Professional Documents
Culture Documents
PS0500 Manual PDF
PS0500 Manual PDF
The PS0500 is a microprocessor-based controller Note: other devices that can remotely start / Stop
that has these abilities. the genset might be as simple as a switch or a push
• Start and stop the genset. button or as sophisticated as other controllers or
computers. This manual introduces the ways the
• Monitor the status of the genset. Control can interact with other devices, but this
• Warn the operator when unsafe conditions manual cannot identify all of the devices that might
are occurring be used in every application.
• Shut down the genset to prevent damage
• Adjust settings that affect genset behavior.
• Provide a way for other devices to remotely
start / Stop the genset ALTERNATOR CONNECTIONS
This section introduces the connections between the PS0500 and other parts of the genset. Some of
the PS0500 and the alternator. these connections are flexible and might be made
to many types of devices.
Main Alternator Output
Customer Input
The PS0500 is connected to the main alternator
output to measure genset voltage and genset The PS0500 has one customer input that can be
frequency. configured to invoke a shutdown or Warning
response
The PS0500 is also connected to current
transformers (CTs) which reduce the genset Battery Charger Failed Switch
current by a known ratio for measuring main
alternator output current. The PS0500’s Customer Input may be connected
to a battery charger’s status output (discrete) to
Battery-charging Alternator monitor the battery charger operation.
The PS0500 may be connected to the battery- Emergency Stop Buttons
charging alternator to make sure the battery-
charging alternator is recharging the battery The PS0500 may be connected to a push button
properly. that shuts the genset down immediately when
pressed.
ENGINE CONNECTIONS
Battery Connections
Starter
The PS0500 is connected to the starter control
relay in order to control the starter.
Ready to Load
Remote Start
CERTIFICATIONS
SAFETY CONSIDERATIONS
STARTING AND STOPPING THE GENSET WARNING The genset might not start or stop
immediately. Do not attempt to service the
The buttons related to changing mode of genset if it does not appear to respond
operation are highlighted in figure 2.1 and immediately. Accidental starting of the
described in Table 2.1 genset during troubleshooting can cause
severe personal injury or death.
The control panel (Figure 2-2) is the front panel
of the PS0500 control.
CONTROL PANEL
Stop (Off) Mode When the remote start signal becomes active,
the PS0500 initiates the start sequence to start
Pressing the STOP button will always put the the genset. The PS0500 continues to run as
PS0500 in STOP mode and the RED LED long as the signal is active. When the Remote
above the STOP button will start blinking. Start signal becomes inactive the PS0500
initiates a normal stop sequence.
In this mode, the PS0500 does not allow the
genset to start / Crank. Pressing the Stop button shall always deactivate
the FSO immediately.
If the genset is running (either in Manual or Auto
Mode) when the Stop button is pressed, the Remote Start Signal
PS0500 stops the genset and enters in the This signal will start the Genset when these
STOP mode. conditions are met.
• The PS0500 is in Auto mode
Setup Mode • There are no active shutdown faults
The Setup mode can be entered only from Stop This signal comes typically from a transfer
mode when the genset is not running. This is switch or an external toggle switch.
accomplished by holding the Reset and the OK
buttons pressed for 5 seconds continuously Manual Mode
while in stop mode. The RED Stop Led flashes
faster (double the normal rate) as long as the Pressing the Manual Button while the PS0500 is
control is in setup mode. While in setup mode, in the Stop Mode will put the PS0500 in the
pressing Start or Stop button has no effect. Manual Mode.
Exiting from setup mode will return the control to
STOP mode. In this mode, the genset is controlled manually.
Pressing the Start button initiates a Manual Start
In the setup mode, a Menu driven setup process sequence. Remote start signal has no effect.
is available for making adjustments that are
allowed to be made from the control panel. Set Note: If you do not press the Start button in ten
up process is described in detail in a separate seconds, the PS0500 changes over to STOP (Off)
section later in this manual. mode.
OR
Wait For the Genset to The Battery Charging Alt Voltage >= Start
Disconnect threshold
reach 90 % of Nominal
Frequency and If the genset frequency does not reach the start
Voltage disconnect threshold (15 Hz in above example)
before PS0500 finishes the cranking cycle, then
it generates shutdown fault 359 (Fail To start).
