Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

Consideration for design and installation 192

Calculation of expansion and contraction 192


Controlled pipework movement 192

191
Pipework expansion Plumbing Engineering Services Design Guide

Example 1
Consideration Calculation of What would be the increase in length and
for design and expansion and the final length of a straight copper pipe 15
metres long when subjected to a
installation contraction temperature increase from 20°C to 80°C.
From Table 1, the coefficient of linear
expansion for copper is 16.9 x 10-6rnm/K.
All pipework will expand and contract The change in length of pipework, for
longitudinally and around the both expansion and contraction, due to From Formula 1
circumference when subjected to temperature variation can be calculated AI = I x a x A t
temperature variations. using the following formula:
= 15 x 16.9 ~ 1 0x. (80
~ - 20)
The temperature variations can occur as Formula 1
a result of fluids within the pipework = 0.0152m (15.2mm)
AI = I x a x A t
being heated or cooled, or from the Therefore the pipe would expand 0.0152m
effects of external heat sources, such as where: and the final length of the pipe would be:
the surrounding air temperatures, solar
AI = The change in length of the pipe =15m + 0.0152m = 15.0152m.
heat, etc.
due to temperature change. Upon cooling down the pipe will return to its
The temperature variations can range original length, unless it has been heated
from gradual, such as the increase and
I = The original length of the pipe.
excessively to such a point where a loss in
decrease in room air temperatures, to a = The coefficient of linear expansion form hasoccurred.
almost instantaneous, such as when hot (mm/K) .
water is discharged from a sanitary
fitting, or when heated water is suddenly
At = The change in temperature to
circulated through the pipework. which the pipe is subjected (K).

Generally the change in diameter of


NOTE
‘ K denotes degrees Kelvin. This is the same
Controlled
pipework used for Building Services
Engineering will not require detailed
as a temperature rise measured in Celsius.
‘I’ can be any metric unit of measurement. pipework
consideration, other than to ensure that AI will be calculated in the same unit of
adequate clearances are maintained measurement as that used for 4: Generally
units of either metres (m) or millimetres (mm)
movement
between pipes, pipe supports, joists,
building structures, etc, to allow free will be used.
movement of the pipework. Freedom of movement
The expansion and contraction along the Consideration must be given during the
Table 1 Typical coefficients of linear design and installation of all pipework
length of pipework can however be very exoansion for various materials
significant, particularly for steam, systems to ensure that they are free to
condensate, heating, domestic hot water Material Coefficient expand and contract. The following
and certain waste pipework installations. fmmK x 1W61 important points should be considered:
Expansion and contraction within cold ABS 60 to 110.2 a. Pipework passing through structures
water pipework systems is minimal and Aluminium 25.6 should be provided with sleeves or
generally does not require any special Brass 19 installed through neatly formed holes,
consideration. Bronze 18 to enable unrestricted movement.
It should be noted that the rate of Cast iron 12 This includes walls, floors, ceilings,
expansion and contraction varies as a Chromium 7 floorboards, floor joists, etc. It must
result of the type of material, as well as Copper 16.9 be ensured that the pipework will not
the temperature variation. PVC pipework, Duralumin 23 come into contact with the sleeve or
for instance, will expand at over three Lead 29
wall of the hole. Any mastic or other
times that of copper, for the same material used to fill the gap must
Mild Steel 11.3
temperature rise. permit movement of the pipe.
Nylon 80
Damage and failure from stress and Polyethylene High Density 140.2 b. Felt pads, or similar, should be
strain can occur to pipework systems, Polyethylene Low Density 225 provided between pipework and
pipework support systems and building PVC unplasticised 60 to 100
notched joists, and between adjacent
structures unless careful consideration is pipes which may come into close
Tin 21
given to the change in pipework length contact with each other.
Zinc 30
due to temperature change and the c. Pipe clips, supports and guides must
direction in which the expansion and not restrict the movement of the pipe,
contraction will take place. NOTE
1P6indicates that the decimal point of the particularly on long pipe runs.
value being considered should be moved six d. Where it is necessary to bury the
places to the left, eg: 10.2 x 1U6equates to pipework in the screed, provision
0.0000 102.
must be incorporated to prevent
damage to the pipework and screed.
This could take the form of a
proprietary plastic coated pipe
wrapped in fibreglass and the whole
surrounded with expanded metal or
similar.

192
~~

I
Plumbing Engineering Services Design Guide Pipework expansion

- Short length of pipe, taken Pipework provided with additional bends to


Dotted line indicates how the Anchor)<, rom original of 'carryin accommodate expansion shown in solid line,
pipework will expand away , iipe' (the length split with 4 anchor positions.

