However, if the

external source of voltage were suddenly removed, as it is

when a short circuit occurs on the system, the flux in the

rotor can not change instantly. Because the rotor flux can

not decay instantly and because the inertia of the rotating

parts drives the induction motor, a voltage is generated in

the stator winding. This causes a short-circuit current to

flow to the short circuit until the rotor flux decays to

zero. The short-circuit current vanishes almost completely

in about four cycles, since there is no sustained field

current in the rotor to provide flux, as in the case of a

synchronous machine.
11
The flux does last long enough to produce enough

short-circuit current to affect the momentary duty on

circuit breakers and the interrupting duty on devices that

open within one or two cycles after a short circuit. Hence,

the short circuit produced by induction motors must be

considered in certain calculations. The magnitude of a

short-circuit current produced by the induction, motor

depends upon the impedance of the system to the point of

short circuit. The machine impedance effective at the time

of short circuit corresponds closely to the impedance at

standstill. Consequently, the inertia value of short-

circuit current is approximately equal to the locked rotor

starting current to the motor.

2.4 ELECTRIC UTILITY SYSTEMS

The electric utility system or the supply


transformer from the electric utility system are often

considered sources of short-circuit current. Strictly

speaking, this is not correct because the utility system or


supply transformer merely delivers the short-circuit current

from the utility system generators. Transformers merely


change the system voltage and magnitude of current but

generate neither. The short-circuit current delivered by a

transformer is determined by its secondary voltage rating


and impedance, the impedance of the generators and system to

the terminals of the transformer and the impedance of the

circuit from the transformer to the short circuit.

As illustrated in figure 2.2, the total


symmetrical short circuit current usually has several

sources. The first includes generators either in the plant

or in the utility system or both. The second comprises

synchronous motors. The third source is induction motors,

which are located in every plant and building. Because

these currents decay with time due to reduction of flux in

the machine after short circuit, the total short-circuit

current decays with time. So even though only the

symmetrical part of the short-circuit current is considered,

the magnitude of current-is highest at the first half cycle

after short circuit and is of lower value a few cycle later.

Note that the induction motor component disappears entirely

after one or two cycles [ 2 ] .

2.5 ROTATING MACHINE REACTANCE

The impedance of a rotating machine consists

primarily of reactance and is not one simple value as it is

for a transformer or a piece of cable, but is complex and

variable with time. For example, if a short circuit is

applied to the terminals of a generator, the short-circuit


- T O T A L ASYMMETRICAL CURRENT

OC COMPONENT

AC COMPONEHT

(a) Symmetrical (b) Asymmetrical


Figure 2.2 Symmetrical short-circuit currents from four

sources [ 2 ] .
14
current behaves as shown in figure 2.2a (generator). The

current starts out at a high value and decays to a

steady-state value after some time has elapsed from the

inception of the short circuit. Since the field excitation

voltage and speed have remained relatively constant within

the short interval of time considered, the reactance of the

machine may be assumed-to explain the change in the current

value-to have changed with time after the short circuit was

initiated.
Expression of such a variable reactance at any

instant requires a comlicated formula involving time as one

of the variables. Therefore, for the sake of


simplification, three values of reactance are assigned to

generators and motors for the purpose of calculating

short-circuit current at specified times. These values are

called the subtransient reactance, transient reactance, and

synchronous reactance and are described as follows:

1> Subtransient reactance (XI'd ) is the apparent reactance


of the stator winding at the instant short circuit

occurs, and it determines the current flow during the

first few cycles after short circuit.

2) Transient reactance (X'd) determines the current


following the period when subtransient reactance is the

controlling value. Transient reactance is effective up

to onehalf second or longer, depending upon the design


of the machine.
3) Synchronous reactance (Xd) is the reactance that
determines the current flow when steady state condition

is reached. It is not effective until several seconds


after the short circuit occurs; consequently, it is not

generally used in short-circuit calculations [ 2 ] .

A synchronous motor has the same kind of reactance


as a generator, but it is of a different value. Induction

motors have no field coils, but the rotor bars act like the

amortisseur winding in a generator; therefore, induction

motors are said to have subtransient reactance only. Refer

to Appendix 1 (impedance data) for the multiple value of

reactances used for the momentary and interrupting

short-circuit calculations for this study.

2.6 Symmetrical and Asymmetrical Currents

The words "symmetrical" and "asymmetrical"

describe the shape of the ac waves about the zero axis. If


the envelopes of the peaks of the current waves are

symmetrical around the zero axis, they are called

"symmetrical current". Figure 2.2a shows the symmetrical


short-circuit currents from four sources combined into

total. If the envelopes are not symmetrical around the zero


16
axis, they are called "asymmetrical current". Figure 2.2b

shows the asymmetrical short-circuit currents plus the dc

component from all sources.

Most short-circuit currents are nearly always

asymmetrical during the first few cycles after the short

circuit occurs. The asymmetrical current is at a maximum

during the first cycle after the short circuit occurs and in

a few cycles gradully becomes symmetrical as shown on figure

2.2b.

Asymmetrical currents are analyzed in terms of two

components, a symmetrical current and a dc component as

shown on figure 2.2b. As previously discussed the

symmetrical component is at a maximum at the inception of

the short circuit and decays to a steady state value due to

the apparent change in machine reactance. In all practical


circuits, that is, those containing resistance, the dc

component will also decay to zero as the energy represented

by the dc component is dissipated as I2R loss in the

resistance of the circuit. The rate of decay of dc

component is a function of the resistance and reactance of

the circuit. In practical circuits, the dc component decays

to zero in from one to six cycles [ Z ] .


CHAPTER THREE

SHORT-CIRCUIT-CURRENT CALCULATIONS

The maximum magnitude of short-circuit current

must be known in order to coordinate protective devices as

well as to select adequate interrupting ratings. As

mentioned earlier, there are three basic methods of

calculating short-circuit current: network analyzer, digital

computer, and longhand calculation. For a radial medium-

voltage system the longhand method is feasible and fairly

simple to use. Determination of short-circuit current for

the Belle plant, which is used as an example in this report,

is done by this longhand calculation method.. Since the

system contains a three-winding transformer and other loops,

delta-wye network transformations is used to combine

impedances. Method of combining impedances are included in

Appendix 2. The following steps identify the basic

considerations in making short circuit calculations.

1> Make certain assumptions in a way that simplifies the


calculation and also maximum short-circuit current can

be calculated.
2) Prepare system single-line diagram which it should

include all significant equipment and components.


3) Prepare system impedance diagram which should display
18
the interconnected circuit impedances that control the

magnitude of short-circuit currents.

4) Identify Type and location of faults required for the


system.

5 > Calculate symmetrical short-circuit current for the


system.

6 > Calculate interrupting and momentary short-circuit


currents for all identified locations, so that proper

protective devices can be selected for the system.

3.1 IMPORTANT ASSUMPTIONS

Certain simplifying assumptions are made for this

calculation. An important assumption is that the fault is


iibolted". That is, it has zero impedance. This assumption

not only simplifies caculation, but also applies a safety

factor since the calculated values are a maximum, and

equipment selected on this basis is rarely stressed beyond

its full rating. Furthermore a three-phase fault should be

assumed, because maximum short-circuit current is required

for device selection.

3.2 SINGLE LINE DIAGRAM

The system one-line diagram is fundamental to


19
short circuit analysis. It should include all significant

equipment and components and show their interconnections.

Refer to Appendix 2 (section 112.4) for the complete Belle


plant single-line diagram.

3.3 IMPEDANCE DIAGRAM

The impedance diagram displays the interconnected

circuit impedances that control the magnitude of

short-circuit currents. Impedance diagrams should be

patterend for momentary and interrupting short-circuit

current calculations. These impedance diagrams are derived

from system single-line diagram, by replacing all elements

of the single-line diagram with their calculated per-unit

reactances. Specified reactances of a motor, generator, or

transformer should be used. The resistance of all

generators, transformers, reactors, motors, and


high-capacity buses (above 1000 A rating) is so low,

compared with their reactance, that their resistance is not

considered in impedance diagram.


Reactance of the cables 600 volts and higher

should be considered in impedance diagram. Appendix 1 shows


the tables used for selecting a reactance of these cables

for the Belle plant impedance diagram.


After it has been decided what elements of the
single-line diagram are to be considered in the impedance

diagram, the mechanics of making the impedance diagram and


of determining the short-circuit current magnitude used in

this report are as follows.


1) The first step is to decide whether to use ohms, per

cent ohms, or per-unit ohms to represent the various

circuit impedances in the impedance diagram. Ohms are

not recommended because of the difficalty of converting

ohms from one voltage base to another without error.

This report is listing the impedance or reactance data

in per-unit.

2) The second step in making an impedance diagram is to


represent every generator and motor and utility supply

by a reactance connected to a zero impedance bus or

so-called "infinit bus" . This bus represents the

internal voltage of the generators and motors. These

reactances can be found as follows:

Utility X= [MVAbaseI / [MVAUtilityI P e l l .


Generator X=(XIfd%)[MVAbase/MVAgenerator1 P.U.
Motor X= (XI1d%)[MVAbase/KvAmo torI P.U.

Since most industrial plants contain many motors

under 50 hp, Unlike other methods available for the short

circuit study, this report recommends that induction motors

smaller than 50 hp should be lumped together and treated as

a single impedance on the secondary side of the supply


21

transformer. This will slightly reduces the equivalent

reactance of the system, which means, the calculated value

for the momentary and interrupting short circuit will be

slightly higher. This will create a safety factor for the

system protection when selecting protective devices.

Table Al-1 in Appendix 1 shows the positive-

sequence reactance of the short-circuit sources with their

multiple factors. These multiple factors are used when

determining momentary and interrupting short-circuit current

for selecting circuit breakers. For example, for a 600 hp

motor in a branch circuit, the positive-sequence reactance

factor is 1.2 for momentary calculation and 3.0 for


interrupting case. The reciprocal of the locked rotor

current factor, which is normally six times full load

current, has to be multiplied by these factors for the

correct Thevinin reactance of the load as shown below.

Xth(momentary)=l.2 (1/6) (base KVA/ KVA load) p . u.


Xth(interrupting) =3.0(1/6) (base KVA/KVA load) p . u .
KVA(1oad) = (power factor) (motor hp)

3) The third step is to add the reactance of cables, buses,

transformers, current transformers and circuit breakers,

in their proper location to complete the impedance

digram. Appendix 2 (section A2.5) shows the calculation

of these reactances for the Belle plant.


3.4 TYPE AND LOCATION OF FAULTS REQUIRED

All buses should be identified. The location


where short circuit studies are required should be selected.

In many studies, all buses are faulted. The type of short-


circuit currents we required is based on the short-circuit

rating of the equipment located at the faulted bus. Figure

A2-1 in Appendix 2 shows the block diagram of system setup

which includes the fault locations calculated for the Belle

plant. Locations were mainly picked on main buses and

feeders .

3.5 SYMMETRICAL SHORT-CIRCUIT CURRENT CALCULATION

After completing the impedance diagram and

inserting the values of reactance or impedance for each part

ot the diagram, it is necessary to reduce this network to

one equivalent value. Longhand method of combining

reactances is used in this report. If there are three

reactances in the system, the following shows how to combine

them.

a) Combining series reactances:


X1+%+X3=X =equivalent reactance
e
X1,%,X3=reactances of circuit components

b) Combining parallel reactances:


Xe=equivalent reactance

Some sytems are such that they cannot be reduced

by merely combining series and parallel reactances. For

example, the equivalent impedance diagram of the Belle plant

is shown in Appendix 2 (figure A2-5). In order to reduce

this circuit to a single reactance, wye-delta transformation

is used. By these transformation any commonly encountered

system impedance diagram can be reduced to one equivalent

reactance.
The calculation to derive the symmetrical

short-circuit current is I=E/X where E is the system driving

voltage and X is the equivalent positive impedance.

When calculations are made in per-unit , there are

four base quantities : base KVA, base voltage, base

impedance, and base current. When any two of the four are

assigned values, the other two values can be derived. It is

common practice to assign study base values to KVA and

voltage. Base current and base impedance are then derived

for each of the voltage levels in the system. For example,

the KVA base assigned for the Belle plant is 5 MVA. The

nominal line-to-line system voltages are normally used as

the base voltages. Following formulas apply for short

circuit calculations:
Basic per-unit relationship:

Per-unit voltage=actual voltage/base voltage

Per-unit current=actual current/base current

Per-unit impedance=actual impedance/base impedance

Change from percent on an old base to per unit on a new

base :

XpUNEW= (XpUOLD) (NEW KVABASE/OLD KVABASE)


(OLD KVBASE/NEW KVBASE
Symmetrical 3 phase short-circuit current in per unit (p.u.)

Ip.u.=Ep.u.jZp.u. , symmetrical 3 phase short-circuit

current in amperes, I=I(base) [ZP.U.I


Symmetrical 3 phase short circuit KVA, KVA=KVA(base) /Z (p .u . )
were, I(base) =KVAbase/\/S (KVLL,base 1
When calculations are made in ohms, symmetrical

three-phase short-circuit in amperes will be I=E /Z where


L-n
EL-n =line to neutral voltage and Z is the equivalent network

impedance in ohms per phase.

Calculation for several points at different

voltage level for the Belle plant is done in Appendix 2,

section A2.6. Calculation of fault duties is done for both


momentary and interrupting current for different fault

locations.
3.6 MOMENTARY SHORT CIRCUIT CALCULATION

The fact that the current changes in magnitude

with time has led to the establishment of two bases of

short-circuit-current ratings on power circuit breakers: (1)

the momentary rating or its ability to withstand mechanical

stresses due to high short-circuit current and (2) the

interrupting rating or its ability to interrupt the flow of


short-circuit current within its interrupting element.

Calculation of the precise rms value of an

asymmetrical current at any time after the inception of a

short circuit may be very involved. Accurate decrument

factors to account for the dc component at any time are

required, as well as accurate factors for the rate of change

of the apparent reactance of the generators. This precise

method may be used if desired, but simplified methods have

been evolved whereby the dc component is accounted for by

simple multiplying factors. The multiplying factor converts

the rms value of the symmetrical (interrupting) ac wave into

rms amperes of the asymmetrical (momentary) wave including a

dc component.

