Download as pdf or txt
Download as pdf or txt
You are on page 1of 38

Release Date: Oct 2006 / Manual Revision: 4.

00

IEC60870-5-104 PROTOCOL
Technical Manual

ENTEC ENTEC
ELECTRIC & ELECTRONIC CO., LTD

Copyright © 2006 by ENTEC ELECTRIC & ELECTRONIC CO., LTD all right reserved. Forerunner Distribution & Automation
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr

TABLE OF CONTENTS

A. Introduction ………………………..…………………………………………………………...4

B. Configuration for IEC 60870-5-104 …......…………………………………………………….5

C. Interoperability Document …...........…...…………………………………………………….6

D. IEC 60870-5-104 Point Table ..………………………………………………...……………..18

ENHANCED TECHNOLOGY 3
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr

A. Introduction

The communication protocol IEC 60870-5 is designed by Internatioal Electrotechnical Commission


(IEC) Technical Committee 57.

This document is based on IEC60870-5-104. Based on IEC 60870-5-104, this document describes
Communication method between EVRC2A and Master Station, and provides IEC60870-5-104
Interoperability Document and IEC60870-5-104 Point table and parameter explanations.

IEC 60870-5-104 applies to telecontrol equipment and systems with coded bit serial data
transmission for monitoring and controlling geographically widespread processes. This standard
defines the use of an open TCP/IP-interface to a network, containing for example a LAN for
telecontrol equipment.

4 ENHANCED TECHNOLOGY
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr

B. Configuration for IEC 60870-5-104

Title Description Range Default

IP Addr’ 1 IP address 1 0~255 0

IP Addr’ 2 IP address 2 0~255 0

IP Addr’ 3 IP address 3 0~255 0

IP Addr’ 4 IP address 4 0~255 0

Gateway Addr’ 1 Gateway address 1 0~255 0

Gateway Addr’ 2 Gateway address 2 0~255 0

Gateway Addr’ 3 Gateway address 3 0~255 0

Gateway Addr’ 4 Gateway address 4 0~255 0

255.000.000.000~
Subnet Mask Subnet mask 255.255.255.000
255.255.255.252

Tcp Port No Tcp port number 1~65535 2404

ASDU Addr’ Application service data unit address 0 ~ 65535 0

Cyclic Period Cyclic period 1~60000 sec 15

ENHANCED TECHNOLOGY 5
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr

C. Interoperability Document

This document is adapted from the IEC 60870-5-104 standard. For the section the boxes indicate
the following: ▣ – used in standard direction; □ – not used; ■ – cannot be selected in IEC 60870-
5-104 standard.

C.1 SYSTEM OR DEVICE:


□ System Definition

□ Controlling Station Definition (Master)

▣ Controlled Station Definition (Slave)

C.2 NETWORK CONFIGURATION:


■ Point-to-Point ■ Multipoint

■ Multiple Point-to-Point ■ Multipoint Star

C.3 PHYSICAL LAYER


Transmission Speed (control direction):

Unbalanced Interchange Unbalanced Interchange Balanced Interchange circuit

Circuit V.24/V.28 Standard: Circuit V.24/V.28 Recommended X.24/X.27:

if>1200 bits/s:

■ 100bits/sec. ■ 2400bits/sec. ■ 2400bits/sec.

■ 200bits/sec. ■ 4800bits/sec. ■ 4800bits/sec.

■ 300bits/sec. ■ 9600bits/sec. ■ 9600bits/sec.

■ 600bits/sec. ■ 19200bits/sec.

■ 1200bits/sec. ■ 38400bits/sec.

■ 56000bits/sec.

■ 64000bits/sec.

6 ENHANCED TECHNOLOGY
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr

Transmission Speed (monitor direction):

Unbalanced Interchange Unbalanced Interchange Balanced Interchange circuit

Circuit V.24/V.28 Standard: Circuit V.24/V.28 Recommended X.24/X.27:

if>1200 bits/s:

■ 100bits/sec. ■ 2400bits/sec. ■ 2400bits/sec.

■ 200bits/sec. ■ 4800bits/sec. ■ 4800bits/sec.

■ 300bits/sec. ■ 9600bits/sec. ■ 9600bits/sec.

■ 600bits/sec. ■ 19200bits/sec.

■ 1200bits/sec. ■ 38400bits/sec.

■ 56000bits/sec.

■ 64000bits/sec.

C.4 LINK LAYER


Link Transmission Procedure: Address Field of the Link:

■ Balanced Transmision ■ Not Present (Balanced Transmission Only)

■ Unbalanced Transmission ■ One Octet

■ Two Octets

■ Structured

■ Unstructured

Frame Length (maximum length, number of octets): Not selectable in companion IEC 60870-5-104 standard

When using an unbalanced link layer, the following ADSU types are returned in class 2 messages (low

priority) with the indicated causes of transmission:

■ The standard assignment of ADSUs to class 2 messages is used as follows:


■ A special assignment of ADSUs to class 2 messages is used as follows:

C.5 APPLICATION LAYER


Transmission Mode for Application Data:
Mode 1 (least significant octet first), as defined in Clause 4.10 of IEC 60870-5-4, is used exclusively in

this companion stanadard.

Common Address of ADSU:

ENHANCED TECHNOLOGY 7
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr

■ One Octet

▣ Two Octets

Information Object Address:


■ One Octet □ Structured

■ Two Octets □ Unstructured

▣ Three Octets

Cause of Transmission:
■ One Octet

▣ Two Octets (with originator address). Originator address is set to zero if not used.

Maximum Length of APDU: 253 (the maximum length may be reduced by the system.

Selection of standard ASDUs:


For the following lists, the boxes indicate the following: ▣– used in standard direction; □ – not used; ■ –

cannot be selected in IEC 60870-5-104 standard.

Process information in monitor direction


▣ <1> := Single-point information M_SP_NA_1

■ <2> := Single-point information with time tag M_SP_TA_1

□ <3> := Double-point information M_DP_NA_1

■ <4> := Double-point information with time tag M_DP_TA_1

□ <5> := Step position information M_ST_NA_1

■ <6> := Step position information with time tag M_ST_TA_1

□ <7> := Bitstring of 32 bits M_BO_NA_1

■ <8> := Bitstring of 32 bits with time tag M_BO_TA_1

▣ <9> := Measured value, normalized value M_ME_NA_1

■ <10> := Measured value, normalized value with time tag M_NE_TA_1

□ <11> := Measured value, scaled value M_ME_NB_1

■ <12> := Measured value, scaled value with time tag M_NE_TB_1

□ <13> := Measured value, short floating point value M_ME_NC_1

■ <14> := Measured value, short floating point value with time tag M_NE_TC_1

▣ <15> := Integrated totals M_IT_NA_1

■ <16> := Integrated totals with time tag M_IT_TA_1

■ <17> := Event of protection equipment with time tag M_EP_TA_1

■ <18> := Packed start events of protection equipment with time tag M_EP_TB_1

■ <19> := Packed output circuit information of protection equipment with time tag M_EP_TC_1

8 ENHANCED TECHNOLOGY
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr

■ <20> := Packed single-point information with status change detection M_SP_NA_1

▣ <21> := Measured value, normalized value without quantity descriptor M_ME_ND_1

▣ <30> := Single-point information with time tag CP56Time2a M_SP_TB_1

□ <31> := Double-point information wiht time tag CP56Time2a M_DP_TB_1

□ <32> := Step position information with time tag CP56Time2a M_ST_TB_1

□ <33> := Bitstring of 32 bits with time tag CP56Time2a M_BO_TB_1

□ <34> := Measured value, normalized value with time tag CP56Time2a M_ME_TD_1

□ <35> := Measured value, scaled value with time tag CP56Time2a M_ME_TE_1

□ <36> := Measured value, short floating point value with time tag CP56Time2a M_ME_TF_1

□ <37> := Integrated totals with time tag CP56Time2a M_IT_TB_1

□ <38> := Event of protection equipment with time tag CP56Time2a M_EP_TD_1

□ <39> := Packed start events of protection equipment with time tag CP56Time2a M_EP_TE_1

□ <40> := Packed output circuit information of protection equipment

with time tag CP56Time2a M_EP_TF_1

Either the ASDUs of the set <2>, <4>, <6>, <8>, <10>, <12>, <14>, <16>, <17>, <18>, and <19> or of the

set <30> to <40> are used.

