Ficha Tecnica 750 GPM
Ficha Tecnica 750 GPM
NAFFCO LLC
World Headquarters Jebel Ali Free Zone Dubai, U.A.E.P.O. Box: 262169
Phone :+971 4 2971720 Fax: +971 4 8816229
Email :pumps@naffco.ae Web: http://www.naffco.com
SL.NO ENCLOSURES PAGE NO.
40 JOCKEY PUMP Product Catalogues 106
41 JOCKEY PUMP Pump Document 107
42 JOCKEY PUMP Prime Mover Document 112
43 JOCKEY PUMP Accessories Document-Jockey Pump Controller 117
44 Attachments 126
45 Listings & Approval 127
NAFFCO LLC
World Headquarters Jebel Ali Free Zone Dubai, U.A.E.P.O. Box: 262169
Phone :+971 4 2971720 Fax: +971 4 8816229
Email :pumps@naffco.ae Web: http://www.naffco.com
Quote # : NAFF-H01-EXP-423 (0) Date : 21/11/2017
Project : PROJECT IN ECUADOR Reference : 14756 C
Location : ECUADOR Contractor : NIL
Project Owner : VESEIND S.A Consultant : NIL
Pump Purchaser : VESEIND S.A
Make KRUEGER SENTRY GAUGE Bushing 2 (In) Material Rods-GS & Floats - HDPE
Remote Mount W/O ALARM Alarm Box N/A Depth 32 (In)
Make NAFFCO Flame Resistant W/O FLAME RESISTANT PIPE Fuel System 150
Features Standard
Make FACTORY CHOICE Type CALCIUM LEAD GRID Set(s) Config 24 VDC,2# (=12 VDC,4#)
Single Battery 12 (V DC) No Of Batteries 4 Battery Length 510
Battery Width 275 Capacity Hour 20 (Hr) Ampere Hour 200 (Ah)
Certification NON-CERTIFIED
GENERAL NOTE:
1 NO INDUSTRIAL MUFFLER
Speed (RPM) Driver PumpModel NF-S-150-100 Pump Test Std ANSI/HI 14.6-2011
2900 Motor Flow 750.0 USGPM Head 120.0 PSI Stage 1 Impeller Dia 253.0 mm
Application Range
Duty Power 63.47 Kw 85.08 HP Flow @150% 1125 USGPM Size Pump Nozzle Recommended Pipe Size
Peak Power 78.8 kw 105.63 HP Shut Off Head 129 PSI Discharge (In) 4 8.00
CQ= 1 CH= 1 CE= 1
Prepared By/Checked By sankar
Tag Number ELECTRIC PUMP Offer No NAFF-H01-EXP-423
Date 21/11/2017
In line with NAFFCO policy for continuous product development, NAFFCO has the right to change specifications without prior notice
Reference: NF-S-150-100-2900
Actual pump performance and impeller diameter values may vary ± 5% which is within normal permissible / expected range
Operating Conditions
Fluid Water
Specific Gravity 1
Temperature -
Viscosity 0 Cst
Speed 2900 RPM
Duty Flow (Q) 750.0 USGPM
Duty Head (H) 120.0 PSI
Suction Pressure 1m
Pump Set Configuration
Pump Test Std ANSI/HI 14.6-2011
140% limit of H at shut-off 168 PSI
65% limit of H @150% of Q 78 PSI
Notes:
In line with NAFFCO policy for continuous product development, NAFFCO has the right to change specifications without prior notice
Actual pump performance and impeller diameter values may vary ± 5% which is within normal permissible / expected range
World Headquarters Jebel Ali Free Zone Dubai, U.A.E.P.O. Box: 262169
www.naffco.com
Referance No :-14756 C Page 11 of 153
NAFFCO
Listed
Fire Pumps
2900 RPM
NAFFCO FZCO is among the world’s leading firefighting technology and fire safety solutions, NAFFCO
manufacturers and suppliers of top-tier firefighting has worked in both the private and government sectors,
equipment, fire protection systems, fire alarms, security as well as manufacturing plants, hospitals, stadiums,
and safety engineering systems worldwide. Since malls and other organizational projects, delivering
its humble beginnings, NAFFCO has grown from its comprehensive fire safety and engineering solutions.
headquarters in Dubai, UAE to expand to serving over
100 countries around the world. NAFFCO is associated with globally renowned
international companies in the fire protection industry
such as Esser, Secutron, Megalights, Evax, Fike, Central,
One Stop Shopping for All Your Fire Safety Shield, Mueller, Giacomini, RB Pumps, Bombas, Ideal
and Security Needs Pumps, Joslyn Pumps, Peerless Pumps.
FEATURES
• Performance characteristics as per NFPA 20
• Complete unit responsibility.
• Complete in-house fabrication capabilities.
• Hydrostatic testing facilities.
• Operation run test as per NFPA 20, UL 448 and
FM 1311 requirements.
• Horizontal Split case pumps for capacities from 750
to 1500 US GPM.
• Drivers: Electric motor drive or diesel engine drive.
• Electrical testing capabilities for motors and
controllers as per NFPA standards.
• Capable of supplying additional accessories wherever
required.
SHAFT SEAL:
are provided for additional cooling of the graphite
impregnated type gland packing.
DESCRIPTION
No. Part Name Material Qty.
1 Lower Casing Cast Iron ASTM A48 Class 40 1
2 Upper Casing Cast Iron ASTM A48 Class 40 1
3 Impeller Bronze SAE 40 1
4 Shaft Sleeve Stainless Steel AISI 420 2
5 Bearing Cover Cast Iron ASTM A48 Class 40 2
6 Gland Bronze SAE 40 2
7 Cast Iron ASTM A48 Class 40 2
8 Shaft Alloy Steel AISI 4340* 1
9 Wear Ring Bronze SAE 40 2
10 Flushing Pipe Stainless Steel, Gr. 304 2
11 Coupling Key Stainless Steel AISI 420 1
12 Gland Packing Graphite Impregnated 8
13 Lantern Ring Bronze SAE 40 2
14 Bearing Housing Cast Iron ASTM A48 Class 40 2
*Optionals shaft materials are available - AISI 316 (except for NF-S-150-100-375), Duplex 2205 or Duplex 2507
CAT.NO.NF/ULFP2900/01/15
NAFFCO FZCO
World Headquarters
Dubai, United Arab Emirates
Email: info@naffco.com
www.naffco.com
In line with NAFFCO policy for continuous product development,
NAFFCO has the right to change specifications without prior notice.
Referance No :-14756 C Page 17 of 153
FIRE PUMP MOTOR
www.naffco.com
Referance No :-14756 C Page 18 of 153
FIRE PUMP MOTORS
OPEN DRIP PROOF
BUILT TO SERVE
With Open Drip Proof enclosures, they provide best possible ventilation suitable for environments
having minimal airborne contaminants and better cooling that contribute to the most efficient
performance available from these motors.
FEATURES
15 to 350 horse power rating
400 – 415 voltage rating at 50 hertz
NEMA Energy efficient design
1.15 Service Factor
Class F insulation
50 °C Ambient Temperature rating*
Regreasable Ball Bearing
Cast Iron construction frame
Frame size from 254T to 449TS
UL File No. EX26863
Stainless Steel name plate
RAL 3000 Standard red painted
IP23 Degree of Protection
Locked Rotor indicating code letter: H
Altitude rating of 1000 meters above sea level*
F1 foot mounting
2 Pole, 2920 - 2945 rpm speed**
Temperature Rise below Class B (80 K)
Suitable for various standard starters such as
across the line, wye-delta, soft starter etc.
NOTE:
** Derating may be required for higher values.
** Rated speed of the motor varies depending on motor size
and it is mentioned on the next page.