The magnitude of the dc component depends upon the

point on the voltage wave at which the short circuit occurs.

For protective-device application, only the maximum dc

component is considered, since the circuit breaker must be


26
applied to handle the maximum short-circuit current that can

occur in a system.

In the general case for circuits rated above 600

volts, the multiplying factor to account for dc component is

1.6 times the rms value of the ac symmetrical component at

the first cycle. For circuits 600 volts and less, the

multiplying factor to calculate the total current at the

first cycle is 1.25 when the circuit breaker is applied on

the average current in three phases. These factors are

listed in table 3.1 [2] .

Since the short-circuit current is maximum at the

first-cycle, the short-circuit current must be determined at

the first-cycle to determine the maximum momentary duty on a

circuit breaker. To determine the short-circuit current at

the first cycle, it is necessary to consider all sources of

short-circuit current, that is, the generators, synchronous

motors, induction motors, and utility connections. The

subtransient reactances (Xud) of generators, synchronous

motors, and induction motors are used in the impedance

diagram.

Procedure for determining momentary current

consists of calculating E/ZM ' the line to neutral voltage at


the breaker divided by the equivalent momentary system

impedance at that point. Since the dc component is present

at this time, it is necessary to account for it by the use


of a multiplying factor as mentioned/ earlier, to find the

first-cycle total short-circuit-current duty per-unit

current. Breaker application (600 volts or above) will be

proper if E/ZM times a factor of 1.6 does not exceed the

momentary current rating of the breaker.

Where IIC is the first-cycle short-circuit asymmetrical

current. Refer to Appendix 2 (section A2.6) for the Belle

plant momentary short-circuit current calculation.

3.7 INTERRUPTING SHORT CIRCUIT CALCULATION

To check the interrupting duty on a power circuit

breaker, the short-circuit current should be determined at

the time that the circuit-breaker contacts part. The time

required for the circuit-breaker contacts to part will vary

over a considerable rang, because of variation in relay time

and in circuit-breaker operating speed. The fewer cycles

required for the circuit-breaker contacts to part, the

greater will be the current to interrupt. Therefore, the

maximum interrupting duty is imposed upon the circuit

breaker when tripping relays operate instantaneously. To

account for variation in the circuit-breaker operating

speed, power circuit breakers have been grouped into several

classes, such as eight-cycle, five-cycle, and three-cycle


circuit breakers.
In industrial plants, eight-cycle circuit breakers

are generally used. Normally, the induction-motor

contribution has disappeared, and that of the synchronous

motors has changed from the subtransient to the transient

condition before the contacts of these circuit breakers

part. Therefore, in calculating the interrupting duty on

commonly used power circuit breakers, generator subtransient

reactance and synchronous-motor transient reactance are used

and unlike other methods, which induction motors are

neglected, induction motor transient reactance are used.

This will cause the calculated interrupting short-circuit

current to be higher than the actual value, which creates a

safety factor for selection of circuit breakers for the

entire system.
Instead of specifying a time at which the

short-circuit current is to be calculated, it is determined

by specifying the generator and motors reactances and using

a multiplying factor. These factors are listed in Table 3.1

The procedure for determining interrupting current


consists of calculating E / Z I , the line to neutral voltage at

the breaker divided by the equivalent interrupting system

impedance at that point, and then applying multiplying

factors to determine total current at the time of breaker


29
contact parting. This total current is compared with the

breaker total current interrupting rating.


Reactance values used with ANSI standard C37.5
1969 for motors, transformers, generators, and utility

sources are listed in Appendix 1, table Al-1.


Table 3.1 Machine Reactance and Multiplying Factors

Used in Simplified calculation of Short-circuit

Duty [I1

Machine Reactances to Use Multiplying Focmr

1 1
to be Applied
Equipmwtt Type of Short-circuit to Calculated
Rating Synchronous Synchronous Induction Syrnmehicoi

I e a t o s Motors Motors Value*

L-V Power Circuit Breakers I


L-V Molded-core Circuit
Qr#kers

L-V Motor Controllers (In- Symmetrical Amperes Subtransient Subtransient Subtronsient None
corporaiing Fusesor M o i d d - Available (x7 (x? (x")
rose Circuit Breakers)

L-V Fuses

1-V Buswoy

k s &racing im

L-V Switchgear
1-V Switchboards
L-V Motor-controi Canters
L-V Panelboards

General Sp&l
Power Circuif Ereakors Interrupting--Symmetrical Caset Caret
(above 600 volts) +aperesor MVA Subtransient Transient Noglut
with Rated Interrupting Available (xl) 1x1
Times of 8 cydes 1 .I
(Refer to the Total
Current Rating k r i s -
ASA C37.6-1964) Mocncntary-Asymmetrical Subtmnsient Subtransient Subtmnsient 15$
Amperes Available (x") (xl)

Fuses and fused Interrupting-Asymmetrical Subtransient Subtransient Subtransient 1.27


Cutouts Ampares Available (x? (x?
( o b a e 1500 volts)
CHAPTER FOUR

GENERAL EQUIPMENT USED FOR PROTECTION

We usually think of an electric power system in

terms of its more impressive parts, the big generating

stations, transformers, high voltage lines, etc. While

these are some of the basic elements, there are many other

necessary and fascinating components. Protective relaying

is one of these [ 3 ] .
The function of protective relaying for system

protection and coordination is to minimize damage to the

system and its components and to limit the extent and

duration of service interruption whenever equipment failure,

human error, or "acts of GOD" occur on any portion of the

system. The relaying equipment is aided in this task by


circuit breakers that are capable of disconnecting the

faulty element when they are called upon to do so by the

relaying equipment.

Overcurrent protection device selection and

coordination is an engineering decision that should be made

to protect the system from short-circuit or fault currents.

Protection for electric systems is an art as well

as science and should be designed with the following

objectives in mind:
1) Prevent or minimize damage to equipment.
2) Minimize the effect of the disturbance on the
un-interrupted portion of the system, both in its extent

and duration.

3) Minimize interruption of power.


4) minimize the effect on the utility system [4].
5) prevent injury to personnel.
The isolation of short circuits requires the

application of protective equipment which will sense an

abnormal current flow and remove the affected portion from

the system. The sensing device and interrupting device may

be completely separate, interconnected only through external

control wiring, or they may be the same device or separate

devices mechanically coupled to function as a single device.

Equipments used for protection are overvurrent relays,

fuses, and circuit breakers. The following sections explain

each of these devices in detail.

4.1 OVERCURRENT RELAYS

Overcurrent relays are sensing devices only and

must be used in conjunction with some type of interrupting

device to interrupt a short circuit and isolate the affected

portion of the system. These relays may be either


directional or non directional in their action. They may be
33
instantaneous or time delay in response. Various time

current characteristics, such as inverse time, very inverse

time, extremely inverse time, and definite minimum time are

available over a wide range of current setting. The


overcurrent relays are generally available in the following

current ratings:

Range Taps
0.5-2.5 0.5,0.6,0.8,1.2,1.5,2.0,2.0,2.5

1.5-6.0 1.5,2.0,2.5,3.0,3.5,4.0,6.0

4.0-16.0 4.0,5.0,6.0,7.0,8.0,10,12,16

The relays can be specified to have either single

or double circuit closing contacts for tripping either one

or two circuit breakers.

Directional relay consists of two units, an

overcurrent element and a directional element. The contact

circuits are arranged insuch a way that tripping occurs only

when current has proper relationship to the voltage with

power flow in the tripping direction. The actual tripping

of the circuit is done by. a contact on the overcurrent

element, the overcurrent element does not operate until the

current is flowing in the proper direction and is above the

pickup setting. The overcurrent element cannot operate on a

fault in the nontripping direction. For typical application

refer to Appendix 5 (section A5.3) , device No.67 (CWC type) .

The instantaneous element is set for a current


34

higher than that which should operate the time-delay


element. The contacts ot this element are either connected

in parallel with the contacts of the time-delay element or

they aconnected to seperate terminals. This element is

mainly used when time interval required between two

overcurrent relays can not be made in the short time region.

Refer to Appendix 5 (section A5.12) for instantaneous

setting used in portion of the Belle plant.

The time-current characteristics for a variety of

relays used in this report are shown in Appendix 6. These

characteristics give the contact closing times for the

various time dial settings when the indicated multiples of

tap current are applied to the relay. In Chapter 5 several

method .of coordination for these relays will be discussed.

4.2 FUSES

Fuses are the oldest and simplest of all

protective devices. The fuse is both the sensing and

interrupting device. They are installed in series with the

circuit and operate by the melting of a fusible link in

response to the current flow through them on an inverse time

current basis. They are one-shot devices since their


fusible elements are destroyed in the process of

interrupting the current flow. Fuses may have only the


ability to interrupt short circuit current up to their
maximum rating or the ability to limit the magnitude of

short circuit current by interrupting the current flow

before it reaches its maximum value.

As shown in table 4.1, several types of fuses are

compared. Each fuse has a different characteristic. For


example, code-type fuses are not recommended because of low

interrupting capability and high melting current (70 times

fuse rated current) at 0.01 second. Current limiting Amptrap

fuses have high interrupting capability and very low melting

current (3.3 times fuse rated current) at 0.01 second.

These fuses are mainly recommended for branch circuits and

should not be used for protection of transformers. Since

transformers have an inrush current (sometimes 12 times full

load current). This type of fuses will melt before the

transformer is energized. Chase Shawmut (C-S) one-time fuse

is the best choice for most applications because of their

low cost and ratings.


Table 4 . 1 Fuse Classification

Melting current Interrupting

Average multiples capability

of rating amperes amperes

melt in melt in

0.01 s 10 s

Code fuse (NEC) 70 3 3,000

Semi lag fuse

( Rowan AIR-SEAL 30 3.5 50,000 i


i

I
25 3

i one time
I

,
50)000
I
dual element fuse

C-S new "trionicn 30

20
5

6
1OO)OOO 1
I

45 5.5 10%
;;;

1 Current limiting

"Amptrap 60011 15 2.5 100, 000

I "Limitron"
I 13 2.5 100 ,000

I G.E. "CLF-J"
I 12 3 100 000 )

Solid state

current limitin

3.3 2 100,000
37
COST OF FUSES [51
Approximate costs of fuse types, for given,

amperage, relative to NEC type are.

NEC fuse
C-S one time
Rowan air seal

C-S trionic
Fusetron

Lo-peak

Current Limiting

a Semi lag and dual element fuses of smaller size than NEC

size may be applicable, with proportionaly reduced cost. On

this basis, the Chase-Sha~ut(C-S) one-time fuse appears the

optimum for all uses within its interrupting capability of

50,000 amperes.

CURRENT LIMITING CHARACTERISTICS OF C-S ONE TIME FUSES


Chase-Shawmut (C-S) one-time fuses are current

limiting, but not so much as Amptraps. A 30-ampere one-


time fuse is about as current limiting as a 60-ampere

Amptrap. Table 4.4 shows the comparison of Chase-Shawmut


one-time fuses and Amptrap fuses.
Table 4 . 2 C-S one time fuses vs Amptrap fuses

I
Available current

( RMS amperes )
Let- through current
(thousands of amperes peak AMPTRAP)

(Amptrap fuse rating)

50,000 7.8 11 16 24 35
--- . --- -"- - - - -- -- ---- -
(C-S) ONE-TIME fuse rating:

--

Fuses, and their characteristics which have been

used in this study is shown in Appendix 6.

4.3 CIRCUIT BREAKERS

Circuit breakers are interrupting devices only and

must be used in conjunction with sensing devices to fulfill

the detection function. In the case of medium-voltage


39

(1-72.5 KV) circuit breakers, the sensing devices are

separate protective relays or combinations of relays. In

the case of low voltage (under 1000 volts) circuit breakers,

sensing devices may be external protective relays or

combination of relays. In most low voltage application,


either molded-case circuit breakers or other low voltage

circuit breakers having series sensing devices built into

the equipment are used.

The ratings which apply to circuit breakers and

the actual assigned numerical values reflect the mechanical,

electrical, and thermal capabilities of their major

components. Basic ratings are

1) Rared voltage

2) Rated frequency

3) Rated continuous current

4) Rated interrupting current


5) Rated short-time current

The basic overcurrent trip device characteristic

used on molded-case circuit breakers and low voltage circuit

breakers are long-time delay and instantaneous. The

combination of these characteristics provides time delay

tripping for those low-level short circuits or overloads


that persist, and instantaneous tripping for higher level

short circuits.
New molded-case circuit breakers are equipped with
40
a short-time-delay characteristic in place of the

instantaneous characteristic. The resulting combination of

long-time-delay and short-time-delay characteristics

provides delayed tripping for all levels of current up to

maximum allowable available short-circuit-current limit of

the circuit breaker without instantaneous trip element.

These new breakers are used for the Belle plant,

so that better protection can be obtained throughout the

system without using instantaneous trip element. Refer to

Appendix 6 (section A6.7) for the device characteristic

curve, which shows available settings for long-time-delay

and short-time-delay pickup values.

4.4 GENERATOR PROTECTION

The protection of generators involves the

consideration of more possible abnormal operating conditions

than the protection of any other system element. An


unnecessary generator outage is undesirable, but one should

not try to avoid it by the omission of otherwise desirable

automatic protection.

The practice of using centralized control is

increasing, which requires more automatic equipment and less

manual supervision. Such practice requires more automatic

protective relaying equipment to provide the protection that


41
was formerly the responsibility of attendants [ 3 ] .

The following protective relays are used for the

generator protection. Refer to Appendix 3 for the type and

settings of protective relays used for the Belle plant

generator protection.

PERCENTAGE DIFFERENTIAL RELAYS

These relays are used for generators rated 1000

KVA or higher [ 3 ] . Percentage differential relaying is the

best for the short-circuit protection of stator windings,

because of its high-speed instantaneous capability.

Generally, the practice is to have the

percentage-differential relays trip a hand-reset


multicontact ,auxiliary relay. This auxiliary relay

simultaneously initiates the following: (1) trip main


breaker, (2) trip field breaker, (3) shut down the prime

mover and (4) operate an alarm. These will result in


minimizing damages to the generator.

SOLID STATE UNDER-FREQUENCY RELAYS

These relays are used for automatic load-shedding.