Process information in control direction


▣ <45> := Single command C_SC_NA_1

□ <46> := Double command C_DC_NA_1

□ <47> := Regulating step command C_RC_NA_1

▣ <48> := Set point command, normalized value C_SE_NA_1

□ <49> := Set point command, scaled value C_SE_NB_1


□ <50> := Set point command, short floating point value C_SE_NC_1

□ <51> := Bitstring of 32 bits C_BO_NA_1

▣ <58> := Single command with time tag CP56Time2a C_SC_TA_1

□ <59> := Double command with time tag CP56Time2a C_DC_TA_1

□ <60> := Regulating step command with time tag CP56Time2a C_RC_TA_1

▣ <61> := Set point command, normalized value with time tag CP56Time2a C_SE_TA_1

□ <62> := Set point command, scaled value with time tag CP56Time2a C_SE_TB_1

□ <63> := Set point command, short floating point value with time tag CP56Time2a C_SE_TC_1

□ <64> := Bitstring of 32 bits with time tag CP56Time2a C_BO_TA_1

Either the ASDUs of the set <45> to <51> or of the set <58> to <64> are used.

System information in monitor direction

ENHANCED TECHNOLOGY 9
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr

▣ <70> := End of initialization M_EI_NA_1

System information in control direction


▣ <100> := Interrogation command C_IC_NA_1

▣ <101> := Counter interrogation command C_CI_NA_1

▣ <102> := Read command C_RD_NA_1

▣ <103> := Clock synchronization command (see Clause 7.6 in standard) C_CS_NA_1

■<104> := Test command C_TS_NA_1

▣<105> := Reset process command C_RP_NA_1

■<106> := Delay acquisition command C_CD_NA_1

▣<107> := Test command with time tag CP56Time2a C_TS_TA_1

Parameter in control direction


▣ <110> := Parameter of measured value, normalized value PE_ME_NA_1

□ <111> := Parameter of measured value, scaled value PE_ME_NB_1

□ <112> := Parameter of measured value, short floating point value PE_ME_NC_1

□ <113> := Parameter activation PE_AC_NA_1

File transfer
□ <120> := File Ready F_FR_NA_1

□ <121> := Section Ready F_SR_NA_1

□ <122> := Call directory, select file, call file, call section F_SC_NA_1
□ <123> := Last section, last segment F_LS_NA_1

□ <124> := Ack file, ack section F_AF_NA_1

□ <125> := Segment F_SG_NA_1

□ <126> := Directory (blank or X, available only in monitor [standard] direction) C_CD_NA_1

Type identifier and cause of transmission assignments


(station-specific parameters)

In the following table:

• Shaded boxes are not required.

• Black boxes are not permitted in this companion standard.

• Blank boxes indicate functions or ASDU not used.

•‘X’ if only used in the standard direction

10 ENHANCED TECHNOLOGY
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr

TYPE DENTIFICATION CAUSE OF TRANSMISSION

PERIODIC, CYCLIC

BACKGROUND SCAN

SPONTANEOUS

INITIALIZED

REQUEST OR REQUESTED

ACTIVATION

ACTIVATION CONFIRMATION

DEACTIVATION

DEACTIVATION CONFIRMATION

ACTIVATION TERMINATION

RETURN INFO CAUSED BY LOCAL CMD

FILE TRANSFER

INTERROGATED BY GROUP <NUMBER>

REQUEST BY GROUP <N> COUNTER REQ

UNKNOWN TYPE IDENTIFICATION

UNKNOWN CAUSE OF TRANSMISSION

UNKNOWN COMMON ADDRESS OF ADSU

UNKNOWN INFORMATION OBJECT ADDR

UNKNOWN INFORMATION OBJECT ADDR


20 37
NO. MNEMONIC 1 2 3 4 5 6 7 8 9 10 11 12 13 to to 44 45 46 47
36 41

<1> M_SP_NA_1 X X X X

<2> M_SP_TA_1

<3> M_DP_NA_1

<4> M_DP_TA_1

<5> M_ST_NA_1

<6> M_ST_TA_1

<7> M_BO_NA_1

<8> M_BO_TA_1

<9> M_ME_NA_1 X X X X

<10> M_ME_TA_1

<11> M_ME_NB_1

<12> M_ME_TB_1

<13> M_ME_NC_1

<14> M_ME_TC_1

<15> M_IT_NA_1 X X

<16> M_IT_TA_1

<17> M_EP_TA_1

<18> M_EP_TB_1

<19> M_EP_TC_1

<20> M_PS_NA_1

<21> M_ME_ND_1 X X

<30> M_SP_TB_1 X X X

<31> M_DP_TB_1

ENHANCED TECHNOLOGY 11
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr

TYPE DENTIFICATION CAUSE OF TRANSMISSION

PERIODIC, CYCLIC

BACKGROUND SCAN

SPONTANEOUS

INITIALIZED

REQUEST OR REQUESTED

ACTIVATION

ACTIVATION CONFIRMATION

DEACTIVATION

DEACTIVATION CONFIRMATION

ACTIVATION TERMINATION

RETURN INFO CAUSED BY LOCAL CMD

FILE TRANSFER

INTERROGATED BY GROUP <NUMBER>

REQUEST BY GROUP <N> COUNTER REQ

UNKNOWN TYPE IDENTIFICATION

UNKNOWN CAUSE OF TRANSMISSION

UNKNOWN COMMON ADDRESS OF ADSU

UNKNOWN INFORMATION OBJECT ADDR

UNKNOWN INFORMATION OBJECT ADDR


20 37
NO. MNEMONIC 1 2 3 4 5 6 7 8 9 10 11 12 13 to to 44 45 46 47
36 41

<32> M_ST_TB_1

<33> M_BO_TB_1

<34> M_ME_TD_1

<35> M_ME_TE_1

<36> M_ME_TF_1

<37> M_IT_TB_1

<38> M_EP_TD_1

<39> M_EP_TE_1

<40> M_EP_TF_1

<45> C_SC_NA_1 X X X X X

<46> C_DC_NA_1

<47> C_RC_NA_1

<48> C_SE_NA_1 X X X X X

<49> C_SE_NB_1

<50> C_SE_NC_1

<51> C_BO_NA_1

<58> C_SC_TA_1 X X X X X

<59> C_DC_TA_1

<60> C_RC_TA_1

<61> C_SE_TA_1 X X X X X

<62> C_SE_TB_1

<63> C_SE_TC_1

<64> C_BO_TA_1

12 ENHANCED TECHNOLOGY
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr

TYPE DENTIFICATION CAUSE OF TRANSMISSION

PERIODIC, CYCLIC

BACKGROUND SCAN

SPONTANEOUS

INITIALIZED

REQUEST OR REQUESTED

ACTIVATION

ACTIVATION CONFIRMATION

DEACTIVATION

DEACTIVATION CONFIRMATION

ACTIVATION TERMINATION

RETURN INFO CAUSED BY LOCAL CMD

FILE TRANSFER

INTERROGATED BY GROUP <NUMBER>

REQUEST BY GROUP <N> COUNTER REQ

UNKNOWN TYPE IDENTIFICATION

UNKNOWN CAUSE OF TRANSMISSION

UNKNOWN COMMON ADDRESS OF ADSU

UNKNOWN INFORMATION OBJECT ADDR

UNKNOWN INFORMATION OBJECT ADDR


20 37
NO. MNEMONIC 1 2 3 4 5 6 7 8 9 10 11 12 13 to to 44 45 46 47
36 41

<70> M_EI_NA_1* X

<100> C_IC_NA_1 X X X X X

<101> C_CI_NA_1 X X X

<102> C_RD_NA_1 X

<103> C_CS_NA_1 X X X

<104> C_TS_NA_1

<105> C_RP_NA_1 X X

<106> C_CD_NA_1

<107> C_TS_TA_1

<110> P_ME_NA_1 X X X

<111> P_ME_NB_1

<112> P_ME_NC_1

<113> P_AC_NA_1

<120> F_FR_NA_1

<121> F_SR_NA_1

<122> F_SC_NA_1

<123> F_LS_NA_1

<124> F_AF_NA_1

<125> F_SG_NA_1

<126> F_DR_TA_1*

* Blank or X only

ENHANCED TECHNOLOGY 13
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr

C.6 BASIC APPLICATION


FUNCTIONS Station Initialization:
▣ Remote initialization

Cyclic Data Transmission:


▣ Cyclic data transmission

Read Procedure:
▣ Read procedure

Spontaneous Transmission:
▣ Spontaneous transmission

Double transmission of information objects with cause of transmission


spontaneous:
The following type identifications may be transmitted in succession caused by a single status change of

an information object. The particular information object addresses for which double transmission is

enabled are defined in a project-specific list.