Genset Running The PS0500 waits for the Genset to reach the
rated frequency and voltage. If that does not
happen within 10 seconds from the starter
FIGURE 2-8. Remote Start Sequence disconnect, the PS0500 generates Shutdown
Fault 2335 (loss of AC Sensing).
Cycle Cranking
− Τhe starter turns on for Cycle Crank Engage
The PS0500 enters the Genset Running (Ready
to Load) state when the genset frequency and
Stopped voltage are both >= 90 percent of the nominal
frequency and nominal voltage respectively.
Meter Calibration
Turn ON Glow Plug
Output and Wait for When running in Manual Mode, the control
Preheat conditions to allows meter calibration process to be invoked,
be met if Glow Plug is when the Genset Running (Ready to Load) state
is reached. The Meter Calibration process is
enabled invoked by holding the Reset and OK buttons
pressed for 5 seconds continuously. The
process allows the arrow keys to be used for
Start Engine adjusting the displayed alternator AC Voltage /
Current values to actual values (as measured
using an independent calibrated instrument) one
by one.
Wait For the Genset to
The Meter Calibration Process is available when
reach 90% of Nominal running the genset in Manual Mode only.
Frequency and
Voltage Nominal Voltage and Frequency
Manual Mode
Fault Shutdown
In this section, italics are used to identify Tables 3.1 to 3.15 show a summary of
a specific parameter by name. the menus offered on the control panel
of the PS0500.
PARAMETERS
Table 3.1 Main Menu Description
See Section 4 for more information
about parameters that you can adjust in Menu Description
the Operator Panel.
Alt Setup Use this menu to select
Capture File alternator setup
parameters like Single /
Use InPower to save the current Three phase, 50 / 60 Hz
settings in a capture file on a PC or operation, Wye / Delta ,
network. You can use the capture file to Voltage etc.
look at the current settings while you are Units Use this menu to select
away from the PS0500 or to restore Metric or US units for
settings if you have to reset the PS0500 Coolant Temperature and
for any reason. See the InPower User Oil Pressure
Guide for more information. Oil Pr Input Use this menu to select the
sensor types used with oil
While InPower can be used with the pressure
PS0500 for facilitating the setup, it is not Customer I/O Use this Menu to configure
essential for carrying out the basic setup the response to Customer
operations. The basic setup can be input and to configure
performed directly from the control panel usage of the customer
of PS0500. Following paragraphs output
Describe the process of carrying out Flt History Use this menu to view last
basic setup from the control panel. five faults that are stored in
the control
Entering and leaving the Setup Mode Load Defaults Use this menu to set the
default values.
The Setup mode can be entered only
from Stop mode when the genset is not
running. This is accomplished by
Table 3.2 Alt Setup Menu Table 3.5 CT Ratio Sub Menu
← Alt Setup //
Current Config
Nom LL Voltage →
Saved ←
PS0500 Default
Parameter Control Possible value
Group Name InPower Panel Values Units
Lo High
Nominal
Voltage (L- Yes Yes 190 600 416 V AC
Genset L)
Nominal Yes 50 or 60 50
Frequency Yes Hz
Connectio Yes Delta or WYE WYE
n type Yes -
Yes Single or Three
Phase Three
type Yes -
Yes 10/15/20/30/ 20
CT ratio Yes 40/50/60
Engine Oil Yes Sensor or Sensor
Pressure switch
Input Type Yes N/A
Cycle Yes 3
Crank Attempt
Attempts 1 7 s
Cycle Yes 5
Crank time 3 30 Sec
Cycle Yes 5
Crank
Rest time 0 60 Sec
Battle Yes Enable or Disable
Short Disable
Enable NA
Start Time Yes 0
Delay 0 300 Sec
PS0500 Default
Parameter Control Possible value
Group Name InPower Panel Values Units
Yes 120
Stop Time
Delay 0 600 Sec
Customer Yes Shutdow
Configurable Input Warning, n