When a system overload occurs, under-frequency relays must

disconnect load to arrest frequency decline. The output of

generating plants may be impaired below 57-57.5 Hz, so


shedding must be completed before this level is reached.
OVER-VOLTAGE RELAYS
This type of relays are used for hydroelectric and

gas-turbine generators. It operates by first causing

additional resistance into the generator or exciter field.

Then if over-voltage persists, the main generator breaker

trips.

OVER-TEMPERATURE RELAYS
Unbalanced three-phase stator currents cause

double-system-frequency currents to be induced in the rotor

iron. These current quickly increase rotor temperature and

cause serious damage to the generator if it continues to

operate with such conditions. These relays will prevent

generators from overheating.

LOSS-OF-EXCITATION
- - RELAYS
When a synchronous generator loses excitation, it

operates as an induction generator, running above

synchronous speed. Round-rotor generators are not suited to

such operation because they do not have amortisseur windings

that can carry the induced rotor currents.

Most systems cannot tolerate the continued

operation of a generator without excitation. In fact, if

the generator is not disconnected immediately when it loses


43
excitation, widespread instability may very quickly develop,

and a major system shutdown may occur. When a generator

loses excitation, it draws reactive power from the system,

amounting to as much as 4 times the generator's rated load.

This will cause extensive instability in the system. The

most selective type of loss of excitation relay is a

directional-distance type operating from the a-c current and

voltage at the main generator terminals [ 3 ] .

REVERSE POWER RELAYS


These relays are used to detect motoring.
Motoring protection is for the benefit of the prime mover or

the system, and not for the generator. However, it is

considered here, because it is closely associated with the

generator.

FIELD GROUND-FAULT PROTECTION RELAYS


Because field circuits are operated ungrounded, a

single ground fault will not cause any damage or affect the

operation of a generator in any way. However, the existence

of a single ground fault increases the stress to ground at

other points in the field winding when voltages are induced

in the field by stator transients. Thus, the probability of

a second ground occuring is increased.


44
Note: refer to Appendix 3 for the types and settings used
for protection of the Belle plant generator.

4.5 TRANSFORMER PROTECTION

The function of transformer protection is to

protect the transformer. Transformer protection is required

to automatically disconnect a transformer from the power

system for any of the following reasons.

1) To prevent higher-than-rated temperatures from

developing in the transformer from excessive load

current and, thereby, causing rapid deterioration of

insulation or conductors. Protection provided to.

achieve this is known as overload protection.

2) To prevent mechanical and thermal effects of large

"through" currents from causing permanent deformation or

other damage to the transformer. Such protection is

known as short-circuit protection.

3) To minimize the spread of damage inside a faulted

transformer, and minimize power-system disturbance


resulting from transformer faults.

TRANSFORMER SHORT CIRCUIT CAPABILITIES

The ability of a transformer to withstand through

short-circuit current is defined as its "ANSI point". This


45

point specifies the magnitude and duration of maximum

permissable through current that a transformer can withstand

without sustaining damage.

Values of the ANSI point vary from 25 times the


rated full-load current for 2 seconds, for a transformer
with four percent or less impedance, to 1 4 . 3 times the rated

full load current for 5 seconds, for transformers with seven

percent impedance as shown in table 4.5. To properly

protect the transformer, the primary fuse must actually

clear in the stated time at 87 percent of the current value

of a delta-delta bank, and 58 percent of the value of a

delta-wye bank.

Table 4.3 Transformer ANSI data

% Z Irms (sym) 87% I


rms
SYM. 58% I
rms
SYM. TIME(s)

Fault PH-PH FAULT L-N Allowable

Delta-Delta Delta-Wye

4% or 25 X Rated 22 X Rated 14 X Rated 2

less Current Current Current

5 20 X Rated 17 X Rated 11 X Rated 3

Current Current Current


6 16.6 X Rated 14 X Rated 9 X Rated 4

Current Current Current


7% or 1 4 . 3 X Rated 12 X Rated 8 X Rated 5

more Current Current Current


1
TRANSFORMER INRUSH CURRENT

A power transformer primary power fuse, as well as


any other protective device used in a transformer protection

scheme, must allow the transformer to be energized without

actuating the protective device on the magnetizing inrush

current.

The precise magnitude and duration of inrush

current vary from one transformer to another, and, for any

specific transformer, can only be determined by test.

Commonly used estimates of magnetizing inrush currents for

primary and secondary substation transformers range from an

equivalent of 8 to 12 times full load rms current, with a


duration of 0.1 second. The power or current-limiting fuse
should be selected so to be capable of carrying at least 12

times the full-load rated primary current of the transformer

for 0.1 second, without damaging the fuse, in order to pass

safely the inrush currents which occur during switching

operations.

Refer to Appendix 4 for tranformer protection used

throughout the Belle plant.


CHAPTER FIVE

COORDINATION OF PROTECTIVE DEVICES

The coordination study of an electric power system

consists of an organized time-current study of all devices

in series from the utilization device to the source. This

study is a comparison of the time it takes the individual

devices to operate when certain levels of normal or abnormal

current pass through the protective devices.

A coordination study or revision of a provious

study should be made for an existing plant when new loads

are added to the system or when existing equipment is

replaced with higher rated equipment. A coordination study


should also be made when the available short-circuit current

of the source to a plant is increased. This study

determines settings or ratings necessary to assure

coordination after system changes have been made.

The objective of a coordination study is to

determine the characteristics, ratings, and settings of

overcurrent protective devices which will ensure that the

minimum unfaulted load is interrupted when the protective

devices isolate a fault or overload anywhere in the system.

At the same time, the devices and settings selected must

provide satisfactory protection against overloads on the


48
equipment, and interrupt short circuits as rapidly as

possible.

5.1 PRIMARY CONSIDERATIONS FOR COORDINATION

In order to obtain complete coordination of the

protective equipment applied, it is necessary to obtain all

of the following requirements.

SHORT-CIRCUIT CURRENTS

The following information on short-circuit

currents should be provided for every bus on the system.

(1) Maximum and minimum 0 to 3 cycle (momentary) total

rms short-circuit current

(2) Maximum and minimum 3 cycle to 1 s (interrupting duty)

total rms short-circuit current


These short-circuit current values are obtained as

described in Chapter Three.

The maximum and minimum 0 to 3 cycle (momentary)

currents are used to determine the maximum and minimum

currents to which instantaneous and direct-acting trip

devices respond, and to verify the capability of circuit

breakers, fuses, switches, and bus bracings.

The maximum 3 cycle to 1 s (interrupting) current


at maximum generation will verify the ratings of circuit
49
breakers, fuses, and cables. This is also the value of
current at which the circuit protection coordination

interval is established. The maximum 3 cycle to 1 s

(interruptig) current at minimum generation is needed to


determine whether the circuit-protection sensitivity of the

circuits is adequate.

TIME INTERVALS FOR COORDINATION


When plotting coordination curves, certain time

intervals must be maintained between the curves of various

protective devices in order to ensure correct sequential

operation of the devices. These intervals are required

because relays have overtravel, fuses have damage

characteristics, and circuit breakers have certain speeds of

operation. These intervals are often called margins.

When coordihating inverse-time overcurrent relays,

the time interval is usually 0.3-0.4 seconds [ 6 ] . This

interval is considered between relay curves, either at the

instantaneous setting of the load side feeder circuit

breaker relay, or at the maximum short circuit current which

can flow through both devices simultaneously, whichever is

the lower value of current. The interval consists of the

following components:
Circuit breaker opening time (5 cycles) .08 seconds
Overtravel .10 seconds
50

Safety factor .12-.22 seconds

This margin may be decreased if field tests of

relays and circuit breakers indicate that the system still

coordinates with the decreased margins. The overtravel of

very inverse and extremely inverse time overcurrent relays

is somewhat less than for inverse relays, allowing a

decrease in time interval for carefully tested systems to

0.3 seconds. 0.3 Seconds time interval is used for

coordination of the Belle plant overcurrent relays.

When circuit breakers equipped with direct-acting

trip units are coordinated with relayed circuit breakers,

the coordination time interval should be 0.3-.4 s.

HOW TO READ CURVES

A basic understanding of time-current

characteristic is essential to any study. Time 0 is


considered as the time at which the fault occurs, and all

times shown on the curve are the elapsed time from that

point. The curves that are drawn are response times, since,

for a radial system, all the devices between the fault and

the source experience the same current until one of them

interrupts the circuit.


A coordination curve is arranged so that the

region below and to the left of the curve represents an area


of no operation. The curves represent a locus of a family
UJ.

of paired coordinates which indicate how long a period of

time is required for device operation at a selected value of

current.

Reading current along the abscissa, the time or

range of times in which any device is expected to operate

corresponds to the ordinate or ordinates of the curve

plotted. Relay curves begin at a point called "pickup" (the

minimum value of current which will cause the relay to close

its contacts) and end at the maximum short-circuit current

to which the device under consideration can be subjected. A


single curve should be drawn for any device under

consideration.

5.2 DATA REQUIRED FOR A COORDINATION

The first requisite for a coordination study is a

single-line diagram of the system. This diagram should show

the following data.

11 Apparent power and voltage ratings as well as the


impedance and connections of all transformers

2) Nameplate ratings and subtransient reactance of all

major motors and generators

3) Conductor sizes, types, and configurations

4) Current transformer ratios


5) Relay, direct-acting trip, and fuse ratings,
52

characteristics, and ranges of adjustment

Refer to Appendix 2 (section A2.4) for the Belle

plant single-line diagram, which includes the above

information.

The second requirement is a complete short-

circuit-current study as described earlier in this Chapter

and also in Chapter Three.

The third requirement is the time-current

characteristics and typical time curve (this curve is used

for the new method of coordination in this report) of all

the devices under consideration.

The forth requirement is starting currents and

accelerating time of large motors.

. Once this information is .assembled, it is then

necessary to select the protective devices so that they

perform their assigned function of protecting individual

pieces of equipment and operate so that only the minimum

amount of circuitry associated with the fault is isolated.

5.3 METHODS OF COORDINATION

There are several methods of overcurrent relay

coordination available to minimize the effects of such

system abnormalities on the system itself or on the

utilization equipment which it supplies. These methods are


as follows.

1) Coordination by table

2) Use of device characteristic curve

3) Use of typical time curve of device (new method

presented in this report)

The following section will explain these method in

detail with some examples.

METHOD ONE COORDINATION BY TABLE


This method mainly uses fuse as the protective

device for the coordination of the system.

In fuse applications, coordination is achieved

through the use of selectivity ratio tables. Table 5.1

shows a typical selectivity schedule for various

combinations of fuses. This schedule is limited to several

class and type of fuses. This table is used as a simple

check for selectivity assuming that identical or reduced

fault currents flow through the circuits in desending order,

that is, main-feeder-branch. A coordination study may be


desired when the simple check as outlined is not sufficient,

and can be accomplished by plotting fuse time-current

characteristic curves on log-log graph paper.

For example, when the largest branch device is a

100 A current limiting fuse, the main fuse may be a 200 A


Arnptrap or 100 A dual-element or one-time fuse.
54
Table 5.2 shows the coordination between the

branch or load protective device and main or supply

protective device when a power air circuit breaker is used

in main or supply circuit. For example, for a current

limiting fuse used in branch or load circuit, a multiple of

2.5 times the ratio of 80 percent long time pickup to 500

percent short time pickup of power air circuit breaker

should be used for proper coordination. This multiple is

1.25 when the ratio of 160 percent long time pickup over

1000 percent short time pickup is used.

Some of the basic rules of coordination for this

method are [6]:

1) Branch fuse-clearing time must be less than the melt time


of the main fuse. That means under the total maximum

clearing I2 t of the largest fuse on the load side should


not exceed 90 percent of the melting I2 t of the supply
side fuse. I2 t values must be used to check coordination
in the current-limiting range. Below the current-limiting

range the time/current characteristic curves may be

compared as follows: (1) add 10 percent to the curve

current values for the downstream fuse, (2) subtract 10


percent from the curve current values for the upstream

fuse. The resulting curves should allow at least a 10


percent current margin between the two fuses based upon

the downstream fuse. The result is a minimum fuse size


55

s p r e a d w h i c h s h o u l d c o o r d i n a t e w i t h o u t damage t o u p s t r e a m

fuse. More s p r e a d w i l l o f c o u r s e i n c r e a s e a s s u r a n c e o f

coordination.

2) Branch device clearing time m u s t be u n d e r 80% o f t h e

sensing time of a breaker.


Table 5.1 Rating Ratios for Safe Coordination

Branch or Main or supply device

1 load device (minimum multiple of branch device) I


I
current limiting, dual element, semi lag,c-s

Amptrap,limitron, trionic and one-time and


Table 5.2 Power air circuit breaker
Minimum band
Branch or load Main or supply device
device (minimum multiple of branch device)
-
80% long time pickup 160%long time pickup
500% short time pickup 1000% short time pickuq
ratio ratio
- - - -- -- -- -- -" -- -- ---- --.-----

1b2r-
b-
--
-
.

current lim. 2.5


dual element 5.0 I

C-S one time 5.0 2.5 I


NEC 10.0 5.0
f

Molded case
I
air circuit
breaker
50 A 4.0 2.0
100 A 5.0 2.5
100 A 7.0 3.5
(heavy duty)
225 A 4.0 2.0
600 A 3.0 1.5
58

METHOD TWO USING DEVICE CHARACTERISTIC CURVES


In order to start drawing curves, a voltage level

and multiple scale current in ampere should be selected and

marked on the bottom of the log-log paper. Then proper

multipliers for the various voltage levels considered in the

study are calculated. protective device characteristic

curves are then placed on a smooth bright surface such as a

window pane, or a glassed-topped box with a lamp in it. The

sheet of log-log paper on which the study is being made is

placed on top of the device characteristic curve, the

current scale of the study lined up with that of the device

characteristic. The curves for all the various setting and

ratings of devices being studied may then be traced or .

examined [4].

