Calculation Guide

WDP100-AL

WDP Water Distribution


System

HC/MIT/CgGB-0648-05/06, © Munters Europe AB 2006


WDP100-AL

Contents
1 Cooling Systems .................................................................................................................................. 3
2 CELdek ................................................................................................................................................ 3
2.1 Calculating the number of pads required .................................................................................... 3
2.2 Performance of CELdek 7090 100mm thick ............................................................................... 5
3 WDP100-AL ......................................................................................................................................... 6
3.1 Compiling a system..................................................................................................................... 6

HC/MIT/CgGB-0468-05/06 WDP100-AL Calculation Guide Page 2 of 11


Munters reserves the right to make alterations to specifications, quantities, etc. for production or other reasons,
© Munters Europe AB, 2006
subsequent to publication.
WDP100-AL

1 Cooling Systems
Typical the WDP100-AL gutter system is used in combination with CELdek® 7090 evaporative cooling
pads and Euroemme® extraction fans. The function of the WDP100-AL is to keep the CELdek® pads in
place and provide a suitable means of distributing the water through the pads. These can be installed in
different ways to provide cooling solutions to various types of structures as depicted below. The
diagrams depict structures as seen from above with the relative placement of Euroemme® extraction fans
and CELdek® evaporative cooling pads:
1. A tunnel ventilated structure with two pad sections, as typically used in livestock structures
2. A tunnel ventilated structure with three pad sections, as typically used in livestock structures
3. A double tunnel ventilated structure with two pad sections, as typically used in livestock
structures
4. A cross ventilated structure with one pad section, as typically used in greenhouses or some
livestock structures

CELdek® evaporative cooling pads Euroemme® extraction fans

A B C D

Figure 1: Typical installation configurations for providing evaporative cooling solutions to


structures

2 CELdek
2.1 Calculating the number of pads required
CELdek 7090 is designed to give optimum performance when the air speed through the pad is 1.5m/s.
When the design is done correctly, the pressure drop across a 100mm thick pad will be 20Pa.
Determining the size and number of pads required can be done in three easy steps
Step 1: Calculate the pad area required
For each 1000m3/h of air passing through the pads 0.185m2 of pad is required. The required pad
area can be calculated by using the following formula:
Area = (0.185 / 1000) x (total air flow through the pad)
Step 2: Calculate the length and height of the pad section
Choose either the length or the height of the pad section and calculate the other one by using
either one of the following formulas:
Length = Area / pad height, or:
Height = Area / pad length
Step 3: Round dimensions to fit pad sizes
HC/MIT/CgGB-0468-05/06 WDP100-AL Calculation Guide Page 3 of 11
Munters reserves the right to make alterations to specifications, quantities, etc. for production or other reasons,
© Munters Europe AB, 2006
subsequent to publication.
WDP100-AL

Round the length or height to fit the pad dimensions and calculate the number of pads required.
Step 4: Determine ordering quantities
List the number of pad that needs to be ordered.

Example 1
A poultry house is fitted with 10 x Euroemme EM50 extraction fans. Under the particular circumstances
each extracts 35,000m3/h from the structure. How much CELdek pads are required if the pads are going
to be installed in two sections as in Figure 1A above? For practical reasons the owner of the structure
would like to install 1.5m high pads.
Step 1: Determine the pad area required
Total airflow through the pads = 10 x 35,000 = 350,000m3/h
Pad area required = (0.185 / 1000) x 350,000 = 64.75m2
Pad are per section = 64.75 / 2 = 32.38 m2
Step 2: Calculate the length per section required
Length = 32.38 / 1.5 = 21.59m
Step 3: Round and select the number of pads
All pads are 0.6m wide; therefore the length of a section needs to be a multiple of 0.6m.
Number of pads required = 21.59 / 0.6 = 35.98
Round up to 36 pads
Length of pad installation = 36 x 0.6 = 21.6m
Step 4: Determine ordering quantities
Since the house will have two sections, the following number of pieces needs to be ordered for the house.
72 x CELdek 7090 1500x600x100
72 x CELdek 70120 600x100x030 (water distribution pads)
It is always advisable to order some extra pieces since pads can easily be damaged during construction
work if care is not taken.

