Series TY-FRL — 2.8, 5.6, and 8.0 K-factor


Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General NOTICE
The Series TY-FRL Sprinklers de-
Description scribed herein must be installed and
maintained in compliance with this
The TYCO Series TY-FRL, 2.8, 5.6, document, as well as with the appli-
and 8.0 K-factor, Upright and Pendent cable standards of the National Fire
Sprinklers described in this data sheet Protection Association, in addition to
are quick response, standard cover- the standards of any other authorities
age, solder type spray sprinklers de- having jurisdiction. Failure to do so
signed for use in light and ordinary may impair the performance of these
hazard commercial occupancies such devices.
as banks, hotels, shopping malls,
schools, hospitals, etc. The owner is responsible for main-
taining their fire protection system
The recessed version of the 2.8 and and devices in proper operating con-
5.6 K-factor, Series TY-FRL Pendent dition. Contact the installing contrac-
Sprinkler, where applicable, is intend- tor or sprinkler manufacturer with any
ed for use in areas with a finished ceil- questions.
ing. It uses a two-piece Style 20 (1/2
inch NPT) Recessed Escutcheon. The
Recessed Escutcheon provides 1/4 Sprinkler
inch (6,4 mm) of recessed adjustment
or up to 1/2 inch (12,7 mm) of total ad- Identification
justment from the flush pen
dent position. The adjustment provid- Numbers
ed by the Recessed Escutcheon re- TY1121. . . . . . Upright 2.8K, 1/2”NPT
duces the accuracy to which the fixed TY1221 . . . . Pendent 2.8K, 1/2”NPT
pipe drops to the sprinklers must be TY3121 . . . . . Upright 5.6K, 1/2”NPT
cut. TY3221 . . . . Pendent 5.6K, 1/2”NPT
An intermediate level version of the TY4121. . . . . . Upright 8.0K, 3/4”NPT
5.6 and 8.0 K-factor, Series TY-FRL TY4221 . . . . Pendent 8.0K, 3/4”NPT
Pendent Sprinkler can be obtained
TY1121 is a redesignation for S1879
by utilizing the Series TY-FRL Pen-
and G8973.
dent Sprinkler in combination with the
Model S4 Shield. TY1221 is a redesignation for S1880
and G8971.
TY3121 is a redesignation for S1864
and G8974.
TY3221 is a redesignation for S1865
and G8972.
TY4121 is a redesignation for S1866
and G8174.
TY4221 is a redesignation for S1867
IMPORTANT and G8172.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cau-
tions with respect to handling
and installation of sprinkler sys-
tems and components. Improp-
er handling and installation can
permanently damage a sprin-
kler system or its components
and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.

Page 1 of 6 OCTOBER 2013 TFP130


TFP130
Page 2 of 6

* Temperature rating ** Pipe thread connections per 1 - Frame 5 - Link 7 - Button


is indicated on ISO 7-1 can be provided on 2 - Strut Assembly 8 - Seal
ESCUTCHEON
Deflector. special request. 3 - Deflector * 6 - Ejection 9 - Bushing
PLATE SEATING
4 - Hook Spring
DEFLECTOR * SURFACE
9 1

WRENCH
8
2-11/16" AREA
(68,3 mm)
2-11/16" 6
7/16" 7
(68,3 mm)
(11,1 mm)
NOMINAL 2" 5 2
MAKE-IN (50,8 mm)
STYLE 20
RECESSED 4
ESCUTCHEON

3*
1/2" NPT** WRENCH DEFLECTOR * 2-7/8" (73,0 mm) DIA.
FLANGES
UPRIGHT PENDENT RECESSED PENDENT CROSS SECTION
FIGURE 1
QUICK RESPONSE SERIES TY-FRL UPRIGHT (TY1121) AND PENDENT (TY1221) SPRINKLERS
2.8 K-FACTOR, 1/2 INCH NPT

* Temperature rating ** Pipe thread connections per 1 - Frame 5 - Link 7 - Button


is indicated on ISO 7-1 can be provided on 2 - Strut Assembly 8 - Seal
ESCUTCHEON
Deflector. special request. 3 - Deflector * 6 - Ejection
PLATE SEATING
4 - Hook Spring
DEFLECTOR * SURFACE
1