J
from anchors I
I
I

.----- - _ _ _ _ _ ,,
I
Anchor
A
I

------ - - _ _ _ _ _ !
I
I
I
I
I
I
I
I
I

>(Anchor
-L / I
Originally intended pipework route
Figure 7 Typical anchor positions solder
shown dotted. .;,
Figure 2 Typical anchor for copper pipework Figure 5 Providing additional bends to
e. Ensure that any branches connected accommodate pipework expansion
to expanding pipework (eg:
Plastic coated
connections to radiators), are of Socket saddle strap
adequate length to provide natural
flexibility to prevent the connection
shearing.
f. Ensure that expanding pipework will
not clash with structures. channel ~ I/ \I Socket LAnchor AnchorA

g. The direction of pipework expansion


must always be controlled using Figure 3 Typical anchor for steel pipework Figure 6 Expansion loop/horseshoe section
suitable anchors, guides and clips. (light load)
Standard pipework clips may be
adequate for short pipework lengths Pipework expansion
of small bore copper and plastic.
devices
h. Open type pipe clips must not be
used where there is a possibility of
Heavy mild steel strap
welded to pipe; bolt
to support
1 Angle or channel
support
dependent on If expansion and contraction of pipework
the pipe springing away from the clip. cannot be controlled with the use of
anchors alone, then consideration must
The above requirements are also Locking be given to providing additional devices
essential to ensure that excessive channel/an to enable movement to take place. These
frictional noises do not occur as a result not require include:
of expansion and contraction. for lightly
loaded a. Routing pipework with additional
anchors
bends or offsets
Anchors b. Providing purpose designed
loop/horseshoe sections in the
Where expansion is excessive, pipe This anchor may be used for copper pipes
movement must be controlled by pipework
using brass strap.
installing anchors. Anchors restrain the c. Installing expansion bellows or
pipework ensuring that any movement comDensators
due to expansion occurs in a direction Figure 4 Typical light to medium load anchor
d. Providing expansion couplings for soil
away from the anchor.
and waste pipework systems.
Anchors are usually fixed to the middle of
c. The anchor fixings to the building The provision of additional bends, offsets
the pipe to enable the pipe to move in structure are adequate or loop/horseshoe pipework systems
two directions, therefore effectively
d. The building structure itself, to which must provide adequate natural flexibility
halving the maximum change of
the anchor is fixed, is adequate to to accommodate the pipework
pipework length in any given direction.
accept the forces. expansion.
Sometimes however, it is desirable to
provide an anchor at one end of a pipe Where necessary, the advice of a Expansion bellows or compensators are
run, for instance, to prevent a pipe from structural engineer should be obtained to proprietary manufactured devices,
coming into contact with an adjacent ensure the anchor and support designed to accommodate or absorb
wall. arrangements are adequate for the expansion and contraction.Various
When anchors are installed to control anticipated forces which may be exerted. different types of these devices are
expansion, forces will be exerted on the available. It is essential that the
anchor. It is therefore essential to ensure manufacturer be consulted for their
that: particular recommendations regarding
the most suitable type for the situation
a. The anchor is adequately secured to and for their requirements for anchors
the pipe and guides.
b. The anchor itself is structurally
adequate

193
Pipework expansion Plumbing Engineering Services Design Guide

The following points should be noted Supports and pipe guides For guides nearest the bellows, the
when using expansion bellows or clearances between the outside pipe and
compensators: The purpose of a support is to transfer inside guide walls should not be greater
the load of the pipe and the contents than 1.6mm for pipe diameter up to
a. Axial type bellows must not be used IOOmm and not greater than 3.2mm for
within the pipe safely to a structure. The
where the pipe is hung or suspended larger pipes. For the guides along the
pipe support should reduce deflection of
freely. The pipe supports must guide pipe run, maximum clearances of 3.2mm
bending of the pipe.
the pipe and allow only axial
and 6.4mm respectively should be used.
movement along the entire length of The purpose of a pipe guide is to control
the pipe. the direction in which a pipe will move
when it expands. A pipe guide is any
b. It is essential to ensure that the pipe
form of constraint which allows the pipe Guides nearest
is guided carefully on each side of
the bellows. The guides must allow
true axial movement along its length but the bellows
prevents offset movement whether
only axial movement onto the The function of guides closest to the
horizontal or vertical. Pipe guides can,
bellows. bellows is to ensure true axial movement
however, be designed to also provide a
c. It is essential to ensure that the pipe support facility. Some typical pipe guides on to the bellows. This can be achieved
is guided carefully at the necessary are indicated in Figures 7 to 11. by using a tubular type guide (as Figure
intervals along the whole pipe run. 10) of such length that the necessary
clearances to permit axial movement do
d. Only the bellows unit should be not allow appreciable offset movement.
installed between two pipe anchors. Generally a tubular guide having a length
e. The line between two anchors should to diameter ratio of 6:l will be adequate.
be straight, in plan and in elevation, Tubular guides are generally only fitted to
with no sets or bends. small pipes. For larger sizes (50mm and
f. Pipe anchors must be of adequate over), proprietary straps and roller guides
strength. are normally employed. Straps and roller
guides are short and individually cannot
g. Bellows must be stretched by half the Figure 7 Strap-type guide control angular movement of the pipe. To
total expansion movement (cold- ensure alignment of the pipe onto the
draw). This does not apply to special bellows, an additional set of guides is
applications or ‘pre-cold drawn’ units. required as follows.
h. Screwed end units must be held firm
when installing to prevent twisting of
the bellows. I-IYz pipe
The most common method of providing
the facility for expansion and contraction
(c,
I 7
lllllllt
r diameters

