08 - 0610 - V4.00 - EVRC2A - Technical Manual IEC60870-5-104
08 - 0610 - V4.00 - EVRC2A - Technical Manual IEC60870-5-104
00
IEC60870-5-104 PROTOCOL
Technical Manual
ENTEC ENTEC
ELECTRIC & ELECTRONIC CO., LTD
Copyright © 2006 by ENTEC ELECTRIC & ELECTRONIC CO., LTD all right reserved. Forerunner Distribution & Automation
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr
TABLE OF CONTENTS
A. Introduction ………………………..…………………………………………………………...4
ENHANCED TECHNOLOGY 3
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr
A. Introduction
This document is based on IEC60870-5-104. Based on IEC 60870-5-104, this document describes
Communication method between EVRC2A and Master Station, and provides IEC60870-5-104
Interoperability Document and IEC60870-5-104 Point table and parameter explanations.
IEC 60870-5-104 applies to telecontrol equipment and systems with coded bit serial data
transmission for monitoring and controlling geographically widespread processes. This standard
defines the use of an open TCP/IP-interface to a network, containing for example a LAN for
telecontrol equipment.
4 ENHANCED TECHNOLOGY
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr
255.000.000.000~
Subnet Mask Subnet mask 255.255.255.000
255.255.255.252
ENHANCED TECHNOLOGY 5
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr
C. Interoperability Document
This document is adapted from the IEC 60870-5-104 standard. For the section the boxes indicate
the following: ▣ – used in standard direction; □ – not used; ■ – cannot be selected in IEC 60870-
5-104 standard.
if>1200 bits/s:
■ 600bits/sec. ■ 19200bits/sec.
■ 1200bits/sec. ■ 38400bits/sec.
■ 56000bits/sec.
■ 64000bits/sec.
6 ENHANCED TECHNOLOGY
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr
if>1200 bits/s:
■ 600bits/sec. ■ 19200bits/sec.
■ 1200bits/sec. ■ 38400bits/sec.
■ 56000bits/sec.
■ 64000bits/sec.
■ Two Octets
■ Structured
■ Unstructured
Frame Length (maximum length, number of octets): Not selectable in companion IEC 60870-5-104 standard
When using an unbalanced link layer, the following ADSU types are returned in class 2 messages (low
ENHANCED TECHNOLOGY 7
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr
■ One Octet
▣ Two Octets
▣ Three Octets
Cause of Transmission:
■ One Octet
▣ Two Octets (with originator address). Originator address is set to zero if not used.
Maximum Length of APDU: 253 (the maximum length may be reduced by the system.
■ <14> := Measured value, short floating point value with time tag M_NE_TC_1
■ <18> := Packed start events of protection equipment with time tag M_EP_TB_1
■ <19> := Packed output circuit information of protection equipment with time tag M_EP_TC_1
8 ENHANCED TECHNOLOGY
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr
□ <34> := Measured value, normalized value with time tag CP56Time2a M_ME_TD_1
□ <35> := Measured value, scaled value with time tag CP56Time2a M_ME_TE_1
□ <36> := Measured value, short floating point value with time tag CP56Time2a M_ME_TF_1
□ <39> := Packed start events of protection equipment with time tag CP56Time2a M_EP_TE_1
Either the ASDUs of the set <2>, <4>, <6>, <8>, <10>, <12>, <14>, <16>, <17>, <18>, and <19> or of the
▣ <61> := Set point command, normalized value with time tag CP56Time2a C_SE_TA_1
□ <62> := Set point command, scaled value with time tag CP56Time2a C_SE_TB_1
□ <63> := Set point command, short floating point value with time tag CP56Time2a C_SE_TC_1
Either the ASDUs of the set <45> to <51> or of the set <58> to <64> are used.