METHOD THREE USING DEVICE TYPICAL TIME CURVES


This method present a new way of drawing

co-ordination curves which has been practiced throughout the

Belle plant coordination study. This method is recommended

for more accurate protective relaying coordination. Instead

of device characteristic curve, Typical time curves of

overcurrent relays used in this method. These curves show

time versus multiples of tap value current. Each

overcurrent relay has several tap value and time dial

settings. Knowing the amount of maximum short circuit


59
current and current transformer ratio is essential. By

dividing several values of short circuit currents to c.t.

ratio and the tap value, several multiples of tap values can
be found. Refering to the curve time for these multiples of

tap value can be found depending upon what time dial setting

have been selected. At this time the short circuit current

and the time for several points are known. These points are

then ploted and traced on log-log paper. Now let's assume

that an overcurrent relay at a different voltage level must

be coordinated with this relay. The minimum interval time

of 0.3 seconds must be allowed between the two relays. In

order to illustrate this method of coordination and decision

making, a portion of Belle plant detailed relaying diagram

is shown as an example in figure 4.2 and the related curves

are shown in figure 4.3. Figure 4.1 shows the typical time

curves of CO-9 overcurrent relay. The following example

illustrates this new method.

EXAMPLE :
Figure 4.2 shows a portion of the Belle plant

overcurrent detailed drawing. There are two overcurrent


relays involved in this portion of the system, which will
need coordination with the incoming power company feeder

overcurrent relay. Let's assume that fault A happened on


the syst'em. in order to isolate the fault from spreading to
other portions of the system, unit 2A breaker must operate

first so that only feeder 2A shuts down. If the short

circuit is not cleared yet, then bank No.1 primary must

operate. Finally if the short circuit is still not cleared,

then power company No.2 primary feeder must operate.

Figure 4.3 shows the CO-9 type overcurrent relay


curves that was selected and ploted for maximum protection

of this portion of the system. Following data are required

for the selection of these curves.

No.2 primary feeder overcurrent relay data

Circuit: Bank No.1 primary


Relay type: Westinghouse CO-9

C.T. ratio: 200/5=40/1

Available Taps=1.0,1.2,1.5,2.0,2.5,3.0,3.5~4.0,5.0,6
7.0,8.0,10.0,12.0

Ampere range of relay=l-12

Circuit voltage: 46 kV level

Maximum available short circuit at 46 kV level: 14,300 A

Unit 2A overcurrent relay data

Circuit: Unit 2A

Relay type: Westinghouse CO-9

C.T. ratio: 800/5=160/1

Available taps= same as relay No.1

Ampere range of relay=l-12

Circuit voltage: 12 kV level


61

Maximum available short circuit at 12 kV level: 19,400 A

Since Bank No.1 is upstream in the system relative

to Unit 2A, its overcurrent relay should be drawn first and

then unit 2A overcurrent curve should be drawn to coordinate

with that.

Relay No.1 settings

C.T.=200/5=40/1

Let's select the following setting to see if proper

coordination can be obtained.

Selected tap=12

Selected time lever=lO

Selected multiple current=lO

Selected voltage level=46kV


Multiple of tap value=(short-circuit
current) / (tap) (C.T.ratio)

Pickup* value= (tap) (C.T. ratio)

*Pickup is the minimum value of the current that can start

the relay to close its contact.


Point No. 1: 14,300 A /(12) (40)=29 off scale on figure 4.1

Point No.2 : 9,000A / (12) (40)=18.75 multiple of tap value

For this value and time lever of 10, time will

be equal to 1.2 seconds from figure 4.1.

Point No.3 : 7,000 A / (12) (40)=14.6 then time=l .3 seconds


Point No.4: 5,000 A / (12) (40)=10.4 then time=l .5 seconds
Pickup value= (12) (40)=480 A
62

These points should be plotted and traced for the

relay curve as shown on figure 4.3 (curve number 1).

Relay No.2 settings

C.T.=800/5=160/1
Let's select the following setting, so that proper

coordination can be obtained with the upstream relay.

Selected tap=7

Selected time lever=7

Selected multiple current=lO

Selected voltage level=12 kV

Maximum available short circuit at 12 kV=19,400 A

(19,400) (12 kV) / (46 kV) =5,060 A at 46 kV level

Point No. 1 : 5060/ (7)(160)=4.5 at 46 kV level

For this value and time lever of 7, time=2.1 s

Point No.2 : 4000/(7)(160) =3.57 then time=3.0 s

Point No.3: 3500/ (7)(160) =3.12 then time=3.9 s

Pickup value=(7) (160) (12 kV) / (46 kV)=292 A at 46 kV level


These points also should be plotted on figure 4.3.

As shown unit 2A overcurrent relay (curve number 7) will

operate first in case of a fault and will clear the fault

before Bank No.1. primary relay operates, since there is

about 0.6 second time interval allowed between the curves.


Both relay were tested and field checked for proper

operation based on the method recommended on section 4.7.


OVER C U R R E Y T R E L A Y
5 0 - 6 0 tiERTZ

V)
a
2
S
W
Y,

MULTIPLES O F TAP VALUE CURREHT

F i g u r e 5 . 1 T y p i c a l t i m e c u r v e s of t y p e CO-9 Relay [7]


I2KV B U S '0"

--

--*-a3;7
--

Figure 5.2 Portion of Belle plant Detailed Relaying Diagram


Figure 5.3 Portion of Belle plant Coordination curves
5.4 TESTING OF PROTECTIVE DEVICES
This requires that the system or protective device
be subjected to abnormal electrical conditions and the

operation of the system or devices compared to

manufacturers' specifications for these conditions.

MOLDED CASE CIRCUIT BREAKERS


In testing a molded-case circuit breaker, several

points must be remembered.

1) Nameplate rated voltage must be available at the input


terminals throughout the test.

2) The values of current are high and voltage is low,

therefore it is.advisable to use connections having the

shortest possible length and largest,.cross sectional area

between test unit and circuit breaker.. In some cases,


pieces of bus bar may be used for these connectors.

3) The connection to the circuit breaker must be tight.


4) The circuit breaker tested one pole at a time.
5) Trip devices must be allowed to fully reset before

performing a check test.


Molded-case circuit breaker should be tested for

(1) timing and (2) instantaneous pickup. The recommended


values of test current is three times the circuit breaker

trip unit rating. The tripping time must be measured and

compared to the manufacturer's specified values or curves.


Molded-case circuit breakers may be relatively

precise; however, the published time-delay characteristic

indicates a wide band of operation. The electrical test

will reveal circuit breakers that will not trip, those that

take abnormally long to trip, and those that have no time

delay. If the test reveals that the circuit breaker is

tripping within plus or minus 15 percent of the outside


limits of its published curves and this tolerance does not

affect the electric system coordination or stability, the

circuit breaker should be considered satisfactory otherwise

should be rejected.

An electrical test for pickup of the instantaneous


unit should be run to verify that the circuit breaker is

tripping magnetically. Testing at one of the lower

calibration marks is satisfactory. The adjustment may be

set to the lowest calibration point to verify that the unit

will pick up. If the instantaneous unit picks up at the


minimum calibration point, then pickup will be assumed to be

within manufacturer's tolerances.

LOW-VOLTAGE POWER CIRCUIT BREAKl3R [6]


Most of these circuit breakers are equipped with

one series overcurrent trip device per phase. The

electrical test must be run on each individual trip device.

The operation of any one of these devices will trip all


68

poles of the circuit breaker.


The recommended test for a low-voltage power

circuit breakers are (1) timing (long-and short-time delay

units if the circuit breaker has both type trip units), and

(2) instantaneous pickup.


The recommended values of test current for long

time delay is three times the trip unit setting, and for

short-time delay it is one and one-half times the circuit

breaker short-time delay setting; determine the

instantaneous pickup. If the circuit breaker does not

operate within the tolerances shown by the manufacturers'

time current curves, then suitable adjustment should be made

as recommended by the manufacturer.

PROTECTIVE RELAYS

The protective relay is the brain of the electric

protective circuit. It is the relay that senses an abnormal

condition and then sends the message to other devices on the

system. Therefore it is imperative that any relay work be

done in a very through manner.

A timing check should be made to see that the

relay closes its contacts within a specified time for a

given abnormal value of current. Normally this test is run


with the relay tap in its designated position. It is

suggested that a test current of four times pickup be used.


69
Based on above methods all the protective
equipment used in the Belle plant were field-checked and

tested for proper operation and coordination for the entire


system. The 12 kV molded-case circuit breakers were tested

as follow:

Minimum pickup long time delay (LTD)

Minimum pickup was checked by applying 10 percent


less than pickup current for 10 minutes. The breaker did

not trip.

Time delay (LTD)

100 Percent pickup value was selected and applied


to the relay. The time was measured until the breaker

tripped. The time measured was within the shaded area of

the characteristic curve for the test current used.

Minimum pickup short time delay (STD)


The LTD was blocked to be sure it does not trip

the breaker. The breaker was closed and set to zero. The

operate button was pushed and test current gradually was

increased. The current at which the STD armature starts to

close is the minimum pickup.

All the overcurrent protective relays were tested

for proper operation as follow:


Zero adjust test

This test is to determine that relay contacts

close when the dial is set at zero. With the continuity

light connected across the terminals, time dial was manually

turned until the indicator light on the test set glowed.

The reading was at zero.

Pickup test

This test is to determine the minimum operating

current needed to close the relay contacts for any

particular tap setting. The pickup value selected for this

test, was equal tap value plus or minus 5 percent. By

alternately increase and decrease current, the point where

continuity indicating light flickers was found and recorded.

This flickering indicates that the contacts are "just"

making and breaking. The recorded values in some relays

were higher than tap value, the spiral-spring tension was

too great and was adjusted for the correct tap value.

Time current characteristics

A timing check should be made to see that the

relay closes its contacts within a specified time for given

values of current. Three times tap value was used as the

minimum amount of test current for the timing check. Timer


selector switch was put in "N.O.MOMENTARYtt
position, the
initiate push button was jogged by using the main and

vernier controls and adjust the test unit to pass the test

current through the relay coil. The timer selector switch

was changed to "N.O.MAINTAIN1'and the main ammeter preset

pointer was set to a value just under the test current.


Then the timer was reset to zero and the initiate push

button was pressed. This puts test current on the relay

coil and starts the timer. When relay contacts close, the

timer will stop and current will be removed from relay. The

test current and time were compared with 3 times tap value.

Some relay operating were too fast and the time dial setting

was increased up to 1/2 division.


CHAPTER S I X

CONCLUSIONS

This report has illustrated methods of longhand

short-circuit-current calculations and new method of

coordination by using typical time curves of the protective

relays for quick isolation of the affected portion of


low-voltage and medium-voltage industrial and commercial

power systems. The method of longhand calculation is not

recommended for large power systems, since these plants

contain many closed loops. Network analyzer or digital


computer technique is favorable from an economic and time

saving standpoint for these systems.

As a result of the study done for the Belle plant

electrical short-circuit-current calculation and

coordination of protective devices which was used as an

example for this report; show that , 12-kV, 2.4-kV, and


480-volt feeder breakers have adequate momentary and

interrupting ratings. Short-circuit duties of the air

circuit breakers installed at the purchased-power substation

should be reviewed again for proper operation and adequate

ratings when significant load is to be added, that time,

the 12-kV bus tie breakers could be opened. Then only one

transformer would supply each 12-kV and worst-case


73
symmetrical interrupting duty would be reduced to

approximately 250-MVA. This will minimize potential damage

to the system, its components, and the utilization

equipment it supplies.

Based on the values of the short-circuit-currents

calculated for the Belle plant, proper protective devices

were selected and coordinated for the detection and prompt

isolation of the affected portion of the system whenever a

short-circuit occurs in the system. The recommended relay

settings associated with these devices were field-tested for

proper operation based on the method of testing mentioned in

section 4.7.

This report will be a good reference manual for

industrial plant engineers, electricians, industrial power

application engineers and others who are involved with the

planning of electrical facilities for low-voltage and

medium-voltage industrial plants or commercial buildings.


BIBLIOGRAPHY

System engineering apparatus distribution sales

division. "Short circuit current calculations for

industrial and commercial power system^,'^ General

Electric Co., September 1978.

Donald Beeman. "Industrial Power Systems Handbook,"

McGraw-Hill Book Company, Inc. New York, N.Y. 1955.

3. Russell C. Mason. "The art and science of protective


relaying," Schenectady, N.Y.: John Wiley & Sons, Inc.,

1956.

4. F.A.Leinberger. !!Relay co-ordination procedures for an

imaginary medium size industrial plant," General

Electric Co. Philadelphia, PA. 19102.

5. R.H.Lee. "Methods and materials for co-ordination of


fault Memo 12-43," E.I.Dupont Co. Wilmington, Delaware.

6. D.Dalasta, Norman peach, R.H.Kaufman and W.A.Weddendorf.

It IEEE recommended practice for protection and

co-ordination of industrial and commercial power

system," IEEE John Wiley and Sons, 1975.


- )

7. Relay instrument division. If Type CO (Hi Lo) overcurrent

relay," Westinghouse 1.L.41-100D.Westinghouse Electric

Co., Coral Springs, FL. December 1976.


8. Relay instrument division. "Type CA Percentage

Differential Relay for Generator Protection,If


Westinghouse 1.L.41-331.2D, Westinghouse Electric
Co.,Coral Springs, FL. February 1975.
9. Relay instrument division. "Type CWC and CWP
Directional Ground Relays instruction," Westinghouse
1.L.41-242.4F, Westinghouse Electric Co., Newark, N.J.
Oct. 1975.
10. Relay instrument division. "Type SDF-1 solid state under
frequency relay instruction," Westinghouse 1.L.41-504.1,
Westinghouse Electric Co., Newark , N.J. August 1975.

11. Relay department. "Type DT-3 temperature and micron


relay instruction," Westinghouse 1.L.41-552.1D,
Westinghouse Electric Co., Newark, N.J. 1975.
12. Relay instrument division. "Type CVE-1 and CVE
Synchro-Verifire relays instruction," Westinghouse
1.L.41-681.1N) Westinghouse Electric Co, Coral Springs,
FL .
13. Relay-instrument division. "Type KAB high impedance bus
differential relay," Westinghouse 1.L.41-337.4F.
Westinghouse Electric Co., Coral Springs, FL. May 1981.
14. Relay instrument division. "Type HU and HU-1 transformer
differential relays instruction, Westinghouse
1.L.41-347.1M, Westinghouse Electric Co. , Newark, N.J.
15. Relay instrument division. "Type SC, SC-1, SV and SV-1
relays instruction," Westinghouse Electric Co. Newark,
N.J. July 1978.
16. Relay instrument division. "Type CV voltage relay,"
Westinghouse 1.L.41-201K. Westinghouse Electric Co.