Example 2
A greenhouse is fitted with 20 x Euroemme EM50 extraction fans. Under the particular circumstances
each extracts 35,000m3/h from the structure. How much CELdek pads are required? For practical
reasons the owner of the structure would like to install pads along the one side of the structure, which is
115m long, as in Figure 1D above.
Step 1: Determine the pad area required
Total airflow through the pads = 20 x 35,000 = 700,000m3/h
Pad area required = (0.185 / 1000) x 700,000 = 129.5m2
Step 2: Calculate the length per section required
Height of pads = 129.5 / 115 = 1.13m
Step 3: Round and select the number of pads
All pads are 0.6m wide; therefore the length of a section needs to be a multiple of 0.6m.
Number of pads required = 115 / 0.6 = 191.7
Round down because the pad section can’t be longer than the structure and use 191 pads.

HC/MIT/CgGB-0468-05/06 WDP100-AL Calculation Guide Page 4 of 11


Munters reserves the right to make alterations to specifications, quantities, etc. for production or other reasons,
© Munters Europe AB, 2006
subsequent to publication.
WDP100-AL

Length of pad installation = 191 x 0.6 = 114.6m


For the pad height, round up to the next available height, which is 1.2m
Step 4: Determine ordering quantities
The following number of pieces needs to be ordered for the house.
191 x CELdek 7090 1200x600x100
191 x CELdek 70120 600x100x030 (water distribution pads)
It is always advisable to order some extra pieces since pads can easily be damaged during construction
work if care is not taken.

2.2 Performance of CELdek 7090 100mm thick


Table 1 provides a quick and easy way to determine how much cooling is possible given a specified air
condition before the pads and that the pads are fully wetted.
Example 3
What will the air temperature after the pads be if the outside temperature is 28˚C and the RH is 20%?
Locate the outside temperature (28˚C) on the vertical axis. Go horizontally to the right until the column
with the appropriate RH (20%) is reached. The temperature and RH inside the two cells is what the
expected temperature and RH would be after the pad if the air speed through the pad is 1.5m/s and it is
100mm thick. In this case it will be 18.1˚C and 68% RH.

Table 1: Performance table for CELdek 7090


Pad thickness: 100mm / Air speed: 1.5m/s / Altitude: 0m above sea level
Air conditions after pad

Tdb RH Tdb RH Tdb RH Tdb RH Tdb RH Tdb RH Tdb RH Tdb RH

50ºC 30.9 56% 34.3 65% 37.2 72% Tdb - Dry bulb temperature [ºC]
48ºC 29.6 56% 32.8 65% 35.5 72% RH - Relative Humidity [%]
46ºC 28.3 56% 31.3 65% 33.9 72% 36.3 78%
44ºC 27.0 57% 29.8 65% 32.3 72% 34.5 78%
Air temperature before pad

42ºC 25.7 57% 28.4 65% 30.7 72% 32.8 78% 34.7 83%
40ºC 24.4 58% 26.9 66% 29.1 72% 31.1 78% 32.9 83% 34.6 87%
38ºC 23.1 58% 25.4 66% 27.5 73% 29.4 78% 31.2 83% 32.8 87% 34.2 91%
36ºC 21.8 59% 24.0 66% 26.0 73% 27.8 78% 29.4 83% 30.9 87% 32.3 91% 33.7 94%
34ºC 20.4 59% 22.5 67% 24.4 73% 26.1 78% 27.7 83% 29.1 87% 30.5 91% 31.7 94%
32ºC 19.1 60% 21.0 67% 22.8 73% 24.4 78% 25.9 83% 27.3 87% 28.6 91% 29.8 94%
30ºC 17.8 60% 19.6 67% 21.2 73% 22.8 78% 24.2 83% 25.5 87% 26.7 91% 27.9 94%
28ºC 16.4 61% 18.1 68% 19.7 73% 21.1 79% 22.4 83% 23.7 87% 24.9 91% 26.0 94%
26ºC 15.1 61% 16.6 68% 18.1 74% 19.4 79% 20.7 83% 21.9 87% 23.0 91% 24.0 94%
24ºC 13.7 62% 15.2 68% 16.5 74% 17.8 79% 18.9 83% 20.1 87% 21.1 91% 22.1 94%
22ºC 12.3 62% 13.7 69% 14.9 74% 16.1 79% 17.2 83% 18.3 87% 19.3 91% 20.2 94%
20ºC 11.0 63% 12.2 69% 13.3 74% 14.4 79% 15.5 83% 16.5 87% 17.4 91% 18.3 94%