□ Single point information: M_SP_NA_1, M_SP_TA_1, M_SP_TB_1, and M_PS_NA_1

□ Double point information: M_DP_NA_1, M_DP_TA_1, and M_DP_TB_1

□ Step position information: M_ST_NA_1, M_ST_TA_1, and M_ST_TB_1

□ Bitstring of 32 bits: M_BO_NA_1, M_BO_TA_1, and M_BO_TB_1 (if defined for a specific project)

□ Measured value, normalized value: M_ME_NA_1, M_ME_TA_1, M_ME_ND_1, and M_ME_TD_1

□ Measured value, scaled value: M_ME_NB_1, M_ME_TB_1, and M_ME_TE_1

□ Measured value, short floating point number: M_ME_NC_1, M_ME_TC_1, and M_ME_TF_1

Station interrogation:
▣ Global

▣ Group 1 ▣ Group 5 ▣ Group 9 ▣ Group 13

▣ Group 2 ▣ Group 6 ▣ Group 10 ▣ Group 14

▣ Group 3 ▣ Group 7 ▣ Group 11 ▣ Group 15

▣ Group 4 ▣ Group 8 ▣ Group 12 ▣ Group 16

14 ENHANCED TECHNOLOGY
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr

Clock synchronization:
▣ Clock synchronization (optional, see Clause 7.6)

Command transmission:
▣ Direct command transmission

▣ Direct set point command transmission

▣ Select and execute command

▣ Select and execute set point command

▣ C_SE ACTTERM used

□ No additional definition

▣ Short pulse duration (duration determined by a system parameter in the outstation)

▣ Long pulse duration (duration determined by a system parameter in the outstation)

□ Persistent output

▣Supervision of maximum delay in command direction of commands and set point commands

Maximum allowable delay of commands and set point commands: 10 s

Transmission of integrated totals:


□ Mode A: Local freeze with spontaneous transmission

▣ Mode B: Local freeze with counter interrogation

▣ Mode C: Freeze and transmit by counter-interrogation commands

□ Mode D: Freeze by counter-interrogation command, frozen values reported simultaneously

▣ Counter read

▣ Counter freeze without reset

□ Counter freeze with reset

□ Counter reset

▣ General request counter

□ Request counter group 1

□ Request counter group 2

□ Request counter group 3

□ Request counter group 4

Parameter loading:
▣ Threshold value

□ Smoothing factor

▣ Low limit for transmission of measured values

▣ High limit for transmission of measured values

ENHANCED TECHNOLOGY 15
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr

Parameter activation:
□ Activation/deactivation of persistent cyclic or periodic transmission of the addressed object

Test procedure:
□ Test procedure

File transfer:
File transfer in monitor direction:

□ Transparent file
□ Transmission of disturbance data of protection equipment

□ Transmission of sequences of events

□ Transmission of sequences of recorded analog values

File transfer in control direction:

□ Transparent file

Background scan:
□ Background scan

Acquisition of transmission delay:


■ Acquisition of transmission delay

Definition of time outs:

PARAMETER DEFAULT REMARKS SELECTED

VALUE VALUE

t0 30 s Timeout of connection establishment 120 s

t1 15 s Timeout of send or test APDUs 15 s

t2 10 s Timeout for acknowledgements in case of no data messages t2 < t1 10 s

t3 20 s Timeout for sending test frames in case of a long idle state 20 s

Maximum range of values for all time outs: 1 to 255 s, accuracy 1 s

16 ENHANCED TECHNOLOGY
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr

Maximum number of outstanding I-format APDUs k and latest acknowledge


APDUs (w):

PARAMETER DEFAULT REMARKS SELECTED

VALUE VALUE

k 12 APDUs Maximum difference receive sequence number to send state variable 12 APDUs

w 8 APDUs Latest acknowledge after receiving w I-format APDUs 8 APDUs

Maximum range of values k: 1 to 32767 (215 – 1) APDUs, accuracy 1 APDU

Maximum range of values w: 1 to 32767 APDUs, accuracy 1 APDU

Recommendation: w should not exceed two-thirds of k.

Portnumber:

PARAMETER VALUE REMARKS

Portnumber 2404 In all cases

RFC 2200 suite:


RFC 2200 is an official Internet Standard which describes the state of standardization of protocols used in

the Internet as determined by the Internet Architecture Board (IAB). It offers a broad spectrum of actual

standards used in the Internet. The suitable selection of documents from RFC 2200 defined in this

standard for given projects has to be chosen by the user of this standard.

▣ Ethernet 802.3

□ Serial X.21 interface

□ Other selection(s) from RFC 2200 (list below if selected)

ENHANCED TECHNOLOGY 17
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr

D. IEC 60870-5-104 Point Table

Table D-1. IEC60870-5-104 INDEX – Single-point information(1/5)

Single-point information

S: Spontaneous , G: General Group, C: cyclic


Object
Description Point Property Group
Address Notes
S G C No.

1000 External AC Power ٧ ٧ 8

1001 Battery Charger ٧ ٧ 8

1002 Battery Discharge ٧ ٧ 8 Value<DC21V

1003 INST Target ٧ ٧ 5

1004 Delay Target ٧ ٧ 5

1005 High Current Target ٧ ٧ 5

1006 A Phase Target ٧ ٧ 5

1007 B Phase Target ٧ ٧ 5

1008 C Phase Target ٧ ٧ 5

1009 Ground Target ٧ ٧ 5

1010 SEF Target ٧ ٧ 5

1011 27 Target ٧ ٧ 5

1012 59 Target ٧ ٧ 5

1013 25 Target ٧ ٧ 5

1014 81 Target ٧ ٧ 5

1015 Self Check ٧ ٧ 9

1016 Protection Enabled ٧ ٧ 1

1017 Ground Enabled ٧ ٧ 1

1018 SEF Enabled ٧ ٧ 1

1019 Reclose Enabled ٧ ٧ 1

1020 Control Locked ٧ ٧ 1

1021 Remote Enabled ٧ ٧ 1

1022 Alternate Setting Enabled ٧ ٧ 1

1023 Program 1 Enabled ٧ ٧ 1

1024 Program 2 Enabled ٧ ٧ 1

1025 Hot Line Tag Enabled ٧ ٧ 1

18 ENHANCED TECHNOLOGY
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr

Table D-1. IEC60870-5-104 INDEX - Single-point information (2/5)


Object Point Property Group
Description Notes
Address S G C No.