WRENCH
8
2-11/16" AREA
(68,3 mm)
2-11/16" 6
7/16" 7
(68,3 mm)
(11,1 mm)
NOMINAL 2" 5 2
MAKE-IN (50,8 mm)
STYLE 20
RECESSED 4
ESCUTCHEON

3*
1/2" NPT** WRENCH DEFLECTOR * 2-7/8" (73,0 mm) DIA.
FLANGES
UPRIGHT PENDENT RECESSED PENDENT CROSS SECTION
FIGURE 2
QUICK RESPONSE SERIES TY-FRL UPRIGHT (TY3121) AND PENDENT (TY3221) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT
TFP130
Page 3 of 6

DEFLECTOR * CEILING PLATE 1 - Frame 6 - Ejection


SEATING SURFACE 2 - Strut Spring
3 - Deflector * 7 - Button
1
4 - Hook 8 - Seal
5 - Link
2-13/16" WRENCH
8 Assembly
(71,4 mm) AREA

1/2" 2-15/16" 7 * Temperature rating is


(12,7 mm) (74,6 mm) 6 indicated on Deflector.
NOMINAL
MAKE-IN 2-3/16" 2
(55,6 mm) 5 ** Pipe thread connections
per ISO 7-1 can be
4 provided on special
request.

3*
3/4" NPT** WRENCH
DEFLECTOR *
FLANGES
UPRIGHT PENDENT CROSS SECTION
FIGURE 3
QUICK RESPONSE SERIES TY-FRL UPRIGHT (TY4121) AND PENDENT (TY4221) SPRINKLERS
8.0 K-FACTOR, 3/4 INCH NPT

Technical Operation Installation


Data The fusible link (heat collector) assem-
bly is comprised of two halves that
The TYCO Series TY-FRL Sprinklers
must be installed in accordance with
Approvals are joined together by a thin layer of this section.
solder. When the rated temperature
UL and C-UL Listed. FM, NYC, and A leak tight 1/2 inch NPT sprinkler
is reached, the solder melts and the
LPCB Approved. (Refer to Table A for joint should be obtained with a torque
two link halves separate, allowing the
complete approval information includ- of 7 to 14 ft./lbs. (9,5 to 19,0 Nm). A
sprinkler to operate.
ing corrosion resistant status.) leak tight 3/4 inch NPT sprinkler joint
should be obtained with a torque of 10
Maximum Working Pressure Design Criteria to 20 ft./lbs. (13,4 to 26,8 Nm). Higher
175 psi (12,1 bar) levels of torque may distort the sprin-
The TYCO Series TY-FRL Pendent kler inlet and cause leakage or impair-
Discharge Coefficient and Upright Sprinklers are intended ment of the sprinkler.
K = 2.8 GPM/psi1/2 (40,3 LPM/bar1/2) for fire protection systems designed in
accordance with the standard instal- Do not attempt to make-up for insuf-
K = 5.6 GPM/psi1/2 (80,6 LPM/bar1/2) ficient adjustment in the escutcheon
K = 8.0 GPM/psi1/2 (115,2 LPM/bar1/2) lation rules recognized by the appli-
cable Listing or Approval agency (e.g., plate by under-or over-tightening the
Temperature Ratings UL Listing is based on the require- sprinkler. Readjust the position of the
ments of NFPA 13, and FM Approval sprinkler fitting to suit.
Refer to Table A
is based on the requirements of FM’s Series TY-FRL Pendent and Upright
Finishes Loss Prevention Data Sheets). Only Sprinkler Installation
Sprinkler: Refer to Table A the Style 20 Recessed Escutcheon, as
applicable, is to be used for recessed The Series TY-FRL Pendent and Up-
Recessed Escutcheon: White Coated, pendent installations. right Sprinklers must be installed in
Chrome Plated, or Brass Plated accordance with this section.
Physical Characteristics Step 1. Pendent sprinklers are to be
installed in the pendent position, and
Frame . . . . . . . . . . . . . . . . . . . . . . . Bronze
upright sprinklers are to be installed in
Strut . . . . . . . . . . . . . . . . . . . . . . . . . Monel the upright position.
Deflector . . . . . . . . . . . . . . . . . . . . . Bronze
Hook . . . . . . . . . . . . . . . . . . . . . . . . Monel Step 2. With pipe thread sealant ap-
Link Assembly ���������������������������������� Nickel
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Ejection Spring �������������������������������Inconel
Button . . . . . . . . . . . . . . . . . . . . . . . Bronze Step 3. Tighten the sprinkler into the
Seal . . . . . . . . . . . . . . . . . . . . . . . . TEFLON sprinkler fitting using only the W-Type
Bushing (2.8K only) ��������������������������� Brass 9 Sprinkler Wrench (Ref. Figure 6).
With reference to Figures 1, 2, and 3,
the W-Type 9 Sprinkler Wrench is to
be applied to the wrench area.
TFP130
Page 4 of 6