10% 20% 30% 40% 50% 60% 70% 80%


Air RH before pad

HC/MIT/CgGB-0468-05/06 WDP100-AL Calculation Guide Page 5 of 11


Munters reserves the right to make alterations to specifications, quantities, etc. for production or other reasons,
© Munters Europe AB, 2006
subsequent to publication.
WDP100-AL

3 WDP100-AL
The WDP100-AL is a modular system from which many combinations of gutter lengths and pad heights
can be combined. The system consists of four basic building blocks:
• Top and bottom gutter kits
• Gutter side kits
• Watering kits
• Drain kit

Top and bottom Gutter side kits Watering kits Drain kit
gutter kits

Figure 2: Basic building blocks of WDP100-AL

3.1 Compiling a system


Some basic rules apply when a system is compiled to ensure even water distribution over the pads and to
prevent the bottom gutter from overflowing. The maximum length of gutter that can be served by the
watering kits and the drain kit are described in Figure 3 for various installation scenarios.
A system can be compiled in 4 easy steps
Step 1: Calculate the number of top and bottom gutter kits, drain kits and watering kits that are
required
Table 2 can be used for determining these quantities. The various combinations of lengths from 9 to 24m
are listed in the Table along with the number of each type of kit that is required to complete a system for
that length.
For sections longer than 24m, combinations of the lengths listed can be used. To ensure proper
functioning of the system the watering kits should be installed in a way that they serve very close to the
same length of gutter. The same is also true for the drain kits.
Step 2: Calculate the number of gutter side kits that are required
Depending on the installation scenario, it must be decided how many end sections are required.
Step 3: Decide on the placement of the kits
Figure 4 can be used to determine where to connect the watering kits and where to connect the drain kits.
Step 4: Determine ordering quantities
List the number of pad that needs to be ordered.

HC/MIT/CgGB-0468-05/06 WDP100-AL Calculation Guide Page 6 of 11


Munters reserves the right to make alterations to specifications, quantities, etc. for production or other reasons,
© Munters Europe AB, 2006
subsequent to publication.
WDP100-AL

Watering kits L1

L1 L1

Maximum Distance (L1):


Watering Kit-A 12m, Watering Kit-B 24m

L2

Maximum Distance (L2):


Watering Kit-A 6m, Watering Kit-B 12m

Drain kit
L3

Maximum Distance (L3):


Drain kit 12m

Figure 3: Installation scenarios and limitations

Example 3
A gutter system with a total length of 87m and a pad height of 1.5m needs to be compiled.
Step 1: Calculate the number of top and bottom gutter kits, drain kits and watering kits are
required
Because the total length is longer than 24m, the most economical solution for watering kits would be to
use Watering kit B that can serve 24m of gutter each.
Number of watering kit Bs required = 87 / 24 = 3.6
Round up and use 4 x Watering kit B
Average length per watering kit = 87 / 4 = 21.75m

HC/MIT/CgGB-0468-05/06 WDP100-AL Calculation Guide Page 7 of 11


Munters reserves the right to make alterations to specifications, quantities, etc. for production or other reasons,
© Munters Europe AB, 2006
subsequent to publication.
WDP100-AL

