Electrical, N/W & Workspace requirements for HP Indigo Press 5000/ 5500/5600.

MCCB (DH 100 L&T OR SIEMENS) 2 Nos (For Raw I/P & UPS O/P)
Make : L&T
Rating : 100A Icu : 25 KA
Inst : 567A Ics : 100 % Icu
Ref : Temp.40C IEC 60947-2
IS13947-2
Ue : 415 V
Ui : 690 V
Freq : 50/60 Hz

MCB For Chiller


32-40A / 4 Pole
3 Phase 240/415 VAC 50 Hz

MCB FOR PRESS


63A/5 POLE, 3PHASE 230/400VAC 50HZ

# Power consumption
Press-16KW
Chiller-12KW

# Use 16-18 sq/mm(R,Y,B,BLACK & GREEN) power cable from mains to UPS input.
Use 10-12 sq/mm (R,Y,B,BLACK & GREEN) flexible power cable from UPS output to Press input MCCB.
Use 8-10 sq/mm (R,Y,B & GREEN) flexible power cable for chiller

# 5 pin female industrial socket for Indigo Press. (Havells / Legrand)

# Make separate earth pit for Indigo Press (0.890- 3Volts), total 4 no. earth pit required

# Press & consumable requires an area of 15 x 20 feet with 9 feet clear height for smooth operation.

# Required ambient relative humidity in the press room, 50-70 % non-condensing.

# Chiller space (5 x 5 feet), enough fresh air sources, enclosed cabin, roof top height min.10 ft fresh air inlet for
condenser unit & duct is must for in-house installation.

For outdoor installation: (Space 5x5 Feet), Proper rooftop to protect chiller from rain & sunlight. Min height of
the roof above the chiller unit is 4 to 5 feet.

# 3 Phase neon indicator

# 100 liter Distilled water for Chiller.(DM water)

# 40KVA online UPS (250-300 Amp IGBT Capacity) with Isolation transformer.
Use 5/15 Amp plugs for all the power points with proper earth cable . All the batteries should have same batch and
manufacturing month / yr.
Net working

1 Use CAT6 cable for network with 1Gbps network switch with internet ready connection.
2 Flooring ( Industrial Kota / Industrial Tiles)
3 AC 2 nos , 2 Tons each(To maintain the room temp. 20-22 degrees)
4 Exhaust Fan in the press room ( To operate when required)
5 2 ft x 5 ft working table & cupboard to store spares, press software cd’s.
6 Non condensing compressed air must be (6-8 bar) with drier unit.(Compressor- 1cfm,25ltr,6 bar)