CUADRO DE AREAS TRIBUTARIAS PARA REALIZAR EN EL

METRADO

AREA TRIBUTARIA (m2) ALTURA DE COLUMNA (m)


COLUMNA
1° PISO 2° - 4° PISO 1° PISO 2° - 4° PISO
C-1 4.83 4.83 4.60 2.80
C-2 9.66 9.66 4.60 2.80
C-3 4.83 4.83 4.60 2.80
C-4 6.69 6.69 4.60 2.80
C-5 13.38 13.30 4.60 2.80
C-6 6.69 6.28 4.60 2.80
C-7 3.40 3.40 4.60 2.80
C-8 12.03 11.40 4.60 2.80
C-9 5.11 3.40 4.60 2.80
C-10 3.40 3.40 4.60 2.80
C-11 12.03 12.03 4.60 2.80
C-12 6.80 6.80 4.60 2.80
C-13 3.40 3.40 4.60 2.80
C-14 6.80 6.80 4.60 2.80
C-15 3.40 3.40 4.60 2.80
UNIVERSIDAD NACIONAL DE JAEN INGENIERIA CIVIL

PARAMETROS PARA REALIZAR METRADO DE CARGAS POR NIVEL

ELEMENTO MEDIDAS PESO

Losa Aligerada Pesos de Losa (kg/m2) Area Tributaria (m2) Kg

Muros Pesos Ladrillo (kg/m3) Long. Total de muro (m) Espesor Muro(m) Altura (m) Kg

Pesos Espec. del C° Long. de viga princ.


Viga Principal Base de la Viga (m) Peralte (m) Kg
(kg/m3) (m)
Pesos Espec. del C° long. de viga
Viga Secundaria Base de la Viga (m) Peralte (m) Kg
(kg/m3) Secundaria (m)
Pesos Espec. del C°
Columna Altura de la Columna (m) Lado de la col. (m) Lado de la col. (m) Kg
(kg/m3)
Pesos Espec. de
Tabiqueria Area Tributaria (m2) Kg
Acabado(kg/m3)
Pesos Espec. de
Acabados Area Tributaria (m2) Kg
Acabado(kg/m3)
Carga Muerta= Kg

Carga Viva S/C (KG/m2)= Sera 100 kg/m2 en la Azotea Area Tributaria (m2) Kg

Carga Viva S/C (KG/m2)= Será 250 kg/m2 en Niveles Inferiores Area Tributaria (m2) Kg

Peso Total= CM+CV

En azotea solo existiran muros perimetrales de una altrura de 1.00 m.

ING. JUAN MORETO CONTRERAS


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

METRADO DE CARGAS

COLUMNA DEL EJE 1-1 y A-A

COLUMNA C-4 (4° piso)

MEDIDAS
ELEMENTO
LONG
PESO UNT. M ANCHO M AREA HM
Losa Aligerada 300 4.83
Muros 1350 4.47 0.12 1.00
Viga Principal 2400 0.25 0.4 1.81
Viga Secundaria 2400 0.25 0.4 2.66
Piso 2100 4.83 0.05
Cielo razo 2000 4.83 0.015
Columna 2400 2.80 0.25 0.25
Tarrageo Columna 2000 4.16 0.51 0.25
Muros azotea 1350 0.12 1.00
Carga Muerta 4 =

Carga Viva 4 100kg/m2 4.83 m2

PG4 = CM4 + CV4=

SECCION: PARA COLUMNAS C - 4:

P= 1.50PE
n= 0.2
f´c= 210kg/cm2

P
b.D=
PTOTAL = 1.5 (PG4 ) n . f'c
PTOTAL = 9032.98 kg
9032.976 kg
b.D=
0.2

Por RNE asumo b =


215.1 cm
14.665294 D= 8.60 cm

Conciderar: D= 25.0 cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

Seccion: 25cm x 25cm

COLUMNA DEL EJE 1-1 y A-A

COLUMNA C-4 (3° piso)

MEDIDAS
ELEMENTO
PESO UNT. LONG M ANCHO M AREA HM
Losa Aligerada 300 4.83
Muros 1350 4.47 0.15 2.40
Viga Principal 2400 0.25 0.4 1.81
Viga Secundaria 2400 0.25 0.4 2.66
piso 2100 4.83 0.05
cielo razo 2000 4.83 0.015
Columna 2400 2.80 0.25 0.25
tarrageo col 2000 4.16 0.015
Carga Muerta 3° =

Carga Viva 3° 250kg/m2 4.83 m2

PG3 = CM3 + CV3 + PG4=

SECCIÓN PARA COLUMNAS C - 4:

P= 1.50PE
n= 0.2
f´c= 210kg/cm2

P
b.D=
PTOTAL = 1.5 (PG6) n . f'c
PTOTAL = 31969.98 kg
31969.977 kg
b.D=
0.2

Por RNE asumo b =

761.19 cm D= 30.448
27.590
D= 35

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

Seccion: 25cm x 25cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

COLUMNA DEL EJE 1-1 y A-A

COLUMNA C-4 (2° piso)

MEDIDAS
ELEMENTO
PESO UNT. LONG M ANCHO M AREA HM

Losa Aligerada 300 4.83


Muros 1350 4.47 0.15 2.40
Viga Principal 2400 0.25 0.4 1.81
Viga Secundaria 2400 0.25 0.4 2.66
piso 2100 4.83 0.05
cielo razo 2000 4.83 0.015
Columna 2400 2.80 0.25 0.25
tarrageo col 2000 4.16 0.015
Carga Muerta 2° =

Carga viva 2° 250kg/m2 4.83 m2

PG2 = CM2 + CV2 + PG3 =

SECCIÓN PARA COLUMNAS C - 4:

P= 1.50PG
n= 0.2
f´c= 210kg/cm2
P
b.D=
PTOTAL = 1.5 (PG5) n . f'c
PTOTAL = 42614.178 Kg
42614.178 kg
b.D=
0.2

Asumo b =

D= 40.5849314 cm

Conciderar: D= 45 cm

Seccion: 25cm x 45cm

COLUMNA DEL EJE 1-1 y A-A

COLUMNA C-4 (1° Piso)

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

MEDIDAS
ELEMENTO
PESO UNT. LONG M ANCHO M AREA HM
Losa Aligerada 300 4.83
Muros 1800 3.62 0.15 3.60
Viga Principal 2400 0.25 0.4 1.81
Viga Secundaria 2400 0.25 0.4 2.66
piso 2100 4.83 0.05
cielo razo 2000 4.83 0.015
Columna 2400 4.60 0.25 0.25
tarrageo col 2000 4.16 0.015
Carga Muerta 1° =

Carga viva 1° 250kg/m2 4.83 m2

PG1= CM1 + CV2 + PG2 =

SECCIÓN PARA COLUMNAS C - 4:

P= 1.50PE
n= 0.2
f´c= 210kg/cm2
P
b.D=
PTOTAL = 1.5 (PG1 ) n . f'c
PTOTAL = 55682.71 kg
55682.709 kg
b.D=
0.2

Asumo b =

D= 33.14447

Conciderar: D= 35

Seccion: 40cm x 35cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

METRADO DE CARGAS

COLUMNA DEL EJE 1-1 y B-B

COLUMNA C-2 (4° piso)

ELEMENTO MEDIDAS
PESO PARCIAL
PESO UNT. LONG M ANCHO M
1447.74 kg Losa Aligerada 300
724.14 kg Muros 1350 6.39 0.15
434.40 kg Viga Principal 2400 0.25 0.4
638.40 kg Viga Secundaria 2400 0.25 0.4
507.15 kg piso 2100
144.77 kg cielo raso 2000
420.00 kg Columna 2400 2.80 0.25
1060.80 kg Columna tarrageo 2000 5.98 0.51
162.00 kg muros azotea 1350 0.12
5539.4 kg Carga Muerta4 =

482.58 kg Carga Viva 4 100kg/m2 9.66 m2

6021.98 kg PG4 = CM4 + CV4=

SECCION PARA COLUMNA C - 2:

P= 1.25PE
n= 0.25
f´c= 210kg/cm2

b.D=
PTOTAL = 1.25 (PG4 )
PTOTAL = 10968.09 kg
9032.976 kg
b.D=
(210 kg/cm2)

25 cm Por RNE asumo b =

D=

Conciderar: D=

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

Seccion: 25cm

COLUMNA DEL EJE 1-1 y B-B

COLUMNA C-2 (3° piso)

PESO PARCIAL ELEMENTO MEDIDAS

1447.74 kg Losa Aligerada 300


2172.42 kg Muros 1800 6.39 0.15
434.40 kg Viga Principal 2400 0.25 0.4
638.40 kg Viga Secundaria 2400 0.25 0.4
507.15 kg piso 2100
144.77 kg cielo razo 2000
420.00 kg Columna 2400 2.80 0.25
8320.00 kg tarrageo col 2000 5.98 0.015
14084.88 kg Carga Muerta 3° =

1206.45 kg Carga Viva 3° 250kg/m2 9.66 m2

21313.32 kg PG3 =CM3 + CV3 + PG4 =

SECCIÓN PARA COLUMNA C - 2:

P= 1.25PE
n= 0.25
f´c= 210kg/cm2

b.D=
PTOTAL = 1.25 (PG3)
PTOTAL = 26941.73625 Kg
31969.977 kg
b.D=
(210 kg/cm2)

25 cm Por RNE asumo b =

cm D=

cm Conciderar: D=

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

Seccion: 25cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

COLUMNA DEL EJE 1-1 y B-B

COLUMNA C-2 (2° Piso)