1026 Panel CLOSE key Press ٧ ٧ 1

1027 Panel OPEN key Press ٧ ٧ 1

1028 Panel TARGET RESET key Press ٧ ٧ 1

1029 Panel BATTERY TEST key Press ٧ ٧ 1

1030 79 RESET ٧ ٧ 4

1031 79 CYCLE ٧ ٧ 4

1032 79 LOCKOUT ٧ ٧ 4

1033 Reclosing Shot 0 ٧ ٧ 4

1034 Reclosing Shot 1 ٧ ٧ 4

1035 Reclosing Shot 2 ٧ ٧ 4

1036 Reclosing Shot 3 ٧ ٧ 4

1037 Reclosing Shot 4 ٧ ٧ 4

1038 Contact(52a) ٧ ٧ 2

1039 Mechanism Lock ٧ ٧ 2

1040 Opto Input 1 Closed ٧ ٧ 7

1041 Opto Input 2 Closed ٧ ٧ 7

1042 Opto Input 3 Closed ٧ ٧ 7

1043 Opto Input 4 Closed ٧ ٧ 7

1044 Opto Input 5 Closed ٧ ٧ 7

1045 Opto Input 6 Closed ٧ ٧ 7

1046 Opto Input 7 Closed ٧ ٧ 7

1047 Opto Input 8 Closed ٧ ٧ 7

1048 Phase Fast Time Overcurrent(51P1) ٧ ٧ 3

1049 Phase Delay Time Overcurrent(51P2) ٧ ٧ 3

1050 Ground Fast Time Overcurrent (51G1) ٧ ٧ 3

1051 Ground Delay Time Overcurrent (51G2) ٧ ٧ 3

1052 Door Open status ٧ ٧ 3

1053 Negative Seq’ Fast Time Overcurrent (46(51)-1) ٧ ٧ 3

1054 Negative Seq’ Delay Time Overcurrent (46(51)-2) ٧ ٧ 3

1055 Phase High Current Lockout(50P2) ٧ ٧ 3

1056 Ground High Current Lockout(50G2) ٧ ٧ 3

1057 Negative Seq’ High Current Lockout(46(50)2) ٧ ٧ 3

ENHANCED TECHNOLOGY 19
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr

Table D-1. IEC60870-5-104 INDEX - Single-point information (3/5)


Object Point Property Group
Description Notes
Address S G C No.

1058 Phase High Current Trip(50P1) ٧ ٧ 3

1059 Ground High Current Trip(50G1) ٧ ٧ 3

1060 Negative Seq’ High Current Trip(46(50)1) ٧ ٧ 3

1061 Sensitive Earth Fault Trip(51SEF) ٧ ٧ 3

1062 Phase Demand Trip ٧ ٧ 3

1063 Ground Demand Trip ٧ ٧ 3

1064 Negative Seq’ Demand Trip ٧ ٧ 3

1065 UnderFrequency Trip ٧ ٧ 3

1066 Synchronism Check Trip(25) ٧ ٧ 3

1067 Under voltage 1 Trip(27-1) ٧ ٧ 3

1068 Under voltage 2 Trip(27-2) ٧ ٧ 3

1069 Over voltage 1 Trip(59-1) ٧ ٧ 3

1070 Over voltage 2 Trip(59-2) ٧ ٧ 3

1071 CLPU - Loss of Load Diversity (Outage Condition) ٧ ٧ 3

1072 CLPU - Restore Min. Trips Condition ٧ ٧ 3

1073 CLPU - Loss of Load Diversity (Outage Condition) T.O ٧ ٧ 3

1074 CLPU - Restore Min. Trips Condition T.O ٧ ٧ 3

1075 CLPU - Phase Overcurrent Elements ٧ ٧ 3

1076 CLPU - Ground Overcurrent Elements ٧ ٧ 3

1077 CLPU - Negative Overcurrent Elements ٧ ٧ 3

1078 Relay Output 1 Operated ٧ ٧ 7

1079 Relay Output 2 Operated ٧ ٧ 7

1080 Relay Output 3 Operated ٧ ٧ 7

1081 Relay Output 4 Operated ٧ ٧ 7

1082 Relay Output 5 Operated ٧ ٧ 7

1083 Relay Output 6 Operated ٧ ٧ 7

1084 Relay Output 7 Operated ٧ ٧ 7

1085 Relay Output 8 (ALARM) Operated ٧ ٧ 7

1086 External OPEN Signal ٧ ٧ 6

1087 Internal Output Logic 1 ٧ ٧ 6

1088 Internal Output Logic 2 ٧ ٧ 6

1089 Internal Output Logic 3 ٧ ٧ 6

20 ENHANCED TECHNOLOGY
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr

Table D-1. IEC60870-5-104 INDEX - Single-point information (4/5)


Object Point Property Group
Description Notes
Address S G C No.

1090 Internal Output Logic 4 ٧ ٧ 6

1091 Internal Output Logic 5 ٧ ٧ 6

1092 Internal Output Logic 6 ٧ ٧ 6

1093 Internal Output Logic 7 ٧ ٧ 6

1094 Internal Output Logic 8 ٧ ٧ 6

1095 Internal Trip Logic Output ٧ ٧ 6

1096 Internal Close Logic Output ٧ ٧ 6

1097 Trip Operation Fail ٧ ٧ 2

1098 Close Operation Fail ٧ ٧ 2

1099 Voltage Transformer Fail ٧ ٧ 2

1100 Battery discharge test Fail ٧ ٧ 8

1101 NO Battery ٧ ٧ 8 Value<15V

1102 System power FAIL ٧ ٧ 8

1103 Panel sleep mode entered ٧ ٧ 1

1104 Power down mode entered ٧ ٧ 8

1105 Gas pressure Low ٧ ٧ 2 Value<0.1Bar

1106 Gas pressure High ٧ ٧ 2 Value<1.5Bar

1107 System power +12V FAIL ٧ ٧ 9

1108 System power +5V FAIL ٧ ٧ 9

1109 System power -12V FAIL ٧ ٧ 9

1110 A/D converter reference vol’ 1 FAIL ٧ ٧ 9

1111 A/D converter reference vol’ 2 FAIL ٧ ٧ 9

1112 System power FAIL ٧ ٧ 9

1113 A/D conversion FAIL ٧ ٧ 9

1114 Serial EEPROM FAIL ٧ ٧ 9

1115 Data RAM FAIL ٧ ٧ 9

1116 System RAM FAIL ٧ ٧ 9

1117 Setting RAM FAIL ٧ ٧ 9

1118 RTC NV RAM FAIL ٧ ٧ 9

1119 RTC Time FAIL ٧ ٧ 9

1120 RTC Battery LOW ٧ ٧ 9

1121 Initial Value FAIL ٧ ٧ 9

ENHANCED TECHNOLOGY 21
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr

Table D-1. IEC60870-5-104 INDEX - Single-point information (5/5)

Object Point Property Group


Description Notes
Address S G C No.

1122 Initial Setting Value FAIL ٧ ٧ 9

1123 Program ROM CheckSum FAIL ٧ ٧ 9

NOTE
Group1: Panel (Other) Function Section

Group2: Tank(Recloser) related

Group3: Protection elements

Group4: Fault on going related

Group5: Target after fault occurred

Group6: System Internal Commnand

Group7: Scada port related

Group8: Power monitoring

Group9: System monitoring

22 ENHANCED TECHNOLOGY
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr

Table D-2. IEC 60870-5-104 INDEX – Single Command (1/2)

Single Command

Object
Description Notes
Address

CLOSE OFF
21000
OPEN ON
Protection Disable OFF
21001
Protection Enable ON
Ground Disable OFF
21002
Ground Enable ON
SEF Disable OFF
21003
SEF Enable ON
Reclose Disable OFF
21004
Reclose Enable ON
Control Unlock OFF
21005
Control Lock ON
Primary Setting Enable OFF
21006
Alternate Setting Enable ON
Program 1 Disable OFF
21007
Program 1 Enable ON
Program 2 Disable OFF
21008
Program 2 Enable ON
Hot Line Tag Disable OFF
21009
Hot Line Tag Enable ON
21010 Target Reset ON
21011 Battery test ON
21012 Reset Max demand value ON
21013 Reset energy ON
21014 Change Setting ON Note 1)
21015 Opto Input 1 operate ON
21016 Opto Input 2 operate ON
21017 Opto Input 3 operate ON
21018 Opto Input 4 operate ON
21019 Opto Input 5 operate ON
21020 Opto Input 6 operate ON

ENHANCED TECHNOLOGY 23
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr

Table D-2. IEC60870-5-104 INDEX - Single Command (2/2)


Object
Description Notes
Address

21021 Opto Input 7 operate ON


21022 Opto Input 8 operate ON

NOTE
1) As changed value by Single Command signal, changed present setting value and restart a system.

24 ENHANCED TECHNOLOGY
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr

Table D-3. IEC60870-5-104 - Integrated Totals

Integrated Totals Point

Object
Description Point Property Notes
Address

3000 Trip counter Static Note 1)

3001 Fault counter Static Note 1)

3002 Restart counter Static Note 1)

NOTE
1) 16 bit rollover Counter.