CAT.NO. NF/NAT-UL/06/16
Email: info@naffco.com
www.national-motors.com | www.naffco.com
In line with NAFFCO policy for continuous product development,
NAFFCO has the right to change specifications without prior notice.
www.naffco.com
Referance No :-14756 C Page 23 of 153
Micro
Processor
Based
Fire Pump
Controllers
NAFFCO was founded in Dubai, UAE to become the world’s leading Our products have been consistently certified by UL, FM, BSI, LPCB
producer and supplier of life safety solutions. By recognizing the and Global Mark according to the latest International Quality
importance and convenience of having easy access to multiple Standard for their strict adherence to ISO 9001 quality management
safety services, we became specialized by offering complete system and certified for ISO 14001 environmental management
solutions under one roof for all types of high quality firefighting systems and BS OHSAS 18001 for occupational safety by UL DQS.
equipment, fire protection systems, fire alarms, addressable
emergency systems, security systems,custom-made vehicles such Our success is driven by our passion to protect; our vision is to
as fire trucks, ambulances, mobile hospitals and airport rescue become the world’s number one provider of innovative solutions
firefighting vehicles (ARFF). in protecting life, environment and property.
RATING
Motor Power Rated Voltage Frequency Rated Current Short Circuit Rating
(HP) (V) (Hz) (A) (KA)
15 27
20 34
25 44
30 51
40 66
50 83
60 103
75 128
380 - 415 50 / 60 100
100 165
125 208
150 240
200 320
250 403
300 482
350 560
400 636
Power ratings vary from 15 to 400 horsepower, 230 / • Circuit breaker with shunt trip coil and rotary handle.
380 / 415 VAC, 50/60 Hz. • Rated motor connectors.
• Emergency run mechanism to mechanically close
Only high quality UL listed or UL recognized motor connector contacts to start motor in case of
components are used in these panels to guarantee emergency.
the best possible reliability. Also high quality UL listed • Manual start and stop push buttons.
enclosures are used. • 20x4 LCD display showing all system parameters and
variables.
This controller is completely wired, assembled, • User friendly software enables user to program all
programmed and tested at the factory before related parameters like timers, pressure, inputs, outputs
shipment, and ready for immediate installation. … etc.
STANDARD FEATURES • Shows 3 phase line voltages.
• 230 / 380 / 415 VAC, 50/60 Hz main 3 phase system • Shows 3 phase line motor currents.
power. • Shows real value of discharge pressure.
• Voltage Surge Protector. • Shows motor running hours.
• Main disconnecting switch with rotary handle sized for • Shows ambient temperature.
disconnecting motor horsepower and voltage. • Starting delay timer (programmable) for sequence
• Motor Run indicator/free contact. multiple pumps starting.
• Phase Loss/Failure alarm / indicator / free contact. • Automatic or manual shutdown after automatic start
• Phase sequence error alarm/indicator / free contact. (selectable).
• System error alarm / indicator / free contact. • Automatic shutdown mode enabled/disabled indicator.
• Fail to start alarm / indicator. • Power ON/Healthy indicator.
• System error alarm / indicator. • Automatic mode indicator.
• Pump lockout indicator / free contact. • Manual mode indicator.
• Push button for alarm silence • Remote start on alarm / indicator / free contact
(only for additional alarms). (programmable).
• Motor locked rotor trip at 600% of FLA, after • Manual local start on alarm/ indicator / free contact
programmable time delay. (programmable).
• Programmable automatic test, which can be • Fail while run alarm / indicator / free contact
programmed to start at any desired day, hour and (programmable).
minute in the week. • Emergency start on alarm / indicator / free contact
• Manual test push button. (programmable).
• Motor overload alarm/ indicator / free contact • Test on alarm/ indicator / free contact (programmable).
(programmable). • 10 additional programmable indicators (LED’s).
• Over voltage alarm/indicator / free contact • 10 additional programmable auxiliary digital inputs.
(programmable). • 7 additional programmable output relays (free
contacts).
• Pressure transducer with analog voltage output.
• Data logging system for pressure and events.
• USB port for saving recorded pressure and events
on USB memory, and can be viewed with MS word
and Excel.
• Electrically actuated built in discharge solenoid valve.
• Under voltage alarm / indicator / free contact
(programmable).
• Low discharge pressure alarm / indicator / free
contact (programmable).
• Deluge valve on alarm / indicator / free contact
(programmable).
• Electrical alarm bell.
• UL listed NEMA 2 enclosure.
ENCLOSURE OPTIONS:
• NEMA 3
• NEMA 4
• NEMA 12
www.naffco.com
Referance No :-14756 C Page 32 of 153
5 1/8”
23 OPTIONAL
14
21 OUTLET
4
2 7
6
3
8 3/8”
13 34
12 1
10
11 6"
17 5
LISTED
28WL
FM
APPROVED
TEST PRESSURE
1.5 TIMES WORKING PRESSURE (W.P.)
INLET
SEE DRAWING NO. VM-22-M FOR STANDARD MATERIAL OF CONSTRUCTION.
VALVE MODEL INLET OUTLET MAX. W.P. ORIFICE
SIZE NO. ** SIZE SIZE P.S.I. SIZE
1 / 2 "_ 3 / 4 " * 22.4 3 / 4 " N .P. T. 1 / 2 " N . P. T. 175 3/32"
1 Scope
1.1 This specification is intended to cover the design, manufacture, and testing of 1 in. through 3 in. Well
Service Air Valves suitable for clean or raw water service in fire protection applications with pressures up to
300 psig.
1.2 Well Service Air Valves shall be fully automatic float operated valves designed to exhaust air which is
present in the vertical pump column on pump startup and allow air to re-enter the column on pump shutdown
or should a negative pressure occur. A top mounted Throttling Device shall provide adjustable control of the
exhaust rate.
2 Connections
2.1 Valve sizes 3 in. (76 mm) and smaller shall have full size NPT inlets and outlets equal to the nominal
valve size.
2.2 The body inlet connection shall be hexagonal for a wrench connection.
3 Design
3.1 The valve body shall provide a through flow area equal to the nominal valve size. A bolted cover with
alloy screws and flat gasket shall be provided to allow for maintenance and repair.
3.2 Floats shall be unconditionally guaranteed against failure including pressure surges. The float shall
have a hexagonal guide shaft supported in the body by circular bushings to prevent binding from debris. The
float shall be protected against direct water impact by an internal baffle and stainless steel diffuser screen to
break up the solid water column before coming in contact with the float.
3.3 The resilient seat shall provide drop tight shut off to the full valve pressure rating. The seat shall be a
minimum of 1/2 in. (12 mm) thick on 2 in. (50 mm) and larger valves and secured in such a manner as to
prevent distortion. The seat shall be precision molded with an o-ring type sealing surface and a slot in the
seat opening to provide a positive seal at low pressures.
3.4 Valves shall be equipped with a throttling device to control the discharge of air from the valve. The
device shall have an externally adjustable screw and locknut for adjusting the discharge control disc.
4 Materials
4.1 The Well Service Air Valve body, cover, and baffle shall be constructed of ASTM A126 Class B cast iron.
4.2 The float, guide shafts, and bushings shall be constructed of Type 316 Stainless Steel. Non-metallic
guides and bushings are not acceptable.
4.3 The seat shall be Buna-N capable of providing drop tight shut off at the valve full pressure rating.
5 Manufacture
5.1 The manufacturer shall demonstrate a minimum of five (5) years experience in the manufacture of air
valves. The valves shall be Underwriters Laboratories Listed and manufactured and tested in accordance
with American Water Works Association Standard (AWWA) C512.
5.2 The exterior of the valve shall be coated with a universal alkyd primer.
5.3 Well Service Air Valves shall be Series #101WST as manufactured by Val-Matic® Valve & Mfg.
Corporation, Elmhurst, IL. USA. or approved equal.
Revised 7-28-04
DATE
FIRE PROTECTION WELL SERVICE AIR VALVE SPECIFICATION 12-19-97
DRWG. NO.