ENHANCED TECHNOLOGY 9
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr
File transfer
□ <120> := File Ready F_FR_NA_1
□ <122> := Call directory, select file, call file, call section F_SC_NA_1
□ <123> := Last section, last segment F_LS_NA_1
10 ENHANCED TECHNOLOGY
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr
PERIODIC, CYCLIC
BACKGROUND SCAN
SPONTANEOUS
INITIALIZED
REQUEST OR REQUESTED
ACTIVATION
ACTIVATION CONFIRMATION
DEACTIVATION
DEACTIVATION CONFIRMATION
ACTIVATION TERMINATION
FILE TRANSFER
<1> M_SP_NA_1 X X X X
<2> M_SP_TA_1
<3> M_DP_NA_1
<4> M_DP_TA_1
<5> M_ST_NA_1
<6> M_ST_TA_1
<7> M_BO_NA_1
<8> M_BO_TA_1
<9> M_ME_NA_1 X X X X
<10> M_ME_TA_1
<11> M_ME_NB_1
<12> M_ME_TB_1
<13> M_ME_NC_1
<14> M_ME_TC_1
<15> M_IT_NA_1 X X
<16> M_IT_TA_1
<17> M_EP_TA_1
<18> M_EP_TB_1
<19> M_EP_TC_1
<20> M_PS_NA_1
<21> M_ME_ND_1 X X
<30> M_SP_TB_1 X X X
<31> M_DP_TB_1
ENHANCED TECHNOLOGY 11
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr
PERIODIC, CYCLIC
BACKGROUND SCAN
SPONTANEOUS
INITIALIZED
REQUEST OR REQUESTED
ACTIVATION
ACTIVATION CONFIRMATION
DEACTIVATION
DEACTIVATION CONFIRMATION
ACTIVATION TERMINATION
FILE TRANSFER
<32> M_ST_TB_1
<33> M_BO_TB_1
<34> M_ME_TD_1
<35> M_ME_TE_1
<36> M_ME_TF_1
<37> M_IT_TB_1
<38> M_EP_TD_1
<39> M_EP_TE_1
<40> M_EP_TF_1
<45> C_SC_NA_1 X X X X X
<46> C_DC_NA_1
<47> C_RC_NA_1
<48> C_SE_NA_1 X X X X X
<49> C_SE_NB_1
<50> C_SE_NC_1
<51> C_BO_NA_1
<58> C_SC_TA_1 X X X X X
<59> C_DC_TA_1
<60> C_RC_TA_1
<61> C_SE_TA_1 X X X X X
<62> C_SE_TB_1
<63> C_SE_TC_1
<64> C_BO_TA_1
12 ENHANCED TECHNOLOGY
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr
PERIODIC, CYCLIC
BACKGROUND SCAN
SPONTANEOUS
INITIALIZED
REQUEST OR REQUESTED
ACTIVATION
ACTIVATION CONFIRMATION
DEACTIVATION
DEACTIVATION CONFIRMATION
ACTIVATION TERMINATION
FILE TRANSFER
<70> M_EI_NA_1* X
<100> C_IC_NA_1 X X X X X
<101> C_CI_NA_1 X X X
<102> C_RD_NA_1 X
<103> C_CS_NA_1 X X X
<104> C_TS_NA_1
<105> C_RP_NA_1 X X
<106> C_CD_NA_1
<107> C_TS_TA_1
<110> P_ME_NA_1 X X X
<111> P_ME_NB_1
<112> P_ME_NC_1
<113> P_AC_NA_1
<120> F_FR_NA_1
<121> F_SR_NA_1
<122> F_SC_NA_1
<123> F_LS_NA_1
<124> F_AF_NA_1
<125> F_SG_NA_1
<126> F_DR_TA_1*
* Blank or X only
ENHANCED TECHNOLOGY 13
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr
Read Procedure:
▣ Read procedure
Spontaneous Transmission:
▣ Spontaneous transmission
an information object. The particular information object addresses for which double transmission is
□ Bitstring of 32 bits: M_BO_NA_1, M_BO_TA_1, and M_BO_TB_1 (if defined for a specific project)
□ Measured value, short floating point number: M_ME_NC_1, M_ME_TC_1, and M_ME_TF_1
Station interrogation:
▣ Global
14 ENHANCED TECHNOLOGY
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr
Clock synchronization:
▣ Clock synchronization (optional, see Clause 7.6)
Command transmission:
▣ Direct command transmission
□ No additional definition
□ Persistent output
▣Supervision of maximum delay in command direction of commands and set point commands
▣ Counter read
□ Counter reset
Parameter loading:
▣ Threshold value
□ Smoothing factor
ENHANCED TECHNOLOGY 15
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr
Parameter activation:
□ Activation/deactivation of persistent cyclic or periodic transmission of the addressed object
Test procedure:
□ Test procedure
File transfer:
File transfer in monitor direction:
□ Transparent file
□ Transmission of disturbance data of protection equipment
□ Transparent file
Background scan:
□ Background scan
VALUE VALUE
16 ENHANCED TECHNOLOGY
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr
VALUE VALUE
k 12 APDUs Maximum difference receive sequence number to send state variable 12 APDUs
Portnumber:
the Internet as determined by the Internet Architecture Board (IAB). It offers a broad spectrum of actual
standards used in the Internet. The suitable selection of documents from RFC 2200 defined in this
standard for given projects has to be chosen by the user of this standard.