Integrated Totals is achieved by Integrated Totals Command.

ENHANCED TECHNOLOGY 25
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr

Table D-4. IEC60870-5-104 – Normalized Measurands (1/6)

Normalized Measurands

S: Spontaneous , G: General Group, C: cyclic


Object
Description Point Property Group
Address Notes
S G C No.

2000 Firmware version(MAIN Part) ٧ 16 DF3

2001 Firmware version(RTU Part) ٧ 16 DF3

2002 RMS Current Magnitude - A (A) ٧ ٧ 10 DF1

2003 RMS Current Magnitude - B (A) ٧ ٧ 10 DF1

2004 RMS Current Magnitude - C (A) ٧ ٧ 10 DF1

2005 RMS Current Magnitude - G (A) ٧ ٧ 10 DF1

2006 RMS Current Magnitude - SEF (A) ٧ ٧ 10 DF1

2007 RMS Current Magnitude - NEQ (A) ٧ ٧ 10 DF1

2008 Current Angle - A (Degree) ٧ 16 DF2

2009 Current Angle - B (Degree) ٧ 16 DF2

2010 Current Angle - C (Degree) ٧ 16 DF2

2011 Current Angle - G (Degree) ٧ 16 DF2

2012 Current Angle - SEF (Degree) ٧ 16 DF2

2013 Current Angle - NEQ (Degree) ٧ 16 DF2

2014 RMS Voltage Magnitude - AN (kV) ٧ ٧ 10 DF3

2015 RMS Voltage Magnitude - BN (kV) ٧ ٧ 10 DF3

2016 RMS Voltage Magnitude - CN (kV) ٧ ٧ 10 DF3

2017 RMS Voltage Magnitude - AB (kV) ٧ ٧ 10 DF3

2018 RMS Voltage Magnitude - BC (kV) ٧ ٧ 10 DF3

2019 RMS Voltage Magnitude - CA (kV) ٧ ٧ 10 DF3

2020 Voltage Angle - AN (Degree) ٧ 16 DF2

2021 Voltage Angle - BN (Degree) ٧ 16 DF2

2022 Voltage Angle - CN (Degree) ٧ 16 DF2

2023 Voltage Angle - AB (Degree) ٧ 16 DF2

2024 Voltage Angle - BC (Degree) v 16 DF2

2025 Voltage Angle - CA (Degree) ٧ 16 DF2

2026 Real Power - A (MW) ٧ ٧ 10 DF7

2027 Real Power - B (MW) ٧ ٧ 10 DF7

26 ENHANCED TECHNOLOGY
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr

Table D-4. IEC60870-5-104 - Normalized Measurands (2/6)


Object Point Property Group
Description Notes
Address S G C No.

2028 Real Power - C (MW) ٧ ٧ 10 DF7

2029 Real Power - 3φ (MW) ٧ ٧ 10 DF7

2030 Reactive Power - A (MVar) ٧ ٧ 10 DF7

2031 Reactive Power - B (MVar) ٧ ٧ 10 DF7

2032 Reactive Power - C (MVar) ٧ ٧ 10 DF7

2033 Reactive Power - 3φ (MVar) ٧ ٧ 10 DF7

2034 Apparent Power - A (MVA) ٧ ٧ 10 DF7

2035 Apparent Power - B (MVA) ٧ ٧ 10 DF7

2036 Apparent Power - C (MVA) ٧ ٧ 10 DF7

2037 Apparent Power - 3φ (MVA) ٧ ٧ 10 DF7

2038 Power factor - A (%) ٧ ٧ 10 DF6

2039 Power factor - B (%) ٧ ٧ 10 DF6

2040 Power factor - C (%) ٧ ٧ 10 DF6

2041 Power factor - 3φ (%) ٧ ٧ 10 DF6

2042 Positive Watt-Hour (MW/H) ٧ 10 DF5

2043 Negative Watt-Hour (MW/H) ٧ 10 DF5

2044 Positive Var-Hour (MVar/H) ٧ 10 DF5

2045 Negative Var-Hour (MVar/H) ٧ 10 DF5

2046 Frequency (Hz) ٧ ٧ 10 DF3

2047 Present Demand Current - A (A) ٧ ٧ 11 DF1

2048 Present Demand Current - B (A) ٧ ٧ 11 DF1

2049 Present Demand Current - C (A) ٧ ٧ 11 DF1

2050 Present Demand Current - G (A) ٧ ٧ 11 DF1

2051 Present Demand Current - SEF (A) ٧ ٧ 11 DF1

2052 Present Demand Current - NEQ (A) ٧ ٧ 11 DF1

2053 Present Demand Real Power - A (MW) ٧ ٧ 11 DF7

2054 Present Demand Real Power - B (MW) ٧ ٧ 11 DF7

2055 Present Demand Real Power - C (MW) ٧ ٧ 11 DF7

2056 Present Demand Real Power - 3φ (MW) ٧ ٧ 11 DF7

2057 Present Demand Reactive Power - A (MVar) ٧ ٧ 11 DF7

2058 Present Demand Reactive Power - B (MVar) ٧ ٧ 11 DF7

ENHANCED TECHNOLOGY 27
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr

Table D-4. IEC60870-5-104 - Normalized Measurands (3/6)


Object Point Property Group
Description Notes
Address S G C No.

2059 Present Demand Reactive Power - C (MVar) ٧ ٧ 11 DF7

2060 Present Demand Reactive Power - 3φ (MVar) ٧ ٧ 11 DF7

2061 Max Demand Current - A (A) ٧ 12 DF1

2062 Max Demand Current - B (A) ٧ 12 DF1

2063 Max Demand Current - C (A) ٧ 12 DF1

2064 Max Demand Current - G (A) ٧ 12 DF1

2065 Max Demand Current - SEF (A) ٧ 12 DF1

2066 Max Demand Current - NEQ (A) ٧ 12 DF1

2067 Max Demand Real Power - A (MW) ٧ 12 DF7

2068 Max Demand Real Power - B (MW) ٧ 12 DF7

2069 Max Demand Real Power - C (MW) ٧ 12 DF7

2070 Max Demand Real Power - 3φ (MW) ٧ 12 DF7

2071 Max Demand Reactive Power - A (MVar) ٧ 12 DF7

2072 Max Demand Reactive Power - B (MVar) ٧ 12 DF7

2073 Max Demand Reactive Power - C (MVar) ٧ 12 DF7

2074 Max Demand Reactive Power - 3φ (MVar) ٧ 12 DF7

2075 Max Demand Current - A Time 1 ٧ 16 DFTIME1

2076 Max Demand Current - A Time 2 ٧ 16 DFTIME2

2077 Max Demand Current - A Time 3 ٧ 16 DFTIME3

2078 Max Demand Current - B Time 1 ٧ 16 DFTIME1

2079 Max Demand Current - B Time 2 ٧ 16 DFTIME2

2080 Max Demand Current - B Time 3 ٧ 16 DFTIME3

2081 Max Demand Current - C Time 1 ٧ 16 DFTIME1

2082 Max Demand Current - C Time 2 ٧ 16 DFTIME2

2083 Max Demand Current - C Time 3 ٧ 16 DFTIME3

2084 Max Demand Current - G Time 1 ٧ 16 DFTIME1

2085 Max Demand Current - G Time 2 ٧ 16 DFTIME2

2086 Max Demand Current - G Time 3 ٧ 16 DFTIME3

2087 Max Demand Current - SEF Time 1 ٧ 16 DFTIME1

2088 Max Demand Current - SEF Time 2 ٧ 16 DFTIME2

2089 Max Demand Current - SEF Time 3 ٧ 16 DFTIME3

2090 Max Demand Current - NEQ Time 1 ٧ 16 DFTIME1

28 ENHANCED TECHNOLOGY
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr

Table D-4. IEC60870-5-104 - Normalized Measurands (4/6)


Object Point Property Group
Description Notes
Address S G C No.