®
AL ATIC VALVE AND MANUFACTURING CORP. SS-1439
Referance No :-14756 C Page 34 of 153
CASING CIRCULATION RELIEF VALVE
www.naffco.com
Referance No :-14756 C Page 35 of 153
Specifications BY003 • Issue Date May 2014
The FW and FWC valves have standard factory pressure settings of 125 psi. The FWC has an
external adjusting screw which allows for occasional changes in pressure setting.
The Cash Acme FW and FWC Valves feature a brass body, silicone seat disc, and stainless
steel pressure spring.
Lead Free* versions of FWC models are also available.
SPECIFICATIONS
FW: A miniature relief valve shall be installed to relieve pressure for applications where tight
shut-off is required. The valve shall be of brass construction with a male inlet and female outlet.
The valve shall have a silicone seat disc and a stainless steel pressure spring. The valve shall
be a Cash Acme FW Relief Valve.
FWC: A miniature relief valve shall be installed to relieve pressure for applications where tight
shut-off is required. The valve shall be of brass construction with a male inlet and female outlet.
The valve shall have a silicone seat disc and a stainless steel pressure spring. The valve shall
have an external adjusting screw to allow changes to the set pressure. The valve shall be a
Cash Acme FWC Relief Valve.
* A device is defined as Lead Free if its normally wetted surface has a weighted average lead
content not exceeding 0.25%
SPECIFICATION DATA
Performance:
Set pressure range …………………….. 15 - 200 psi (Type FW) and
25 - 175 psi (Type FWC) factory set at 125 psi
Maximum temperature ………………… 210° F
Service ………………………………….. Water
Materials:
Body …………………………………….. Brass
Pressure Spring ………………………... Stainless steel
Seat Disc ……………………………….. Silicone
CONNECTIONS
Threaded (NPT) ……………………….. Male inlet and female outlet
CERTIFICATIONS
The Cash Acme FW and FWC miniature relief valves are non-code valves.
www.naffco.com
Referance No :-14756 C Page 38 of 153
bourdon tube pressure gauges
anti-vibration version MS4
DS 4” (100mm)
Laser calibration up to 400bar
Free zero
Safety plug
Compliance to requirement of
PED 97/23/EC
Instruments designed for use on power units, pump, hydro-cleaning machines, presses, engine compressors, turbines, diesel engines,
chemical, petrochemical and refrigerating plants and on machines and equipment where pulsating pressures or mechanical vibrations
are apparent. They can be used with gaseous or liquid media which do not corrode copper alloy and which do not have high viscosity
or do not cristalize.
Design: EN 837-1.
Safety designation: S1 as per EN 837-2.
Ranges: from -1...0 to 0...15000 PSI (from 0...1 to 0...1000 bar or
other equivalent units).
Accuracy class: 1,6 as per EN 837-1.
Ambient temperature: -13...+149°F (-25...+65 °C).
Process fluid temperature: +212°F (max +100 °C).
Thermal drift: max ±0,4 %/10 K of ranges (starting from 68°F- 20°C).
Working pressure:
75% of FSV for static pressure;
66% of FSV for pulsating pressure.
Overpressure (max 15 min):
25% of FSV of ranges ≤ 1500 psi (100 bar);
15% of FSV for ranges over 1500 psi (100 bar).
Protection degree: IP 67 as per IEC 529.
Socket material: copper alloy, with internal restrictor ø 0.03”
(0,8 mm)
Bourdon tube:
copper alloy for ranges ≤ 10000 psi (600 bar);
AISI 316L st.st. for ranges 15000 psi (1000 bar).
Case: stainless steel.
Ring: stainless steel, polished , crimped.
Window: tempered glass.
Movement: copper and stainless steel.
Dial: aluminium, white with black markings
Pointer: not adjustable, aluminium,black
RB4 - 01/09
IN ORDER TO IMPROVE THEIR PRODUCTION, MESSRS. NUOVA FIMA RESERVE THE RIGHT TO THEMSELVES TO MAKE ALL THE MODIFICATIONS THAT THEY DEEM INDISPENSABLE AT ANY TIME. UPDATED DATA-SHEETS ARE AVAILABLE ON SITE: www.nuovafima.com
A - LOWER CONNECTION D - BACK CONNECTION
(1) Add 0.5 Ibs (0,23 kg) when filled - (2) Add 0.53 Ibs (0,24 kg) when filled - (3) quote “e” will become 0,73 lbs (18,5 mm) within 2009
RANGES bar kPa MPa bar ext. bar ext. bar ext. RANGES psi psi ext. psi ext. RANGES bar kPa bar ext. bar ext. RANGES psi* psi ext.* psi ext.*
(1)
bar int. kg/cm 2 int. psi int.* kPa int. Bar int. kg/cm 2 int.
psi int. kPa int. MPa int.
0...15 ✦ ✦ ✦ -1...0 ✦ ✦ ✦ -30...0 ✦ ✦ ✦
0...1 ✦ ✦ ✦ ✦
0...30 ✦ ✦ ✦ -1...0,6 ✦ ✦ ✦ -30...15 ✦ ✦ ✦
0...1,6 ✦ ✦ ✦ ✦
0...60 ✦ ✦ ✦ -1...1,5 ✦ ✦ ✦ -30...100 ✦ ✦ ✦
0...2,5 ✦ ✦ ✦ ✦
0...100 ✦ ✦ ✦ -1...3 ✦ ✦ ✦ -30...150 ✦ ✦
0...4 ✦ ✦ ✦ ✦
0...160 ✦ ✦ ✦ -1...5 ✦ ✦ ✦ * vacuum measurement unit : "inHg"
0...6 ✦ ✦ ✦ ✦
0...200 ✦ ✦ ✦ -1...9 ✦ ✦ ✦
0...10 ✦ ✦ ✦ ✦
0...300 ✦ ✦ ✦ -1...15 ✦ ✦ ✦
0...16 ✦ ✦ ✦ ✦
0...400 ✦ ✦ ✦ -1...24 ✦ ✦ ✦
0...25 ✦ ✦ ✦ ✦
0...600 ✦ ✦ ✦ -100...0 ✦
0...40 ✦ ✦ ✦ ✦
0...1000 ✦ ✦ ✦ -100...150 ✦
0...60 ✦ ✦ ✦ ✦
0...1500 ✦ ✦ ✦ -100...300 ✦
0...100 ✦ ✦ ✦ ✦ ✦
0...2000 ✦ ✦ ✦ -100...500 ✦
0...160 ✦ ✦ ✦ ✦
0...3000 ✦ ✦ ✦ -100...900 ✦
0...250 ✦ ✦ ✦ ✦
0...4000 ✦ ✦ ✦ -100...1500 ✦
0...300 ✦
0...5000 ✦ ✦ ✦ -100...2400 ✦
0...400 ✦ ✦ ✦ ✦
0...6000 ✦ ✦ ✦
0...600 ✦ ✦ ✦ ✦ * vacuum measurement unit : "inHg"
0...10000 ✦ ✦ ✦
0...1000 ✦ ✦ ✦ ✦
0...15000 ✦ ✦ ✦
0...1600 ✦
0...2500 ✦
2
(1) Available also kg/cm
www.naffco.com
Referance No :-14756 C Page 41 of 153
PRESSURE GAUGE
MODEL: SD-P1
TECHNICAL DATA
DIAL SIZE 90mm (3½”)
MOUNTING Direct
DESCRIPTION
www.naffco.com
Referance No :-14756 C Page 43 of 153
VENTURI FIRE PUMP FLOW SYSTEM
DATED 07-01-07
Line Pump Meter Range Model Number Model Number Model Number Model Number
Size GPM Min. & Max. Grooved Butt Weld 150# Flanged <Threaded>
GPM *300#
FLANGED*
**1-1/4” 25 12.5 – 50 * 1.25”-25-G 1.25”-25-B * 1.25”-25-F 1.25”-25-T
* DENOTES NON-
NON-STOCK ITEM, PLEASE CHECK WITH FACTORY FOR AVAILA
AVAILABILITY
**SIZES 1-1/4”, 2”, 2-1/2", & 14” ARE NOT FM APPROVED PER FACTORY MUTUAL**
DATED 07-01-07
Line Pump Meter Range Model Number Model Number Model Number Model Number
Size GPM Min. & Max. Grooved Butt Weld Flanged 300 # Flanged
GPM
8” 1000 500 – 2000 8”-1000-G 8”-1000-B 8”-1000-F 8”-1000-F3
8” 1250 625 – 2500 8”-1250-G 8”-1250-B 8”-1250-F 8”-1250-F3
8” 1500 750 – 3000 8”-1500-G 8”-1500-B 8”-1500-F 8”-1500-F3
8” 2000 1000 – 4000 8”-2000-G 8”-2000-B 8”-2000-F 8”-2000-F3
8” 2500 1250 – 5000 8”-2500-G 8”-2500-B 8”-2500-F 8”-2500-F3