Table 2: Number of kits required per length


Number of top Number of Number of top Number of
Gutter Number of Gutter Number of
and bottom watering and bottom watering
length drain kits length drain kits
gutter kits kits gutter kits kits
Kit Kit Kit Kit
[m] 3m 1.8m 1.2m [m] 3m 1.8m 1.2m
A B A B

9.0 3 0 0 1 0 1 16.8 5 1 0 0 1 2
9.6 2 2 0 1 0 1 17.4 5 0 2 0 1 2
10.2 3 0 1 1 0 1 18.0 6 0 0 0 1 2
10.8 3 1 0 1 0 1 18.6 5 2 0 0 1 2
11.4 3 0 2 1 0 1 19.2 6 0 1 0 1 2
12.0 4 0 0 1 0 1 19.8 6 1 0 0 1 2
12.6 3 2 0 0 1 2 20.4 6 0 2 0 1 2
13.2 4 0 1 0 1 2 21.0 7 0 0 0 1 2
13.8 4 1 0 0 1 2 21.6 6 2 0 0 1 2
14.4 4 0 2 0 1 2 22.2 7 0 1 0 1 2
15.0 5 0 0 0 1 2 22.8 7 1 0 0 1 2
15.6 4 2 0 0 1 2 23.4 7 0 2 0 1 2
16.2 5 0 1 0 1 2 24.0 8 0 0 0 1 2

From Table 2 the closest lengths of section available are 22.2m or 21.6m. Therefore use a combination
of the two lengths (3 x 21.6 + 1 x 22.2 = 87m)
Use Table 2 to determine how many of the various kits are required
Per 21.6m section
6 x 3m top and bottom gutter kits
2 x 1.8m top and bottom gutter kits
1 x Watering kit A
2 x Drain kits
Per 22.2m section
7 x 3m top and bottom gutter kits
1 x 1.2m top and bottom gutter kits
1 x Watering kit A
2 x Drain kits
Since the 87m of gutter will be a continuous section, only 1 x Gutter side kit 1.5m high will be require
Step 3: Decide on the placement of the kits
For the placement of the water inlets, drains and the various lengths of top and bottom gutter, use Figure
4 and treat each section of 21.6 or 22.2m separately. In this way water distribution will be even and the
drains will be able to handle the water flow.
Step 4: Determine ordering quantities
To complete the whole section, the following items need to be ordered
25 x 3m top and bottom gutter kits
2 x 1.8m top and bottom gutter kits
1 x 1.2m top and bottom gutter kits
4 x Watering kit A
8 x Drain kits

HC/MIT/CgGB-0468-05/06 WDP100-AL Calculation Guide Page 8 of 11


Munters reserves the right to make alterations to specifications, quantities, etc. for production or other reasons,
© Munters Europe AB, 2006
subsequent to publication.
WDP100-AL

1 x Gutter side kit 1.5m high


Example 4
Further examples of how to compile systems are illustrated in Figure 5.
water supply

drain

length [m]

16.8

17.4

18.6

19.2

19.8

20.4

21.6

22.2

22.8

23.4
18

21

24
L= 1.2 m
L= 1.8 m
L= 3.0 m
sections

length [m]

10.2

10.8

11.4

12.6

13.2

13.8

14.4

15.6

16.2
9.6

12

15
9

Figure 4: Guide for placement of the water inlets and drains.

HC/MIT/CgGB-0468-05/06 WDP100-AL Calculation Guide Page 9 of 11


Munters reserves the right to make alterations to specifications, quantities, etc. for production or other reasons,
© Munters Europe AB, 2006
subsequent to publication.
CELdek Area:
10.2 x 1.8m
Components Used:
WDP100-AL

3 x 3m Top and bottom gutter, 1 x 1.2m top and bottom gutter, 1 x gutter sides 1.8m,1 x watering kit B, 1 x drain kit

HC/MIT/CgGB-0468-05/06

© Munters Europe AB, 2006


CELdek Area:
22.2 x 1.5m
Components Used:
7 x 3m Top and bottom gutter, 1 x 1.2m top and bottom gutter, 1 x gutter sides 1.5m,1 x watering kit A, 2 x drain kit

subsequent to publication.
WDP100-AL Calculation Guide
CELdek Area:

Figure 5: Examples of how to compile systems for various gutter lengths.