MEDIDAS
PESO PARCIAL ELEMENTO
PESO UNT. LONG M ANCHO M
1447.74 kg Losa Aligerada 300
2172.42 kg Muros 1350 6.39 0.15
434.40 kg Viga Principal 2400 0.25 0.4
638.40 kg Viga Secundaria 2400 0.25 0.4
507.15 kg piso 2100
144.77 kg cielo razo 2000
420.00 kg Columna 2400 2.80 0.25
124.80 kg tarrageo col 2000 5.98 0.015
5889.68 kg Carga Muerta 2° =

1206.45 kg Carga Viva 2° 250kg/m2 9.66 m2

28409.45 kg PG2 = CM2 + CV2 + PG3 =

SECCIÓN PARA COLUMNA C - 2:

P= 1.25PE
n= 0.25
f´c= 210kg/cm2

b.D=
PTOTAL = 1.25 (PG5)
PTOTAL = 41621.40375 Kg
42614.178 kg
b.D=
(210 kg/cm2)

25 cm Asumo b =

D=

Conciderar: D=

Seccion: 25cm

COLUMNA DEL EJE 1-1 y B-B

COLUMNA C-2 (1° piso)

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

PESO PARCIAL ELEMENTO MEDIDAS

1447.74 kg Losa Aligerada 300


3518.64 kg Muros 1350 3.38 0.15
434.40 kg Viga Principal 2400 0.25 0.4
638.40 kg Viga Secundaria 2400 0.25 0.4
507.15 kg piso 2100
144.77 kg cielo razo 2000
690.00 kg Columna 2400 4.60 0.25
124.80 kg tarrageo columna 2000 5.98 0.015
7505.90 kg Carga Muerta 1° =

1206.45 kg Carga Viva 1° 250kg/m2 9.66 m2

37121.8 kg PG1= CM1 + CV2 + PG2 =

SECCIÓN PARA COLUMNA C - 2:

P= 1.25PE
n= 0.25
f´c= 210kg/cm2

b.D=
PTOTAL = 1.25 (PG1 )
PTOTAL = 58841.92 kg
55682.709 kg
b.D=
(210 kg/cm2)

40 cm Asumo b =

cm D=

cm Conciderar: D=

Seccion: 45cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

E CARGAS

MEDIDAS PESO PARCIAL

AREA HM
9.66 2898
1.00 1293.975
3.63 871.2
2.66 638.4
9.66 0.05
9.66 0.015
0.25 420
0.25 1524.9
1 162
Carga Muerta4 = 7808.48 kg

9.66 m2 966.00 kg

PG4 = CM4 + CV4= 8774.48 kg

P
n . f'c
PTOTAL =
10968.09 kg
0.25 (210 kg/cm2)

Por RNE asumo b = 25 cm

8.356643 cm

25 cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

x 25cm

MEDIDAS PESO PARCIAL


AREA
9.66 2898.00 kg
2.40 4140.72 kg
3.63 871.20 kg
2.66 638.40 kg
9.66 0.05 1014.30 kg
9.66 0.015 289.80 kg
0.25 420.00 kg
0.51 91.49 kg
Carga Muerta 3° = 10363.91 kg

9.66 m2 2415.00 kg

PG3 =CM3 + CV3 + PG4 = 21553.39 Kg

P
n . f'c
PTOTAL =
26941.736 kg
0.25 (210 kg/cm2)

Por RNE asumo b = 25 cm

20.52704 cm

25 cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

x 25cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

MEDIDAS PESO PARCIAL

AREA HM
9.66 2898.00 kg
2.40 3105.54 kg
3.63 871.20 kg
2.66 638.40 kg
9.66 0.05 1014.30 kg
9.66 0.015 289.80 kg
0.25 420.00 kg
0.51 91.49 kg
Carga Muerta 2° = 9328.73 kg

9.66 m2 2415.00 kg

M2 + CV2 + PG3 = 33297.12 kg

P
n . f'c
PTOTAL =
41621.404 kg
0.25 (210 kg/cm2)

Asumo b = 25 cm

31.71155 cm

35 cm

x 35cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

MEDIDAS PESO PARCIAL


AREA
9.66 2898.00 kg
3.60 2464.02 kg
1.81 434.40 kg
3.63 871.20 kg
9.66 0.05 1014.30 kg
9.66 0.15 2898.00 kg
0.25 690.00 kg
0.51 91.49 kg
Carga Muerta 1° = 11361.41 kg

9.66 m2 2415.00 kg

PG1= CM1 + CV2 + PG2 = 47073.54 kg

P
n . f'c
PTOTAL =
58841.921 kg
0.25 (210 kg/cm2)

Asumo b = 45 cm

24.90663 cm

25 cm

x 25cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

METRADO DE CARGAS

COLUMNA DEL EJE 1-1 y C-C

COLUMNA C-4 (4° piso)

ELEMENTO MEDIDAS

AREA
Losa Aligerada 300 4.83
Muros 1350 4.57 0.15 1.00
Viga Principal 2400 0.25 0.4 1.81
Viga Secundaria 2400 0.25 0.4 2.66
piso 2100 4.83 0.05
cielo raso 2000 4.83 0.015
Columna 2400 2.80 0.25 0.25
tarrageo col 2000 1.96 0.51 0.25
muro azotea 1350 0.12 1
Carga Muerta 4 =

Carga Viva 4 100kg/m2 4.83 m2

PG4 = CM4 + CV4=

SECCION: PARA COLUMNA C - 4:

P= 1.50PE
n= 0.2
f´c= 210kg/cm2

P
b.D=
PTOTAL = 1.5 (PG4 ) n . f'c
PTOTAL = 8492.74 kg
8492.742 kg
b.D=
0.2

Por RNE asumo b =

D= 8.09 cm

Conciderar: D= 25.0 cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

Seccion: 25cm x 25cm

COLUMNA DEL EJE 1-1 y C-C

COLUMNA C-4 (3° piso)

ELEMENTO MEDIDAS
AREA
Losa Aligerada 300 4.83
Muros 1800 4.57 0.15 2.40
Viga Principal 2400 0.25 0.4 1.81
Viga Secundaria 2400 0.25 0.4 2.66
piso 2100 4.83 0.05
cielo razo 2000 4.83 0.015
Columna 2400 2.80 0.25 0.25
tarrageo col 2000 1.96 0.51 0.25
Carga Muerta 3° =

Carga Viva 3° 250kg/m2 4.83 m2

PG3 = CM3 + CV3 + PG4=

SECCIÓN PARA COLUMNA C - 4:

P= 1.50PE
n= 0.2
f´c= 210kg/cm2

P
b.D=
PTOTAL = 1.5 (PG6) n . f'c
PTOTAL = 20882.19 kg
20882.192 kg
b.D=
0.2

Por RNE asumo b =

D= 19.888

Conciderar: D= 25

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

Seccion: 25cm x 25cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

COLUMNA DEL EJE 1-1 y C-C

COLUMNA C-4 (2° piso)

ELEMENTO MEDIDAS

AREA
Losa Aligerada 300 4.83
Muros 1350 4.57 0.15 2.40
Viga Principal 2400 0.25 0.4 1.81
Viga Secundaria 2400 0.25 0.4 2.66
piso 2100 4.83 0.05
cielo razo 2000 4.83 0.015
Columna 2400 2.80 0.25 0.25
tarrajeo de columnas 2000 1.96 0.015 0.51
Carga Muerta 2° =

Carga viva 2° 250kg/m2 4.83 m2

PG2 = CM2 + CV2 + PG3 =

SECCIÓN PARA COLUMNA C - 4:

P= 1.50PE
n= 0.2
f´c= 210kg/cm2
P
b.D=
PTOTAL = 1.5 (PG5) n . f'c
PTOTAL = 30475.46709 Kg
30475.467 kg
b.D=
0.2

Asumo b =

D= 29.02425 cm

Conciderar: D= 30 cm

Seccion: 25cm x 30cm

COLUMNA DEL EJE 1-1 y C-C

COLUMNA C-4 (1° Piso)

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

ELEMENTO MEDIDAS
AREA
Losa Aligerada 300 4.83
Muros 1350 3.87 0.15 3.60
Viga Principal 2400 0.25 0.4 1.81
Viga Secundaria 2400 0.25 0.4 2.66
piso 2100 4.83 0.05
cielo razo 2000 4.83 0.015
Columna 2400 4.60 0.25 0.25
tarrajeo de columnas 2000 1.96 0.015 0.51
Carga Muerta 1° =

Carga viva 1° 250kg/m2 4.83 m2

PG1= CM1 + CV2 + PG2 =

SECCIÓN PARA COLUMNA C - 4:

P= 1.50PE
n= 0.2
f´c= 210kg/cm2
P
b.D=
PTOTAL = 1.5 (PG1 ) n . f'c
PTOTAL = 41419.04 kg
41419.04 kg
b.D=
0.2

Asumo b =

D= 24.65419

Conciderar: D= 25

Seccion: 40cm x 25cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

METRADO DE CARGAS

COLUMNA DEL EJE 2-2 y A-A

COLUMNA C-3 (4° piso)

PESO PARCIAL ELEMENTO MEDIDAS

AREA
1447.74 kg Losa Aligerada 300 6.69
925.43 kg Muros 1350 3.69 0.15
434.40 kg Viga Principal 2400 0.25 0.4
638.40 kg Viga Secundaria 2400 0.25 0.4
506.71 kg piso 2100 6.69
144.77 kg cielo raso 2000 6.69
420.00 kg Columna 2400 2.80 0.25
499.80 kg muro azotea 2000 0.51
162.00 kg tarrageo col 1350 4.00
5179.25 kg Carga Muerta4 =

482.58 kg Carga Viva 4 100kg/m2 6.69 m2

5661.83 kg PG4 = CM4 + CV4=

SECCION PARA COLUMNA C - 3:

P= 1.25PE
n= 0.25
f´c= 210kg/cm2

b.D=
PTOTAL = 1.25 (PG4 )
PTOTAL = 8002.97 kg
8492.742 kg
b.D=
(210 kg/cm2)

25 cm Por RNE asumo b =

D= 6.0975

Conciderar: D= 25

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

Seccion: 25cm

COLUMNA DEL EJE 2-2 y A-A

COLUMNA C-3 (3° piso)

PESO PARCIAL ELEMENTO MEDIDAS


AREA
1447.74 kg Losa Aligerada 300 6.69
2961.36 kg Muros 1350 3.69 0.15
434.40 kg Viga Principal 2400 0.25 0.4
638.40 kg Viga Secundaria 2400 0.25 0.4
506.71 kg piso 2100 6.69
144.77 kg cielo raso 2000 6.69
420.00 kg Columna 2400 2.80 0.25
499.80 kg tarrageo col 1350 4.00 0.51
7053.18 kg Carga Muerta 3° =

1206.45 kg Carga Viva 3° 250kg/m2 6.69 m2

13921.46 kg PG3 =CM3 + CV3 + PG4 =

SECCIÓN PARA COLUMNA C - 3:

P= 1.25PE
n= 0.25
f´c= 210kg/cm2

b.D=
PTOTAL = 1.25 (PG3)
PTOTAL = 18199.59375 Kg
20882.192 kg
b.D=
(210 kg/cm2)

25 cm Por RNE asumo b =

cm D=

cm Conciderar: D=

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

Seccion: 25cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

COLUMNAS DEL EJE 2-2 y A-A

COLUMNA C-3 (2° Piso)

PESO PARCIAL ELEMENTO MEDIDAS

AREA
1447.74 kg Losa Aligerada 300 6.69
2221.02 kg Muros 1350 3.69 0.15
434.40 kg Viga Principal 2400 0.25 0.4
638.40 kg Viga Secundaria 2400 0.25 0.4
25.34 kg piso 2100 6.69
2.17 kg cielo raso 2000 6.69
420.00 kg Columna 2400 2.80 0.25
29.99 kg tarrageo col 1350 4.00 0.51
5189.07 kg Carga Muerta 2° =

1206.45 kg Carga Viva 2° 250kg/m2 6.69 m2

20316.98 kg PG2 = CM2 + CV2 + PG3 =

SECCIÓN PARA COLUMNA C - 3:

P= 1.25PE
n= 0.25
f´c= 210kg/cm2

b.D=
PTOTAL = 1.25 (PG5)
PTOTAL = 28344.58125 Kg
30475.467 kg
b.D=
(210 kg/cm2)

25 cm Asumo b =

D= 21.59587

Conciderar: D= 25

Seccion: 25cm

COLUMNAS DEL EJE 2-2 y A-A

COLUMNA C-3 (1° piso)

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

PESO PARCIAL ELEMENTO MEDIDAS


AREA
1447.74 kg Losa Aligerada 300 6.69
2821.23 kg Muros 1350 5.50 0.15
434.40 kg Viga Principal 2400 0.25 0.4
638.40 kg Viga Secundaria 2400 0.25 0.4
25.34 kg piso 2100 6.69
2.17 kg cielo raso 2000 6.69
690.00 kg Columna 2400 4.60 0.25
29.99 kg tarrageo col 1350 4.00 0.51
6089.27 kg Carga Muerta 1° =

1206.45 kg Carga Viva 1° 250kg/m2 6.69 m2

27612.69 kg PG1= CM1 + CV2 + PG2 =

SECCIÓN PARA COLUMNA C - 3:

P= 1.25PE
n= 0.25
f´c= 210kg/cm2

b.D=
PTOTAL = 1.25 (PG1 )
PTOTAL = 41648.91 kg
41419.04 kg
b.D=
(210 kg/cm2)

40 cm Asumo b =

cm D=

cm Conciderar: D=

Seccion: 45cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

RGAS

PESO PARCIAL

2007.00 kg
1.00 747.23 kg
1.81 434.40 kg
3.69 885.60 kg
0.05 702.45 kg
0.02 200.70 kg
0.25 420.00 kg
0.25 255.00 kg
0.015 81.00 kg
Carga Muerta4 = 5733.38 kg

6.69 m2 669.00 kg

PG4 = CM4 + CV4= 6402.38 kg

P
n . f'c
PTOTAL =
8002.97 kg
0.25 (210 kg/cm2)

Por RNE asumo b = 25 cm

cm

cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

x 25cm

PESO PARCIAL

2007.00 kg
2.40 1793.34 kg
1.81 434.40 kg
3.69 885.60 kg
0.05 702.45 kg
0.02 200.70 kg
0.25 420.00 kg
0.015 41.31 kg
Carga Muerta 3° = 6484.80 kg

6.69 m2 1672.50 kg

PG3 =CM3 + CV3 + PG4 = 14559.68 Kg

P
n . f'c
PTOTAL =
18199.594 kg
0.25 (210 kg/cm2)

Por RNE asumo b = 25 cm

13.866357 cm

15 cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

x 15cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

PESO PARCIAL

2007.00 kg
2.40 1793.34 kg
1.81 434.40 kg
3.69 885.60 kg
0.05 702.45 kg
0.02 200.70 kg
0.25 420.00 kg
0.015 41.31 kg
Carga Muerta 2° = 6443.49 kg

6.69 m2 1672.50 kg

+ CV2 + PG3 = 22675.67 kg

P
n . f'c
PTOTAL =
28344.581 kg
0.25 (210 kg/cm2)

sumo b = 25 cm

cm

cm

x 25cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

PESO PARCIAL

2007.00 kg
3.60 4009.50 kg
1.81 434.40 kg
3.69 885.60 kg
0.05 702.45 kg
0.02 200.70 kg
0.25 690.00 kg
0.015 41.31 kg
Carga Muerta 1° = 8970.96 kg

6.69 m2 1672.50 kg

= CM1 + CV2 + PG2 = 33319.13 kg

P
n . f'c
PTOTAL =
41648.906 kg
0.25 (210 kg/cm2)

sumo b = 45 cm

17.629167 cm

20 cm

x 20cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

METRADO DE CARGAS

COLUMNA DEL EJE 2-2 y B-B

COLUMNA C-1 (4° piso)

ELEMENTO MEDIDAS

AREA
Losa Aligerada 300 13.30
Muros 1350 6.97 0.15 1.00
Viga Principal 2400 0.25 0.4 3.63
Viga Secundaria 2400 0.25 0.4 3.69
piso 2100 13.30 0.05
cielo raso 2000 13.30 0.02
Columna 2400 2.80 0.25 0.25
muro azotea 2000 0.51 0.25
tarrageo col 1350 4.07 0.015
Carga Muerta4 =

Carga Viva 4 100kg/m2 13.30 m2

PG4 = CM4 + CV4=

SECCION PARA COLUMNA C - 1:

P= 1.10PE
n= 0.25
f´c= 210kg/cm2

P
b.D=
PTOTAL = 1.10 (PG4 ) n . f'c
PTOTAL = 12145.26 kg
12145.26 kg
b.D=
0.25

Por RNE asumo b =

D= 9.253529 cm

Conciderar: D= 25 cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

Seccion: 25cm x 25cm

COLUMNA DEL EJE 2-2 y B-B

COLUMNA C-1 (3° piso)

ELEMENTO MEDIDAS
AREA
Losa Aligerada 300 13.30
Muros 1350 6.97 0.15 2.40
Viga Principal 2400 0.25 0.4 3.63
Viga Secundaria 2400 0.25 0.4 3.69
piso 2100 13.30 0.05
cielo raso 2000 13.30 0.02
Columna 2400 2.80 0.25 0.25
tarrageo col 1350 4.07 0.015
Carga Muerta 3° =

Carga Viva 3° 250kg/m2 13.30 m2

PG3 =CM3 + CV3 + PG4 =

SECCIÓN PARA COLUMNA C - 1:

P= 1.10PE
n= 0.25
f´c= 210kg/cm2
P
b.D=
PTOTAL = 1.10 (PG3) n . f'c
PTOTAL = 28378.11 kg
28378.108 kg
b.D=
0.25

Por RNE asumo b =

D= 21.621416

Conciderar: D= 25

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

Seccion: 25cm x 25cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

COLUMNA DEL EJE 2-2 y B-B

COLUMNA C-1 (2° Piso)

ELEMENTO MEDIDAS

AREA
Losa Aligerada 300 13.30
Muros 1350 6.97 0.15 2.40
Viga Principal 2400 0.25 0.4 3.63
Viga Secundaria 2400 0.25 0.4 3.69
piso 2100 13.30 0.05
cielo raso 2000 13.30 0.02
Columna 2400 2.80 0.25 0.25
tarrageo col 1350 4.07 0.015
Carga Muerta 2° =

Carga Viva 2° 250kg/m2 13.30 m2

PG2 = CM2 + CV2 + PG3 =

SECCIÓN PARA COLUMNA C - 1:

P= 1.10PE
n= 0.25
f´c= 210kg/cm2
P
b.D=
PTOTAL = 1.10 (PG5) n . f'c
PTOTAL = 44610.96 kg
44610.959 kg
b.D=
0.25

Asumo b =

D= 33.9893 cm

Conciderar: D= 35 cm

Seccion: 25cm x 35cm

COLUMNA DEL EJE 2-2 y B-B

COLUMNA C-1 (1° piso)

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

ELEMENTO MEDIDAS
AREA
Losa Aligerada 300 13.38
Muros 1800 3.39 0.15 3.60
Viga Principal 2400 0.25 0.4 3.63
Viga Secundaria 2400 0.25 0.4 3.69
piso 2100 13.38 0.05
cielo raso 2000 13.38 0.02
Columna 2400 4.60 0.25 0.25
tarrageo col 1350 4.07 0.015
Carga Muerta 1° =