8” 3000 1500 – 6000 8”-3000-G 8”-3000-B 8”-3000-F 8”-3000-F3
* DENOTES NON-
NON-STOCK ITEM, PLEASE CHECK WITH FACTORY FOR AVAILA
AVAILABILITY
**SIZES 1-1/4”, 2”, 2-1/2", & 14” ARE NOT FM APPROVED PER FACTORY MUTUAL**
Speed (RPM) Driver PumpModel NF-S-150-100 Pump Test Std ANSI/HI 14.6-2011
2900 Engine Flow 750.0 USGPM Head 120.0 PSI Stage 1 Impeller Dia 253.0 mm
Application Range
Duty Power 63.47 Kw 85.08 HP Flow @150% 1125 USGPM Size Pump Nozzle Recommended Pipe Size
Peak Power 78.8 kw 105.63 HP Shut Off Head 129 PSI Discharge (In) 4 8.00
CQ= 1 CH= 1 CE= 1
Prepared By/Checked By sankar
Tag Number DIESEL PUMP Offer No NAFF-H01-EXP-423
Date 21/11/2017
In line with NAFFCO policy for continuous product development, NAFFCO has the right to change specifications without prior notice
Reference: NF-S-150-100-2900
Actual pump performance and impeller diameter values may vary ± 5% which is within normal permissible / expected range
Operating Conditions
Fluid Water
Specific Gravity 1
Temperature -
Viscosity 0 Cst
Speed 2900 RPM
Duty Flow (Q) 750.0 USGPM
Duty Head (H) 120.0 PSI
Suction Pressure 1m
Pump Set Configuration
Pump Test Std ANSI/HI 14.6-2011
140% limit of H at shut-off 168 PSI
65% limit of H @150% of Q 78 PSI
Notes:
In line with NAFFCO policy for continuous product development, NAFFCO has the right to change specifications without prior notice
Actual pump performance and impeller diameter values may vary ± 5% which is within normal permissible / expected range
World Headquarters Jebel Ali Free Zone Dubai, U.A.E.P.O. Box: 262169
www.naffco.com
Referance No :-14756 C Page 54 of 153
NAFFCO
Listed
Fire Pumps
2900 RPM
NAFFCO FZCO is among the world’s leading firefighting technology and fire safety solutions, NAFFCO
manufacturers and suppliers of top-tier firefighting has worked in both the private and government sectors,
equipment, fire protection systems, fire alarms, security as well as manufacturing plants, hospitals, stadiums,
and safety engineering systems worldwide. Since malls and other organizational projects, delivering
its humble beginnings, NAFFCO has grown from its comprehensive fire safety and engineering solutions.
headquarters in Dubai, UAE to expand to serving over
100 countries around the world. NAFFCO is associated with globally renowned
international companies in the fire protection industry
such as Esser, Secutron, Megalights, Evax, Fike, Central,
One Stop Shopping for All Your Fire Safety Shield, Mueller, Giacomini, RB Pumps, Bombas, Ideal
and Security Needs Pumps, Joslyn Pumps, Peerless Pumps.
FEATURES
• Performance characteristics as per NFPA 20
• Complete unit responsibility.
• Complete in-house fabrication capabilities.
• Hydrostatic testing facilities.
• Operation run test as per NFPA 20, UL 448 and
FM 1311 requirements.
• Horizontal Split case pumps for capacities from 750
to 1500 US GPM.
• Drivers: Electric motor drive or diesel engine drive.
• Electrical testing capabilities for motors and
controllers as per NFPA standards.
• Capable of supplying additional accessories wherever
required.
SHAFT SEAL:
are provided for additional cooling of the graphite
impregnated type gland packing.
DESCRIPTION
No. Part Name Material Qty.
1 Lower Casing Cast Iron ASTM A48 Class 40 1
2 Upper Casing Cast Iron ASTM A48 Class 40 1
3 Impeller Bronze SAE 40 1
4 Shaft Sleeve Stainless Steel AISI 420 2
5 Bearing Cover Cast Iron ASTM A48 Class 40 2
6 Gland Bronze SAE 40 2
7 Cast Iron ASTM A48 Class 40 2
8 Shaft Alloy Steel AISI 4340* 1
9 Wear Ring Bronze SAE 40 2
10 Flushing Pipe Stainless Steel, Gr. 304 2
11 Coupling Key Stainless Steel AISI 420 1
12 Gland Packing Graphite Impregnated 8
13 Lantern Ring Bronze SAE 40 2
14 Bearing Housing Cast Iron ASTM A48 Class 40 2
*Optionals shaft materials are available - AISI 316 (except for NF-S-150-100-375), Duplex 2205 or Duplex 2507
CAT.NO.NF/ULFP2900/01/15
NAFFCO FZCO
World Headquarters
Dubai, United Arab Emirates
Email: info@naffco.com
www.naffco.com
In line with NAFFCO policy for continuous product development,
NAFFCO has the right to change specifications without prior notice.
Referance No :-14756 C Page 60 of 153
FIRE PUMP DIESEL ENGINE
www.naffco.com
Referance No :-14756 C Page 61 of 153
Referance No :-14756 C Page 62 of 153
Referance No :-14756 C Page 63 of 153
Referance No :-14756 C Page 64 of 153
Referance No :-14756 C Page 65 of 153
Referance No :-14756 C Page 66 of 153
ENGINE FIRE PUMP CONTROLLER
www.naffco.com
Referance No :-14756 C Page 67 of 153
Micro
Processor
Based
Fire Pump
Controllers
NAFFCO was founded in Dubai, UAE to become the world’s leading Our products have been consistently certified by UL, FM, BSI, LPCB
producer and supplier of life safety solutions. By recognizing the and Global Mark according to the latest International Quality
importance and convenience of having easy access to multiple Standard for their strict adherence to ISO 9001 quality management
safety services, we became specialized by offering complete system and certified for ISO 14001 environmental management
solutions under one roof for all types of high quality firefighting systems and BS OHSAS 18001 for occupational safety by UL DQS.
equipment, fire protection systems, fire alarms, addressable
emergency systems, security systems,custom-made vehicles such Our success is driven by our passion to protect; our vision is to
as fire trucks, ambulances, mobile hospitals and airport rescue become the world’s number one provider of innovative solutions
firefighting vehicles (ARFF). in protecting life, environment and property.
RATINGS
STANDARD FEATURES
• System error alarm / indicator. • Test running indicator / free contact.
• AC power healthy indicator. • Automatic mode indicator / free contact.
• DC power healthy indicator / free contact. • Manual mode indicator.
• Speed switch error or failed while running alarm / • Battery Charger 1 error indicator.
indicator. • Battery Charger 2 error indicator.
• Automatic shutdown enabled/disabled indicator. • Battery 1 failure alarm / indicator.
• Low discharge pressure alarm / indicator / free contact • Battery 2 failure alarm / indicator.
(programmable). • Low oil pressure alarm / indicator.