2091 Max Demand Current - NEQ Time 2 ٧ 16 DFTIME2

2092 Max Demand Current - NEQ Time 3 ٧ 16 DFTIME3

2093 Max Demand Real Power - A Time 1 ٧ 16 DFTIME1

2094 Max Demand Real Power - A Time 2 ٧ 16 DFTIME2

2095 Max Demand Real Power - A Time 3 ٧ 16 DFTIME3

2096 Max Demand Real Power - B Time 1 ٧ 16 DFTIME1

2097 Max Demand Real Power - B Time 2 ٧ 16 DFTIME2

2098 Max Demand Real Power - B Time 3 ٧ 16 DFTIME3

2099 Max Demand Real Power - C Time 1 ٧ 16 DFTIME1

2100 Max Demand Real Power - C Time 2 ٧ 16 DFTIME2

2101 Max Demand Real Power - C Time 3 ٧ 16 DFTIME3

2102 Max Demand Real Power - 3φ Time 1 ٧ 16 DFTIME1

2103 Max Demand Real Power - 3φ Time 2 ٧ 16 DFTIME2

2104 Max Demand Real Power - 3φ Time 3 ٧ 16 DFTIME3

2105 Max Demand Reactive Power - A Time 1 ٧ 16 DFTIME1

2106 Max Demand Reactive Power - A Time 2 ٧ 16 DFTIME2

2107 Max Demand Reactive Power - A Time 3 ٧ 16 DFTIME3

2108 Max Demand Reactive Power - B Time 1 ٧ 16 DFTIME1

2109 Max Demand Reactive Power - B Time 2 ٧ 16 DFTIME2

2110 Max Demand Reactive Power - B Time 3 ٧ 16 DFTIME3

2111 Max Demand Reactive Power - C Time 1 ٧ 16 DFTIME1

2112 Max Demand Reactive Power - C Time 2 ٧ 16 DFTIME2

2113 Max Demand Reactive Power - C Time 3 ٧ 16 DFTIME3

2114 Max Demand Reactive Power - 3φ Time 1 ٧ 16 DFTIME1

2115 Max Demand Reactive Power - 3φ Time 2 ٧ 16 DFTIME2

2116 Max Demand Reactive Power - 3φ Time 3 ٧ 16 DFTIME3

2117 Today Max Demand Current - A (A) v 13 DF1

2118 Today Max Demand Current - B (A) ٧ 13 DF1

2119 Today Max Demand Current - C (A) ٧ 13 DF1

2120 Today Max Demand Current - G (A) ٧ 13 DF1

2121 Today Max Demand Current - SEF (A) ٧ 13 DF1

2122 Today Max Demand Current - NEQ (A) ٧ 13 DF1

ENHANCED TECHNOLOGY 29
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr

Table D-4. IEC60870-5-104 Normalized Measurands (5/6)


Object Point Property Group
Description Notes
Address S G C No.

2123 Today Max Demand Real Power - A (MW) ٧ 13 DF7

2124 Today Max Demand Real Power - B (MW) ٧ 13 DF7

2125 Today Max Demand Real Power - C (MW) ٧ 13 DF7

2126 Today Max Demand Real Power - 3φ (MW) ٧ 13 DF7

2127 Today Max Demand Reactive Power - A (MVar) ٧ 13 DF7

2128 Today Max Demand Reactive Power - B (MVar) ٧ 13 DF7

2129 Today Max Demand Reactive Power - C (MVar) ٧ 13 DF7

2130 Today Max Demand Reactive Power - 3φ (MVar) ٧ 13 DF7

2131 Yesterday Max Demand Current - A (A) ٧ 13 DF1

2132 Yesterday Max Demand Current - B (A) ٧ 13 DF1

2133 Yesterday Max Demand Current - C (A) ٧ 13 DF1

2134 Yesterday Max Demand Current - G (A) ٧ 13 DF1

2135 Yesterday Max Demand Current - SEF (A) ٧ 13 DF1

2136 Yesterday Max Demand Current - NEQ (A) ٧ 13 DF1

2137 Yesterday Max Demand Real Power - A (MW) ٧ 13 DF7

2138 Yesterday Max Demand Real Power - B (MW) ٧ 13 DF7

2139 Yesterday Max Demand Real Power - C (MW) ٧ 13 DF7

2140 Yesterday Max Demand Real Power - 3φ (MW) ٧ 13 DF7

2141 Yesterday Max Demand Reactive Power - A (MVar) ٧ 13 DF7

2142 Yesterday Max Demand Reactive Power - B (MVar) ٧ 13 DF7

2143 Yesterday Max Demand Reactive Power - C (MVar) ٧ 13 DF7

2144 Yesterday Max Demand Reactive Power - 3φ (MVar) ٧ 13 DF7

2145 Phase A Contact wear percentage (%) ٧ 2 DF3

2146 Phase B Contact wear percentage (%) ٧ 2 DF3

2147 Phase C Contact wear percentage (%) ٧ 2 DF3

2148 Battery Voltage (V) ٧ 8 DF7

2149 Control Box Temperature (℃) ٧ 8 DF7

2150 Gas Pressure ٧ 2 DF7

2151 +12V ٧ 9 DF7

2152 -12V ٧ 9 DF7

2153 +5V ٧ 9 DF7

30 ENHANCED TECHNOLOGY
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr

Table D-4. IEC60870-5-104 - Normalized Measurands (6/6)


Object Point Property Group
Description Notes
Address S G C No.

2155 Last Fault Current - B (A) ٧ 5 DF1

2156 Last Fault Current - C (A) ٧ 5 DF1

2157 Last Fault Current - G (A) ٧ 5 DF1

2158 Last Fault Current - SEF (A) ٧ 5 DF1

2159 Last Fault Current - NEQ (A) ٧ 5 DF1

NOTE
Object Address Point of Normalized Measurands has three Parameter normalized Value( Threshold, Low Limit, Hight

Limit) and these are dedicated for Group 14 in General Interrogation.

Following tables shows IOA, Value, Flags( Threshold, Low Limit, Hight Limit) at address 2002.

Address IOA Value Flags

10006 99 0х01(Threshold)

2002 10007 -32768 0х03(Low Limit)

10008 32767 0х04(Hight Limit)

To change Value, do Parameter normalized value command and dedicate new Address and Flags.

Each Object Address Point are 2000~2159 and it has three values (Threshold, Low Limit, Hight Limit). Threshold IOA at

address 2000 is 10000 and Hight Limit IOA of Last Fault Current NEQ at address 2159 is, 10521.

Group10: Measuring
Group11: Measuring

Group12: Max value measuing

Group13: TMax value measuring

Group14: Normalized Measurands’ Threshold, Low limit, High limit measuring

Group16: Angle measuring

ENHANCED TECHNOLOGY 31
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr

Table D-5. IEC60870-5-104 – Normalized Measurands Without Quality(1/6)

Normalized Measurands Without Quality

Object Point Group


Description Notes
Address Property No.

6000 Value of change event setting 1 Static 15 DF1 (0:OFF, 1-50 %)

6001 Value of change event limit value 1 Static 15 DF3 (4-320 xCT Phase ratio)

6002 Value of change event setting 2 Static 15 DF1 (0:OFF, 1-50 %)

DF3 (0-125 xVT secondary


6003 Value of change event limit value 2 Static 15
nominal volt)

6004 Value of change event setting 3 Static 15 DF1 (0:OFF, 1-50 %)

6005 Value of change event limit value 3 Static 15 DF1 (0-60000)

6006 Fault cycle Event record Static 15 DF1 (0:OFF, 1:ON)

6007 Length of prefault in fault cycle Static 15 DF1 (0-14 cycle)

6008 Load profile event record Static 15 DF1 (0:OFF, 1:ON)

DF1 (0:5, 1:10, 2:15, 3:20,


6009 Load profile save interval Static 15
4:30, 5:60 minute)

6010 Operations to lockout - phase Static 15 DF1 (1-5)

6011 Operations to lockout - ground Static 15 DF1 (1-5)

6012 Operations to lockout - SEF Static 15 DF1 (1-5)

6013 Operations to lockout - NEQ Static 15 DF1 (1-5)

6014 Operations - phase fast curve Static 15 DF1 (0-5)

6015 Operations - ground fast curve Static 15 DF1 (0-5)

6016 Operations - NEQ fast curve Static 15 DF1 (0-5)

6017 Reclosing time 1 (sec) Static 15 DF3 (50-60000)

6018 Reclosing time 2 (sec) Static 15 DF3 (100-60000)

6019 Reclosing time 3 (sec) Static 15 DF3 (100-60000)

6020 Reclosing time 4 (sec) Static 15 DF3 (100-60000)

Reset time from autoreclose


6021 Static 15 DF3 (100-60000)
cycle (sec)

6022 Reset time from lockout (sec) Static 15 DF3 (100-60000)

6023 Limit time to waiting closing power (sec) Static 15 DF3 (100-60000)

6024 Pickup current - phase Static 15 DF3 (0:OFF, 4-320)

6025 Pickup current - ground Static 15 DF3 (0:OFF, 2-320)

6026 Pickup current - SEF Static 15 DF4 (0:OFF, 5-160)

32 ENHANCED TECHNOLOGY
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr

Table D-5. IEC60870-5-104 - Normalized Measurands Without Quality (2/6)


Object Point Group
Description Notes
Address Property No.