Coral Springs, FL. December 1979.

17. Relay instrument division. 'I Type COM overcurrent

relay," Westinghous 1.L.41-102E.Westinghouse Electric

Co. Coral Springs, FL. June 1979.

18. Relay instrument division. "Characteristic curves for

type DS and DSL circuit breaker,"Westinghouse


Application Data 32-860. Westinghouse Electric Co. East

Pittsburg, Pa. 15112, November 1978.


APPENDIX 1 - IMPEDANCE DATA
Al.l ANSI standard reactance values calculation

Table Al-1 ANSI Standard Reactance Values


--
First-Cycle (Momentary) Positive-Sequence

Calculation for H.V. Breaker Reactance

Utility Supply XS
Plant Generators X"
Synchronous Motors XIf
Induction Motors

(Above 1000 hp >I200 rpm) x1 r


(Above 250 hp >I800 rpm) .I' r
(All other motors 50-1000 hp) 1.2Xlr

(Less than 50 hp) .25X"

Non-rotating equipment X
Interrupting Calculations for H.V. Breakers

Utility supply %
Plant Generators XIf
Synchronous Motors 1 . 5X"

Induction Motors

(Above 1000 hp >I200 rpm) 1.5Xlr


(Above 250 hp >I800 rpm) 1.5Xlr
(All other motors 50 - 1000 hp) 3.OXlr

(Less than 50 hp) Infinity

Non-rotating Equipment X 1

lr = Locked Rotor, %=utility reactance


A1.2 Transmission line impedances
Table A1-2 Transmission Line Impedances

I . . . . . . . . . . . . . . . . . . . . .

/ ~ , 0 0 0 0 C 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ~
/ I

$ ' N * 6 m W O m N m m * P O r n v N P P W 9
c
V) o
~ l I c om ~n -, o~ e . c ~: ~* m
m q - n e~ ~q o~ w* - no ~
m ~
c *y m~ v m c u @ ~ . m m
u
C
1
......................
i * ~ * ~ ~ m m m m m m q q q q v q o n o o o
X O C O O C O O O O O O O Q O C O O O O O O O
A1.3 15-kV cable impedances
Table A1-3 15-kV Cable Impedances

6 AhG
3 AhO

U O ALtG
3/0 AkG
410 AkG
2 5 0 MC!A
300 MCM
3 5 0 !.CCU
400 YC!I
5 0 0 IACM
6a0 MCM
753 MC!A
1000 A!CN
12>0 ).{C!.i
15CC UCM
1750 MCX
2 0 0 0 MCM
A1.4 5-kV cable impedances
Table A1-4 5-kV Cable Impedances

Approximate Resistance, Reactance, and Impedance of


M00.volt Cables in Magnetic Ducts per 100 H

Throe singlo-conduda cabiu p u duct, Woo-eonductor cablo induding Intor-


ohm p u 100 * locked onnor coblo, ohms p u 100 f l
Coblo ria.

P X z R X I

Ma 14 Awq.. . 0.3135 0.W969 0.313s 0.3133 0.006664 0.3291


WalOAwq.. 0.1240 0.00150 0.1210 0.1240 0.005745 0.1241
No.8Awg ... 0.0779 0.CG781 0.0781 0.0779 0.005308 0.07808

lb. 6 AwQ.. . 0.0491 0.0U741 0.0503 0.0493 0.004941 0.04944


4A . 0.0118 .- 0.00681 0.0325 0.0112 0.004619 0.03154
g . 0.0203 0.00623 0.0212 0.0197 0.004366 0.02017

Mo. 1 A . 0.0163 0.00566 0.0173 0.0157 0.003961 0.01619


Mo. 1/0 Awq. 0.0131 0.00567 0.0143 0.0125 0.003792 0.01304
No.Z/OAwq.. 0.0106 0.00545 0.0119 0.0100 0.003677 0.01061

Wo.l/OAwg.. 0.00860 0.00535 0.0101 0.00800 0.003631 0.008785


4 0A . 0.0070a 0.00529 0.00817 0.00640 0.003313 0.007335
2SO M C M . . .. 0.00609 0.0056 0.00102 0.W7 0.003362 0.006527

100 M C M . ... 0:00520 0.00519 0.00733 0.00460 0.003311 0.003791


350 M C M . . .. 0.00461 0.00314 0.00690 0.00400 0.003U7 0.005299
..
400 M U . . 0.00119 0.00506 0.00657 0.00354 0.a3436 0.001923

so ma.. .. 0.- 0.W95 0.0061 1 0.00292 o.oo3wr 0 . ~ 9


750MCM .... 0.00219 0.W4 0.00U1 0.0010( 0.001018 0.003723
1
A1.5 Correction factors for non-magnetic ducts
Table A1-5 Correction Factors for Non-Magnetle Ducts
s+k.an.lw)cr b b k
1
t 1
fadom Fa wrr.cclng r e d e a r n
foefar kv concctinq
mctoncm, 011 S U ~ S
of cabk No. 6 to No.0010 300 to
No. 8 A r g No. 0 A r g 250 MCM 500 MCM

0.8 0.96 0.93 0.83 0.72

Correction Factors for Nonmagnetic Ducts.


Thr-ductor Cables
Dotormino correct Z from corrected voluu of X and r0. No comedim is required for intedocked
armor.

f o c t m for correcting ruistoncm


f o a a for ronocting
rooctoncm, all rizm
of coblo No. 14 to No. 00 A r g N a 0000 A r g to 750 MCM

0.17 1 .O 0.98

Per Cmt Reactonce of Typical Three-phase Cable Circuits


Per Cont Rooctonc. of 1000 Crcuit F W ~on o
1000-tw lose

System rdtogo I / 1 / / /
230 4 575 2,400 4,160 6,900 1
I
13,100

I Coblo h e , No. 4 to 1 Awg I


throo ringltcamdw9or coblw in
iron conduit................ 91.3 24.6 15-14 1.075 0,351
Thrononducror coblo m iron con-
duit or in#-d 0rolor.d l
cable.. ................... 71.8 18 11.5 0.669 0.222 0.11 0.0276
kao-conductor enblo in m a g -
neticduct.................. 511.5 14.7 9.4 0.581 0.194 0.0955 0.024
I
Cablo siro..No. 1 /0 No. 4/0 Awg

hrw nnglccarc)uctor cobla in


ironconduit ................ 92.5 23.2 14.83 0.953 0.318
n*eo-conducta cublo in imn con-
duit or i n t . r k c t d o-ad
coblo.. ................... 68
ecconductor cable in nommog-
wnetic+& .................. 34.8
17.1

13.72
10.9

1.1
0.6 0.2
I I/0.0943

0.52 ~0.17310.01111 0.0101


I
0.0237

!
Cable Six., 250 lo 750 MCM 1

re* singlrconductu cablu m


.............
$: iron condvtt..
recconductor coblo in irom con-
5 11.3 13-63 0.868 0.219

I dwt or interlocked armored


coblo. .................... 61.4
he.-conductor coble in -mag-
I . 9.85 0.331 0.179 0.0796 0.01

! d c d w .................. 51
For a~nglc-phwcueuru mult~plyvduea by 2-
11.8 1.19 0.477 /
I
0.139 O.W 0.0176
APPENDIX 2
BELLE PLANT SHORT CIRCUIT STUDY

A2.1 DESCRIPTION OF THE WORK

This work shows the short-circuit study and relay


coordination for the entire power-house electrical

distribution system for the Belle plant, (one of the

biochemical sites of E.I.dupont de Nemours & Company). This

plant is required to modernize power house coal handling and


electrical distribution reliability for the entire system so

that greater load capacity, improved reliability and safety

can be achieved for the entire sytem. Modernization of the

power-house electrical facilities will improve the

electrical reliability of the power house by installation of

a new 46-kV feeder from the existing structure between the

"A1' and "B" switch house to a new 7.5MVA, 46/12-kV

transformer with a primary circuit switcher. A secondary


12-kV feeder will be provided from the transformer to the
power house complete with a new secondary air circuit

breaker in the !'A" switch house and a new incoming air

circuit breaker located in the turbine area switchgear room.


The new incoming circuit breaker in the turbine area

switchgear room will be connected to, and become a part of,


the 12-kV switchgear. Figure A2.1 shows the system setup as
83
a block diagram.

T h i s s t u d y w i l l i n s u r e a d e q u a t e r a t i n g s of a l l t h e

air circuit breakers and proper relay coordination

throughout t h e system.

Utility
. W 9 9/1
, t N t '0" 46Kv
n
Bus

B n k tb.7, IWcl

F i g u r e A2-1 Block d i a g r a m of s y s t e m s e t u p
A2.2 12-kV AIR CIRCUIT BREAKER RATING

Westinghouse electric magnetic blast eight cycles


air circuit breakers are installed at the purchased power

substation as 12-kV incoming supply and feeder breakers.

Breaker specifications are as follows:

1. Symmetrical three-phase rating = 500MVA

2. Continuous current rating = 1200 amperes


3. Maximum voltage = 12-kV rms

4. Momentary rating = 37-kA rms asymmetrical,


momentary 2 s.

5. Minimum contact-parting time = 3 cycles


5. Rated interrupting time = 5 cycles

A2.3 SYSTEM ASSUMPTIONS

ANSI Standard C 37.5-1969 contains a guide for

calculation of fault currents for application of AC high-


voltage circuit breakers rated on a total current basis.

The procedures used in this study are the same as those

suggested in ANSI standard by using jX impedance only.


Certain simplifying assumptions were made for this

calculation which are as follows.

1. Base MVA is 5MVA

2. Three-phase symmetrical fault


3. Line resistance is neglected
4. Fault is "bolted", that is, it has zero impedance
5. Tie breaker in 2.4kV switchgear is open,
Refer to figure A2-2 in section A2.4 for the system single-

line diagram.

A2.4 BELLE PLANT SINGLE LINE DIAGRAU

The electrical distribution switching diagram was

used as a starting point in developing the system single-

line diagram. This diagram shows the normal distribution

and represents the best available definition of the system

for fault studies.

For purposes of this study, the system was defined

to start at the 46-kV bus at the purchased power substation

and continue through the 12-kV overhead distribution system

to transformers supplying secondary loads at 12-kV,2.4-kV or

480 volt. Motors smaller than 50 hP were lumped together

and treated as a single impedance on the secondary side of

the supply transformer.

Data on transformer impedances, transmission line

conductor sizes and lengths and bus duct capacity at the

purchased power substation were obtained from drawings.

The single-line diagram used for this study is

shown in its final form in figure A2-2.


Figure A2-2 Belle Plant Single Line Diagram
A2.5 BELLE PLANT IMPEDANCE DIAGRAMS

A few impedance diagrams are patterned after the

one line diagram. The arrangement of elements should aid in

easy identification of any given component in the two types

of diagrams (one-line vs impedance) even though

identification of components and significant points in the

circuits may become impossible as the network is reduced

into a single-value impedance. The per-unit system lends

itself to analysis of this system because of the several

voltage levels. A base MVA of 5MVA is assigned. The base

voltage will be 46-kV, 12-kV, 2.4-kV, and 480 volt. Base

current and base impedance for each of the voltage levels

can then be derived as shown in Appendix 3. Impedance

diagrams for the one-line diagram shown in figure A2-2 in

Appendix 2, which contains the subtransient reactance of the

system generator, the utility system reactance, and the per-

unit value of all the transformers, feeder cables and the

motor loads is shown in figure A2-4, Appendix 2.

The per-unit values for all components on

impedance diagram (figure A2-4) are derived and listed as


follows.
Utility: X=5MVA/1020MVA=.0049 P.U.

Transformer (TI) : X= (6.46%)(5MVA/lOMVA) = .0323 P .U.


Transformer(T2): three winding transformer

Zp=1/2(ZpS+ZpT-ZST)
=1/2 (5MVA/15MVA) (19.66%+7.91%-18.83%)
=

.0146 P.U.
Zs=1/2(2PS+ Z ST-Z PT)=1/2 (5MVA/15MVA) (19.66%+18.83%-7.91%)
=

.0509 P.U.
ZT=1/2 (ZPT+ZST-ZPS)=1/2 (5MVA/15MVA) (7.91%+18.83%-19.66%)
=

,0118 P.U.
Transformer (T3) : X= (5.09%)(5MVA/2.8MVA)= .0909 P . U.
Transformer (T4) : X= (5.32%)(5MVA/3.75MVA)= . 0709 P.U.
Transformer (T5) : X= (5.39%)(5MVA/3.75MVA)= .0719 P .U.
Transformer(T6) : X=(5.09%)(5MVA/2.8MVA)= .0909 P .U.
Transformer(T7): X=(5.55%) (5MVA/2.OMVA)=.139 P.U.
049 P . U.
Generator : X1'=5MVA/102MVA=.
Motors :
Typical calculation for Xth momentary short circuit is as
follows. Appendix 1 will show the multiple factors for
different size of motors.
I. Xth(momentary)=l .2(1/6) (base kVA/load kVA)
1/6 is the lock rotor current.

2. Induction motors 50-1000 hp,


3X1r
Xth (interrupting) =3 (1/6) (base kva/load kVA)
3. Full load current=largest motor (~vA)
/fl(kVLL)
Lock rotor current=5(full load current)+-total load

Cables :

The per-unit values of all the cable impedances can be

determined by referring to Appendix 1 , which will show the

approximate reactances of cables for various voltage levels

These values will be the actual impedance (ohm) values of

the feeders. The per-unit values then can be calculated by

using the following equations.


2
Base impedance=(base voltage,kVLL) /base MVA3phase
Per unit impedance=actual impedance/base impedance

Examples :

1. 12-kV feeder, 1-3/C-500MCM (50ft)


2
Base impedance= (kVLL ' base) /baseMVA3phase
2
Base impedance=(12kV) /5MVA=28.8 ohms
Appendix 1 section A1.3 shows the ohmic values of

15-kV copper and aluminum cables in magnetic and non-

magnetic conduit per 1000ft. For 1-3/C-500MCM copper cable

non-magnetic conduit, R=.0279ohms/1000ft and

X=.0317ohms/1000ft therefore:
Z=( R ~ + x ~'I2=
) [ ( .0279)2+ ( .0317)2] I/'=. 0422ohms/1000f t

For 50ft cable;

50ft(.0422/1000ft)=.0021ohms/50ft
Per-unit impedance=.0021/28.8=.0001 P.U.