• Deluge valve on alarm / indicator / free • High water temperature alarm / indicator.
contact(programmable). • Over speed shut down alarm / indicator.
• Remote start on alarm / indicator / free • Engine failed to start alarm / indicator.
contact(programmable). • Cranking coil 1 failure alarm / indicator.
• 10 additional programmable indicators. • Cranking coil 2 failure alarm / indicator.
• 11 additional programmable digital inputs. • UL listed NEMA 2 enclosure.
• 8 additional programmable output relays (free
contacts). ENCLOSURE OPTIONS:
• Common alarm free contact. • NEMA 3
• Electrical alarm bell. • NEMA 4
• Push button for alarm silence (only for additional
• NEMA 12
alarms).
• Pressure transducer with analog voltage output.
• Data logging system for pressure and events.
• USB port for saving recorded pressure and events
on USB memory, and can be viewed with MS word
and Excel.
• Electrically actuated built in discharge solenoid valve.
• 220 / 110 VAC main line system power.
• 12 / 24 VDC system control voltage.
• Automatic / Manual / OFF mode (selectable).
• Two 12 / 24 VDC, 10 Amps smart automatic
microprocessor battery chargers.
• Protection circuit breakers before and after battery
chargers.
• 20x4 LCD display showing all system parameters and
variables.
• User friendly software enable user to program alliterated
parameters like timers, pressure, inputs,outputs … etc.
• Shows battery 1 and 2 voltages.
• Shows battery 1 and 2 charging currents.
• Shows real value of discharge pressure.
• Shows engine running hours.
• Showing ambient temperature.
• Automatic cranking from two different batteries.
• Two push buttons for manual cranking from two
different batteries.
• Manual stop push button.
• Programmable automatic weekly test, which can be
programmed to start at any desired day, hour and
minute in a week.
• Manual test push button.
• Starting delay timer (programmable) for sequence
multiple pumps starting.
• Automatic or manual shutdown after automatic start
(selectable).
• Compatible with fuel solenoid engines and stopped
solenoid engines.
• Engine run indicator / free contact.
www.naffco.com
Referance No :-14756 C Page 76 of 153
Referance No :-14756 C Page 77 of 153
Referance No :-14756 C Page 78 of 153
FUEL LEVEL GAUGE
www.naffco.com
Referance No :-14756 C Page 79 of 153
®
Part Number—
D-(size opening)-(tank depth)+(ext)-(list options)
Sample—D-2-48+12
Model Calibration Indicator Lock Nut Bushing Internal Rods Rivets Floats Gasket
www.naffco.com
Referance No :-14756 C Page 82 of 153
Scanned by CamScanner Referance No :-14756 C Page 83 of 153
Scanned by CamScanner Referance No :-14756 C Page 84 of 153
Scanned by CamScanner Referance No :-14756 C Page 85 of 153
Scanned by CamScanner Referance No :-14756 C Page 86 of 153
Scanned by CamScanner Referance No :-14756 C Page 87 of 153
Scanned by CamScanner Referance No :-14756 C Page 88 of 153
AIR RELEASE VALVE
www.naffco.com
Referance No :-14756 C Page 89 of 153
5 1/8”
23 OPTIONAL
14
21 OUTLET
4
2 7
6
3
8 3/8”
13 34
12 1
10
11 6"
17 5
LISTED
28WL
FM
APPROVED
TEST PRESSURE
1.5 TIMES WORKING PRESSURE (W.P.)
INLET
SEE DRAWING NO. VM-22-M FOR STANDARD MATERIAL OF CONSTRUCTION.
VALVE MODEL INLET OUTLET MAX. W.P. ORIFICE
SIZE NO. ** SIZE SIZE P.S.I. SIZE
1 / 2 "_ 3 / 4 " * 22.4 3 / 4 " N .P. T. 1 / 2 " N . P. T. 175 3/32"
1 Scope
1.1 This specification is intended to cover the design, manufacture, and testing of 1 in. through 3 in. Well
Service Air Valves suitable for clean or raw water service in fire protection applications with pressures up to
300 psig.
1.2 Well Service Air Valves shall be fully automatic float operated valves designed to exhaust air which is
present in the vertical pump column on pump startup and allow air to re-enter the column on pump shutdown
or should a negative pressure occur. A top mounted Throttling Device shall provide adjustable control of the
exhaust rate.
2 Connections
2.1 Valve sizes 3 in. (76 mm) and smaller shall have full size NPT inlets and outlets equal to the nominal
valve size.
2.2 The body inlet connection shall be hexagonal for a wrench connection.
3 Design
3.1 The valve body shall provide a through flow area equal to the nominal valve size. A bolted cover with
alloy screws and flat gasket shall be provided to allow for maintenance and repair.
3.2 Floats shall be unconditionally guaranteed against failure including pressure surges. The float shall
have a hexagonal guide shaft supported in the body by circular bushings to prevent binding from debris. The
float shall be protected against direct water impact by an internal baffle and stainless steel diffuser screen to
break up the solid water column before coming in contact with the float.
3.3 The resilient seat shall provide drop tight shut off to the full valve pressure rating. The seat shall be a
minimum of 1/2 in. (12 mm) thick on 2 in. (50 mm) and larger valves and secured in such a manner as to
prevent distortion. The seat shall be precision molded with an o-ring type sealing surface and a slot in the
seat opening to provide a positive seal at low pressures.
3.4 Valves shall be equipped with a throttling device to control the discharge of air from the valve. The
device shall have an externally adjustable screw and locknut for adjusting the discharge control disc.
4 Materials
4.1 The Well Service Air Valve body, cover, and baffle shall be constructed of ASTM A126 Class B cast iron.
4.2 The float, guide shafts, and bushings shall be constructed of Type 316 Stainless Steel. Non-metallic
guides and bushings are not acceptable.
4.3 The seat shall be Buna-N capable of providing drop tight shut off at the valve full pressure rating.
5 Manufacture
5.1 The manufacturer shall demonstrate a minimum of five (5) years experience in the manufacture of air
valves. The valves shall be Underwriters Laboratories Listed and manufactured and tested in accordance
with American Water Works Association Standard (AWWA) C512.
5.2 The exterior of the valve shall be coated with a universal alkyd primer.
5.3 Well Service Air Valves shall be Series #101WST as manufactured by Val-Matic® Valve & Mfg.
Corporation, Elmhurst, IL. USA. or approved equal.
Revised 7-28-04
DATE
FIRE PROTECTION WELL SERVICE AIR VALVE SPECIFICATION 12-19-97
DRWG. NO.
®
AL ATIC VALVE AND MANUFACTURING CORP. SS-1439
Referance No :-14756 C Page 91 of 153
PRESSURE RELIEF VALVE
www.naffco.com
Referance No :-14756 C Page 92 of 153
MODEL
50B-4KG1 Globe
2050B-4KG1 Angle
Listed/Approved Fire Protection Pressure Relief Valve
LA
BLLED BY
• U.L. Listed / U.L.C. Listed
ULC
U N D E R W RIT
CANADA
• Factory Mutual Approved
OF
R
S
S E
LAB RI
O R AT O
Check Valve
www.naffco.com
Referance No :-14756 C Page 95 of 153
bourdon tube pressure gauges
anti-vibration version MS4
DS 4” (100mm)
Laser calibration up to 400bar
Free zero
Safety plug
Compliance to requirement of
PED 97/23/EC
Instruments designed for use on power units, pump, hydro-cleaning machines, presses, engine compressors, turbines, diesel engines,
chemical, petrochemical and refrigerating plants and on machines and equipment where pulsating pressures or mechanical vibrations
are apparent. They can be used with gaseous or liquid media which do not corrode copper alloy and which do not have high viscosity
or do not cristalize.
Design: EN 837-1.
Safety designation: S1 as per EN 837-2.
Ranges: from -1...0 to 0...15000 PSI (from 0...1 to 0...1000 bar or
other equivalent units).
