PUMPS SCHEDULE ELECTRIC WATER HEATERES SCHEDULE IT IS FORBIDDEN TO USE THE CAD FILES TO CHANGE OR / AND MODIFY THE
DESIGN WITHOUT WRITTEN APPROVAL FROM CONSOLIDATED CONSULTANTS.
CAPACITY ELECTRICAL DATA POWER SUPPLY
QTY ORIENTATION REMARKS KEY PLAN RTA OFFICE BUILDING
UNIT TAG LITER POWER (kW)* V / Hz / Ø NORMAL EMERGENCY 214 - 657

NO
SIKKA 30'

RT
H
ELECTRICAL DATA/ EACH PUMP ELECTRICAL FEEDER QUANTITY
FLOW HEAD EWH-01 6 30 0.8 230 / 50 / 1 Y N HORIZONTAL COMPLETE WITH ALL ACCESSORIES
PUMP LOCATION
L/S M REMARKS NOTES: ROAD 40'

RPM ESTIM. - ALL FIUGERS INDICATED WITH ( * ) ARE APPROXIMATE VALUE FINAL VALUE WILL BE AS PER FINAL SELECTED EQUIPMENT.
V / Ph / Hz DUTY
PLOT LIMIT

NORMAL / EMERGENCY TOTAL STAND BY


(KW)*

DOMESTIC BOOSTING PUMP SET, WITH PRESSURE

ROAD 40'
CWBP-01 TOP OF ROOF 5.1 50 2900 4.5 400/50/3Ø E 2 1 1 VESSEL, CONTROL PANEL AND NECESSARY ACCESSORIES G.F. + 5 PARKING FLOORS
214-744

JOKEY FIRE PUMP, WITH CONTROL PANEL AND


FJP-01 PUMPS ROOM 0.95 117 2850 2.5 400/50/3Ø E 1 1 - NECESSARY ACCESSORIES

HORIZONTAL SPLIT CASE ELECTIRC MOTOR DRIVEN FIRE ROAD 40' SIKKA 30'

FEP-01 PUMPS ROOM 63.1 112 2945 120 400/50/3Ø N 1 1 -


PUMP, WITH CONTROL PANEL AND NECESSARY ACCESSORIES

SIKKA 30'
65
9 59 4-6
65 4-8 21
21
4- 21

HORIZONTAL SPLIT CASE DIESEL ENGINE DRIVEN FIRE PUMP,


FDP-01 PUMPS ROOM 63.1 112 2945 - - - 1 1 -
WITH CONTROL PANEL AND NECESSARY ACCESSORIES SEWAGE MANHOLES SCHEDULE NOTES :
1.GROUND FINISH FLOOR LEVEL (±0.00 = 3.965)
CIRCULATING PUMP SET, WITH CONTROL PANEL M.H COVER INVERT MANHOLE MANHOLE COVER COVER
CCP-01 PUMPS ROOM 2.5 15 2900 0.8 230/50/1Ø N 1 1 1 AND NECESSARY ACCESSORIES REMARK 2.MAIN ELECTRICAL ROOM, TRANSFORMER ROOM
LEVEL (m) LEVEL (m) DEPTH (m) SIZE SIZE TYPE
NO. (m ) (m ) AND RMU ROOM TO APPROVED BY DEWA
CENTRIFUGAL TRANSEFER PUMP SET, WITH CONTROL PANEL
CWTP-01 PUMP ROOM 6.7 32 2900 4.0 400/50/3Ø N 2 1 1 AND NECESSARY ACCESSORIES MH-01 +4.165 +2.875 1.29 0.80 x 0.80 0.60 x 0.60 MEDIUM DUTY DROP MANHOLE
NOTES: MH-FIC +4.165 +2.855 1.31 0.80 x 0.80 0.60 x 0.60 HEAVY DUTY WITH 6mm THICK GRP PUSH FIT SEALING PLATE
- CONTRACTOR SHALL SUBMIT CALCULATIONS OF PUMPS TOTAL HEAD.
- THE CONTRACTOR SHALL TAKE INTO CONSIDERATION THE ACTUAL PRESSURE DROP THROUGH PIPES, FITTINGS, VALVES, EQUIP,...ETC. NOTES :-
- PUMPS TOTAL HEAD AND FLOW RATE CALCULATED WITH ALLOWANCE FOR FOUR FLOORS FUTURE EXPANSION . ALL LEVELS SHALL BE SPECIFIED EXACTLY BY THE CONTRACTOR WITH REFERANCE TO THE ACTUAL SITE LEVELS
CONTRACTOR SHALL VERIFY THE CONNECTION OF THE DRAINAGE NETWORK AND INVERT LEVEL WITH THE EXISTING MANHOLES AND LEVELS
IT SHOULD BE HIS RESPONSIBILITY TO PROVIDE ANY MODIFICATION AND NECESSARY MATERIALS REQUIRED TO CONNECT THE BUILDING WITH THE EXISTING MUNICIPALITY NETWORK

STAIRWELL PRESSURIZATION FANS


QTY. AIR ELECTRICAL DATA M.C.C. NO. ESP
DUCTED SPLIT UNITS SCHEDULE
FAN TAG TYPE CAP. REMARKS COOLING CAPACITY
ESTM. V / Hz / Ph FLOW POWER ELECTRICAL DETIALS M.C.C. NO.
NORMAL EMERGENCY Pa TOTAL CAPACITY SENSIBLE CAPACITY ON COIL OFF COIL
DUTY STAND BY (L/S) (KW) REMARKS
NO. QTY (KW*)
(KW)* (KW)* DB °C WB °C DB °C WB °C L/S V / Hz / Ø NORMAL EMERGENCY
VARIABLE SPEED DRIVER, COMPLETE WITH INLET
PF-01 3 3 CENTRIFUGAL DUCTED INLINE 7900 6.0 380/ 50 / 3Ø Y Y 300 GUARD (BIRD SCREEN) ,MOTOROIZED DAMPER DSPI-01/DSPO-01 6 7.4 5.6 - - - - 428 3.0 220 / 50 / 1 N - COMPLETE WITH ALL NECESSARY ACCESSORIES
AND ALL REQUIRED ACCESSORIES.
NOTES: NOTES:

- ALL FANS SHALL BE UL LISTED FM APPROVED. 1- REFRIGERANT TYPE SHALL BE R410a


- CONTRACTOR SHALL SUBMIT CALCULATIONS OF FANS EXTERNAL STATIC PRESSURE AND THE REQUIRED MOTOR KW 2- SELECTION BASED ON OUTDOOR TEMPERATURE OF 46.2 °C IN SUMMER & INDOOR TEMPERATURE OF 24 C° .
3- SELECTION BASED ON OUTDOOR TEMPERATURE OF 46.2 °C IN SUMMER & INDOOR TEMPERATURE OF 18 C°IN TELECOM ROOMS .

SPLIT UNITS SCHEDULE


EXHAUST AIR FANS ELECTRICAL FEEDER
ELECTRICAL ELECTRICAL DATA
AIR ESP.
NORMAL / EMERGENCY UNIT QTY COOLING CAPACITY REMARKS
ITEM NO QTY. TYPE CAP. REMARKS (TON)
ESTM. Pa POWER
(L/S) V / Hz / Ph V/Hz/ph
(KW)* (KW)*

N SPI-01 5.0 1 2.0 220/50/1Ø COMPLETE WITH ALL REQUIRED ACCESSORIES


EXF-01 41 WALL MOUNTED 25 0.1 220/50/1Ø 25 COMPLETE WITH ALL NECESSARY ACCEESSORIES
SPI-02 5.0 1.5 3.0 220/50/1Ø COMPLETE WITH ALL REQUIRED ACCESSORIES
EXF-02 WALL MOUNTED 220/50/1Ø N
12 50 0.1 25 COMPLETE WITH ALL NECESSARY ACCEESSORIES
21 2.0 3.5 220/50/1Ø COMPLETE WITH ALL REQUIRED ACCESSORIES ADDENDUM 01- 16/11/2015
SPI-03
EXF-03 1 CENTRIFUGAL INLINE FAN 360 0.30 N additional items: telecom room, 2 car parks
220/50/1Ø 110 COMPLETE WITH ALL NECESSARY ACCEESSORIES deleted items: pavement and handrail at entrance
SPI-04 16 2.5 4.0 220/50/1Ø COMPLETE WITH ALL REQUIRED ACCESSORIES
1 16/11/2015 and along core and service room
EXF-04 1 CENTRIFUGAL INLINE FAN 6400 4.5 E COMPLETE WITH ALL NECESSARY ACCEESSORIES screed finish from floors ground to 4th
380/50/3Ø 150 ramp to Sekka loength increased and slope
1- SELECTION BASED ON OUTDOOR TEMPERATURE OF 46.2 °C IN SUMMER & INDOOR TEMPERATURE OF 24 C° . decreased
NOTES: 2- SELECTION BASED ON OUTDOOR TEMPERATURE OF 46.2 °C IN SUMMER & INDOOR TEMPERATURE OF 18 C°IN TELECOM ROOMS .
REV. No DATE DESCRIPTION CHECKED
3- REFRIGERANT TYPE SHALL BE (R-407C, OR R-410A)
- CONTRACTOR SHALL CALCULATE PRESSURE LOSSES THROUGH DUCTS, DAMPERS, GRILLS, DIFFUSERS TO FINALIZE THE FAN EXTERNAL STATIC PRESSURE CLIENT:
HE SHALL BEAR FULL RESPONSIBILITY FOR DETERMINATION OF FAN EXTERNAL STATIC PRESSURE ACCORDING TO LAYOUTS. 4- ALL FIGUERS INDICATED WITH ( * ) ARE APPROXIMATE VALUE FINAL VALUE WILL BE AS PER FINAL SELECTED EQUIPMENT.
- ALL FIGUERS INDICATED WITH ( * ) ARE APPROXIMATE VALUE FINAL VALUE WILL BE AS PER FINAL SELECTED EQUIPMENT.

PROJECT NAME:
MULTI STOREY CAR PARKING
OIL/SAND INTERCEPTOR DUBAI -UAE

QTY. STSTIC HOLDING FLOW RATE DIMENSIONS


REF. SERVED AREA REMARKS CONSULTANT:
CAPACITY ( L ) ( L/s ) (mm)

OSI - 01 CAR PARKING AREAS 1 1325 2 1300 L X 1100 Ø COMPLETE WITH ALL NECESSARY ACCESSORIES.

Tel + 962 6 4612377 Fax +962 6 4612380


www.ccjo.com , ccpost @ ccjo.com

DRAWING NAME:

MECHANICAL
SCHEDULES
DESIGNED BY M. YOUSEF DATE:-
DRAWN BY CAD NOVEMBER, 2015

REVIEWED BY H. HIJJAWI STAGE:-


APPROVED BY A. HASHIMI T.D
1 UNIT = 10 mm WHEN PRINTED @ A1 SHEET SIZE SCALE:-
0 1 2 3 4 5
NTS
CC PROJECT No ZONE FAC DIS SHEET NUMBER REVISION No

2551 A 00 M4 100 01