2. 2.4-kV feeder, 3-3/C-750MCM/phase, 130ft long


2
Base impedance= (2.4kV) /5MVA=1.152

Appendix 1 Section A1.4, shows the ohmic values of

5-kV cables in magnetic ducts per 100ft. Section A1.5 shows

the correction factors for non-magnetic ducts. For

1-3/C-750MCM copper cable magnetic duct, R=.00208ohms/100ft

and X=.003088ohms/100ft then Z=.003723ohms/100ft

For 3-3/C-750MCM, Z=1/3(.003723ohms/10Oft)=.0013/100ft

For 130ft, Z=130ft(.0013ohms/10Oft)=.0017 ohms

From section A1.5 correction factor for 750MCM cable in non-


magnetic ducts is 0.72, so 2=.0017(.72)=.0012 ohms

Per unit impedance=.0012/1.152=.0011 P.U.


Table A2-1 in Appendix 2 shows the results of the

short-circuit calculations for momentary and interrupting

case at different locations of the system. This information

will be used for specifying the 12-kV switchgear, 2.4-kV

switchgear and 480-volt switchgear.


91
Multiplying factors for three-phase and line-to-

ground faults.

,MULTIPLYINGFACTORS FOR E / X AMPERES

Figure A 2 - 3 multiplying factors [2]


Figure A2-4 Belle P . l a n t Simplified Impedance Diagram
A2.6 BELLE PLANT SHORT CIRCUIT CALCULATION

CASE 1: Momentary short-circuit calculation for fault "A"at


12-kV bus as shown in figure A2-1 and A2-5.

The simplified impedance diagram for the entire


system is shown on figure A2-4. The equivalent circuit for
the impedance diagram is shown on figure A2-5 and A2-6.

Figure A2-5 The equivalent circuit for the impedance diagram

The Wye-Delta transformation for fault "A" is


shown on figure A2-7.
MVASC=BASE MVA/XthP.U.=5MVA/.0188=416MVA

IBASE--BASE MVA/ (kVLL BASE) 103=5 (lo6) /12 (lo3) ~ = 2 4 A


0

ISC'IBASE /XthP.U.=240/.0188=20,000.00A
'Tp,u,
1
Infinite Bus

0 P*u*

D.il7*i/Zb+iizcrJ82.e C
,85337
mgQTA
Infinite Ru

,kw

C
P.u.

Za&DZ~W(,W9)(.OiG)=,8216p,u.
&DZbfc=382(.81G)(.83397)=. 1487 p.u. B
Z;lcrDZdc=W(.W9)(.83397)=.8583 p.u.
Inf initr Bus Infinite Bus
I L I

Figure A2-6 Simplified equivalent circuit

By siylifing thr &ow circuit w get:


Infinite Bus
ee49.P.U.
5263 ,8146
P.U. p*u.

8123 *em
A p.u. P*U.

I "
"
Fault 'A'
To s i y l i Q this portin of t h c i r r i t . W-DELTA trrrrfmtim
is brar wrd.

Figure A2-7 The WYE-DELTA transformation


95

CASE 2: Interrupting short-circuit calculation for fault


I 1 All .
The simplified impedance diagram for the entire

system is shown on figure A2-4. The equivalent circuit for

the impedance diagram is shown on figure A2-8.

Infinitr RJS

Figure A2-8 The equivalent circuit (interrupting case)


The Wye-Delta transformation for fault "A" is

shown on figure A2-9.

-BASE M V A / (kYLL
~ BASE) 103=5 ( l o 6 ) / 1 2 (103)\/T = 2 4 0 A
IBASE-
IS C=IBASE /XthP . U . = 2 4 0 / . 0 1 3 2 = 1 8 , 2 0 0 . 0 0 A

The same method of short circuit calculation is

used for other locations of the system. Result of

calculations for other points in the system is shown in

table A2-1.

Infinite Bus Infinite Bus

-> DELTA
*
UYE

Infinite Bus Infinite Wu


IT

Figure A2-9 The WYE-DELTA transformation


T a b l e A2-1 R e s u l t of B e l l e P l a n t S h o r t - C i r c u i t S t u d y

/--
F a u l t Location
---.
Momentary S h o r t C i r c u i t C u r r e n t ;i

B a s e 5 MVA Amperes
..----- .-- .----- MVP.s~
-- I
F a u l t "B" 46 KV 1140
I
I Fault l f ~ l l 46 KV 1 14,326 i
I 1140 I
F a u l t "A" 1 2 KV 19,400

F a u l t "D" 2 . 4 KV 17,480

F a u l t "El1 2 . 4 KV 27,097
F a u l t "F" 2 . 4 KV 1 17,660
I

L
F a u l t "MIf 2 . 4 KV 10,400

F a u l t " N " 2 . 4 KV Ii 40,880

F a u l t "I" 4 8 0 V 63,123
I
F a u l t "K" 480 V 64,317 53
.. --- - -.....-..
F a u l t Location Interrupting Short Circuit

B a s e 5 MVA Amperes
MvAsc
F a u l t "B" 4 6 KV

F a u l t "C" 46 KV
14,036

14,036
I 1121

1121
F a u l t "A" 1 2 KV 18,178 378
F a u l t "Dlf 2 . 4 KV 13,136 52

F a u l t "Elf 2 . 4 KV 22,396 89

F a u l t "F" 2 . 4 KV 12,923 51
F a u l t "MI1 2 . 4 KV 8,010 32
F a u l t "N" 2 . 4 KV 37,240 148
F a u l t "1"480 V 48,440 40
1 F a u l t "K" 480 V 48,600 40
APPENDIX 3
BELLE PLANT GENERATOR AND BUS PROTECTION

A3.1 BELLE PLANT GENERATOR PROTECTION


TYPE CA PERCENTAGE DIFFERENTIAL RELAY 10% (WESTINGHOUSE) [8]
The type CA generator relay is available in two
designs: one for 10 percent sensitivity and the other for 25
percent sensitivity. Figure A3-1 shows the operating curves
for 10 percent sensitivity. That means 10 percent of the
smaller restraint current must flow in the operating coil to
cause tripping when the restraining currents are in phase.
One setting is required for this relay, that is,
the setting of the time dial. This setting should be on the
number one position as manufacturer recommended .
The only setting required on the indicating
contactor switch (ICS) unit is the selection of the 0.2 A or
2.0 A tap setting. Since this relay is energizing a 125
volt d-c relay switch in this system, the 0.2 A tap is used
instead of 2.0 A tap.
set time dial 1, figure A3-1.
ICS (indicating contactor switch) . 2 amps
CWC GENERATOR GROUND A-C DIRECTIONAL OV3RCURRENT RELAY [9]

The following information is required to set this

relay:
1) The maximum and minimum ground fault current for

fualts at the relay and at the remote bus. These

values should be residual current which is three times

the zero sequence current.


2) The maximum and minimum polarizing current (IU) or
voltage values for the faults above. These values

should be residual current which is three times the

zero sequence values.

Cuur 5.rr- H; La t . #&.A


rc%v e u i

ZOO/*
SFF occa3Sq , -
YRCT

Ull.Z,'l4 uua-
3) The current transformer ratios (C.T.) of the main and

polarizing current transformer.

CASE 1: Tie breaker is closed and generator is down.


Since generator is down, either fault F1 or F2 can see

current I1

R=M (I1/IU),for the 0.25 to 4.0 product range


Iprimary (polarizing)=50 A, C.T. ratio=50/5=10/1
Isecondary (polarizing)=50 A, C.T. ratio=50/5=10/1
Secondary current (Iu)=Iprimary /C.T. ratio=50/10=5
Secondary current (I1)=Isecondary/C.T. ratio=50/10=5
Product of (IUXT1)
=25 and IU/I1=l.0

With tap product=25, R limit constant should be 4.0or 5.0.

OCCRATINO C O K A Y C C R C S

Figure A3-1 Typical time curves for the 10% sensitivity type

CA generator relay [8]


R=M ( 1 I u ) select upper tap=l.O and lower tap=0.25 from

table A3-1, then M=4.0 from the table A3-1.

Multiple of tap product=I1.Iu/(upper tap)(lower tap)

=25/1( .25)=I00

from figure A3-3 at multiples of tap product=100 and time

dial=2 , then operating time=.09 s .


Note :

The typical time curves for the type CWC relay

apply i f the values of (R) falls within the shaded area of

the curve shown on figure A3-3, and if neither relay

current is greater than (K) in amperes.

Figure A.3-2 limits for application of the CWC time curve[9]


WLTlPLU OC TAP CIOOYCT
- - -

Figure A3-3 typical time curves of the type CWC relay

current coils in series [ 9 ] .


Total time = operating time + relay time + breaker time
Total time = 0.09 s + 2(0.0167) + S(0.0167) = .21 s

The ground relay 50/GN has 0.5 s delay, this allows 0.29 s

for resetting of the 50/GN relay.

CASE 2: Tie breaker is closed and the generator is on.


IU(polarizing) = 50amps.

Since generator is on, fault F1 and F2 see 11+12=100 A, so

By using figure A3-2 and table A3-1, for the 0.25 to 4.0

product range M=4.0

I,=lOO A I1/IU=lOO A/50 A=2, R=M(I1/IU) R=4 (100/50) =8


Multiple of tap product = (10) (5) /1( .25)=200

from figure A3-3 at multiple of tap product= 200, and time

dial=2, operating time will be .065 s .

Total time= .065 + 2(.0167) + 5(.0167)=. 18 s


Time to reset 50/GN relay=.5-.18=.32 s

Since the calculated value of delay time for this

relay is proper for coordination with the ground relay on

delta wye ground transformer, then relay setting will be as

follows:

Set: Upper tap=l

Lower tap=.25

Time dial=2
ITH generator ground relay (westinghouse)
This relay is factory set for minimum pickup of

0.25 amperes, no setting was required for this relay.

Set: All ITH relays on minimum pickup .25amps.

Device 59G generator over voltage relay

The relay is energized from a potential

transformer, P.T.= 12000/120=100 volts, maximum voltage

permitted on generator continuously is about 105 percent or

1.05(120)=126 volts. 120 volts relay set at tap=5 designed

to operate at 122 volts, then 122/120 = 1.016 percent, Relay

is factory set for tap = 5 and lever = 10, field to adjust

per curve shown on figure A3-4. 104 percent continuous over

voltage limit is desired.

Device 53G volts per hertz relay

Type SVF form 2E1, hitachi, maximum permissable

volt/hertz for generator is 1 . 2 per-unit. Relay setable

.lvolt/hertz increment. Relay setting of 1.9 volt/hertz is

maximum. This relay was set at factory for 1.2 volt/hertz.

Device 60G voltage balance relay

Type SDV3 form W-3E2, hitachi, these voltages will


normally be balanced. Therefore most sensitive setting will

be selected. This relay was set at factory for 1 0 volts.


Device 64F field ground relay

Relay type SG form C-Dl, hitachi, this relay is

used, because field circuits are operated ungrounded. A


single ground fault will not damage or affect the operation

of a generator in any way. However, the existence of a

single ground fault increases the stress to ground at other

points in the field winding when voltages are induced in the

field by stator transients [ 4 ] . This relay is factory set,

therefore no setting is required for this relay.

Device 27G high speed under-voltage relay

Type W3-UT21-21 E2, this relay functions on


agiven value of under-voltage, The dropout is normally set

at approximately 80 to 90 percent of normal voltage. This

relay is factory set for maximum value of voltage 95 volt.

KLF loss of excitation relay (Westinghouse)


Refer to figure A3-5 to see generator reactive

capability curve. The machine capability curve on figure

A3-6, was generated from figure A3-5. A reactive circle has


been drawn on an R-X diagram. The equivalent generator
impedance traces a path from first quadrant into a region of

the fourth quadrant that is entered only when excitation is

severely reduced or lost. By encompassing this region


107
within the relay characteristic, the relay will operate when
the generator first starts to slip poles and will trip the
field breaker and disconnect the generator from the system
before either the generator or the system can be harmed. As
shown on figure A3-6 ZA-
-1.98 and R=1.03.

'base
= [ (KV)2 / ~ [ ~ ~ ] ]=12'/14.564
(RC/RV) (200/100) =19.776 ohms
ZA=l.98(19.776)=39.16 ohms.
Zc=.08(19.776)=1.58 ohms.
(SA) must be greater than or equal Z
'base A' therefore:
19.7(SA)> 39.16, then SA must be atleast 3.0, so set S
A

TA=ZA/SA=39.16/3=13.05, set TA on tap=11.5


9 ), set MA =-0.12
MA= [TA SA/ZA] -I= [ll.5 (3)/39.16] - ( -
This requires: L, lead on .03 and R, lead on upper .06
Actual Z=TA SA/(1-MA)=11.5(3)/(1-.12)=39.2
39.16/39.2=99.88% of setting required. Set ZC=1,58, set
SC for 6(Sc)>1.58. SC=l minimum tap so set S C = l Set TC
tap closest to Zc/Sc=1.58/1=1.58. Set TC tap=1.84
Mc= [(TCXSC) /ZC]-I= [I.84(1) /I.581 -I=.165
Set MC for 0.15, L(1ead upper)=.06 and R(lead)=O.O
ZC=1.84(1)/(1+.15)=1.6
1.58/1.6=98.75% of required setting.
Set under voltage unit at 77% (factory set check).
Figure A3-4 Generator Overvoltage Curve.
Figure A3-5 Generator .Reactive Capability Curve.
Figure A 3 - 6 Generator Capability Curve,
CRN-1 Reverse power relay (Westinghouse)

Set relay to detect monitoring in approximate 6

seconds. Using time dial of 2 for 120 volts. Set timing

relay at 30 seconds (Agastat) to trip the generator.

