Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 7

LARSEN & TOUBRO LIMITED

ECC Division - EDRC

PROJECT: DOCUMENT NO. DATE

TITLE: DESIGNED CHECKED SHEET


Design of Cable trench
KBR

50

GL TC = 0.15

W1 = 1.0

Insert Plate BCT = 0.75

W2 = 1.0 c = 0.35 H = 1.90

W3 = 1.0 b = 0.35

a = 0.15

TB = 0.25

B = 2.00

TW = 0.25 TW = 0.25

Fig. 1 (All Dimensions are in "m" & Loads are in "KN/m" )

Design Input Data:

Clear width of Trench B= 2.00 m

Clear depth of Trench H= 1.90 m

Tickness of wall TW = 0.25 m

Thickness of Base Slab TB = 0.25 m

Thickness of Cover slab TC = 0.15 m

Allowable safe bearing capacity of soil qsafe = 150.0 KN/m2

Grade of Concrete = C35

Grade of steel = Fe460

Charecteristic strength of concrete Fcu= 35.0 N/mm2

Fy= 460 N/mm2

Unit weight of soil gs = 21 KN/m3

Unit weight of concrete gc = 24.6 KN/m3

381178643.xls 1
LARSEN & TOUBRO LIMITED
ECC Division - EDRC

PROJECT: DOCUMENT NO. DATE

TITLE: DESIGNED CHECKED SHEET


Design of Cable trench
KBR

Earth pressure co-efficient Ka = 0.33

381178643.xls 2
LARSEN & TOUBRO LIMITED
ECC Division - EDRC

PROJECT: DOCUMENT NO. DATE

TITLE: DESIGNED CHECKED SHEET


Design of Cable trench
KBR

Coefficient of Friction m= 0.4

Live Load on Cover slab WL = 5.0 KN/m2

Surcharge pressure q = 15.0 KN/m2

Spacing of Insert Plates Sip = 1.0 m

Cable Tray Load Data:

Ref. Fig. 1 a= 0.15 mm

b= 0.35 mm

c= 0.35 mm

W1 = 1.0 KN/m

W2 = 1.0 KN/m

W3 = 1.0 KN/m

Maximum width of Cable tray BCT = 0.75 mm

Check for Bearing Pressure:

Consider 1.0m length of Cable trench.

Self weight of Cable trench SW1 = 40.221 KN

SW1 = {((B + 2TW) x TB) + (2 x (H x TW)) + (2 x (TC x (TW - 0.05)))} gc

Self weight of Cover Slab SW2 = 7.749 KN

SW2 = {((B + 0.1) x TC)} gc

Total Live Load on Cover slab per 1 m lengt WLT = 12.5 KN

WLT = (B + 2TW) x WL

Total weight of Cables & Trays Wcab = 3.0 KN

Wcab = (W1 + W2 + W3) x Sip

Total Vertical Load at Base level P= 63.5 KN

P = (SW1 + SW2 + WLT + Wcab)


Maximum Bearing Pressure P Max. = 25.388 KN/m2

P Max. =P / (B + 2Tw)

Hnce Safe in Bearing pressure

381178643.xls 3
LARSEN & TOUBRO LIMITED
ECC Division - EDRC

PROJECT: DOCUMENT NO. DATE

TITLE: DESIGNED CHECKED SHEET


Design of Cable trench
KBR

Structural Design:
Considere 1.0m length of Cable trench.

Total Horizontal Active Earth Pressure Pact. = 26.659 KN

Pact. = 0.5 x (Ka x gs x (H + TB)2) + (q x Ka) x (H + TB)

Moment due to soil pressure Msoil. = 16.857 KN.m

Msoil. = 0.16667 x (Ka x gs x H3) + 0.5 (q x Ka x H2)

Moment due to cable load Mcab. = 1.125 KN.m

Mcab. = 0.5 x (W1 + W2 + W3) x BCT x Sip

Total Moment at base level of wall MTotal. = 17.982 KN.m

MTotal. = Msoil.+ Mcab.

