Professional Documents
Culture Documents
Apr63 5 Basler Electric Automatic Voltage Regulator Avr Data Sheet
Apr63 5 Basler Electric Automatic Voltage Regulator Avr Data Sheet
Instructions
Publication Revision Date Page
9168700991 F 08/11 1 of 6
Instructions
Publication Revision Date Page
9168700991 F 08/11 2 of 6
When the generator is operated with the regulator for “Corner Frequency”
Generator Output
80
(% From Nominal)
generator voltage does not build up, stop the prime
mover and proceeds as follows:
60
1. With the prime mover at rest, apply an
ungrounded dc source of not more than 48 Vdc
60 Hz
to terminals F+ and F– in series with a limiting 40
resistor. Use 1 Ω of resistance for each volt from
the dc source. The resistor should have a power
20
rating of at least 1 watt per volt.
2. Allow approximately 30 seconds to elapse before
removing the dc source. 0
0 10 20 30 40 50 60
3. Start the prime mover and measure the voltage
D2717-05 Frequency (Hz)
at regulator terminals 3 and 4. If the voltage is
greater than 6 Vac, voltage buildup should occur.
Repeat the flashing procedure if less than 6 Vac Figure 1. Frequency Compensation Curves
500
is measured. 400
300
200
2
4. Rotate the VOLT control counterclockwise until
the lamp turns off. 1
70 80 90 100 110 120 130 140 150
D2717-06 135 ±5
Field Voltage (dc)
Instructions
Publication Revision Date Page
9168700991 F 08/11 3 of 6
Instructions
Publication Revision Date Page
9168700991 F 08/11 4 of 6
GEN B GEN B
C C
FIELD
FIELD 2 2
ISOLATION
2 TRANSFORMER
2
3 4
E1
SHUTDOWN
SWITCH SHUTDOWN
SWITCH
EXTERNAL
EXTERNAL VOLTAGE
VOLTAGE ADJUST
ADJUST
1 TO CBS 305
TO CBS 305 (OPTIONAL)
1 CW
(OPTIONAL) 4
CW
4 3
3
60 50
COM CB- CB+ F- F+ 4 6 7 3 240 480
HZ HZ
60 50
COM CB- CB+ F- F+ 4 6 7 3 240 480
HZ HZ APR 63-5 VOLTAGE REGULATOR
D2717-11
D2717-09
APR 63-5 VOLTAGE REGULATOR
1 Jumper for 60 Hz or 50 Hz. 3 Remove jumper if CBS 305
is used.
1 Jumper for 60 Hz or 50 Hz. 3 Remove jumper if CBS 305 2 Use 5 A, 250 V, fast-blowing,
is used. high-interrupting capacity 4 If external voltage adjust is not
2 Use 5 A, 250 V, fast-blowing, fuses. used, jumper terminals 6 and 7.
high-interrupting capacity 4 If external voltage adjust is not
fuses. used, jumper terminals 6 and 7. Figure 6. Typical Connections with
Isolation Transformer
Figure 4. Typical Single-Phase Connections
A 240 Vac
100W
480V B Lamp
GEN
C
FIELD
N
10 ohms
10W
2 2
60 50
SHUTDOWN COM CB- CB+ F- F+ 4 6 7 3 240 480
HZ HZ
SWITCH
D2717-12
APR 63-5 VOLTAGE REGULATOR
1 TO CBS 305
(OPTIONAL)
CW
4
3
60 50
COM CB- CB+ F- F+ 4 6 7 3 240 480
HZ HZ
D2717-10
APR 63-5 VOLTAGE REGULATOR
Instructions
Publication Revision Date Page
9168700991 F 08/11 5 of 6
9168700991 F 08/11 6 of 6