COQ Generator negative sequence relay (westinghouse)

From hitachi generator data C.T.ratio = 1000/5 or

200/1 and -701


Ifullload-- amperes. 701/200 = 3.505

Set relay: Tap=3.5 A

Time dial = 4.0 and ICS = .2 A

SDF-1 Under frequency relay (westinghouse) r101

Figure A3-7 shows the effect of time delay on the

actual frequency at which tripping takes placeunder

declining frequency conditions. The curves show how the

frequency continues to drop in the time interval required

for the relay to operate after its frequency set point is

crossed.

For example, suppose that for a system of inertia

constant H=2, it is required that the frequency not dip

below 57.5Hz for any overload upto 46 percent. Assume the

relay is set to trip at 59.2Hz. The scale at the bottom of

figure A3-7 indicates that a 46 % overload will cause a

6Hz/s rate of decline. The SDF-1 relay with 15 cycles of

delay setting will close its trip contact when the frequency
112
has dropped 1.7Hz below the set point, or 57.5Hz, for this

overload condition. Thus 15 cycles is the maximum

acceptable time delay setting to obtain the desired

protection.

In this system the relay is set to trip at 57.5Hz,

30 cycles delay provided. Breaker No.1 and No.10 under

frequency relay are set to trip at 58.5 Hz(3 cycle delay).

Refer to figure A3-7.

DT-3 Generator temperature relay (westinghouse) rll]


Normal setting for this type of relay is 120

degree centigrade. Since this relay alarms high temperature

only, set relay at 115 degrees C to provide operator a


pre-warning to increase cooling water supply.
RATE OF FREQUENCY D E C L I N E . HZ / SEC.
10 20 30 40 50 60 70
H-2 I 1 I 1 I 1 I 1 I 1 1
H=4 1 1 I 1 I I I 1 1 1
10 20 30 40 50 60 70 80 90 100 120 140
APPROX. PERCENT SYSTEM OVERLOAD
(ASSUME LOAD CONSTANT WITH FREQUENCY AND PF . x .as)
H = SYSTEM INERTIA CONSTANT, KW-SECMVA

Fig k3-7 SDF-1 Relay Tripping Delay Under Declining


Fig A3-7 SDF-1 Relay Tripping Delay Under Declining

Frequency Conditions [lo]


CVE-1 Syncheck relays (Westinghouse) [ I 2 1

For breaker No.10 (in unit No.4) CVE-1 setting is

as follows: The time dial should be set so that the relay

will not operate when the system are swinging too fast. From

figure A3-8 (Westinghouse) for a 20 degree circle as the

relay calibrated from factory, set the time dial setting =1,

then the operating time will be about 2.8 seconds.

It is recommended by the manufacturer to set the

time dial equal 11, when 60 degree circle setting is used

and time dial of 4 when 40 degree circle is used.

Figure 113-8 Operating time variations with changes in

time-dial settings. Rated in phase voltage on

both circuits, 20, 40 and 60 degrees circle

setting [I21
Automatic synchronizer W U (Westinghouse)
The following are suggested settings and may have

to be altered in field due to various voltage differences

that occur.

Voltage acceptor: Lower limit 110 volts

Upper limit 120 volts

Difference limit 5 volts

Voltage matcher 2 volts times 3 second

Pulse duration time .25 second

Field check closing times of all synchronizing breaker and

set EQ breaker closing equalizer.

A3.2 BUS DIFFERENTIAL PROTECTION [13]

KAB bus differential relay is an instantaneous

relay of the high impedance type used for bus protection.

The following points should be considered on any proposed

type KAB relay application.


1) All ct's in the bus differential circuit should have the
same ratio and should be operated on their full tap.

2) The leakage impedance of the ct's should be low.


3) To insure a substantial margin of operation on internal

faults, the voltage unit should not be set any higher

than knee voltage Vk, value of poorest ct which is

connected to the relay.

4) To insure a substantial margin for preventing the relay


from operation on external faults, the knee voltage value

of the best ct which is connected to the relay should be

used to determine value of (RS+RL)IF/NVK in figure A3-9.

The knee voltage is defined as the intersection of the

extention of the two straight line portions of the

saturation curve, ordinate and abscissa must be same

scale for each decade.

5) The maximum number of circuits which can be connected to

the relay or the minimum internal fault current required

to operate the relay can be estimated from the following

equation

Imin=(XI,+IR+IV)N ,where Imin=minimum internal fault

current, RMS. Ie=ct secondary excitation current at a

voltage. equal to ,the setting value of V-unit.

IR--Current in V-unit at setting voltage VR. I ~ C u r r e n t


in varistor circuit at a voltage equal to the setting

value of V-unit. N=ct turn's ratio and X=Number of

circuits connected to the bus.

Device maximum ground fault is the sum of

transformer ground and the generator ground.

Maximum ground fault=50A+50A=100 Amps

Switchgear short circuit available=500 MVA


3 Phase symmetrical f ault=500 M V A / (~1 2 ~ =24
~ ) KA

1200/5 CT, VK, voltage Knee=160 volt, N=1200/5=240


Current Transformer resistance= R =.471 ohms
S
One way lead resistance 80ft of #14 wire=RL=.156

Voltage unit setting (3 phase fault)

C.T. Saturation Factor=(RS+RL)IF/N.VK=.392

Margin Factor, K=1.32, found from figure A 3 - 9 .

Relay voltage, VR=K(R S+RL)IF/N, then VR=82 volt,

so pick the relay voltage, VR=90 volts.

Current unit setting

~ L)IF/N=63 From figure A3-10


( R +R
Unit setting=3 A (rms)

2.4KV Bus differential type KAB relay, Westinghouse style

NO. 6668D37A12 87 device.

Switchgear rating = 200 MVA

Maximum fault = 48,000 A

Minimum fault = 24,000 A

Maximum ground fault = 340 A

C.T. 2000/5 = 400/1 = N


Knee voltage = 240 volts = VK

C.T. DC Resistance = .858ohms = RS

One way lead resistance = .032 (50ft of # 8) = RL

R S+RL-
- . 8 9 ohms
Current unit setting (instantaneous 3-48 amps)

~ L) IF/N= ( .89) (48,000amps/400) =106.8


( R +R
From figure A3-10 setting is 3 amperes.

Figure A3-9 KAB Relay Voltage Unit Setting[l3].


Voltage unit setting (75-300 VAC)
C .T . Saturation Factor = (RS+RL) I F / N . VK

C . T. Saturation Factor = .89(48,000amps) /400(240)= .445

From figure A3-9, margin factor, K> .95

VR=K (RS+RL) IF/N=.95 ( .89 ohms) (48,000amps) /400 = 101.5

Pick relay voltage, VR = 120 volts


Check minimum fault current required to operate the relay.

X = 6 circuits VR=120 volts

IE = .015 A 1 . 0A

Figure A3-10 KAB Relay Current Unit Setting[l3]


APPENDIX 4
BELLE PLANT TRAiiSFORMER PROTECTION

A4.1 TYPE HU-1 TRANSFORMER DIFFERENTIAL RELAY r14]


(Westinghouse)

In order to calculate the required tap settings

and check current transformer performance the following

information is required.

1) Maximum transformer power rating (KVA)M


2) Maximum external fault currents

3) Voltage ratings of power transformer (VH,VI,VL)


4) One way current transformer lead resistance at 25 degree

5) Current tr-ansf
ormer copnections (wye or delta)

6) ct secondary winding resistance, RS

Definition of terms
-Primary current at (KVA)M
IP-
IR=Relay input current at (KVA)M

IRH IRL IRI are


) )
same as IR except for high, low and
intermediate voltage sides respectively.

IS=CT secondary current at (KVA)


T=Relay tap setting.

TH ,TL ,TI-
-T except for high, low and intermediate voltage
winding, respectively.
N=Number of current transformer turns that are in use.

NP-
-N/N T (Proportion of turns in use)
NT=Current transformer ratio, full tap
ZA-
-Burden impedance of any devices other than HU-1 relay

=Maximum symmetrical external fault current in


Iext .
secondary RMS amperes.

ZT=Total secondary burden in ohms (excluding current

transformer winding resistance.)

Calculation procedure

Three-winding transformer bank N0.7

High Intermediate Low

(KVA)M= 15MVA (KVA)M= 15MVA (KVA)M= 15MVA


1) Selection of C.T. ratio
I, (high)=15,OOOKYA/: 5' (46KV)=I88 A 300/5 C . T. ratio
1 ~ ( i n t e r m . ) = 1 5 , 0 0 0 ~ ~ (12KV)=721
~/'~~ A 1200/5 C .T. ratio
I (low) =l5,OOOKVA/'F
(2.4KV)=3600 A 5000/5 C.T. ratio
P

2) Selection of relay taps


Is(high) =Ip/N=188/60=3. 13 A
IS(interm.) =Ip/N=721/240=3.0 A
IS(low)=I,/N=3600/1121=3.22 A
IR(high) =Is(high) =3.13 A
IR(interm.)=IS (interm.)=3.0 A
IR(low) =IS(low)=3.22 A
TAPhigh=TH=3.
2 (3.13/3.22)=3.11
TAPinterm.=TI-
-3.2 (3.0/3.22)=2.98
TAPlOw=TL=3.2

3) Mismatch calculation
High side
%Mismatch=100 [(IRhigh/IRinterm. ) - (TH/TI) ] /S
S=The smaller of IRhigh/IRinterm. or TH/TI
TH/TI=3.2/2.9=1.10 and IRhigh/IRinterm.=3.13/3.0=1.043
Then S=1.043
%Mismatch=100(1.043-1.103)/1.043=-5.79 %
Intermediate side
%M=lOO [ (1,intex-m. /IRlow) - (TI/TL) 1 / S
T /T -2.9/3.2=.906 and I interm./I low=3.0/3.22=.932
I L- R R
Then S=.906
%M=100(.932-.906)/.906=2.87%

Low side

%M=lOO [ (IRlow/IRhigh) - (TL/TH) ] /S


IR low/IRhigh=3.22/3.13=1.0288 and TL/TH=3.2/3.2=1.0
Then S=1.0
%M=lOO(l.O288-l.O)/l.O=2.88 %

4) Check C.T. performance for WYE connection

High side
ZT=1.13RL+0.15/T +Z ohms, where R =.I63 Q 75 degree
H A L
ZT=1.13(.5)+0.15/3.2=.61 ohms

Np=N/NT=60/60=1
NP(VCL/lOO)>ZT, since 1(100/100)>.61, then it is 0.k.

Intermediate side
C.T.=1200/5
RL=.471 Q 75 degree=.396 Q 25 degree
ZT=1.13RL+.15/TI=1.13(.396)+.15/2.9

ZT-
-.499 ohms, Np=N/NT=240/240=1, VCL=200

Np(VCL/lOO)>ZT, since 1(200/100)>.499, then it is 0.k.


Low side

HU-1 style 290B346A10 setting are as follows.


Instantaneous = 3 times of tap setting

Pickup = . 3 times of tap setting

Taps available = 2.9, 3.2, 3.5, 3.8, 4.2, 4.6, 5.0, 8.7

Setting used, (Thigh'3.2, Tintermz3 ' T ~ o=3.2)


w

Type SC circuit switcher relay (Westinghouse) r151

The type SC current relay is adjustable over a

Wide range of voltage or current and can be calibrated for

the proper pickup setting. The type that is used here is a

d-c, 25 to 60hz frequency with a current adjustable range of

40 to 160 A, with a maximum continuous current equal 40 A.

Dropout ratio for a-c is between 90-98% and for d-c would be

65-80%.
The proper adjustments to insure correct operation

of this relay have been made at the factory.

Range=40-160 amps.

Circuit switcher interrupting rating =8,000A

for primary faults. Primary C.T. ratio=200/5=40/1


125
160(40/1)=6400 amps, maximum current which will operate

the relay. Since circuit switcher has to clear the fault


before No.2 primary feeder and coordinate with overcurrent

relay on bank No.1 then, the instantaneous setting =I60 A as

shown in Appendix 5 section A5.1.


126

APPENDIX 5 - BELLE PLANT OVERCURRENT PROTECTION DETAILED

DRAWINGS
A 5 . 1 "A" s w i t c h h o u s e , Bank N o . 1 and 1 2 k V B u s " D M
A5.1 continued

Refer to Appendix 6 section A6.2 for selection of type CO-9

relay curves.
A 5 . 2 ECR No.6, 12kV Bus "A"

FROM IZKV SWGR


UNIT 2
A5.2 continued

Refer to Appendix 6 sections A 6 . 1 and A 6 . 2 for selection of

type CO-7 and CO-9 relay curves respectively.

r u 4 i~L
clALn/Fz43n
c m ~ mrm
r Ln
A 5 . 3 ECR No.6 , 12kV Bus "B"
A5.3 continued

Refer to Appendix 6 section A6.2 for selection of type CO-9

relay curves.
A5.4 Co-generation generator

ZEPO SEQUENCE

!' , NOTE: REFER TO W615413 FOR hE TAl LED


G E N E R A T O R RELAY SINGLE LINE
DIAGRAM.
A 5 . 4 continued
A 5 . 5 Bank No.7 feeder No.18
A5.5 continued
Refer to Appendix 6 section A6.2 for selection of type CO-9

relay curves.
A 5 . 6 2.4kV 600hp motor river pump house
A 5 . 6 continued
A 5 . 7 2.4kV 4 5 0 h p motor boiler feeder pump No.5

CuQRErJT
RELAY

# 5 B ~ I C E RFEEDWATER -
PUMP
A5.7 continued
Refer to Appendix 6 section A6.9 for selection of type AA12P

overload relay curves. Fuse curves are shown in Appendix 7.

-----
-----I--
.---
--..--.-. - - -,,*-
------.
--:
-----.-A
--
- -.-- .-,--..-
.-.----

, . . L

- -
. --- - .
... .
.. - . -..-.. - - -- - . -

. .

1
. .,.*- . - - - ----,
U v L r m r ruu cunxrwr IN A n s x a X & A T ~xv.
A
A 5 . 8 2.4kV 7 5 h p m o t o r a s h pump

Z 4 K V UNIT 3 A

p;RuADa

(3
50/5 L.R.
OVER
CURREUT
RELAY
A5.8 continued
Refer to Appendix 6 section A6.9 for selection of type AA12P

overload relay curves. Fuse curves are shown in Appendix 7.