Design of Wall:

Consider 1.0m length of wall b= 1.0 m

Clear cover to main reinforcement cv. = 50 mm

Diameter of bar to be used f = 10 mm

Effective thickness of wall TWeff. = 0.195 m

TWeff. = TW - cv - f/2

Load factor to be used during design f= 1.4

k= 0.0189

k = (MTotal x f)/(b x TWeff2 x Fcu)

Zcal = 0.979 TWeff.

Z = [ 0.5 + 0.25 - k/0.9 ] x TWeff

Zmax = 0.95 TWeff.

Hence Z = 0.95 TWeff.

Z = 185.25 m

Area of steel required, Ast= 339.57 mm2

Ast= f. MTotal/(0.87*Fy*Z)

Minimum Are of steel required. Astmini= 325.0 mm2

Astmini= (0.13 b TW)/100

381178643.xls 4
LARSEN & TOUBRO LIMITED
ECC Division - EDRC

PROJECT: DOCUMENT NO. DATE

TITLE: DESIGNED CHECKED SHEET


Design of Cable trench
KBR

Hence Provide area of steel as = 339.6 mm2

Hence Provid 10 mm dia bars at 225 mm c/c. as vertical reinforcement

on outer face of the wall.

Provide Minimu percentage of steel as horizontal reinforcement.

Hence Provide 8mm dia bars at 175 c/c. as horizontal reinforcement.

Shear Check:

Total Horizontal shear force Pact. = 26.659 KN

Maximu shear stress developed. n = 0.191 N/mm2

n = (f . Pact.)/ (b . TWeff)
Allowable Shear stress nMini.= 4.733 N/mm2

nMini.= Minimum of 5 Mpa & 0.8 .Sqrt(Fcu)

Conclusion:Hence size is Okay

Design concrete shear strength.

Percentage of steel Provided. Pt. = 0.140

Pt. = Astprov. 100/ b.TW

From BS 8110 Part 1, Page no.23 Table 3.8

For TWeff. = 0.195 and Pt. = 0.140

Allowable shear strength of concrete ncon.= 0.23 N/mm2

Conclusion: IF (n < ncon. , "Hence Safe in Shear check", Fail in Shear check.")

Conclusion:Hence Safe in Shear check

Design of Base Slab:

Consider 1.0m length of wall b= 1.0 m

Clear cover to main reinforcement cv. = 50 mm

Diameter of bar to be used f = 10 mm

Effective thickness of Base slab TBeff. = 0.195 m

TBeff. = TB - cv - f/2

Load factor to be used during design f= 1.4

Moment at base slab due to base pressure MBase= 12.853 KN.m

381178643.xls 5
LARSEN & TOUBRO LIMITED
ECC Division - EDRC

PROJECT: DOCUMENT NO. DATE

TITLE: DESIGNED CHECKED SHEET


Design of Cable trench
KBR

MBase= PMax.(B+ TW) b /10


2

381178643.xls 6
LARSEN & TOUBRO LIMITED
ECC Division - EDRC

PROJECT: DOCUMENT NO. DATE

TITLE: DESIGNED CHECKED SHEET


Design of Cable trench
KBR

k= 0.0135

k = (MBase x f)/(b x TBeff2 x Fcu)

Zcal = 0.985 TBeff.

Z = [ 0.5 + 0.25 - k/0.9 ] x TBeff

Zmax = 0.95 TBeff.

Hence Z = 0.95 TBeff.

Z = 185.25 m

Area of steel required, Ast= 242.71 mm2

Ast= f. MBase/(0.87*Fy*Z)

Minimum Are of steel required. Astmini= 325.0 mm2

Astmini= (0.13 b TB)/100

Hence Provide area of steel as = 325.0 mm2

Hence Provid 10 mm dia bars at 225 mm c/c. as vertical reinforcement

on outer face of the wall.

Provide Minimu percentage of steel as horizontal reinforcement.

Hence Provide 8mm dia bars at 175 c/c. as horizontal reinforcement.