I/O Function Yes Shutdown,
Yes Turn on if any Turn on
shutdown fault if any
is active/ Turn shutdow
On if any n fault is
warning fault active,
is active/
/Turn on when
Customer genset
output running
Function Yes
High AC Yes 110 %
Alternator Voltage
Protection Threshold 105 125 %
High AC Yes 5
Voltage
Delay 1 10 Sec
Low AC Yes 85%
Voltage
Threshold 50 95 %
Low AC Yes 5
Voltage
Delay 2 20 Sec
Under Yes 5
Frequency
Threshold 2 10 Hz
Under Yes 1000
Frequency ½
Delay 500 2000 cycles
Over Yes 5
Frequency
Threshold 2 10 Hz
Over Yes 1000
Frequency 1/2
Delay 100 2000 cycles
Low Oil Yes 25
Pressure
Protection – Shutdown
Engine Threshold 10 100 Psig
Low Oil Yes 5
Pressure
Shutdown
Delay 2 15 Sec
Low Oil Yes 30
Pressure
Warning
Threshold 10 100 Psig
PS0500 Default
Parameter Control Possible value
Group Name InPower Panel Values Units
Low Oil Yes 5
Pressure
Warning
Delay 2 15 Sec
High Yes 212
Coolant
Temperatu
re
Shutdown
Threshold 180 300 deg f
High Yes 5
Coolant
Temperatu
re
Shutdown
Delay 2 10 Sec
High Yes 200
Coolant
Temperatu
re Warning
Threshold 150 290 deg f
High Yes 5
Coolant
Temperatu
re Warning
Delay 2 10 Sec
Low 11
Battery
Voltage
Threshold Yes 11 13 VDC
Low Yes 30
Battery
Delay 2 60 Sec
High Yes 16
Battery
Voltage
Threshold 14 17 VDC
High Yes 30
Battery
Delay 2 60 Sec
Weak Yes 8
Battery
Voltage
Threshold 6 10 VDC
Weak Yes 3
Battery
Delay 1 5 sec
5. Hardware
TB15 – Tool Connector
Arrow at Pin 1
J12 – CT connector
Arrow at Pin 1
J12 –Pin 4
J16 –Pin 7
TB2 – Customer TB
Arrow at Pin 1
The dot designates pin 1 on the connectors,
J22
Alternator Voltage J16 Engine Connections
Sense inputs and Coolant Sensor, Lube Oil
• • Pressure sensor, Run / OFF /
Field Output
Auto Switch, FSO, Starter,
Battery, Mag Pick Up, Starter
PS0500 Disconnect Feed Back,
CONTROL BOARD Battery Charger D+, Chassis
• GND. Governor PWM
•
•
Engine Connector
The engine connector (J16) is a 12 pin connector-plug (12 MINI M-N-L). A possible supplier is
Molex; their part number is 39299123. The Cummins part number for this connector is 0323-
2589. The PCB outline drawing shows where the connector is located as above .Each signal is
described as below –
CT Connector
The CT connector is a 6- pin MATE-N-LOCK connector. The possible manufacturer is Tyco, and
the supplier part number for the part is 643749-1. The Cummins part number for this connector is
0323-2154. Connector details are as follows –
Customer Connection TB
The customer connection TB2 is a 6 pin terminal block. The possible supplier is Magnum:
The terminal pins details are as shown below-
Terminal Signal
pins
TB2-1 Remote start Switch Input
TB2-2 Glow Plug Output Relay
Driver (Low Side)
TB2-3 Customer Output Relay
Driver (Low Side)
TB2-4 Customer Input
TB2-5 E-Stop
TB2-6 NC
All the inputs are active GND. And outputs are low side drivers. Remote E-Stop switch should
have two independent potential free contacts. One NC contact for cutting out the Battery supply
to the Fuel Solenoid and another NC contact to disconnect controller’s E-Stop input from GND to
indicate to the control when the E-Stop is pushed in active state.
Battery Positive is not provided on the Customer terminal block (TB2). External provision needs
to be made in the harness to provide fused B+ via a 1 amp fuse for wiring up external relays.
External Relays of suitable contact ratings must be used for controlling FSO, Starter, Customer
Output and Glow plug.
PC Tool Connector
The PC tool connector is a dedicated 5 pin connector header block. The possible supplier is
Tyco, with the supplier part numbers are 796643-5. The Cummins part number for the same is
0323-2191-04.
Terminal Signal
pins
TB15-1 GND
TB15-2 NC
TB15-3 RS485_DATA_A
TB15-4 RS485_DATA_B
TB15-5 TOOL_WAKEUP
Remarks
Manufacturer’s Cummins
Quantity Name Description Manufacturer
part number part no