30.6 x 1.2m (15 x 1.2m + 15.6 x 1.2m)
Components Used:
9 x 3m Top and bottom gutter, 2 x 1.8m top and bottom gutter, 1 x gutter sides 1.2m,2 x watering kit A, 4 x drain kit

Munters reserves the right to make alterations to specifications, quantities, etc. for production or other reasons,
Page 10 of 11
WDP100-AL

® Euroemme and ®CELdek are trademarks of Munters AB. ® CELdek is a registered trademark of Carl Munters AB.

Munters, HumiCool Division, Kung Hans Väg 8, P.O. Box 434, SE-191 24 Sollentuna, Sweden. Phone
+46 8 626 63 00, Fax +46 8 754 56 66.
www.munters.com
Australia Munters Pty Limited, Phone +61 2 6025 6422, Fax +61 2 6025 8266, Austria via sales organization in Germany, Brazil Munters Brasil Industria e Comercio Ltda, Phone
+55 11 5054 0150, Fax +55 11 5054 0883, China Munters Air Treatment Equipment (Beijing) Co., Ltd., Phone +86 10 80 481 121, Fax +86 10 80 483 493, Denmark via sale
organization in Sweden, Finland Munters Oy, Phone +358 9 83 86 030, Fax +358 9 83 86 0336, France Munters France S.A., Phone +33 1 34 11 57 50, Fax +33 1 34 11 57 51,
Germany Munters Euroform GmbH, Phone +49 241 89 00 0, Fax +49 241 89 00 5199, Indonesia Munters, Phone +62 21 9105446-7, Fax +62 21 5310509,
Italy Munters Italy S.p.A., Phone +39 0183-52 11, Fax +39 0183-521 333, Japan Munters K.K., Phone +81 3 5970 0021, Fax +81 3 5970 3197, Kingdom of Saudi Arabia and
Middle East Hawa Munters, c/o Hawa United Cooling Syst. Co. Ltd., Phone +966 1 477 15 14, Fax +966 1 476 09 36, Korea Munters Korea Co,. Ltd, Phone +82 2 761 8701,
Fax +82 2 761 8777, Mexico Munters Mexico Phone +52 722 270 40 30, Fax +52 722 270 41 95, Norway via sales organization in Sweden, South Africa and Sub-Sahara
Countries Munters (Pty) Ltd, Phone +27 11 971 9700, Fax +27 11 971 9701, Spain Munters Spain S.A., Phone +34 91-640 09 02, Fax +34 91-640 11 32,
Sweden Munters Europe AB, Phone +46 8 626 63 00, Fax +46 8 754 56 66, Switzerland via sales organization in Germany, Thailand Munters (Thailand) Co. Ltd., Phone +66 2
645 2708-12, Fax +66 2 645 2710, United Kingdom Munters Ltd, Phone +44 845 644 3980, Fax +44 845 644 3981, USA Munters Corporation Fort Myers, Phone +1 239 936
1555, Fax +1 239 936 8858, Munters Corporation Mason, Phone +1 888 335 0100, Fax +1 517 676 7078, Export & Other countries Munters Europe AB, Phone +46 8 626 63
00, Fax +46 8 754 56 66.

Munters reserves the right to make alterations to specifications, quantities, etc., for production or other reasons, subsequent to publication.
© Munters Europe AB, 2006

HC/MIT/CgGB-0468-05/06 WDP100-AL Calculation Guide Page 11 of 11


Munters reserves the right to make alterations to specifications, quantities, etc. for production or other reasons,
© Munters Europe AB, 2006