Carga Viva 1° 250kg/m2 13.38 m2

PG1= CM1 + CV2 + PG2 =

SECCIÓN PARA COLUMNA C - 1:

P= 1.10PE
n= 0.25
f´c= 210kg/cm2
P
b.D=
PTOTAL = 1.10 (PG1 ) n . f'c
PTOTAL = 61099.52 kg
61099.517 kg
b.D=
0.25

Asumo b =

D= 25.862229

Conciderar: D= 30

Seccion: 45cm x 30cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

METRADO DE CARGAS

COLUMNA DEL EJE 2-2 y C-C

COLUMNA C-3 (4° piso)

PESO PARCIAL ELEMENTO MEDIDAS

3990 Losa Aligerada 300


1411.425 Muros 1350 5.37 0.15
871.2 Viga Principal 2400 0.25 0.4
885.6 Viga Secundaria 2400 0.25 0.4
1396.50 kg piso 2100
399.00 kg cielo raso 2000
420 Columna 2400 2.80 0.25
255.00 kg muro azotea 2000 0.51
82.42 kg tarrageo col 1350
9711.14 kg Kg Carga Muerta4

1330.00 kg Carga Viva 4 100kg/m2 6.28 m2

11041.14 kg PG4 = CM4 + CV4

SECCION PARA COLUMNA C - 3:

P= 1.25PE
n= 0.25
f´c= 210kg/cm2

b.D=
PTOTAL = 1.25 (PG4 )
PTOTAL = 8142.74 kg
12145.26 kg
b.D=
(210 kg/cm2)

25 cm Por RNE asumo b =

D=

Conciderar: D=

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

Seccion: 25cm

COLUMNA DEL EJE 2-2 y C-C

COLUMNA C-3 (3° piso)

PESO PARCIAL ELEMENTO MEDIDAS

3990.00 kg Losa Aligerada 300


3387.42 kg Muros 1350 5.37 0.15
871.20 kg Viga Principal 2400 0.25 0.4
885.60 kg Viga Secundaria 2400 0.25 0.4
1396.50 kg piso 2100
399.00 kg cielo raso 2000
420.00 kg Columna 2400 2.80 0.25
82.42 kg tarrageo col 1350
11432.14 kg Carga Muerta 3°

3325.00 kg Carga Viva 3° 250kg/m2 6.28 m2

25798.28 kg PG3 =CM3 + CV3 + PG4

SECCION PARA COLUMNA C - 3:

P= 1.25PE
n= 0.25
f´c= 210kg/cm2

b.D=
PTOTAL = 1.25 (PG3)
PTOTAL = 19047.23125 Kg
28378.108 kg
b.D=
(210 kg/cm2)

25 cm Por RNE asumo b =

cm D=

cm Conciderar: D=

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

Seccion: 25cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

COLUMNA DEL EJE 2-2 y C-C

COLUMNA C-3 (2° Piso)

PESO PARCIAL ELEMENTO MEDIDAS

3990.00 kg Losa Aligerada 300


3387.42 kg Muros 1800 5.37 0.15
871.20 kg Viga Principal 2400 0.25 0.4
885.60 kg Viga Secundaria 2400 0.25 0.4
1396.50 kg piso 2100
399.00 kg cielo raso 2000
420.00 kg Columna 2400 2.80 0.25
82.42 kg tarrageo col 1350
11432.14 kg Carga Muerta 2°

3325.00 kg Carga Viva 2° 250kg/m2 6.28 m2

40555.42 kg PG2 = CM2 + CV2 + PG3 =

SECCION PARA COLUMNA C - 3:

P= 1.25PE
n= 0.25
f´c= 210kg/cm2

b.D=
PTOTAL = 1.25 (PG5)
PTOTAL = 31039.14375 Kg
44610.959 kg
b.D=
(210 kg/cm2)

25 cm Asumo b =

D=

Conciderar: D=

Seccion: 25cm

COLUMNA DEL EJE 2-2 y C-C

COLUMNA C-3 (1° piso)

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

PESO PARCIAL ELEMENTO MEDIDAS

4014.00 kg Losa Aligerada 300


3295.08 kg Muros 1800 3.87 0.15
871.20 kg Viga Principal 2400 0.25 0.4
885.60 kg Viga Secundaria 2400 0.25 0.4
1404.90 kg piso 2100
401.40 kg cielo raso 2000
690.00 kg Columna 2400 4.60 0.25
82.42 kg tarrageo col 1350
11644.60 kg Carga Muerta 1°

3345.00 kg Carga Viva 1° 250kg/m2 6.69 m2

55545.02 kg PG1= CM1 + CV2 + PG2 =

SECCION PARA COLUMNA C - 3:

P= 1.25PE
n= 0.25
f´c= 210kg/cm2

b.D=
PTOTAL = 1.25 (PG1 )
PTOTAL = 44082.35 kg
61099.517 kg
b.D=
(210 kg/cm2)

45 cm Asumo b =

cm D=

cm Conciderar: D=

Seccion: 45cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

DE CARGAS

MEDIDAS PESO PARCIAL

AREA
6.28 1884.00 kg
1.00 1087.43 kg
1.81 434.40 kg
3.46 830.40 kg
6.28 0.05 659.40 kg
6.28 0.02 188.40 kg
0.25 420.00 kg
0.25 255.00 kg
6.28 0.015 127.17 kg
Carga Muerta4 = 5886.20 kg

6.28 m2 628.00 kg

PG4 = CM4 + CV4= 6514.20 kg

P
n . f'c
PTOTAL =
8142.74 kg
0.25 (210 kg/cm2)

Por RNE asumo b = 25 cm

6.203995 cm

25 cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

x 25cm

MEDIDAS PESO PARCIAL


AREA
6.28 1884.00 kg
2.40 2609.82 kg
1.81 434.40 kg
3.46 830.40 kg
6.28 0.05 659.40 kg
6.28 0.02 188.40 kg
0.25 420.00 kg
6.28 0.015 127.17 kg
Carga Muerta 3° = 7153.59 kg

6.28 m2 1570.00 kg

PG3 =CM3 + CV3 + PG4 = 15237.79 Kg

P
n . f'c
PTOTAL =
19047.231 kg
0.25 (210 kg/cm2)

Por RNE asumo b = 25 cm

14.51 cm

25 cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

x 25cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

MEDIDAS PESO PARCIAL

AREA
6.28 1884.00 kg
2.40 3479.76 kg
1.81 434.40 kg
3.46 830.40 kg
6.28 0.05 659.40 kg
6.28 0.02 188.40 kg
0.25 420.00 kg
6.28 0.015 127.17 kg
Carga Muerta 2° = 8023.53 kg

6.28 m2 1570.00 kg

M2 + CV2 + PG3 = 24831.32 kg

P
n . f'c
PTOTAL =
31039.144 kg
0.25 (210 kg/cm2)

Asumo b = 25 cm

23.64887 cm

25 cm

x 25cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

MEDIDAS PESO PARCIAL


AREA
6.69 2007.00 kg
3.60 3761.64 kg
1.81 434.40 kg
3.46 830.40 kg
6.69 0.05 702.45 kg
6.69 0.02 200.70 kg
0.25 690.00 kg
6.69 0.015 135.47 kg
Carga Muerta 1° = 8762.06 kg

6.69 m2 1672.50 kg

PG1= CM1 + CV2 + PG2 = 35265.88 kg

P
n . f'c
PTOTAL =
44082.347 kg
0.25 (210 kg/cm2)

Asumo b = 45 cm

18.65919 cm

20 cm

x 20cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

METRADO DE CARGAS

COLUMNA DEL EJE 3-3 y A-A

COLUMNA C-3 (4° piso)

ELEMENTO MEDIDAS

AREA
Losa Aligerada 300 3.40
Muros 1350 5.46 0.15 1.00
Viga Principal 2400 0.25 0.4 1.81
Viga Secundaria 2400 0.25 0.4 1.88
piso 2100 3.40 0.05
cielo raso 2000 3.40 0.02
Columna 2400 2.80 0.25 0.25
muro azotea 2000 0.51 0.25
tarrageo col 1350 3.40 0.015
Carga Muerta4 =

Carga Viva 4 100kg/m2 3.40 m2

PG4 = CM4 + CV4=

SECCION PARA COLUMNA C - 3:

P= 1.25PE
n= 0.25
f´c= 210kg/cm2

P
b.D=
PTOTAL = 1.25 (PG4 ) n . f'c
PTOTAL = 5691.51 kg
5691.51 kg
b.D=
0.25

Por RNE asumo b =

D= 4.336392 cm

Conciderar: D= 25 cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

Seccion: 25cm x 25cm

COLUMNA DEL EJE 3-3 y A-A

COLUMNA C-3 (3° piso)

ELEMENTO MEDIDAS
AREA
Losa Aligerada 300 3.40
Muros 1350 5.46 0.15 2.40
Viga Principal 2400 0.25 0.4 1.81
Viga Secundaria 2400 0.25 0.4 1.88
piso 2100 3.40 0.05
cielo raso 2000 3.40 0.02
Columna 2400 2.80 0.25 0.25
tarrageo col 1350 3.40 0.015
Carga Muerta 3° =

Carga Viva 3° 250kg/m2 3.40 m2

PG3 =CM3 + CV3 + PG4 =

SECCION PARA COLUMNA C - 3:

P= 1.25PE
n= 0.25
f´c= 210kg/cm2
P
b.D=
PTOTAL = 1.25 (PG3) n . f'c
PTOTAL = 13636.3665 Kg
13636.367 kg
b.D=
0.25

Por RNE asumo b =

D= 10.39

Conciderar: D= 25

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

Seccion: 25cm x 25cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

COLUMNA DEL EJE 3-3 y A-A

COLUMNA C-3 (2° Piso)