Accuracy class: 1,6 as per EN 837-1.
Ambient temperature: -13...+149°F (-25...+65 °C).
Process fluid temperature: +212°F (max +100 °C).
Thermal drift: max ±0,4 %/10 K of ranges (starting from 68°F- 20°C).
Working pressure:
75% of FSV for static pressure;
66% of FSV for pulsating pressure.
Overpressure (max 15 min):
25% of FSV of ranges ≤ 1500 psi (100 bar);
15% of FSV for ranges over 1500 psi (100 bar).
Protection degree: IP 67 as per IEC 529.
Socket material: copper alloy, with internal restrictor ø 0.03”
(0,8 mm)
Bourdon tube:
copper alloy for ranges ≤ 10000 psi (600 bar);
AISI 316L st.st. for ranges 15000 psi (1000 bar).
Case: stainless steel.
Ring: stainless steel, polished , crimped.
Window: tempered glass.
Movement: copper and stainless steel.
Dial: aluminium, white with black markings
Pointer: not adjustable, aluminium,black
RB4 - 01/09
IN ORDER TO IMPROVE THEIR PRODUCTION, MESSRS. NUOVA FIMA RESERVE THE RIGHT TO THEMSELVES TO MAKE ALL THE MODIFICATIONS THAT THEY DEEM INDISPENSABLE AT ANY TIME. UPDATED DATA-SHEETS ARE AVAILABLE ON SITE: www.nuovafima.com
A - LOWER CONNECTION D - BACK CONNECTION
(1) Add 0.5 Ibs (0,23 kg) when filled - (2) Add 0.53 Ibs (0,24 kg) when filled - (3) quote “e” will become 0,73 lbs (18,5 mm) within 2009
RANGES bar kPa MPa bar ext. bar ext. bar ext. RANGES psi psi ext. psi ext. RANGES bar kPa bar ext. bar ext. RANGES psi* psi ext.* psi ext.*
(1)
bar int. kg/cm 2 int. psi int.* kPa int. Bar int. kg/cm 2 int.
psi int. kPa int. MPa int.
0...15 ✦ ✦ ✦ -1...0 ✦ ✦ ✦ -30...0 ✦ ✦ ✦
0...1 ✦ ✦ ✦ ✦
0...30 ✦ ✦ ✦ -1...0,6 ✦ ✦ ✦ -30...15 ✦ ✦ ✦
0...1,6 ✦ ✦ ✦ ✦
0...60 ✦ ✦ ✦ -1...1,5 ✦ ✦ ✦ -30...100 ✦ ✦ ✦
0...2,5 ✦ ✦ ✦ ✦
0...100 ✦ ✦ ✦ -1...3 ✦ ✦ ✦ -30...150 ✦ ✦
0...4 ✦ ✦ ✦ ✦
0...160 ✦ ✦ ✦ -1...5 ✦ ✦ ✦ * vacuum measurement unit : "inHg"
0...6 ✦ ✦ ✦ ✦
0...200 ✦ ✦ ✦ -1...9 ✦ ✦ ✦
0...10 ✦ ✦ ✦ ✦
0...300 ✦ ✦ ✦ -1...15 ✦ ✦ ✦
0...16 ✦ ✦ ✦ ✦
0...400 ✦ ✦ ✦ -1...24 ✦ ✦ ✦
0...25 ✦ ✦ ✦ ✦
0...600 ✦ ✦ ✦ -100...0 ✦
0...40 ✦ ✦ ✦ ✦
0...1000 ✦ ✦ ✦ -100...150 ✦
0...60 ✦ ✦ ✦ ✦
0...1500 ✦ ✦ ✦ -100...300 ✦
0...100 ✦ ✦ ✦ ✦ ✦
0...2000 ✦ ✦ ✦ -100...500 ✦
0...160 ✦ ✦ ✦ ✦
0...3000 ✦ ✦ ✦ -100...900 ✦
0...250 ✦ ✦ ✦ ✦
0...4000 ✦ ✦ ✦ -100...1500 ✦
0...300 ✦
0...5000 ✦ ✦ ✦ -100...2400 ✦
0...400 ✦ ✦ ✦ ✦
0...6000 ✦ ✦ ✦
0...600 ✦ ✦ ✦ ✦ * vacuum measurement unit : "inHg"
0...10000 ✦ ✦ ✦
0...1000 ✦ ✦ ✦ ✦
0...15000 ✦ ✦ ✦
0...1600 ✦
0...2500 ✦
2
(1) Available also kg/cm
www.naffco.com
Referance No :-14756 C Page 98 of 153
PRESSURE GAUGE
MODEL: SD-P1
TECHNICAL DATA
DIAL SIZE 90mm (3½”)
MOUNTING Direct
DESCRIPTION
Speed (RPM) Driver PumpModel JVS-4-100 Pump Test Std ANSI/HI 14.6-2011
2900 Motor Flow 10.54 USGPM Head 130.0 PSI Stage 10 Impeller Dia 100.0 mm
Application Range
Duty Power 1.38 Kw 1.85 HP Size Pump Nozzle Recommended Pipe Size
Peak Power 1.76 kw 2.36 HP Shut Off Head 144 PSI Discharge (In) 1.25 1.50
CQ= 1 CH= 1 CE= 1
Prepared By/Checked By sankar
Tag Number JOCKEY PUMP Offer No NAFF-H01-EXP-423
Date 21/11/2017
In line with NAFFCO policy for continuous product development, NAFFCO has the right to change specifications without prior notice
Reference: JVS-4-2900
Actual pump performance and impeller diameter values may vary ± 5% which is within normal permissible / expected range
Operating Conditions
Fluid Water
Specific Gravity 1
Temperature -
Viscosity 0 Cst
Speed 2900 RPM
Duty Flow (Q) 10.54 USGPM
Duty Head (H) 130.0 PSI
Suction Pressure 1m
Pump Set Configuration
Pump Test Std ANSI/HI 14.6-2011
Notes:
In line with NAFFCO policy for continuous product development, NAFFCO has the right to change specifications without prior notice
Actual pump performance and impeller diameter values may vary ± 5% which is within normal permissible / expected range
World Headquarters Jebel Ali Free Zone Dubai, U.A.E.P.O. Box: 262169
www.naffco.com
Referance No :-14756 C Page 107 of 153
Referance No :-14756 C Page 108 of 153
Referance No :-14756 C Page 109 of 153
Referance No :-14756 C Page 110 of 153
Referance No :-14756 C Page 111 of 153
JOCKEY PUMP
www.naffco.com
Referance No :-14756 C Page 112 of 153
Referance No :-14756 C Page 113 of 153
Referance No :-14756 C Page 114 of 153
Referance No :-14756 C Page 115 of 153
Referance No :-14756 C Page 116 of 153
JOCKEY PUMP CONTROLLER
www.naffco.com
Referance No :-14756 C Page 117 of 153
UL LISTED JOCKEY PUMP CONTROLLER
MODEL NFY-JSD1 REDUCED VOLTAGE/
STAR – DELTA (OPEN TRANSITION)
MODEL NFY-JDO1 DIRECT ON LINE
NAFFCO Jockey Pump Controllers for fire pumps are UL recognized components are used in these panels
listed by Underwriters Laboratories (UL file number to guarantee the best possible reliability. Also high
E309408), in accordance with UL508a (Standard for quality UL listed enclosures are used.
Industrial Control Panel), NFPA70 (National Electric
Code) and NEMA. The controller is completely wired, assembled and
tested at the factory before shipment, and ready for
Power ratings vary from 1.5 to 40 horsepower, 380 to immediate installation.
415 volts, 50 or 60 Hz. Only high quality UL listed or
STANDARD FEATURES
• Main disconnected switch with rotary handle, sized for
disconnecting motor horsepower and voltage.
• Motor Starter rated to motor’s horsepower, with
thermal and short circuit protection.
• Rated motor contactors.
• Circuit breaker for protection of control circuit.