6027 Pickup current - NEQ Static 15 DF3 (0:OFF, 4-320)

6028 Operations curve - PHASE FAST Static 15 DF1 (0-56)

6029 Time dial - PHASE FAST Static 15 DF3 (5-1500)

6030 Constant time adder - PHASE FAST Static 15 DF3 (0-1000)

6031 Minimum response time - PHASE FAST Static 15 DF3 (0-1000)

6032 Select reset method - PHASE FAST Static 15 DF1 (0:INST, 1:LINEAR)

6033 Operations curve - PHASE DELAY Static 15 DF1 (0-56)

6034 Time dial - PHASE DELAY Static 15 DF3 (5-1500)

6035 Constant time adder - PHASE DELAY Static 15 DF3 (0-1000)

6036 Minimum response time - PHASE DELAY Static 15 DF3 (0-1000)

6037 Select reset method - PHASE DELAY Static 15 DF1 (0:INST, 1:LINEAR)

6038 Operations curve - GROUND FAST Static 15 DF1 (0-56)

6039 Time dial - GROUND FAST Static 15 DF3 (5-1500)

6040 Constant time adder - GROUND FAST Static 15 DF3 (0-1000)

6041 Minimum response time - GROUND FAST Static 15 DF3 (0-1000)

6042 Select reset method - GROUND FAST Static 15 DF1 (0:INST, 1:LINEAR)

6043 Operations curve - GROUND DELAY Static 15 DF1 (0-56)

6044 Time dial - GROUND DELAY Static 15 DF3 (5-1500)

6045 Constant time adder - GROUND DELAY Static 15 DF3 (0-1000)

6046 Minimum response time - GROUND DELAY Static 15 DF3 (0-1000)

6047 Select reset method - GROUND DELAY Static 15 DF1 (0:INST, 1:LINEAR)

6048 Time delay - SEF ELEMENT Static 15 DF3 (00-1000)

6049 Operations curve - NEG SEQ FAST Static 15 DF1 (0-56)

6050 Time dial - NEG SEQ FAST Static 15 DF3 (5-1500)

6051 Constant time adder - NEG SEQ FAST Static 15 DF3 (0-1000)

6052 Minimum response time - NEG SEQ FAST Static 15 DF3 (0-1000)

6053 Select reset method - NEG SEQ FAST Static 15 DF1 (0:INST, 1:LINEAR)

6054 Operations curve - NEG SEQ DELAY Static 15 DF1 (0-56)

6055 Time dial - NEG SEQ DELAY Static 15 DF3 (5-1500)

6056 Constant time adder - NEG SEQ DELAY Static 15 DF3 (0-1000)

6057 Minimum response time - NEG SEQ DELAY Static 15 DF3 (0-1000)

6058 Select reset method - NEG SEQ DELAY Static 15 DF1 (0:INST, 1:LINEAR)

ENHANCED TECHNOLOGY 33
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr

Table D-5. IEC60870-5-104 - Normalized Measurands Without Quality (3/6)


Object Point Group
Description Notes
Address Property No.

DF1
6059 H/C Trip function - phase Static 15
(0:OFF, 1:TRIP, 2:TRIP&ALARM)

6060 H/C Trip Pickup current - phase Static 15 DF3 (10-2000)

6061 H/C Trip Time delay - phase Static 15 DF3 (0-1000)

6062 H/C Trip Active Trip No - phase Static 15 DF1 (0-5)

DF1
6063 H/C Trip function - ground Static 15
(0:OFF, 1:TRIP, 2:TRIP&ALARM)

6064 H/C Trip Pickup current - ground Static 15 DF3 (10-2000)

6065 H/C Trip Time delay - ground Static 15 DF3 (0-1000)

6066 H/C Trip Active Trip No - ground Static 15 DF1 (0-5)

DF1
6067 H/C Trip function - NEQ Static 15
(0:OFF, 1:TRIP, 2:TRIP&ALARM)

6068 H/C Trip Pickup current - NEQ Static 15 DF3 (10-2000)

6069 H/C Trip Time delay - NEQ Static 15 DF3 (0-1000)

6070 H/C Trip Active Trip No- NEQ Static 15 DF1 (0-5)

DF1
6071 H/C LOCKOUT function - phase Static 15
(0:OFF, 1:TRIP, 2:TRIP&ALARM)

6072 H/C LOCKOUT Pickup current - phase Static 15 DF3 (10-2000)

6073 H/C LOCKOUT Time delay - phase Static 15 DF3 (0-1000)

6074 H/C LOCKOUT Active Trip No - phase Static 15 DF1 (0-5)

DF1
6075 H/C LOCKOUT function - ground Static 15
(0:OFF, 1:TRIP, 2:TRIP&ALARM)

6076 H/C LOCKOUT Pickup current - ground Static 15 DF3 (10-2000)

6077 H/C LOCKOUT Time delay - ground Static 15 DF3 (0-1000)

6078 H/C LOCKOUT Active Trip No - ground Static 15 DF1 (0-5)

DF1
6079 H/C LOCKOUT function - NEQ Static 15
(0:OFF, 1:TRIP, 2:TRIP&ALARM)

6080 H/C LOCKOUT Pickup current - NEQ Static 15 DF3 (10-2000)

6081 H/C LOCKOUT Time delay - NEQ Static 15 DF3 (0-1000)

6082 H/C LOCKOUT Active Trip No - NEQ Static 15 DF1 (0-5)

DF1
6083 Cold Load PickUp function Static 15
(0:OFF, 1:TRIP, 2:TRIP&ALARM)

34 ENHANCED TECHNOLOGY
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr

Table D-5. IEC60870-5-104 - Normalized Measurands Without Quality (4/6)


Object Point Group
Description Notes
Address Property No.