in plastic soil and waste pipe systems is Figure 8 Strap-typeguide with tube roller
l-----I
the use of proprietary expansion Tubular guides 5-6 pipe
couplings incorporating socket and spigot diameters
joints having rubber sealing rings. The
couplings should be of the same Figure 12 Guide near bellows
manufacture as the pipework system.
The expansion couplings should be I I
introduced at 1.8 metre intervals or as
recommended by the manufacturer, to
connect pipes together.
Plastic pipework should be anchored and
supported in accordance with the
Figure 9 Strap-typeguide with roller and chair
I/ Guides as
necessary
7
I - I pipe
~
diameters

manufacturer’s recommendations.This BeIIow s 15-20 pipe


will depend on the system employed. diameters

Figure 13 Installation of additional strap and


roller guides

Figure 14 Pipework failure may occur without


figure 10 Tube-type Guide pipe guides
Figure 11 Slip-on Flange Type Guide
I Bowing force

Clearance

Correct guides
1 Anchor

1 Andhor No ghdes

194
Plumbing Engineering Services Design Guide Pipework expansion

A
It is essential to ensure that the complete
pipe run is adequately guided and not
just local to the bellows. If this is not
carried out, the pipework may bow
outwards as a result of the compressive
forces imposed on it.
It is essential that all support
Ci = 0.3
arrangements, except for purpose
designed anchors, enable controlled
pipework movement. If the pipework is ~~

incorrectly restrained, damage to the Figure 18a Point contact Figure 186 Line contact
pipe supports or structure may result,
due to excessive friction or forces.

Cold draw of bellows


It is normal for bellows to be ‘cold drawn’
(eg. stretched) by half the total calculated
expansion when installed into a pipe. The
U Ci = 0.25
bellows will then absorb the total Ci = 0.4
expansion, half in tension and half in
compression from the neutral position. Figure 18c Line contact Figure 18d Face-to-face contact
This keeps the stress in the bellows
material to a minimum for a given Cold draw can be achieved by:
expansion and provides maximum
Calculating forces
bellows life. a. for flanged bellows: on anchors
Leaving a gap internally between the
In steam and high temperature heating bellows and pipe flange at one end of The following main factors have to be
applications, it is not necessary to allow the unit and then tightening up the taken into consideration when
for ambient temperature variation flange using over-sized flange bolts. determining forces on anchors:
(dayhight, summer/winter) when
installing the bellows, since this variation b. for screwed bellows: a. The effect of test pressure on the
is very small compared with the working Under-cuttingthe length of an cross-sectional area of any bellows
temperature range. However, on low adjacent pipe section and allowing installed within the pipework system.
temperature applications, allowances the thread of a connecting union to
b. The elasticity force to stretch and
must be made when calculating cold expand the bellows. Care must be
compress bellows installed through
draw. Where very small movements, taken that the bellow is not twisted
the working movement.
vibration or subsidence are to be during the tightening process.
absorbed, the bellows manufacturers c. Frictional forces between the pipe
c. for welded end bellows:
often recommend that cold draw is not and pipe supports, acting against the
Installing a pair of flanges in the
used. direction of movement.
pipework adjacent to the bellows with
a gap initially between the flange d. The slope of the pipe, affecting the

,
,
II II I ,1
II I 1 I I I I
I Bellows - cold draw

1 Bellows - neutral I
faces and then tightening up the
flange using over-sized flange bolts.
d. for all bellows:
lower anchor (vitally important if the
pipe is vertical).
e. Fluid pulsation and flow effects in the
I I Bellows-
By purchasing pre-cold drawn pipe.
hot bellows.
I f. Differential forces due to changes in
Total expansion
Cold draw movement pipe diameter.
Quoted friction coefficients between
pipework and supports vary considerably
Figure 15 Cold draw in expansion bellows but the values shown in Figures 18(a),
(b), (c), and (d) may be used as a
general guide for steel on steel.
The frictional resistance (kg) = dead load
at point of support (kg) x coefficient of
friction.