• Selector switch for Hand—Off—Automatic operation.
• Star—Delta starting timer. ( in Model NFY-JSD1 )
• Power ON/Healthy indicator/free contact.
• Pump Run indicator/free contact.
• Pump Trip indicator/free contact.
• Adjustable pressure switch.
• UL listed enclosure.
SEQUENCE OF OPERATION
This controller is working under three modes automatic
off and manual mode.
AUTOMATIC START
In this mode, controller will start the Jockey pump
automatically and directly at low pressure detection
by the pressure switch, and will stop the pump
automatically and directly when the pressure goes up
again.
MANUAL START
In this mode, controller will start the Jockey pump
directly, and will not stop until selector switch is
switched off or in Auto mode.
Table (7)
[HP] MCM mm Sq. MCM mm Sq. MCM mm Sq. MCM mm Sq. MCM mm Sq. MCM mm Sq.
1.5 16 1.3 8 8.4 16 1.3 8 8.4 8 8.4 6 13.3
2 16 1.3 8 8.4 16 1.3 8 8.4 8 8.4 6 13.3
3 14 2.1 8 8.4 14 2.1 8 8.4 8 8.4 6 13.3
5 14 2.1 8 8.4 14 2.1 8 8.4 8 8.4 6 13.3
7.5 14 2.1 8 8.4 14 2.1 8 8.4 8 8.4 6 13.3
10 12 3.3 8 8.4 12 3.3 8 8.4 8 8.4 6 13.3
15 10 5.3 6 13.3 10 5.3 6 13.3 8 8.4 6 13.3
20 8 8.4 6 13.3 8 8.4 6 13.3 8 8.4 6 13.3
25 8 8.4 6 13.3 8 8.4 6 13.3 8 8.4 6 13.3
30 6 13.3 6 13.3 6 13.3 6 13.3 6 13.3 1/0 53.5
40 4 21.2 1 42.4 4 21.2 1 42.4 4 21.2 1/0 53.5
AWG OR TIGHTENING
TORQUE USING
CIRCULAR EXTERNAL DRIVE
WRENCH
MILL SIZE LP.In N.m
14 75 8.5
12 75 8.5
10 75 8.5
8 75 8.5
6 110 12.4
4 110 12.4
2 150 16.9
1 150 16.9
1/0 180 20.3
2/0 180 20.3
3/0 250 28.2
4/0 250 28.2
250 325 36.7
350 325 36.7
500 375 42.4
600 375 42.4
700 375 42.4
750 375 42.4
800 500 56.5
1000 500 56.5
CAT.NO.NF/MPBFPC/01/15
NAFFCO FZCO
World Headquarters
Dubai, United Arab Emirates
Email: info@naffco.com
www.naffco.com
In line with NAFFCO policy for continuous product development,
NAFFCO has the right to change specifications without prior notice.
Referance No :-14756 C Page 125 of 153
Attachments
Page Bottom
Page Bottom
Number Rated
Model FL Service of Ins Prot. Ambient
No. Output Hz/DC Volts Amps Factor Poles Speeds RPM Phases Class Type (°C)
© 2017 UL LLC
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory
with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in
the following format: "© 2017 UL LLC".
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory
with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in
the following format: "© 2017 UL LLC".
Page Bottom
See General Information for Internal-combustion Engines for Driving Stationary Fire Pumps
Rated
No. of Rated Speed
Model Cylinders HP (rpm)
FD 30 H 3 19 2900
FD 50 H 4 36 2900
FD 80 H 4 50 2900
FD 80 R 4 50 2900
FD 110 R 6 87 2900
FD 95 H 6 95 2900
6 175 3000
6 255 3000
© 2017 UL LLC
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory
with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in
the following format: "© 2017 UL LLC".
Page Bottom
Diesel Engine Fire Pump Controller, Model NFY-D, followed by R1, followed by -110 or -230, followed by -50 or -60, followed by -12 or -24,
may be followed by additional suffixes.
Microprocessor-Based Diesel Engine Fire Pump Controller, NFY Type Diesel Engine Fire Pump Controllers, Model NFY, followed by -D,
followed by -M1, followed by -110 or -230, followed by -50 or -60, followed by -12 or -24, may be followed by additional suffixes.
Electric Fire Pump Controller, Model NFY, followed by -SD or -DO, followed by R1 followed by -380 or -415, followed by .yyy, where yyy
represents two or three digits denoting hp from 40-400 hp, followed by -50 or -60, may be followed by additional suffixes.
Microprocessor-Based Electric Fire Pump Controller, NFY Type Electric Fire Pump Controllers, Model NFY, may be followed bt -ATS,
followed by -SD - DO or -SS, followed by -M1, followed by 230, 380 or 415, followed by yyy where yyy represents two or three digits denoting
power in HP, followed by 50 or 60, and may be followed by additional suffixes.
Microprocessor-based variable speed drive electric fire pump controller, Model NFY, may be followed by -ATS, followed by -VFD,
followed by -DO or -SS, followed by M1, followed by 380 or 415, followed by yyy where yyy represents two or three digits denoting power in HP,
followed by 50 or 60, and may be followed by additional suffixes.
These controllers are suitable for use on circuits capable of delivering high fault currents with maximum values as shown in the following table.
For NFY-DO and NFY-SS Series Utilizing LSIS CO LTD Circuit Breakers
Models with suffix "-ATS are provided with Automatic Transfer Switches and are suitable for use on circuits capable of delivering high fault
currents. The withstand rating of the normal power side is the same as the withstand ratings of controllers without transfer switches. The
withstand rating of the alternate power side is determined by the transfer switch as indicated by the following tables:
+ - Branch Circuit Protection provided by same circuit breaker models specified in the NFY-SD, NFY-DO and NFY-SS short-
circuit tables.
Referance No :-14756 C Page 133 of 153
Last Updated on 2016-10-04
© 2017 UL LLC
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory
with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in
the following format: "© 2017 UL LLC".
Page Bottom
Air release valves for use with split case fire pumps.
Inlet Size Orifice Outlet Size Rated Pressure
Model NPT In. Size In. NPT In. psig
Well service air valves for use with vertical turbine fire pumps.
Inlet Size Orifice Outlet Size Rated Pressure
Model NPT In. Size In. NPT In. psig
102 ST 2 2 2 300
103 ST 3 3 3 300
© 2017 UL LLC
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory
with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in
the following format: "© 2017 UL LLC".
Page Bottom
© 2017 UL LLC
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory
with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in
the following format: "© 2017 UL LLC".
Rated Rated
Rated Rated Net Head Net Head Rated Suction Discharge
Listing Certification
Product Capacity, Capacity, at Rated at Rated Speed, Inlet, Outlet, Stage(s)
Country Type
(gal/min) (dm³/min) Capacity, Capacity, r/min dia., in. dia., in.