Series TY-FRL Recessed Pendent


SPRINKLER FINISH
Sprinkler Installation
K TYPE TEMP. FRAME NATURAL CHROME
RATING COLOR BRASS PLATED The Series TY-FRL Recessed Pendent
CODE Sprinklers must be installed in accor-
dance with the following instructions.
PENDENT 165°F (74°C) Unpainted
(TY1221) Step A. After installing the Style 20
212°F (100°C) White Mounting Plate, as applicable, over
2.8 165°F (74°C) Unpainted the sprinkler threads and with pipe
UPRIGHT thread sealant applied to the pipe
1/2” 1, 2, 5
(TY1121)
NPT 212°F (100°C) White threads, hand tighten the sprinkler into
RECESSED
the sprinkler fitting.
165°F (74°C) Unpainted
PENDENT Step B. Tighten the sprinkler into the
(TY1221 w/Style 20) 212°F (100°C) White sprinkler fitting using only the W-Type
165°F (74°C) Unpainted 1, 2, 3, 4, 5 12 Recessed Sprinkler Wrench (Ref.
PENDENT
(TY3221) Figure 7). With reference to Figure 1,
212°F (100°C) White 1, 2, 3, 5 or 2, the W-Type 12 Recessed Sprin-
5.6 165°F (74°C) Unpainted 1, 2, 3, 4, 5 kler Wrench is to be applied to the
UPRIGHT sprinkler wrenching flanges.
1/2” (TY3121)
NPT 212°F (100°C) White 1, 2, 3, 5
Step C. After the ceiling has been in-
RECESSED 165°F (74°C) Unpainted stalled or the finish coat has been ap-
PENDENT 1, 2, 5 plied, slide on the Style 20 Escutch-
(TY3221 w/Style 20) 212°F (100°C) White eon over the Series TY-FRL Sprinkler
165°F (74°C) Unpainted and push the Escutcheon over the
PENDENT Mounting Plate until its flange comes
8.0 (TY4221)
212°F (100°C) White in contact with the ceiling.
3/4” 1, 2, 3, 5
NPT UPRIGHT 165°F (74°C) Unpainted
(TY4121)
212°F (100°C) White

NOTES:
(1) Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers
(2) Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Response Sprinklers.
(3) Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
(4) Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/03) as Quick Response
Sprinklers.
(5) Approved by the City of New York under MEA 112-04-E.
TABLE A
LABORATORY LISTINGS AND APPROVALS
TFP130
Page 5 of 6

1/2±1/8" 2-7/8" DIA. 1/2" (12,7 mm)


(12,7±3,2 mm) (73,0 mm) 1/4" (6,4 mm)

FACE OF 2-1/4" DIA. MOUNTING


SPRINKLER (57,2 mm) PLATE
FITTING
1/8" WRENCH
(3,2 mm) RECESS

MOUNTING FIGURE 6
SURFACE W-TYPE 9 SPRINKLER
1-3/4" (44,5 mm)
WRENCH
1-1/2" (38,1 mm)

