DESIGN OF SLAB

DESIGN PARAMETER

LS (m) = 5.00 Ultimate Load Stress:


Lb (m) = 5.00 wU (kPa) = 1.4wDL + 1.7wLL
m= 1.000 wU (kPa) = 18.048
Min. t (mm) = 111.111 Considering 1.00m strip:
Say t (mm) = 150 wU (kN/m) = 18.048
overing (mm) = 20
Bar φ(mm)= 12 fc' (MPa) = 20.70
fy (MPa) = 276.00
Dead Load: ø = 0.900
wslab (kPa) = 3.532 ρmin = 0.0051
wother (kPa) = 3.532 ρmax = 0.0278
wDL (kPa) = 7.063
Live Load:
wLL (kPa) = 4.800

Negative Moments at Continuous Edge: Positive Dead Load Moments


MS (kN-m) = CSwULS2 MSDL (kN-m) =
MuS (kN-m) = 22.561 MSDL (kN-m) =
MSLL (kN-m) =
Mb (kN-m) = CbwULb2 MSLL (kN-m) =
Mub (kN-m) = 22.561 MuST (kN-m) =

Negative Moments at Discontinuous Edg Positive Live Load Moments


MuS (kN-m) = 1 MbDL (kN-m) =
( M S )
MuS (kN-m) = 3.955
3 MbDL (kN-m) =
MbLL (kN-m) =
Mub (kN-m) = 1 MbLL (kN-m) =
( M b )
3
Mub (kN-m) = 3.955 MubT (kN-m) =

MIDDLE STRIP

Along Short Span @ Midspan: Along Short Span @ Continuous E


MU = MU =
f C ' bd
MU (kN-m) = 11.865
2
w(1  0.59 w) f C ' bd
MU (kN-m) = 22.561
2
w(1  0.59 w)
w = 0.042 w = 0.083

wf C ' wf C '
 
fy
ρ = 0.0032 Use pmin. fy
ρ = 0.0062
AS (mm )= ρbd
2
AS (mm2)= ρbd
AS (mm2)= 628.986 AS (mm2)= 770.070

Use ø (mm) = 12 Use ø (mm) = 12


S (mm) = 179.809 S (mm) = 146.866
Say S (mm) = 175 Say S (mm) = 125

Along Short Span @ Discontinuous Edge:


S (mm) = 3*(Midspan Spacing)
S (mm) = 450
MIDDLE STRIP

Along Long Span @ Midspan: Along Long Span @ Continuous Ed


MU = MU =
f C ' bd 2 w(1  0.59 w)
MU (kN-m) = 11.865 f C ' bd 2 w(1  0.59 w)
MU (kN-m) = 22.561
w = 0.052 w = 0.103

wf C ' wf '
    C
fy
ρ = 0.0039 Use pmin. ρ = 0.0077f y

AS (mm2)= ρbd AS (mm )= ρbd


2

AS (mm )= 568.116
2
AS (mm2)= 863.269

Use ø (mm) = 12 Use ø (mm) = 12


S (mm) = 199.074 S (mm) = 131.010
Say S (mm) = 175 Say S (mm) = 125

Along Long Span @ Discontinuous Edge:


S (mm) = 3*(Midspan Spacing)
S (mm) = 450

COLUMN STRIP

Along Short Span @ Midspan: Along Short Span @ Continuous E


S (mm) = S (mm) =
3 3
* (Spacing of Middle Strip) * (Spacing of Middle S
2
S (mm) = 262.500 2
S (mm) = 187.500
Say S (mm) = 250 Say S (mm) = 175

Along Short Span @ Discontinuous Edge:


S (mm) =
3
* (Spacing of Middle Strip)
2
S (mm) = 675.000
Say S (mm) = 450

Along Long Span @ Midspan: Along Long Span @ Continuous Ed


S (mm) = 3 S (mm) =
3
* (Spacing of Middle Strip) * (Spacing of Middle S
2 2
S (mm) = 262.500 S (mm) = 187.500
Say S (mm) = 250 Say S (mm) = 175
Along Long Span @ Discontinuous Edge:
S (mm) =
3
* (Spacing of Middle Strip)
2
S (mm) = 675.000
Say S (mm) = 450

TEMPERATURE BARS:

AS (mm) = 0.002bt Use ø (mm) = 10.000 Say S (mm) =


AS (mm) = 300.000 S (mm) = 261.799
SLAB 1 DETAIL : S-1
CASE: 4

12 mm φ bar @
450 mm spacing

12 mm φ bar @
175 mm spacing

5m

5.00

5m

12 mm φ bar @
175 mm spacing

12 mm φ bar @
175 mm spacing

12 mm φ bar @
125 mm spacing
DESIGN OF SLAB S-1

DESIGN PARAMETER

Case No. 4
Negative Moment Coefficients:
CS = 0.0500
Cb = 0.0500
Positive DL Moment Coefficients:
CS = 0.0270
Cb = 0.0270
Positive LL Moment Coefficients:
CS = 0.0320
Cb = 0.0320

Positive Dead Load Moments at Midspan:


CSwDLLS2
5.721
CSwLLLS2
6.144
11.865

Positive Live Load Moments at Midspan:


CbwDLLb2
5.721
CbwLLLb2
6.144
11.865

MIDDLE STRIP

Along Short Span @ Continuous Edge:

f C ' bd 2 w(1  0.59 w)

Use pmin.
MIDDLE STRIP

Along Long Span @ Continuous Edge:

f C ' bd 2 w(1  0.59w)

Use pmin.

COLUMN STRIP

Along Short Span @ Continuous Edge:

3
* (Spacing of Middle Strip)
2

Along Long Span @ Continuous Edge:

3
* (Spacing of Middle Strip)
2
TEMPERATURE BARS:

250
12mm φ bar spaced 450 mm O.C.

12mm φ bar spaced 250 mm O.C.

12mm φ bar spaced 450 mm O.C.

12mm φ bar spaced 450 mm O.C.

12mm φ bar spaced 175 mm O.C.

12mm φ bar spaced 175 mm O.C.

12mm φ bar spaced 450 mm O.C.

12mm φ bar spaced 250 mm O.C.

12mm φ bar spaced 250 mm O.C.

12mm φ bar spaced 450 mm O.C.

12mm φ bar spaced 175 mm O.C.

12mm φ bar spaced 250 mm O.C.


12mm φ bar spaced 125 mm O.C.