6084 CLPU Pickup current - phase Static 15 DF3 (10-2000)

6085 CLPU Pickup current - ground Static 15 DF3 (100-2000)

6086 CLPU Pickup current - SEF Static 15 DF3 (100-2000)

6087 CLPU Pickup current - NEQ Static 15 DF3 (100-2000)

6088 CLPU outage time Static 15 DF3 (0-60000)

6089 CLPU RMT time Static 15 DF3 (0-60000)

6090 CLPU RMT Function - phase Static 15 DF1 (0:OFF, 1:ON)

6091 CLPU RMT Function - ground Static 15 DF1 (0:OFF, 1:ON)

6092 CLPU RMT Function - SEF Static 15 DF1 (0:OFF, 1:ON)

6093 CLPU RMT Function - NEQ Static 15 DF1 (0:OFF, 1:ON)

6094 CLPU Reset time Static 15 DF3 (0-60000)

DF1 (0:OFF, 1:FORWARD,


6095 Direction of current Flow - phase Static 15
2:REVERSE)

6096 Maximum torque angle (M.T.A) - phase Static 15 DF1 (0-359)

DF3 (0-125 xVT secondary


6097 Minimum polarizing voltage (M.P.V) - phase Static 15
nominal volt)

6098 Block overcurrent under M.P.V - phase Static 15 DF1 (0:NO, 1:YES)

DF1 (0:OFF, 1:FORWARD,


6099 Direction of current Flow - ground Static 15
2:REVERSE)

6100 Maximum torque angle (M.T.A) - ground Static 15 DF1 (0-359)

DF3 (0-125 xVT secondary


6101 Minimum polarizing voltage (M.P.V) - ground Static 15
nominal volt)

6102 Block overcurrent under M.P.V - ground Static 15 DF1 (0:NO, 1:YES)

DF1 (0:OFF, 1:FORWARD,


6103 Direction of current Flow - SEF Static 15
2:REVERSE)

6104 Maximum torque angle (M.T.A) - SEF Static 15 DF1 (0-359)

DF3 (0-125 xVT secondary


6105 Minimum polarizing voltage (M.P.V) - SEF Static 15
nominal volt)

6106 Block overcurrent under M.P.V - SEF Static 15 DF1 (0:NO, 1:YES)

DF1 (0:OFF, 1:FORWARD,


6107 Direction of current Flow - NEQ Static 15
2:REVERSE)

6108 Maximum torque angle (M.T.A) - NEQ Static 15 DF1 (0-359)

ENHANCED TECHNOLOGY 35
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr

Table D-5. IEC60870-5-104 - Normalized Measurands Without Quality (5/6)


Object Point Group
Description Notes
Address Property No.

Minimum polarizing voltage


6109 Static 15 DF3 (0-125 xVT secondary nominal volt)
(M.P.V) - NEQ

6110 Block overcurrent under M.P.V - NEQ Static 15 DF1 (0:NO, 1:YES)

6111 Under Voltage 1 function Static 15 DF1 (0:OFF, 1:TRIP, 2:TRIP&ALARM)

6112 Under Voltage 1 Pickup Static 15 DF3 (0-125 xVT secondary nominal volt)

6113 Under Voltage 1 Time delay Static 15 DF3 (0-60000)

6114 Under Voltage 1 Minimum voltage Static 15 DF3 (0-125 xVT secondary nominal volt)

6115 Under Voltage 1 Pickup type Static 15 DF1 (0:1-Phase, 1:2-Phase, 2:3-Phase)

6116 Under Voltage 2 function Static 15 DF1 (0:OFF, 1:TRIP, 2:TRIP&ALARM)

6117 Under Voltage 2 Pickup Static 15 DF3 (0-125 xVT secondary nominal volt)

6118 Under Voltage 2 Time delay Static 15 DF3 (0-60000)

6119 Under Voltage 2 Minimum voltage Static 15 DF3 (0-125 xVT secondary nominal volt)

6120 Under Voltage 2 Pickup type Static 15 DF1 (0:1-Phase, 1:2-Phase, 2:3-Phase)

6121 Over Voltage 1 function Static 15 DF1 (0:OFF, 1:TRIP, 2:TRIP&ALARM)

6122 Over Voltage 1 Pickup Static 15 DF3 (0-125 xVT secondary nominal volt)

6123 Over Voltage 1 Time delay Static 15 DF3 (0-60000)

6124 Over Voltage 1 Pickup type Static 15 DF1 (0:1-Phase, 1:2-Phase, 2:3-Phase)

6125 Over Voltage 2 function Static 15 DF1 (0:OFF, 1:TRIP, 2:TRIP&ALARM)

6126 Over Voltage 2 Pickup Static 15 DF3 (0-125 xVT secondary nominal volt)

6127 Over Voltage 2 Time delay Static 15 DF3 (0-60000)

6128 Over Voltage 2 Pickup type Static 15 DF1 (0:1-Phase, 1:2-Phase, 2:3-Phase)

6129 Under Frequency function Static 15 DF1 (0:OFF, 1:TRIP, 2:TRIP&ALARM)

6130 Under Frequency Pickup Static 15 DF3 (4000-6500)

6131 Under Frequency Time delay Static 15 DF3 (0-60000)

6132 Under Frequency Minimum voltage Static 15 DF3 (0-125 xVT secondary nominal volt)

6133 Under Frequency Minimum current Static 15 DF3 (1-320 xCT Phase ratio)

6134 Sequence coordination Function Static 15 DF1 (0:OFF, 1:ON)

6135 Lockout Priority Static 15 DF1 (0:GROUND, 1:PHASE)

6136 Fault indicator reset method Static 15 DF1 (0:AUTO, 1:MANUAL)

6137 Manual close time delay Static 15 DF3 (0-60000)

6138 Monitoring demand function Static 15 DF1 (0:OFF, 1:TRIP, 2:TRIP&ALARM)

6139 Demand method Static 15 DF1 (0:THERMAL, 1:ROLLING)

36 ENHANCED TECHNOLOGY
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr

Table D-5. IEC60870-5-104 - Normalized Measurands Without Quality (6/6)


Object Point Group
Description Notes
Address Property No.

6140 Time interval Static 15 DF1 (0:5, 1:10, 2:15, 3:20, 4:30, 5:60 minite)

6141 Demand Pickup - phase Static 15 DF3 (0:OFF, 4-320 xCT Phase ratio)

6142 Demand Pickup - ground Static 15 DF3 (0:OFF, 2-320 xCT Ground ratio)

6143 Demand Pickup - NEQ Static 15 DF3 (0:OFF, 4-320 xCT Phase ratio)

6144 Synchrocheck function Static 15 DF1 (0:OFF, 1:ALARM)

6145 Dead line maximum voltage Static 15 DF3 (0-125 xVT 2nd norminal volt)

6146 Live line minimum voltage Static 15 DF3 (0-125 xVT 2nd norminal volt)

6147 Maximum voltage difference Static 15 DF3 (0-125 xVT 2nd norminal volt)

6148 Maximum angle difference Static 15 DF1 (0-100 deg)

6149 Maximum frequency difference Static 15 DF3 (0-500 Hz)

6150 Synchrocheck phase Static 15 DF1 (0:R(AB), 1:S(CB), 2:T phase)

6151 Fault Locator Function Static 15 DF1 (0:OFF, 1:ON)

6152 Length of Feeder Static 15 DF2 (1-999 km)

Real impedance of the feeder


6153 Static 15 DF2 (1-60000 ohms)
positive sequence

Imaginary impedance of the


6154 Static 15 DF2 (1-60000 ohms)
feeder positive sequence

Real impedance of the feeder zero


6155 Static 15 DF2 (1-60000 ohms)
sequence

Imaginary impedance of the

6156 feeder Static 15 DF2 (1-60000 ohms)

zero sequence

NOTE
Each Object Address’ : Normalized Measurands Without Quality value change method.

- Do Normalized Measurand command to change new address.

- For example, to change the value at address 6156, conduct Normalized Measurand command so that address can be

dedicated to 20000+6156, and then, input the new value.

Group15: Normalized Measurands Without Quality measuring

ENHANCED TECHNOLOGY 37
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr

Table D-6. Data Format Description


Data Format Description
Unsigned Value
DF1
Ex: 1234 stored as 1234
Unsigned Value, 1 Decimal Place
DF2
Ex: 123.4 stored as 1234
Unsigned Value, 2 Decimal Place
DF3
Ex: 12.34 stored as 1234
Unsigned Value, 3 Decimal Place
DF4
Ex: 1.234 stored as 1234
Signed Value
DF5
Ex: -1234 stored as -1234
Signed Value, 1 Decimal Place
DF6
Ex: -123.4 stored as -1234
Signed Value, 2 Decimal Place
DF7
Ex: -12.34 stored as -1234
Signed Value, 3 Decimal Place
DF8
Ex: -1.234 stored as -1234
2Byte (High 1Byte: Year, Low 1Byte: Month)
DFTIME1
Ex: 0x020a → 2002 year, 10 month
2Byte (High 1Byte: Day, Low 1Byte: Hour)
DFTIME2
Ex: 0x0b0c → 11 day, 12 hour
2Byte (High 1Byte: Minute, Low 1Byte: Second)
DFTIME3
Ex: 0x0d0e → 13 minute, 14 second

38 ENHANCED TECHNOLOGY

You might also like