N A I L -
CI --/%-A
mmarrcrIS_n
a l m H

cr & - A
m rm r r r rn
nnmnro-H

1 U I L -
Cf -,%-A
cmlr miu
Imr mu *
-
u
n
l
m u R - X
A5.9 2.4kV 200hp motor recirculating pump
A 5 . 9 continued
A5.10 2.4kV 200hp motor F . D . fan boilers No.6 & 9

I UNIT 68

F.D. FACJ
A5.10 continued

Refer to Appendix 6 section A6.4 for selection of type CON-5

overcurrent relay curves. Type AA12P overload relay curves

are shown in section A6.9.


A 5 . 1 1 2.4kV f e e d e r s , s h e e t No.1 & Bank No.60

.AN< '60 &,


5250 KVA
I2KV /2.4KV
A5.11 continued

Refer to Appendix 6 section A6.2 for selection of type CO-9

relay curves.

MULTIPLY $CALL C U R R E N T IN A M P E R E S X =AT-?& KV


A5.12 2.4kV f e e d e r s , s h e e t No.2 & Bank No.59

SECIPC,
PUMP
A 5 . 1 2 continued

Refer to Appendix 6 section A 6 . 2 for selection of type CO-9

relay curves.
A5.13 2.4kV f e e d e r s , ECR No.5

A.f? CO. %KV

BANK *7
4GKV 4CKY 1 5M V A
IZKV
IZKY
i
A 5 . 1 3 continued

Refer to Appendix 6 sections A 6 . 1 , A 6 . 2 and A 6 . 3 for the

selection of type CO-7, CO-9 and CO-11 relay curves

respectively.
A5.14 2.4kV 15Ohp motor boiler No.10 mills
A5.14 continued
Refer to Appendix 6 sections A6.4 and A6.9 for selection of

type COM-5 overcurrent relay curves and type AA12P overload


relay curves.
A 5 . 1 5 2.4kV 550hp motor I . D . f a n boilers No.14 & 15

UNIT 4 A

I UNIT 4 6
A 5 . 1 5 continued

Refer to Appendix 6 sections A6.4 and A 6 . 9 for selection of

type COM-5 overcurrent relay curves and type AA12P overload

relay curves.

er -+-n-
TY__ IL

nanmrrcr> n
al mlDAsl

mr-m-I2

1
U
-1
1
CT
-
-- ' 5 - n
c w n mrrcr n
.n ma-um 1
ur-m-x

'
CI
U IL -,
L-/I
I n n/

mm3us-
MUL'flPLT Sa2AI.X CU8EXNT IN A Y P I I C I X 'OAT=
KV.
A 5 . 1 6 2.4kV 4 0 0 h p motor I . D . f a n boilers No.6 & 9

UNIT 4A
-

I UNIT 4 8
A5.16 continued

Refer to Appendix 6 section A6.4 and A6.9 for selection of

type COM-5 overcurrent relay curves and type AA12P overload

relay curves.

(n roowe 4- a
W T L -
cr. -R--n
NLllRUM&#V
mr m m w R

cr. a ,%>/I
m ~ mrm
r Ll LV

N%TLL_!
Lr-,%
c:m11 YalW 0

NI-;anvrunr
m1'mb
an
BLLI rm-
T Y i L I
cm
i 11Y a r m -<'
A5.17 4 8 0 V feeders, ECR No.8 sheet 1
A5.17 continued

Refer to Appendix 6 sections A6.7 and A6.8 for selection of

type Amptector 11-A and type DSL-206 Limiters. Appendix 7


shows the selection of type LPS-RK Buss fuses.
A 5 . 1 8 4 8 0 V f e e d e r s , ECR No.8 s h e e t 2

BLR* 9 MCC

=Rat4 MCC BLR'ISUCC


AS.18 continued

Refer to Appendix 6 sections A6.7 and A6.8 for selection of

type Amptector 11-A and type DSL-206 Limiters. Appendix 7


shows the selection of type LPS-RK Buss fuses.
A 5 . 1 9 480V feeders, ECR No.8 sheet 3
AS.19 continued
Refer to Appendix 6 sections A6.7 and A 6 . 8 for selection of

type Arnptector 11-A and DSL-206 limiters. Appendix 7 shows

the selection of type LPS-RK Buss fuses.


A 5 . 2 0 2.4kV 5 5 0 h p motors I.D. f a n boiler No.10
A5.20 continued

Refer to Appendix 6 sections A6.4 and A6.9 for selection of

type COM-5 overcurrent relay curves and type AA12P overload


relay curves.
APPENDIX 6 - WESTINGHOUSE OVERCURRENT, OVER VOLTAGE AND

UNDER VOLTAGE RELAY CURVES [ 7 ] , [16]


A 6 . 1 T y p e CO-7 Over C u r r e n t R e l a y [ 7 ]

V)
Q
2
0
U
W
m

2 3 4 5 6 7 8 9 10 12 14 16 18 20
M U L T I P L E S OF TAP VALUE CURRENT
Typical Time C u r v e o i t h e T y p e C O - 7 Relay
A6.2 Type CO-9 Over Current Relay[7]

'TYP T C:V,'T Ty1E C U R V E S


'1,Y 1' 1: LO- $1
OVER CURRENT RELAY

M U L T i P L E S OF T A P V A L U E C U R R E H T

T,r cul T - P C , r v e q i thr T v o e CO 9 RCIO~


A 6 . 3 Type

TIME D I A L
SETTING

HULTIPLES OF TAP VALUE CURRENT

T y p , c o l Trme C u r v e o i the T y p e C O -l i Relay


A6.4 Type COM-5 Over Current R e l a y [ l ? ]

I
I
,
,
I

i
l
'
/ [ ,
I

I
J I
1
/ , ,
I , ,
I ,
,.*
I
1
. .
TYPICAL T I M E CURVES j
OVER CURRENT R E L A Y

2 3 5 6 7 8 910
M U L T I P L E S OF TAP VALUE CURRENT
AB.5 T y p e CV-2 U n d e r Voltage Relay[lG]
32
TYPICAL T I M E CURVES

UNDER VOLTAGE RELAY 30

28

26

24

22

20

18

v)

16
0
U
W
v)

14

12

10

1)

0
u 1C 2C 30 40 50 60 7G 80 90 1OC
P E A C E N T TAP V A L U E V O L T A G E

TIP,cal60-crcle T ~ , ~ W C U ~ O S t y p o C V 2 S h o e T ; m * Undorvoltope R e l o r .
or* tho
A 6 . 6 Type CV-7 Over a n d Under V o l t a g e R e l a y [ l G ]

T r P . < a l Y 1 - c y c ~ +t ~ m rc v r e x o f t h e t y p e C V 7 I h r r T . 0 . Ow.. o l d Umd.rroltap* R.iey,


A6.7 Type Amptector II-A Time-Current Characteristics[l8]

CURRENT IN MULTIPLES OF SENSOR RATING

CURRENT IN MULTIPLES OF SENSOR R l T l N G


A 6 . 8 Type DSL-206 L i m i t e r s [ 1 8 ]
A 6 . 9 Two p o l e t y p e AA12P Overload Relay

TRIP nME IN SECONDS


- " . - n - - - -
- Y
I.
,#
I
L.
G.
.
" "
" "
c,
.
U
) ..--;
-.
"- -
-3
2
.(

--
- - - . ..

M
-
,.__,
I '
- - A--L, L+--J--&+
. . . - .- .. .
---&i
&--
-.+-,-_LJ--.
LIW' ---.--. . .--
" - - " ---"I
- I----

-
D
I
.-.-.-
II
- --..-,.z
_ . . - ' . n . . o
i..---Lm - T f --I7
3 f $ 'i~bl'tj
TRIP T \ M E 'N .(SFCONDS
A 6 . 9 Continued

TRIP TlPAE IN SECONDS


- - - - - - - o
- ." . . . . . ... . . .
I. - . - - I .
-
S
...........
'"
- 0
0
-
-- - -- ., ,.o - .-
0 ' +:-

. I ,

,_ _. . "
---, --

. . . . . . . .
-- ----- ---. . .......... '.-. . . . . . . . . - . . . < . .
a
I
. , - - - 'r)
.
. . . . . . . . . . . . . -. .,. . .,.
i --+

...? 4 4 . ! * I
, ,
. . .
., & , , . .
. .
, > - . . . . . . . . . . .
1,. . .I ; 7 . y - 1 , 8 I ...
-,..-..-+-- ---- -- . .' - r I ,
..........,..................
,. +Ail). .-----.
I ,
L l n O i - . - & - -
uo---
- --.--..
8 -c 1 I--; ---i-.-
--,-.----
-.-- ....
I.:
;-., : - , . --,
_ . _ _ - - .. . . . . . . . . -
1.-
.,A.
.
-0

- - - ------ -_-A

3
3-t

K t 2 Zd:6i 3 5 f IIS6,jf
b:

TRtP T I H E SECO&JDf
A 6 . 9 Continued

f R I P TIME IN SECONDS

4hl, ----
.
. .
b
6.--
. 4
-.. . - ",
"
4.- d m

.- .
...
. -
.l -. .-
I . . .
- - --.I . . .
- I:
. I . -.
. ! :... .--r.-. : .. 3m
. . . . . . . -.. . . . . . ...
. . -. . . . . . . . . . .
., - 4 -.-
.
.- ........
xw
.m .-. - - - i d .

.- + ~ --,.- + - k. t f "-----
- l.--. -
- ----
i+*
i-C
-- r .
.-----.
-T7
. .
w- -
,i-.- - .
- .. a
L.-.
-----..
--I
- L I-
: ::
. 7:-=-
r r g r z x i "
2 -
; 522i!?f
1rZa

T R I P TIWE IN S E C O N D S .
A 6 . 9 Continued

TRlP TtME IN SECONDS

, i--1--7- ta

LX:, - -----------
...
. . a , i . ? .
------
i
--..

.-..
-.-
,
-. ,
-.---.
. , #
, ,. .
- -. - -..--
. . I
.
..
.
.
-.-,
,
-.
, I
.-
- l . . r ..-.--.---...A- L... L.. i . --*
<,.*.
. . -
rur .----
,-
----.-,--.-..
-,- '
-r*+-,l-
: .,- --.--.--- -: -..-. :--!A_
---.-
--* __;
--
--;..-____ ._A _ _ #

, . --
- . . --.. ...-..-- --. . - .
-----.. 8 ,
'
-0
-..-1 . L - I -1 1-
M
: . - ..
- L
* 8

. -.--..
" - - - a - - L
U . ..-----
a O d . O O
. 8

o
I .-.

2 f 5 3 $
-
8Z.i:
. \..-

TRlP T I W E IN S E C O N D S
A 6 . 9 Continued

T R I P TIME IN SECONDS
A 6 . 9 Continued.
APPENDIX 7 - BUSS FUSES CURVES
- PEAK Dual-Element Fuses (600v) [I91
LOW
A7.1 Type LPS-RK(R.Kl) -

Minimum Melting Tlme-Current Characteristic Curves


L47.2 Type KRP-C H I - C A P F u s e s ( 6 0 0 ~[I91
)

Total Clearing Tlme-Current Characteristic Curves


APPENDIX 8 - ASA DEVICE NUMBERS AND FUNCTIONS

A8.1 ASA DEVICE NUMBERS AND FUNCTIONS


Each device in an automatic switching equipment has

a device function number which is placed adjacent to or

within the device symbol on all wiring diagrams and

arrangement drawings so that its function and operation may

be readily identified. These numbers are based on a system

which was adopted as standard for Automatic Switchgear by

the American Standards Association and appear in ASA

The following is a list of device numbers and

functions as taken from this standard.

DEVICE No. FUNCTION AND DEFINITION


.1 Master Element

2 Time delay Starting or Closing Relay

3 Checking or Interlocking relay

Master Contactor

Stopping Device

Starting Circuit Breaker

Anode Circuit Breaker

Control Power Disconnecting Device

Reversing Device

Unit Sequence Device

Reversed for future application


Overspeed Device

Synchronous speed Device

Underspeed Device

Speed or Frequency Matching Device

Reversed for future application

Shunting or Discharge Switch

Accelarating or Decelerating Device


Starting to Run Transition Contactor

Electrically Operated Valve

Distance Relay

Equalizer Circuit Breaker

Temperature Control Device

Reversed for future application

Synchronizing or synchronism Check Device

Apparatus Thermal Device

Undervoltage Relay

Reserved for future application

Isolating Contactor

Annunciator Relay

Separate Excitation Device

Direction power Relay

Position Switch

Motor Operated Sequence Switch

Brush operating or Slip ring Short cir. Device

Polarity Device
Undercurrent or Under power Relay
Bearing Protective Device

Reversed for future application

Field Relay
Field Circuit Breaker

Running Circuit Breaker

Manual Transfer or Selector Device

Unit Sequence Starting Relay

Reversed for future application

Reversed Phase or Phase Balanced Relay

Phase Sequence Voltage Relay

Incomplete Sequence Relay

Machine or Transformer Thermal Relay

Instantaneous Overcurrent or Rate of rise

A-C Time Overcurrent Relay

A-C Circuit Breaker

Exciter or DC Generator

High speed D-C Circuit Breaker

Power Factor Relay


Field Application Relay

Short Circuit or Grounding Device


Power Rectifier Misfire Relay

Overvoltage Relay

Voltage Balance Relay


Current Balance Relay
185
Time delay Stopping or Opening Relay

Liquid or Gas Pressure, Level, or Flow Relay

Ground Protection Relay

Governor

Notching or Jogging Device

A-C Directional Overcurrent Relay

Blocking Relay

Permissive Control Device


Electrically Operated Rheostat

Reserved for future application

D-C Circuit Breaker

Load Resistor Contactor

Alarm Relay

Position Changing Mechanism

D-C Overcurrent Relay

Pulse Transmitter

Phase Angle Measuring

A-C Reclosing Relay

Reserved for future application

Frequency Relay

D-C Reclosing Relay

Automatic Selective Control or Transfer Relay

Operating Mechanism

Carrier or pilot wire Receiver Relay

Locking out Relay


Differential Protective Relay

Auxiliary Motor or Motor Generator

Line Switch

Regulating Device

Voltage Directional Relay

Voltage and Power Directional Relay

Field Changing Contactor

Tripping or Trip Free Relay

You might also like