ELEMENTO MEDIDAS

AREA
Losa Aligerada 300 3.40
Muros 1350 5.46 0.15 2.40
Viga Principal 2400 0.25 0.4 1.81
Viga Secundaria 2400 0.25 0.4 1.88
piso 2100 3.40 0.05
cielo raso 2000 3.40 0.02
Columna 2400 2.80 0.25 0.25
tarrageo col 1350 3.40 0.015
Carga Muerta 2° =

Carga Viva 2° 250kg/m2 3.40 m2

PG2 = CM2 + CV2 + PG3 =

SECCION PARA COLUMNA C - 3:

P= 1.25PE
n= 0.25
f´c= 210kg/cm2
P
b.D=
PTOTAL = 1.25 (PG5) n . f'c
PTOTAL = 21495.1965 Kg
21495.197 kg
b.D=
0.25

Asumo b =

D= 16.37729 cm

Conciderar: D= 20 cm

Seccion: 25cm x 20cm

COLUMNA DEL EJE 3-3 y A-A

COLUMNA C-3 (1° piso)

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

ELEMENTO MEDIDAS
AREA
Losa Aligerada 300 3.40
Muros 1350 3.69 0.15 3.60
Viga Principal 2400 0.25 0.4 1.81
Viga Secundaria 2400 0.25 0.4 1.88
piso 2100 3.40 0.05
cielo raso 2000 3.40 0.02
Columna 2400 4.60 0.25 0.25
tarrageo col 1350 3.40 0.015
Carga Muerta 1° =

Carga Viva 1° 250kg/m2 3.40 m2

PG1= CM1 + CV2 + PG2 =

SECCION PARA COLUMNA C - 3:

P= 1.25PE
n= 0.25
f´c= 210kg/cm2
P
b.D=
PTOTAL = 1.25 (PG1 ) n . f'c
PTOTAL = 29823.11 kg
29823.111 kg
b.D=
0.25

Asumo b =

D= 12.623539

Conciderar: D= 15

Seccion: 45cm x 15cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

METRADO DE CARGAS

COLUMNA DEL EJE 3-3 y B-B

COLUMNA C-1 (4° piso)

PESO PARCIAL ELEMENTO MEDIDAS

AREA
1019.52 kg Losa Aligerada 300 11.40
1105.65 kg Muros 1350 9.9 0.15
434.40 kg Viga Principal 2400 0.25 0.4
451.20 kg Viga Secundaria 2400 0.25 0.4
356.83 kg piso 2100 11.40
101.95 kg cielo raso 2000 11.40
420.00 kg Columna 2400 2.80 0.25
255.00 kg muro azotea 2000 0.51
68.82 kg tarrageo col 1350 11.40
4213.37 kg Carga Muerta4 =

339.84 kg Carga Viva 4 100kg/m2 11.40 m2

4553.21 kg PG4 = CM4 + CV4=

SECCION PARA COLUMNA C - 1:

P= 1.10PE
n= 0.25
f´c= 210kg/cm2

b.D=
PTOTAL = 1.10 (PG4 )
PTOTAL = 11858.88 kg
5691.51 kg
b.D=
(210 kg/cm2)

25 cm Por RNE asumo b =

D= 9.035337

Conciderar: D= 25

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

Seccion: 25cm

COLUMNA DEL EJE 3-3 y B-B

COLUMNA C-1 (3° piso)

PESO PARCIAL ELEMENTO MEDIDAS


AREA
1019.52 kg Losa Aligerada 300 11.40
2653.56 kg Muros 1350 9.90 0.15
434.40 kg Viga Principal 2400 0.25 0.4
451.20 kg Viga Secundaria 2400 0.25 0.4
356.83 kg piso 2100 11.40
101.95 kg cielo raso 2000 11.40
420.00 kg Columna 2400 2.80 0.25
68.82 kg tarrageo col 1350 11.40
5506.28 kg Carga Muerta 3° =

849.60 kg Carga Viva 3° 250kg/m2 11.40 m2

10909.09 Kg PG3 =CM3 + CV3 + PG4 =

SECCION PARA COLUMNA C - 1:

P= 1.10PE
n= 0.2
f´c= 210kg/cm2

b.D=
PTOTAL = 1.10 (PG3)
PTOTAL = 28405.575 Kg
13636.367 kg
b.D=
(210 kg/cm2)

25 cm Por RNE asumo b =

cm D=

cm Conciderar: D=

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

Seccion: 25cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

COLUMNA DEL EJE 3-3 y B-B

COLUMNA C-1 (2° Piso)

PESO PARCIAL ELEMENTO MEDIDAS

AREA
1019.52 kg Losa Aligerada 300 11.40
2653.56 kg Muros 1350 9.90 0.15
434.40 kg Viga Principal 2400 0.25 0.4
451.20 kg Viga Secundaria 2400 0.25 0.4
356.83 kg piso 2100 11.40
101.95 kg cielo raso 2000 11.40
420.00 kg Columna 2400 2.80 0.25
68.82 kg tarrageo col 1350 11.40
5437.46 kg Carga Muerta 2° =

849.60 kg Carga Viva 2° 250kg/m2 11.40 m2

17196.16 kg PG2 = CM2 + CV2 + PG3 =

SECCION PARA COLUMNA C - 1:

P= 1.10PE
n= 0.25
f´c= 210kg/cm2

b.D=
PTOTAL = 1.10 (PG5)
PTOTAL = 44698.335 Kg
21495.197 kg
b.D=
(210 kg/cm2)

25 cm Asumo b =

D= 34.05587

Conciderar: D= 35

Seccion: 25cm

COLUMNA DEL EJE 3-3 y B-B

COLUMNA C-1 (1° piso)

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

PESO PARCIAL ELEMENTO MEDIDAS


AREA
1019.52 kg Losa Aligerada 300 12.03
2690.01 kg Muros 1800 4.47 0.15
434.40 kg Viga Principal 2400 0.25 0.4
451.20 kg Viga Secundaria 2400 0.25 0.4
356.83 kg piso 2100 12.03
101.95 kg cielo raso 2000 12.03
690.00 kg Columna 2400 4.60 0.25
68.82 kg tarrageo col 1350 12.03
5812.73 kg Carga Muerta 1° =

849.60 kg Carga Viva 1° 250kg/m2 12.03 m2

23858.49 kg PG1= CM1 + CV2 + PG2 =

SECCION PARA COLUMNA C - 1:

P= 1.10PE
n= 0.25
f´c= 210kg/cm2

b.D=
PTOTAL = 1.10 (PG1 )
PTOTAL = 61513.67 kg
29823.111 kg
b.D=
(210 kg/cm2)

45 cm Asumo b =

cm D=

cm Conciderar: D=

Seccion: 45cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

GAS

PESO PARCIAL

3420.00 kg
1.00 2004.75 kg
3.63 871.20 kg
3.75 900.00 kg
0.05 1197.00 kg
0.02 342.00 kg
0.25 420.00 kg
0.25 255.00 kg
0.015 230.85 kg
Carga Muerta4 = 9640.80 kg

11.40 m2 1140.00 kg

PG4 = CM4 + CV4= 10780.80 kg

P
n . f'c

11858.88 kg
0.25 (210 kg/cm2)

Por RNE asumo b = 25 cm

cm

cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

x 25cm

PESO PARCIAL

3420.00 kg
2.40 4811.40 kg
3.63 871.20 kg
3.75 900.00 kg
0.05 1197.00 kg
0.02 342.00 kg
0.25 420.00 kg
0.015 230.85 kg
Carga Muerta 3° = 12192.45 kg

11.40 m2 2850.00 kg

PG3 =CM3 + CV3 + PG4 = 25823.25 Kg

P
n . f'c

28405.575 kg
0.2 (210 kg/cm2)

Por RNE asumo b = 25 cm

27.05 cm

30 cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

x 30cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

PESO PARCIAL

3420.00 kg
2.40 4811.40 kg
3.63 871.20 kg
3.75 900.00 kg
0.05 1197.00 kg
0.02 342.00 kg
0.25 420.00 kg
0.015 230.85 kg
Carga Muerta 2° = 11961.60 kg

11.40 m2 2850.00 kg

CV2 + PG3 = 40634.85 kg

P
n . f'c

44698.335 kg
0.25 (210 kg/cm2)

sumo b = 25 cm

cm

cm

x 35cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

PESO PARCIAL

3607.50 kg
3.60 4344.84 kg
3.63 871.20 kg
3.75 900.00 kg
0.05 1262.63 kg
0.02 360.75 kg
0.25 690.00 kg
0.015 243.51 kg
Carga Muerta 1° = 12280.42 kg

12.03 m2 3006.25 kg

CM1 + CV2 + PG2 = 55921.52 kg

P
n . f'c

61513.673 kg
0.25 (210 kg/cm2)

sumo b = 45 cm

26.037534 cm

30 cm

x 30cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

METRADO DE CARGAS

COLUMNA DEL EJE 3-3 y C-C

COLUMNA C-3 (4° piso)

ELEMENTO MEDIDAS

AREA
Losa Aligerada 300 3.40
Muros 1350 3.79 0.15 1.00
Viga Principal 2400 0.25 0.4 1.81
Viga Secundaria 2400 0.25 0.4 1.88
piso 2100 3.40 0.05
cielo raso 2000 3.40 0.02
Columna 2400 2.80 0.25 0.25
muro azotea 2000 0.51 0.25
tarrageo col 1350 3.40 0.015
Carga Muerta4 =

Carga Viva 4 100kg/m2 3.40 m2

PG4 = CM4 + CV4=

SECCION PARA COLUMNA C - 3:

P= 1.25PE
n= 0.25
f´c= 210kg/cm2

P
b.D=
PTOTAL = 1.25 (PG4 ) n . f'c
PTOTAL = 5269.91 kg
5269.91 kg
b.D=
0.25

Por RNE asumo b =

D= 4.015167 cm

Conciderar: D= 25 cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

Seccion: 25cm x 25cm

COLUMNA DEL EJE 3-3 y C-C

COLUMNA C-3 (3° piso)

ELEMENTO MEDIDAS
AREA
Losa Aligerada 300 3.40
Muros 1800 3.79 0.15 2.40
Viga Principal 2400 0.25 0.4 1.81
Viga Secundaria 2400 0.25 0.4 1.88
piso 2100 3.40 0.05
cielo raso 2000 3.40 0.02
Columna 2400 2.80 0.25 0.25
tarrageo col 1350 3.40 0.015
Carga Muerta 3° =

Carga Viva 3° 250kg/m2 3.40 m2

PG3 =CM3 + CV3 + PG4 =

SECCIÓN PARA COLUMNA C - 3:

P= 1.25PE
n= 0.25
f´c= 210kg/cm2
P
b.D=
PTOTAL = 1.25 (PG3) n . f'c
PTOTAL = 12969.11875 Kg
12969.119 kg
b.D=
0.25

Por RNE asumo b =

D= 9.88

Conciderar: D= 10

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

Seccion: 25cm x 10cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

COLUMNA DEL EJE 3-3 y C-C

COLUMNA C-3 (2° Piso)

ELEMENTO MEDIDAS

AREA
Losa Aligerada 300 3.40
Muros 1350 3.79 0.15 2.40
Viga Principal 2400 0.25 0.4 1.81
Viga Secundaria 2400 0.25 0.4 1.88
piso 2100 3.40 0.05
cielo raso 2000 3.40 0.02
Columna 2400 2.80 0.25 0.25
tarrageo col 1350 3.40 0.015
Carga Muerta 2° =

Carga Viva 2° 250kg/m2 3.40 m2

PG2 = CM2 + CV2 + PG3 =

SECCIÓN PARA COLUMNA C - 3:

P= 1.25PE
n= 0.25
f´c= 210kg/cm2
P
b.D=
PTOTAL = 1.25 (PG5) n . f'c
PTOTAL = 19814.79375 Kg
19814.794 kg
b.D=
0.25

Asumo b =

D= 15.09699 cm

Conciderar: D= 20 cm

Seccion: 25cm x 20cm

COLUMNA DEL EJE 3-3 y C-C

COLUMNA C-3 (1° piso)

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

ELEMENTO MEDIDAS
AREA
Losa Aligerada 300 5.11
Muros 1350 2.93 0.15 3.60
Viga Principal 2400 0.25 0.4 1.81
Viga Secundaria 2400 0.25 0.4 1.88
piso 2100 5.11 0.05
cielo raso 2000 5.11 0.02
Columna 2400 4.60 0.25 0.25
tarrageo col 1350 5.11 0.015
Carga Muerta 1° =

Carga Viva 1° 250kg/m2 5.11 m2

PG1= CM1 + CV2 + PG2 =

SECCIÓN PARA COLUMNA C - 3:

P= 1.25PE
n= 0.25
f´c= 210kg/cm2
P
b.D=
PTOTAL = 1.25 (PG1 ) n . f'c
PTOTAL = 28959.04 kg
28959.041 kg
b.D=
0.25

Asumo b =

D= 12.257795

Conciderar: D= 15

Seccion: 45cm x 15cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

METRADO DE CARGAS

COLUMNA DEL EJE 4-4 y A-A

COLUMNA C-3 (4° piso)

PESO PARCIAL ELEMENTO MEDIDAS

AREA
1020.00 kg Losa Aligerada 300 3.40
767.48 kg Muros 1350 5.60 0.15
434.40 kg Viga Principal 2400 0.25 0.4
451.20 kg Viga Secundaria 2400 0.25 0.4
357.00 kg piso 2100 3.40
102.00 kg cielo raso 2000 3.40
420.00 kg Columna 2400 2.80 0.25
255.00 kg muro azotea 2000 0.51
68.85 kg tarrageo col 1350 3.40
3875.93 kg Carga Muerta4 =

340.00 kg Carga Viva 4 100kg/m2 3.40 m2

4215.93 kg PG4 = CM4 + CV4=

SECCION PARA COLUMNA C - 3:

P= 1.25PE
n= 0.25
f´c= 210kg/cm2

b.D=
PTOTAL = 1.25 (PG4 )
PTOTAL = 5726.95 kg
5269.91 kg
b.D=
(210 kg/cm2)

25 cm Por RNE asumo b =

D= 4.363392

Conciderar: D= 25

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

Seccion: 25cm

COLUMNA DEL EJE 4-4 y A-A

COLUMNA C-3 (3° piso)

PESO PARCIAL ELEMENTO MEDIDAS


AREA
1020.00 kg Losa Aligerada 300 3.40
2455.92 kg Muros 1350 5.60 0.15
434.40 kg Viga Principal 2400 0.25 0.4
451.20 kg Viga Secundaria 2400 0.25 0.4
357.00 kg piso 2100 3.40
102.00 kg cielo raso 2000 3.40
420.00 kg Columna 2400 2.80 0.25
68.85 kg tarrageo col 1350 3.40
5309.37 kg Carga Muerta 3° =

850.00 kg Carga Viva 3° 250kg/m2 3.40 m2

10375.30 Kg PG3 =CM3 + CV3 + PG4 =

SECCION PARA COLUMNA C - 3:

P= 1.25PE
n= 0.25
f´c= 210kg/cm2

b.D=
PTOTAL = 1.25 (PG3)
PTOTAL = 13756.854 Kg
12969.119 kg
b.D=
(210 kg/cm2)

25 cm Por RNE asumo b =

cm D=

cm Conciderar: D=

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

Seccion: 25cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

COLUMNA DEL EJE 4-4 y A-A

COLUMNA C-3 (2° Piso)

PESO PARCIAL ELEMENTO MEDIDAS

AREA
1020.00 kg Losa Aligerada 300 3.40
1841.94 kg Muros 1350 5.60 0.15
434.40 kg Viga Principal 2400 0.25 0.4
451.20 kg Viga Secundaria 2400 0.25 0.4
357.00 kg piso 2100 3.40
102.00 kg cielo raso 2000 3.40
420.00 kg Columna 2400 2.80 0.25
68.85 kg tarrageo col 1350 3.40
4626.54 kg Carga Muerta 2° =

850.00 kg Carga Viva 2° 250kg/m2 3.40 m2

15851.84 kg PG2 = CM2 + CV2 + PG3 =

SECCION PARA COLUMNA C - 3:

P= 1.25PE
n= 0.25
f´c= 210kg/cm2

b.D=
PTOTAL = 1.25 (PG5)
PTOTAL = 21700.734 Kg
19814.794 kg
b.D=
(210 kg/cm2)

25 cm Asumo b =

D= 16.53389

Conciderar: D= 20

Seccion: 25cm

COLUMNA DEL EJE 4-4 y A-A

COLUMNA C-3 (1° piso)

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

PESO PARCIAL ELEMENTO MEDIDAS


AREA
1533.00 kg Losa Aligerada 300 3.40
2135.97 kg Muros 1350 3.69 0.15
434.40 kg Viga Principal 2400 0.25 0.4
451.20 kg Viga Secundaria 2400 0.25 0.4
536.55 kg piso 2100 3.40
153.30 kg cielo raso 2000 3.40
690.00 kg Columna 2400 4.60 0.25
103.48 kg tarrageo col 1350 3.40
6037.90 kg Carga Muerta 1° =

1277.50 kg Carga Viva 1° 250kg/m2 3.40 m2

23167.23 kg PG1= CM1 + CV2 + PG2 =

SECCION PARA COLUMNA C - 3:

P= 1.25PE
n= 0.25
f´c= 210kg/cm2

b.D=
PTOTAL = 1.25 (PG1 )
PTOTAL = 30028.65 kg
28959.041 kg
b.D=
(210 kg/cm2)

45 cm Asumo b =

cm D=

cm Conciderar: D=

Seccion: 45cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

GAS

S PESO PARCIAL

1019.52 kg
1.00 1134.00 kg
1.81 434.40 kg
1.88 451.20 kg
0.05 356.83 kg
0.02 101.95 kg
0.25 420.00 kg
0.25 255.00 kg
0.015 68.82 kg
Carga Muerta4 = 4241.72 kg

3.40 m2 339.84 kg

PG4 = CM4 + CV4= 4581.56 kg

P
n . f'c

5726.95 kg
0.25 (210 kg/cm2)

Por RNE asumo b = 25 cm

cm

cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

x 25cm

S PESO PARCIAL

1019.52 kg
2.40 2721.60 kg
1.81 434.40 kg
1.88 451.20 kg
0.05 356.83 kg
0.02 101.95 kg
0.25 420.00 kg
0.015 68.82 kg
Carga Muerta 3° = 5574.32 kg

3.40 m2 849.60 kg

PG3 =CM3 + CV3 + PG4 = 11005.48 Kg

P
n . f'c

13756.854 kg
0.25 (210 kg/cm2)

Por RNE asumo b = 25 cm

10.48 cm

15 cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

x 15cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

S PESO PARCIAL

1019.52 kg
2.40 2721.60 kg
1.81 434.40 kg
1.88 451.20 kg
0.05 356.83 kg
0.02 101.95 kg
0.25 420.00 kg
0.015 68.82 kg
Carga Muerta 2° = 5505.50 kg