▣ Ethernet 802.3
ENHANCED TECHNOLOGY 17
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr
Single-point information
1011 27 Target ٧ ٧ 5
1012 59 Target ٧ ٧ 5
1013 25 Target ٧ ٧ 5
1014 81 Target ٧ ٧ 5
18 ENHANCED TECHNOLOGY
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr
1030 79 RESET ٧ ٧ 4
1031 79 CYCLE ٧ ٧ 4
1032 79 LOCKOUT ٧ ٧ 4
1038 Contact(52a) ٧ ٧ 2
ENHANCED TECHNOLOGY 19
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr
20 ENHANCED TECHNOLOGY
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr
ENHANCED TECHNOLOGY 21
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr
NOTE
Group1: Panel (Other) Function Section
22 ENHANCED TECHNOLOGY
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr
Single Command
Object
Description Notes
Address
CLOSE OFF
21000
OPEN ON
Protection Disable OFF
21001
Protection Enable ON
Ground Disable OFF
21002
Ground Enable ON
SEF Disable OFF
21003
SEF Enable ON
Reclose Disable OFF
21004
Reclose Enable ON
Control Unlock OFF
21005
Control Lock ON
Primary Setting Enable OFF
21006
Alternate Setting Enable ON
Program 1 Disable OFF
21007
Program 1 Enable ON
Program 2 Disable OFF
21008
Program 2 Enable ON
Hot Line Tag Disable OFF
21009
Hot Line Tag Enable ON
21010 Target Reset ON
21011 Battery test ON
21012 Reset Max demand value ON
21013 Reset energy ON
21014 Change Setting ON Note 1)
21015 Opto Input 1 operate ON
21016 Opto Input 2 operate ON
21017 Opto Input 3 operate ON
21018 Opto Input 4 operate ON
21019 Opto Input 5 operate ON
21020 Opto Input 6 operate ON
ENHANCED TECHNOLOGY 23
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr
NOTE
1) As changed value by Single Command signal, changed present setting value and restart a system.
24 ENHANCED TECHNOLOGY
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr
Object
Description Point Property Notes
Address
NOTE
1) 16 bit rollover Counter.
ENHANCED TECHNOLOGY 25
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr
Normalized Measurands
26 ENHANCED TECHNOLOGY
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr
ENHANCED TECHNOLOGY 27
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr
28 ENHANCED TECHNOLOGY
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr
ENHANCED TECHNOLOGY 29
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr
30 ENHANCED TECHNOLOGY
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr
NOTE
Object Address Point of Normalized Measurands has three Parameter normalized Value( Threshold, Low Limit, Hight
Following tables shows IOA, Value, Flags( Threshold, Low Limit, Hight Limit) at address 2002.
10006 99 0х01(Threshold)
To change Value, do Parameter normalized value command and dedicate new Address and Flags.
Each Object Address Point are 2000~2159 and it has three values (Threshold, Low Limit, Hight Limit). Threshold IOA at
address 2000 is 10000 and Hight Limit IOA of Last Fault Current NEQ at address 2159 is, 10521.
