Professional Documents
Culture Documents
Understanding - Harmonics - ممتاز PDF
Understanding - Harmonics - ممتاز PDF
Understanding - Harmonics - ممتاز PDF
-1-
Grady/Santoso, September 1, 2001
especially, rms current. Table 1 shows the current distortion is due to the arc and to the ballast.
theoretical maximum true power factor of a Typically distortions are dominated by the third
distorting load as a function of current THD. The harmonic with a magnitude in the range of 15% to
table assumes the optimum case, i.e., the 30% of the fundamental. Figure 1a shows the
displacement power factor is 1.0. harmonic current of a fluorescent lamp with a
standard magnetic ballast.
Table 1 – Maximum true power factor of a nonlinear Power electronic loads draw power only during
load. portions of the applied voltage waveform. These
Current Maximum loads include switch-mode power supplies,
THD true pf fluorescent lights (with electronic ballasts), voltage
20% 0.98 source converters, pulse-width modulated
50% 0.89 converters, to mention just a few. Figure 1b shows
100% 0.71 the line current of a fluorescent lamp with an
electronic ballast that employs a switch-mode power
When a three-phase power system is balanced, supply. Desktop computers, video monitors, and
harmonics fall into the phase sequence pattern televisions have similar waveforms. The current
shown in Table 2. THD is approximately 100%.
0.3
Table 2 – Harmonic phase sequence in a balanced
three-phase power system. 0.2
0.1
Phase Current (A) 0.0
Harmonic Sequence -0.1
1 +
-0.2
2 –
-0.3
3 0 0 10 20 30 40
(a) Time (ms)
4 + 0.4
5 –
6 0 0.2
Current (A)
… …
0.0
-2-
Grady/Santoso, September 1, 2001
80
Current (A)
60
40
20 Harmonic
0
(a) Source
0 200 400 600 800 1000 1200 1400 1600 1800 2000
(b) Frequency (Hz)
-3-
Grady/Santoso, September 1, 2001
because of the inverse relationship between shared neutral wire to have at least twice the current
capacitor impedance and frequency. Voltage rating of each phase wire.
distortions of 5% and 10% can easily increase rms Overloaded neutral currents are usually only a
currents by 10% to 50%. Capacitors may also fail local problem inside a building, for example at a
because of overvoltage stress on dielectrics. A 10% service panel. At the building service entrance, the
harmonic voltage for any harmonic above the 3rd harmonic currents produced by PCs, ASDs, and
increases the peak voltage by approximately 10% other nonlinear loads are not totally additive because
because the peak of the harmonic usually coincides, of phase angle diversity in their phasor currents.
or nearly coincides, with the peak of the Research has shown this diversity to be inversely
fundamental voltage. proportional to frequency, so that the 3rd harmonic
Harmonics can also cause transformer currents are almost totally additive, but harmonic
overheating. This usually occurs when a dedicated currents above the 15th add to only about 0.20 of
transformer serves only one large nonlinear load. In their individual magnitude sums.
such a situation, the transformer must be derated In addition to phase angle diversity, harmonic
accordingly. Derating to 0.80 of nameplate kVA is currents are diluted by the addition of many linear
common. loads in the building, including air conditioners,
Overloaded neutrals appear to be the most pumps, fans, and incandescent lights. Thus, the net
common problems in commercial buildings. In a current distortion of a large building is usually less
three-phase, four-wire system, the sum of the three than 10-15%.
phase currents returns through the neutral conductor.
Positive and negative sequence components add to Control of Harmonics
zero at the neutral point, but zero sequence Based on the above discussion, the two
components are additive at the neutral. common causes of harmonic problems are
Power system engineers are accustomed to the
traditional rule that “balanced three-phase systems • Nonlinear loads injecting excessive harmonic
have no neutral currents.” However, this rule is not currents,
true when power electronic loads are present. Their • The interaction between harmonic currents and
zero sequence harmonics (i.e., primarily the 3rd the system frequency response.
harmonic and “triplens”) sum in the neutral wire and
can overload the neutral conductor. Figure 4 When harmonics become a problem, commonly-
illustrates this problem. employed solutions are
-4-
Grady/Santoso, September 1, 2001
Harmonic controls can be exercised at the utility [2] J. Arrillaga, D. A. Bradley, P. S. Bodger, Power
and end-user sides. IEEE 519 attempts to establish System Harmonics, John Wiley & Sons, New York,
reasonable harmonic goals for electrical systems that 1985.
contain nonlinear loads. The objective is to propose [3] R. C Dugan, M. F McGranaghan, H. W. Beaty,
steady-state harmonic limits that are considered Electrical Power Systems Quality,McGraw Hill
reasonable by both electric utilities and their Inc., New York, 1996.
customers. The underlying philosophy is that [4] G. T. Heydt, Electric Power Quality, Stars in a
Circle Publications, Scottsdale, AZ, 1995.
• customers should limit harmonic currents, since [5] IEEE 519-1992, Recommended Practices and
they have control over their loads, Requirements for Harmonic Control in Electric
• electric utilities should limit harmonic voltages Power Systems.
since they have control over the system
impedances, and
• both parties share the responsibility for holding
harmonic levels in check.
Conclusions
Harmonic distortion is not a new phenomenon.
Concern over harmonic distortion emerged during
the early history of ac power systems. Widespread
applications of power electronic-based loads
continue to increase concerns over harmonic
distortion. Harmonic problems have sparked
research that has led to much of the present-day
understanding of power quality problems.
Bibliography
[1] C. P Steinmetz, Theory and Calculation of
Alternating Current Phenomena, McGraw-Hill, Inc.,
New York, 1916.
-5-