3.40 m2 849.60 kg

+ CV2 + PG3 = 17360.59 kg

P
n . f'c

21700.734 kg
0.25 (210 kg/cm2)

sumo b = 25 cm

cm

cm

x 20cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

S PESO PARCIAL

1019.52 kg
3.60 2690.01 kg
1.81 434.40 kg
1.88 451.20 kg
0.05 356.83 kg
0.02 101.95 kg
0.25 690.00 kg
0.015 68.82 kg
Carga Muerta 1° = 5812.73 kg

3.40 m2 849.60 kg

= CM1 + CV2 + PG2 = 24022.92 kg

P
n . f'c

30028.649 kg
0.25 (210 kg/cm2)

sumo b = 45 cm

12.710539 cm

15 cm

x 15cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

METRADO DE CARGAS

COLUMNA DEL EJE 4-4 y B-B

COLUMNA C-1 (4° piso)

ELEMENTO MEDIDAS

AREA
Losa Aligerada 300 12.03
Muros 1800 5.98 0.15 1.00
Viga Principal 2400 0.25 0.4 3.63
Viga Secundaria 2400 0.25 0.4 3.75
piso 2100 12.03 0.05
cielo raso 2000 12.03 0.02
Columna 2400 2.80 0.25 0.25
muro azotea 2000 0.51 0.25
tarrageo col 1350 12.03 0.015
Carga Muerta4 =

Carga Viva 4 100kg/m2 12.03 m2

PG4 = CM4 + CV4=

SECCION PARA COLUMNA C - 1:

P= 1.10PE
n= 0.25
f´c= 210kg/cm2

P
b.D=
PTOTAL = 1.10 (PG4 ) n . f'c
PTOTAL = 11811.45 kg
11811.45 kg
b.D=
0.25

Por RNE asumo b =

D= 8.9992 cm

Conciderar: D= 25 cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

Seccion: 25cm x 25cm

COLUMNA DEL EJE 4-4 y B-B

COLUMNA C-1 (3° piso)

ELEMENTO MEDIDAS
AREA
Losa Aligerada 300 12.03
Muros 1350 5.98 0.15 2.40
Viga Principal 2400 0.25 0.4 3.63
Viga Secundaria 2400 0.25 0.4 3.75
piso 2100 12.03 0.05
cielo raso 2000 12.03 0.02
Columna 2400 2.80 0.25 0.25
tarrageo col 1350 12.03 0.015
Carga Muerta 3° =

Carga Viva 3° 250kg/m2 12.03 m2

PG3 =CM3 + CV3 + PG4 =

SECCION PARA COLUMNA C - 1:

P= 1.10PE
n= 0.25
f´c= 210kg/cm2
P
b.D=
PTOTAL = 1.10 (PG3) n . f'c
PTOTAL = 26747.37 kg
26747.372 kg
b.D=
0.25

Por RNE asumo b =

D= 20.38

Conciderar: D= 25

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

Seccion: 25cm x 25cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

COLUMNA DEL EJE 4-4 y B-B

COLUMNA C-1 (2° Piso)

ELEMENTO MEDIDAS

AREA
Losa Aligerada 300 12.03
Muros 1350 7.67 0.15 2.40
Viga Principal 2400 0.25 0.4 3.63
Viga Secundaria 2400 0.25 0.4 3.75
piso 2100 12.03 0.05
cielo raso 2000 12.03 0.02
Columna 2400 2.80 0.25 0.25
tarrageo col 1350 12.03 0.015
Carga Muerta 2° =

Carga Viva 2° 250kg/m2 12.03 m2

PG2 = CM2 + CV2 + PG3 =

SECCION PARA COLUMNA C - 1:

P= 1.25PE
n= 0.25
f´c= 210kg/cm2
P
b.D=
PTOTAL = 1.10 (PG5) n . f'c
PTOTAL = 42586.768125 Kg
42586.768 kg
b.D=
0.25

Asumo b =

D= 32.44706 cm

Conciderar: D= 35 cm

Seccion: 25cm x 35cm

COLUMNA DEL EJE 4-4 y B-B

COLUMNA C-1 (1° piso)

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

ELEMENTO MEDIDAS
AREA
Losa Aligerada 300 12.03
Muros 1350 7.77 0.15 3.60
Viga Principal 2400 0.25 0.4 3.63
Viga Secundaria 2400 0.25 0.4 3.75
piso 2100 12.03 0.05
cielo raso 2000 12.03 0.02
Columna 2400 4.60 0.25 0.25
Tabiqueria 100 12.03 12.03
tarrageo col 1350 12.03 0.015
Carga Muerta 1° =

Carga Viva 1° 250kg/m2 12.03 m2

PG1= CM1 + CV2 + PG2 =

SECCION PARA COLUMNA C - 1:

P= 1.25PE
n= 0.25
f´c= 210kg/cm2
P
b.D=
PTOTAL = 1.10 (PG1 ) n . f'c
PTOTAL = 62176.30 kg
62176.296 kg
b.D=
0.25

Asumo b =

D= 26.318009

Conciderar: D= 30

Seccion: 45cm x 30cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

METRADO DE CARGAS

COLUMNA DEL EJE 4-4 y C-C

COLUMNA C-3 (4° piso)

PESO PARCIAL ELEMENTO MEDIDAS

3607.50 kg Losa Aligerada 300


1614.60 kg Muros 1350 5.56 0.15
871.20 kg Viga Principal 2400 0.25 0.4
900.00 kg Viga Secundaria 2400 0.25 0.4
1262.63 kg piso 2100
360.75 kg cielo raso 2000
420.00 kg Columna 2400 2.80 0.25
255.00 kg muro azotea 2000 0.51
243.51 kg tarrageo col 1350
9535.18 kg Carga Muerta

1202.50 kg Carga Viva 4 100kg/m2 6.80 m2

10737.68 kg PG4 = CM4 + C

SECCION PARA COLUMNA C - 3:

P= 1.25PE
n= 0.25
f´c= 210kg/cm2

b.D=
PTOTAL = 1.25 (PG4 )
PTOTAL = 8636.53 kg
11811.45 kg
b.D=
(210 kg/cm2)

25 cm Por RNE asumo b

D=

Conciderar: D=

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

Seccion: 25cm

COLUMNA DEL EJE 4-4 y C-C

COLUMNA C-3 (3° piso)

PESO PARCIAL ELEMENTO MEDIDAS

3607.50 kg Losa Aligerada 300


2906.28 kg Muros 1350 5.56 0.15
871.20 kg Viga Principal 2400 0.25 0.4
900.00 kg Viga Secundaria 2400 0.25 0.4
1262.63 kg piso 2100
360.75 kg cielo raso 2000
420.00 kg Columna 2400 2.80 0.25
243.51 kg tarrageo col 1350
10571.86 kg Carga Muerta 3

3006.25 kg Carga Viva 3° 250kg/m2 6.80 m2

24315.79 Kg PG3 =CM3 + CV3 + P

SECCION PARA COLUMNA C - 3:

P= 1.25PE
n= 0.25
f´c= 210kg/cm2

b.D=
PTOTAL = 1.25 (PG3)
PTOTAL = 20199.033 Kg
26747.372 kg
b.D=
(210 kg/cm2)

25 cm Por RNE asumo b

cm D=

cm Conciderar: D=

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

Seccion: 25cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

COLUMNA DEL EJE 4-4 y C-C

COLUMNA C-3 (2° Piso)

PESO PARCIAL ELEMENTO MEDIDAS

3607.50 kg Losa Aligerada 280


3727.62 kg Muros 1350 5.56 0.15
871.20 kg Viga Principal 2400 0.25 0.4
900.00 kg Viga Secundaria 2400 0.25 0.4
1262.63 kg piso 2100
360.75 kg cielo raso 2000
420.00 kg Columna 2400 2.80 0.25
243.51 kg tarrageo col 1350
11393.20 kg Carga Muerta 2

3006.25 kg Carga Viva 2° 250kg/m2 6.80 m2

38715.24 kg PG2 = CM2 + CV2 + PG3 =

SECCION PARA COLUMNA C - 3:

P= 1.25PE
n= 0.25
f´c= 210kg/cm2

b.D=
PTOTAL = 1.25 (PG5)
PTOTAL = 31419.573 Kg
42586.768 kg
b.D=
(210 kg/cm2)

25 cm Asumo b =

D=

Conciderar: D=

Seccion: 25cm

COLUMNA DEL EJE 4-4 y C-C

COLUMNA C-3 (1° piso)

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

PESO PARCIAL ELEMENTO MEDIDAS

3607.50 kg Losa Aligerada 300


5664.33 kg Muros 1350 7.47 0.15
871.20 kg Viga Principal 2400 0.25 0.4
900.00 kg Viga Secundaria 2400 0.25 0.4
1262.63 kg piso 2100
360.75 kg cielo raso 2000
690.00 kg Columna 2400 4.60 0.25
1202.50 kg tarrageo col 1350
243.51 kg Carga Muerta 1
14802.41 kg
Carga Viva 1° 250kg/m2 6.80 m2
3006.25 kg
PG1= CM1 + CV2 + PG2
56523.91 kg
SECCION PARA COLUMNA C - 3:

P= 1.25PE
n= 0.25
f´c= 210kg/cm2

b.D=
PTOTAL = 1.25 (PG1 )
PTOTAL = 46748.91 kg
b.D=
62176.296 kg
(210 kg/cm2)
Asumo b =
45 cm
D=
cm
Conciderar: D=
cm
Seccion: 45cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

DE CARGAS

MEDIDAS PESO PARCIAL

AREA
6.80 2039.04 kg
1.00 1125.90 kg
1.81 434.40 kg
3.75 900.00 kg
6.80 0.05 713.66 kg
6.80 0.02 203.90 kg
0.25 420.00 kg
0.25 255.00 kg
6.80 0.015 137.64 kg
Carga Muerta4 = 6229.54 kg