Group10: Measuring
Group11: Measuring
ENHANCED TECHNOLOGY 31
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr
6001 Value of change event limit value 1 Static 15 DF3 (4-320 xCT Phase ratio)
6023 Limit time to waiting closing power (sec) Static 15 DF3 (100-60000)
32 ENHANCED TECHNOLOGY
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr
6032 Select reset method - PHASE FAST Static 15 DF1 (0:INST, 1:LINEAR)
6037 Select reset method - PHASE DELAY Static 15 DF1 (0:INST, 1:LINEAR)
6042 Select reset method - GROUND FAST Static 15 DF1 (0:INST, 1:LINEAR)
6047 Select reset method - GROUND DELAY Static 15 DF1 (0:INST, 1:LINEAR)
6051 Constant time adder - NEG SEQ FAST Static 15 DF3 (0-1000)
6052 Minimum response time - NEG SEQ FAST Static 15 DF3 (0-1000)
6053 Select reset method - NEG SEQ FAST Static 15 DF1 (0:INST, 1:LINEAR)
6056 Constant time adder - NEG SEQ DELAY Static 15 DF3 (0-1000)
6057 Minimum response time - NEG SEQ DELAY Static 15 DF3 (0-1000)
6058 Select reset method - NEG SEQ DELAY Static 15 DF1 (0:INST, 1:LINEAR)
ENHANCED TECHNOLOGY 33
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr
DF1
6059 H/C Trip function - phase Static 15
(0:OFF, 1:TRIP, 2:TRIP&ALARM)
DF1
6063 H/C Trip function - ground Static 15
(0:OFF, 1:TRIP, 2:TRIP&ALARM)
DF1
6067 H/C Trip function - NEQ Static 15
(0:OFF, 1:TRIP, 2:TRIP&ALARM)
6070 H/C Trip Active Trip No- NEQ Static 15 DF1 (0-5)
DF1
6071 H/C LOCKOUT function - phase Static 15
(0:OFF, 1:TRIP, 2:TRIP&ALARM)
DF1
6075 H/C LOCKOUT function - ground Static 15
(0:OFF, 1:TRIP, 2:TRIP&ALARM)
DF1
6079 H/C LOCKOUT function - NEQ Static 15
(0:OFF, 1:TRIP, 2:TRIP&ALARM)
DF1
6083 Cold Load PickUp function Static 15
(0:OFF, 1:TRIP, 2:TRIP&ALARM)
34 ENHANCED TECHNOLOGY
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr
6098 Block overcurrent under M.P.V - phase Static 15 DF1 (0:NO, 1:YES)
6102 Block overcurrent under M.P.V - ground Static 15 DF1 (0:NO, 1:YES)
6106 Block overcurrent under M.P.V - SEF Static 15 DF1 (0:NO, 1:YES)
ENHANCED TECHNOLOGY 35
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr
6110 Block overcurrent under M.P.V - NEQ Static 15 DF1 (0:NO, 1:YES)
6112 Under Voltage 1 Pickup Static 15 DF3 (0-125 xVT secondary nominal volt)
6114 Under Voltage 1 Minimum voltage Static 15 DF3 (0-125 xVT secondary nominal volt)
6115 Under Voltage 1 Pickup type Static 15 DF1 (0:1-Phase, 1:2-Phase, 2:3-Phase)
6117 Under Voltage 2 Pickup Static 15 DF3 (0-125 xVT secondary nominal volt)
6119 Under Voltage 2 Minimum voltage Static 15 DF3 (0-125 xVT secondary nominal volt)
6120 Under Voltage 2 Pickup type Static 15 DF1 (0:1-Phase, 1:2-Phase, 2:3-Phase)
6122 Over Voltage 1 Pickup Static 15 DF3 (0-125 xVT secondary nominal volt)
6124 Over Voltage 1 Pickup type Static 15 DF1 (0:1-Phase, 1:2-Phase, 2:3-Phase)
6126 Over Voltage 2 Pickup Static 15 DF3 (0-125 xVT secondary nominal volt)
6128 Over Voltage 2 Pickup type Static 15 DF1 (0:1-Phase, 1:2-Phase, 2:3-Phase)
6132 Under Frequency Minimum voltage Static 15 DF3 (0-125 xVT secondary nominal volt)
6133 Under Frequency Minimum current Static 15 DF3 (1-320 xCT Phase ratio)
36 ENHANCED TECHNOLOGY
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr
6140 Time interval Static 15 DF1 (0:5, 1:10, 2:15, 3:20, 4:30, 5:60 minite)
6141 Demand Pickup - phase Static 15 DF3 (0:OFF, 4-320 xCT Phase ratio)
6142 Demand Pickup - ground Static 15 DF3 (0:OFF, 2-320 xCT Ground ratio)
6143 Demand Pickup - NEQ Static 15 DF3 (0:OFF, 4-320 xCT Phase ratio)
6145 Dead line maximum voltage Static 15 DF3 (0-125 xVT 2nd norminal volt)
6146 Live line minimum voltage Static 15 DF3 (0-125 xVT 2nd norminal volt)
6147 Maximum voltage difference Static 15 DF3 (0-125 xVT 2nd norminal volt)
zero sequence
NOTE
Each Object Address’ : Normalized Measurands Without Quality value change method.
- For example, to change the value at address 6156, conduct Normalized Measurand command so that address can be
ENHANCED TECHNOLOGY 37
IEC 60870-5-104 PROTOCOL http://www.entecene.co.kr
38 ENHANCED TECHNOLOGY