CLOSURE TY-FRL WRENCH


RECESS
FIGURE 4
SERIES TY-FRL (TY1221) RECESSED PENDENT SPRINKLER
ASSEMBLY WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON 2.8 K-FACTOR, 1/2 INCH NPT

1/2±1/8" 2-7/8" DIA. 1/2" (12,7 mm)


(12,7±3,2 mm) (73,0 mm) 1/4" (6,4 mm)

FACE OF 2-1/4" DIA. MOUNTING


SPRINKLER (57,2 mm) PLATE
FITTING PUSH WRENCH UP TO
1/8" ENSURE ENGAGEMENT
(3,2 mm) WITH SPRINKLER
WRENCHING AREA
FIGURE 7
W-TYPE 12 RECESSED
MOUNTING SPRINKLER WRENCH
SURFACE 1-3/4" (44,5 mm)
1-1/2" (38,1 mm)

CLOSURE TY-FRL
FIGURE 5
SERIES TY-FRL (TY3221) RECESSED PENDENT SPRINKLER
ASSEMBLY WITH TW0-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON 5.6 K-FACTOR, 1/2 INCH NPT

Care and Sprinklers that are found to be leaking


or exhibiting visible signs of corrosion
tection Association (e.g., NFPA 25), in
addition to the standards of any oth-
Maintenance must be replaced.
Automatic sprinklers must never be
er authorities having jurisdiction. The
installing contractor or sprinkler man-
The TYCO Series TY-FRL Sprinklers ufacturer should be contacted relative
painted, plated, coated or otherwise
must be maintained and serviced in to any questions.
altered after leaving the factory. Modi-
accordance with this section. fied or over-heated sprinklers must be It is recommended that automatic
Before closing a fire protection sys- replaced. sprinkler systems be inspected, test-
tem main control valve for mainte- ed, and maintained by a qualified In-
Care must be exercised to avoid dam-
nance work on the fire protection sys- spection Service in accordance with
age to the sprinklers -before, during,
tem that it controls, permission to shut local requirements and/or national
and after installation. Sprinklers dam-
down the affected fire protection sys- codes.
aged by dropping, striking, wrench
tem must be obtained from the prop- twist/slippage, or the like, must be
er authorities and all personnel who replaced.
may be affected by this action must
The owner is responsible for the in-
be notified.
spection, testing, and maintenance
Absence of an escutcheon, which is of their fire protection system and de-
used to cover a clearance hole, may vices in compliance with this docu-
delay the time to sprinkler operation in ment, as well as with the applicable
a fire situation. standards of the National Fire Pro-
TPF130
Page 6 of 6

P/N 58 - XXX - X - XXX

SIN TEMPERATURE
SPRINKLER
RATING
973 2.8K UPRIGHT (1/2”NPT) TY1121 1 NATURAL BRASS
165 165°F (74°C)
981 2.8K PENDENT (1/2”NPT) TY1221 9 CHROME PLATED
212 212°F (100°C)
974 5.6K UPRIGHT (1/2”NPT) TY3121
982 5.6K PENDENT (1/2”NPT) TY3221
174 8.0K UPRIGHT (3/4”NPT) TY4121
172 8.0K PENDENT (3/4”NPT) TY4221

TABLE B
SERIES TY-FRL PENDENT AND UPRIGHT SPRINKLERS
PART NUMBER SELECTION

Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indi-
cate the full product name and Part
Number (P/N).
Sprinkler Assemblies with NPT
Thread Connections
Specify: Series TY-FRL (specify
SIN), (specify K-factor), (specify Up-
right, Pendent, or Recessed Pendent)
Sprinkler Quick Response, (specify)
temperature rating, (specify type of
finish), P/N (specify from Table B)
Recessed Escutcheon
Specify: Style 20 Recessed Es-
cutcheon with (specify*) finish, P/N
(specify*)
*Refer to Technical Data Sheet TFP770
Sprinkler Wrench
Specify: W-Type 9 Sprinkler Wrench,
P/N 56-000-1-849
Specify: W-Type 12 Sprinkler Wrench,
P/N 56-798-1-001

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


Copyright © 2013 Tyco Fire Products, LP. All rights reserved.