Figure 16 Taking up cold draw on flanged bellows


Figure 19
Figure 17 Taking up cold draw on welded end bellows

Anchor BeIIow s
Anchor
Guide at necessary
intervals

~~

195
Pipework expansion Plumbing Engineering Services Design Guide

This resistance acts against the direction Pipework system under test conditions vi. The pipe between bellows and
of movement e.g. it can act either way, anchors is frequently in compression
depending on whether the pipe is Thrust due to internal pressure on bellow
and unless the pipe is guided
warming up or cooling down. = test pressure x effective area carefully, and runs accurately in a
Should the above figures give straight line from anchor to anchor,
= 830 x 1O3 x 0.023N
unacceptably high forces consideration the pipe may bow out sideways. This
= 190909 pushing outwards on anchors will pull the bellows with it and may
could be given to using special PTFE
support pads which gives figures as low Force due to bellows stiffness (bellows cause failure.
as 0.02. stretched in cold-draw position) vii. Never use axial bellows in pipework
= 6700N pulling inwards on anchors systems incorporating suspended
Example 2 hanger supports or any other support
Frictional resistance systems which can readily swing.
The following example illustrates the = NIL as pipe only moves under
calculation to determine the force imposed viii. Confirmation should always be
temperature effect obtained from the bellows
on an anchor under normal working and
test conditions on a pipework installation Total thrust on anchor manufacturer regarding any special
indicated in Figure 19, which incorporates requirements they may have
=19090-6700
axial type bellows. regarding the position of anchors and
= 12390N pushing outwards on guides.
The designer must obtain the relevant data anchors.
from the bellows manufacturer.
It can be seen in this instance that the
Pipe weight = 22kg/m greatest force acting on the anchor is under
Water weight = 19.5kgh normal working conditions, this however is
Lagging weight = 6kgh not always the case.
Effective area of bellows = 0.023m2
Thrust to compress or extend bellows
through full movement = 6700N The following important points should be
from manufacturer’s data (Newtons) considered when installing bellows:
Coefficient of friction between I. When a fitting such as a bend, valve
pipe and supports = 0.3 or distance piece is installed into a
System working pressure = 550kPa pipe and subjected to internal
(550 x 1 0 3 ~ 4 pressure. The fitting will act just like a
System test pressure = 830kPa pipe itself, holding the internal
Length of pipe = 42.5 pressure, but not pushing or pulling
on the pipe.
Pipework system under ii When an axial bellows is fitted into a
normal working conditions pipe and subjected to internal
pressure, it reacts to the internal
Thrust due to internal pressure on bellows pressure by trying to open out
= working pressure x effective area lengthways. An outward pressure is
therefore exerted by the bellows.
= 550 x 103x 0.023N
iii, When a pipe restrained by an anchor
= 12650N pushing outwards on anchors
at one end, but otherwise free to
Force due to bellows stiffness (bellows move longitudinally, is subjected to
compressed in working platform) heat, it will expand away from the
= 6700N pushing outwards on anchors. anchor position, exerting an outward
force away from the anchor.
Frictional resistance to pipe movement over
its supports: iv. When a pipe anchored at two points
and provided with a bellows between
= coefficient of friction x (total weight of the anchor points is subjected to
pipe + water + lagging) heat, pressure is exerted by both
= 0.3 x [(22 x 42.5) + (19.5 x 42.5) pipework sections towards the
+ (6 x 42.5)Ikg bellows. Meanwhile the pressurised
bellows is exerting pressure outwards
= Converted to Newtons (1kg = 9.807N)
towards the two anchor points.
= 0.3 x [(22 x 42.5 + (19.5 x 42.5)
+ (6 x 42.5)] x 9.807N V. When the pipe gets hot, it expands
towards the bellows and tries to
= approximately 6000N against the compress it. Meanwhile, the
direction of movement, eg. pushing pressurised bellows is trying to open
outwards on anchors. out lengthways. The expanding pipe
Total Thrust on Anchor therefore has to overcome this
pressure force as well as the stiffness
= 12650 + 6700 + 6000 of the bellows and the friction of the
= 25350N (Newtons) pushing outwards pipe supports. Hence the need for
on anchors. firm anchors at each end of the pipe
run, and careful guiding not only on
each side of the bellows but also
along the pipe run.

196

You might also like