psi kPa
United
NF-S-125-80 Arab 750 2840 236 1625 2900 5 3 1 FM Approved
Emirates
United
NF-S-150-100 Arab 750 2840 108-216 745-1490 2900 6 4 1 FM Approved
Emirates
United
NF-S-150-100 Arab 1000 3785 101-215 695-1485 2900 6 4 1 FM Approved
Emirates
United
NF-S-150-100-375 Arab 750 2840 227-280 1565-1930 2900 6 4 1 FM Approved
Emirates
United
NF-S-150-100-375 Arab 1000 3785 215-273 1485-1880 2900 6 4 1 FM Approved
Emirates
United
NF-S-200-125 Arab 1000 3785 143-252 985-1735 2900 8 5 1 FM Approved
Emirates
United
NF-S-200-125 Arab 1250 4730 134-250 925-1725 2900 8 5 1 FM Approved
Emirates
United
NF-S-200-125 Arab 1500 5680 121-242 835-1670 2900 8 5 1 FM Approved
Emirates
United
NF-SS-150-100 Arab 500 1895 127-239 875-1650 3550 6 4 1 FM Approved
Emirates
United
NF-SS-150-100 Arab 750 2840 122-235 840-1620 3550 6 4 1 FM Approved
Emirates
United
NF-SS-150-100 Arab 1000 3785 112-232 770-1600 3550 6 4 1 FM Approved
Emirates
United
NF-SS-200-125 Arab 1250 4730 127-214 875-1475 3550 8 5 1 FM Approved
Emirates
United
NF-SS-200-125 Arab 1500 5860 126-211 870-1455 3550 8 5 1 FM Approved
Emirates
National Fire Fighting Mfg. FZCO
P. O. Box 17014, Jebel Ali Free Zone, Dubai, United Arab Emirates
Fire Pump Installation Systems Diesel Engines for Fire Pump Drivers Diesel Engines for Fire Pump Drivers, Liquid Cooled
Product Listing Country Rated Power, hp Rated Power, kW Rated Speed, r/min Certification Type
FD30H United Arab Emirates 20 15 3000 FM Approved
FD30H United Arab Emirates 19 15 2900 FM Approved
FD30H United Arab Emirates 18 13 2800 FM Approved
FD50H United Arab Emirates 40 30 3000 FM Approved
FD50H United Arab Emirates 36 26 2900 FM Approved
FD50H United Arab Emirates 30 22 2800 FM Approved
FD80H United Arab Emirates 60 45 3000 FM Approved
FD80H United Arab Emirates 50 37 2900 FM Approved
FD80H United Arab Emirates 46 34 2800 FM Approved
FD140H United Arab Emirates 127 94 2900 FM Approved
FD140H United Arab Emirates 124 92 2800 FM Approved
FD175H United Arab Emirates 172 128 3000 FM Approved
FD175H United Arab Emirates 170 127 2900 FM Approved
FD175H United Arab Emirates 170 127 2800 FM Approved
FD190H United Arab Emirates 190 142 2900 FM Approved
FD190H United Arab Emirates 176 131 2800 FM Approved
FD250H United Arab Emirates 250 186 3000 FM Approved
FD250H United Arab Emirates 250 172 2950 FM Approved
FD250H United Arab Emirates 194 145 2800 FM Approved
https://www.approvalguide.com/CC_host/pages/custom/templates/FM/index.cfm?line=3820&searchtype=product&keywords=fire%20driver 1/1
Referance No :-14756 C Page 140 of 153
Fire Pump Controllers- Full Service Electric Motor
Controllers for electric motor-driven fire pumps as listed are for alternating current squirrel-cage motors unless indicated as for slip
ring motors. They are available for manual operation alone or for combined manual and automatic operation. Controllers for
squirrel-cage motors are FM Approved for three phase power. They are of two types: across-the-line and reduced voltage. All model
code combinations may not apply.
Model NFY
Model NFY-aM1-b-c-d-e Electric Motor Fire Pump Controller - Low Voltage
Standard Enclosure: NEMA/UL Type 2.
Ambient Temperature Operating Range: 39°F (4°C) to 122°F (50°C)
b=
a= M1 =
Voltage, VAC
Starting Type Control Type Ho
(3 phase)
d = Frequency (Hz)
e = Additional suffixes denoting optional equipment
50
60
Model NFY-DM1
Model NFY-Da-b-c-d-e Diesel Engine Fire Pump Controller
Standard Enclosure: NEMA/UL Type 2.
Ambient Temperature Operating Range: 39°F (4°C) to 122oF (50°C)
b= c=
a=
Voltage Frequency
Control Type
(VAC) (Hz)
M1 –
110 50
Microprocessor
230 60
Based
d=
e = Additional suffixes denoting optional equipment
Battery Voltage (VDC)
86 of 99
50B-4KG1, 2050B-4KG1
Cat. Nos. 50B-4KG1, 2050B-4KG1. 3, 4, 6, 8 in. NPS (76, 102, 152, 203 mm). Assembly consists of Clayton 100 (globe) or Clayton
2100 (angle) hydraulically operated, diaphragm-actuated valve, pilot valve (FM Approved pilot valve configurations are listed
below), Clayton X44A, X46A strainers, Clayton Model 81-01 check valve, pressure gauge and 3⁄32 in. (2 mm) dia. orifice assembly.
Clayton X101C valve position indicator is available as optional equipment.
Model CRL, bronze body, spring range of 20 psi (135 kPa) to 200 psi (1380 kPa);
Model CRL, bronze body, spring range of 100 psi (670 kPa) to 300 psi (2070 kPa);
Model CRL, ASTM A216 grade WCB cast steel body, spring range of 20 psi (135 kPa) to 200 psi (1380 kPa);
Model CRL, ASTM A216 grade WCB cast steel body, spring range of 100 psi (670 kPa) to 300 psi (2070 kPa);
Model CRL60, bronze body, spring range of 20 psi (135 kPa) to 200 psi (1380 kPa);
Model CRL60, bronze body, spring range of 100 psi (670 kPa) to 300 psi (2070 kPa);
Model CRL60, ASTM A216 grade WCB cast steel body, spring range of 20 psi (135 kPa) to 200 psi (1380 kPa);
Model CRL60, ASTM A216 grade WCB cast steel body, spring range of 100 psi (670 kPa) to 300 psi (2070 kPa);
Model CRL60, stainless steel body, spring range of 20 psi (135 kPa) to 200 psi (1380 kPa);
Model CRL60, stainless steel body, spring range of 100 psi (670 kPa) to 300 psi (2070 kPa).
Remarks:
a. Valve supplied with Male NPT inlet connection and Female NPT outlet connection.
b. Adjustable relief pressure settings from 60 to 125, 126 to 175, or 176 to 250 psi (415 to 860, 870 to 1205, or 1215 to 1725 kPa).
c. Not suitable for discharging the full rated pump capacity.
Model SD-P1
Air or Water Pressure Gauge - Model SD-P1, 3-1/2 in. (89 mm) size, Steel Case
• 0 to 300 psi (0 to 2070 kPa)
This gauge has a 1/4 in. male BSPT or NPT bottom connection.
Pump
Rating, Meter
gal/min Line
(dm3 Size, Model
/min) in. Designation
50 2 2-50-X*#
(190)
150 3 3-150-X*#
(570)
200 3 3-200-X*#
(755)
250 4 4-250-X*#
(945)
300 4 4-300-X*#
(1135)
400 4 4-400-X*#
(1515)
450 4 4-450-X*#
(1705)
450 5 5-450-X*#
(1705)
500 5 5-500-X*#
(1895)
750 5 5-750-X*#
(2840)
500 6 6-500-X*#
(1895)
750 6 6-750-X*#
(2840)
1000 6 6-1000-X*#
(3785)
1250 6 6-1250-X*#
(4730 )
1000 8 8-1000-X*#
(3785)
1500 8 8-1500-X*#
(5680)
2000 8 8-2000-X*#
(7570)
2500 8 8-2500-X*#
(9465)
3000 8 8-3000-X*#
(11 355)
1500 10 10-1500-X*#
(5680)
2000 10 10-2000-X*#
(7570)
2500 10 10-2500-X*#
(9465)
3000 10 10-3000-X*#
(11 355)
3500 10 10-3500-X*#
(13 250)
4000 10 10-4000-X*#
(15 140)
4500 10 10-4500-X*#
(17 035)
2000 12 12-2000-X*#
(7570)
2500 12 12-2500-X*#
(9465)
3000 12 12-3000-X*#
(11 355)
3500 12 12-3500-X*#
(13 250)
4000 12 12-4000-X*#
(15 140)
4500 12 12-4500-X*#
(17 035)
5000 12 12-5000-X*
(18 925)
Each system consists of a Global Vision Venturi, a differential pressure meter (for portable or permanent installation) and
associated fittings. Meter faces are available in direct readout in both GPM (gallons per minute) and LPM (liters per minute), or
optional 3
m/h (cubic meters per hour).