6.80 m2 679.68 kg

PG4 = CM4 + CV4= 6909.22 kg

P
n . f'c
PTOTAL =
8636.53 kg
0.25 (210 kg/cm2)

Por RNE asumo b = 25 cm

6.580213 cm

25 cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

x 25cm

MEDIDAS PESO PARCIAL


AREA
6.80 2039.04 kg
2.40 2702.16 kg
1.81 434.40 kg
3.75 900.00 kg
6.80 0.05 713.66 kg
6.80 0.02 203.90 kg
0.25 420.00 kg
6.80 0.015 137.64 kg
Carga Muerta 3° = 7550.80 kg

6.80 m2 1699.20 kg

PG3 =CM3 + CV3 + PG4 = 16159.23 Kg

P
n . f'c
PTOTAL =
20199.033 kg
0.25 (210 kg/cm2)

Por RNE asumo b = 25 cm

15.39 cm

20 cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

x 20cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

MEDIDAS PESO PARCIAL

AREA
6.80 1903.10 kg
2.40 2702.16 kg
1.81 434.40 kg
3.75 900.00 kg
6.80 0.05 713.66 kg
6.80 0.02 203.90 kg
0.25 420.00 kg
6.80 0.015 137.64 kg
Carga Muerta 2° = 7277.23 kg

6.80 m2 1699.20 kg

CM2 + CV2 + PG3 = 25135.66 kg

P
n . f'c
PTOTAL =
31419.573 kg
0.25 (210 kg/cm2)

Asumo b = 25 cm

23.93872 cm

25 cm

x 25cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

MEDIDAS PESO PARCIAL


AREA
6.80 2039.04 kg
3.60 5445.63 kg
1.81 434.40 kg
3.75 900.00 kg
6.80 0.05 713.66 kg
6.80 0.02 203.90 kg
0.25 690.00 kg
6.80 0.015 137.64 kg
Carga Muerta 1° = 10564.27 kg

6.80 m2 1699.20 kg

PG1= CM1 + CV2 + PG2 = 37399.13 kg

P
n . f'c
PTOTAL =
46748.915 kg PTOTAL =
0.25 (210 kg/cm2)

Asumo b = 45 cm

19.7879 cm

20 cm

x 20cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

METRADO DE CARGAS

COLUMNA DEL EJE 5-5 y A-A

COLUMNA C-4 (4° piso)

ELEMENTO PARAMETROS DE MEDIDA

AREA
Losa Aligerada 280 3.40
Muros 1350 3.69 0.15 1.00
Viga Principal 2400 0.25 0.4 1.81
Viga Secundaria 2400 0.25 0.4 1.88
piso 2100 3.40 0.05
cielo raso 2000 3.40 0.02
Columna 2400 2.80 0.25 0.25
muro azotea 2000 0.51 0.25
tarrageo col 1350 3.40 0.015
Carga Muerta 4 =

Carga Viva 4 100kg/m2 3.40 m2

PG4 = CM4 + CV4=

SECCION: PARA COLUMNA C - 4:

P= 1.50PE
n= 0.2
f´c= 210kg/cm2

P
b.D=
PTOTAL = 1.5 (PG4 ) n . f'c
PTOTAL = 6190.23 kg
6190.228 kg
b.D=
0.2

Por RNE asumo b =

D= 5.90 cm

Conciderar: D= 25.00 cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

Seccion: 25cm x 25cm

COLUMNA DEL EJE 5-5 y A-A

COLUMNA C-4 (3° piso)

DESCRIPCION MEDIDAS
AREA
Losa Aligerada 300 3.40
Muros 1800 3.69 0.15 2.40
Viga Principal 2400 0.25 0.4 1.81
Viga Secundaria 2400 0.25 0.4 1.88
piso 2100 3.40 0.05
cielo raso 2000 3.40 0.02
Columna 2400 2.80 0.25 0.25
tarrageo col 1350 3.40 0.015
Carga Muerta 3° =

Carga Viva 3° 250kg/m2 3.40 m2

PG3 = CM3 + CV3 + PG4=

SECCION: PARA COLUMNA C - 4:

P= 1.50PE
n= 0.2
f´c= 210kg/cm2

P
b.D=
PTOTAL = 1.5 (PG6) n . f'c
PTOTAL = 15330.39 kg
15330.390 kg
b.D=
0.2

Por RNE asumo b =

D= 14.600

Conciderar: D= 15

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

Seccion: 25cm x 15cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

COLUMNA DEL EJE 5-5 y A-A

COLUMNA C-4 (2° piso)

DESCRIPCION MEDIDAS

AREA
Losa Aligerada 180 3.40
Muros 1350 3.69 0.15 2.40
Viga Principal 2400 0.25 0.4 1.81
Viga Secundaria 2400 0.25 0.4 1.88
piso 2100 3.40 0.05
cielo raso 2000 3.40 0.02
Columna 2400 2.80 0.25 0.25
tarrageo col 1350 3.40 0.015
Carga Muerta 2° =

Carga viva 2° 250kg/m2 3.40 m2

PG2 = CM2 + CV2 + PG3 =

SECCION: PARA COLUMNA C - 4:

P= 1.50PE
n= 0.2
f´c= 210kg/cm2
P
b.D=
PTOTAL = 1.5 (PG5) n . f'c
PTOTAL = 22858.9443 Kg
22858.944 kg
b.D=
0.2

Asumo b =

D= 21.77 cm

Conciderar: D= 25 cm

Seccion: 25cm x 25cm

COLUMNA DEL EJE 5-5 y A-A

COLUMNA C-4 (1° Piso)

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

DESCRIPCION MEDIDAS
AREA
Losa Aligerada 280 3.40
Muros 1350 3.69 0.15 3.60
Viga Principal 2400 0.25 0.4 1.81
Viga Secundaria 2400 0.25 0.4 1.88
piso 2100 3.40 0.05
cielo raso 2000 3.40 0.02
Columna 2400 4.60 0.25 0.25
tarrageo col 1350 3.40 0.015
Carga Muerta 1° =

Carga viva 1° 250kg/m2 3.40 m2

PG1= CM1 + CV2 + PG2 =

SECCION: PARA COLUMNA C - 4:

P= 1.50PE
n= 0.2 P
b.D=
f´c= 210kg/cm2 n . f'c

PTOTAL = 1.5 (PG1 ) 32750.490 kg


b.D=
PTOTAL = 32750.49 kg 0.2

Asumo b =

D= 19.4943391

Conciderar: D= 20

Seccion: 40cm x 20cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

METRADO DE CARGAS

COLUMNA DEL EJE 5-5 y B-B

COLUMNA C-2 (4° piso)

PESO PARCIAL ELEMENTO MEDIDAS

951.55 kg Losa Aligerada 300


747.23 kg Muros 1350 5.71 0.15
434.40 kg Viga Principal 2400 0.25 0.4
451.20 kg Viga Secundaria 2400 0.25 0.4
356.83 kg piso 2100
101.95 kg cielo raso 2000
420.00 kg Columna 2400 2.80 0.25
255.00 kg muro azotea 2000 0.51
68.82 kg tarrageo col 1350
3786.98 kg Carga Muerta4

339.84 kg Carga Viva 4 100kg/m2 6.80 m2

4126.82 kg PG4 = CM4 + CV

SECCION PARA COLUMNA C - 2:

P= 1.25PE
n= 0.25
f´c= 210kg/cm2

b.D=
PTOTAL = 1.25 (PG4 )
PTOTAL = 8659.50 kg
6190.228 kg
b.D=
(210 kg/cm2)

25 cm Por RNE asumo b

D=

Conciderar: D=

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

Seccion: 25cm

COLUMNA DEL EJE 5-5 y B-B

COLUMNA C-2 (3° piso)

PESO PARCIAL DESCRIPCION MEDIDAS

1019.52 kg Losa Aligerada 300


2391.12 kg Muros 1350 5.71 0.15
434.40 kg Viga Principal 2400 0.25 0.4
451.20 kg Viga Secundaria 2400 0.25 0.4
356.83 kg piso 2100
101.95 kg cielo raso 2000
420.00 kg Columna 2400 2.80 0.25
68.82 kg tarrageo col 1350
5243.84 kg Carga Muerta 1°

849.60 kg Carga viva 1° 250kg/m2 6.80 m2

PG3= CM1 + CV2 + PG4 =


10220.26 kg

SECCION PARA COLUMNA C - 2:

P= 1.25PE
n= 0.25
f´c= 210kg/cm2
b.D=
PTOTAL = 1.25 (PG3)
PTOTAL = 20484.12675 Kg
b.D=
15330.390 kg
(210 kg/cm2)
Por RNE asumo b
25 cm
D=
cm
Conciderar: D=
cm
Seccion: 25cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

COLUMNA DEL EJE 5-5 y B-B

COLUMNA C-2 (2° Piso)

PESO PARCIAL MEDIDAS


DESCRIPCION

611.71 kg Losa Aligerada 300


1793.34 kg Muros 1350 5.71 0.15
434.40 kg Viga Principal 2400 0.25 0.4
451.20 kg Viga Secundaria 2400 0.25 0.4
356.83 kg piso 2100
101.95 kg cielo raso 2000
420.00 kg Columna 2400 2.80 0.25
68.82 kg tarrageo col 1350
4169.44 kg Carga Muerta 1°

849.60 kg Carga viva 1° 250kg/m2 6.80 m2


PG2 = CM2 + CV2 + PG3 =
15239.30 kg SECCION PARA COLUMNA C - 2:

P= 1.25PE
n= 0.25
f´c= 210kg/cm2
b.D=
PTOTAL = 1.25 (PG5)
PTOTAL = 29573.95575 Kg

b.D=

22858.944 kg
(210 kg/cm2) Asumo b =

25 cm D=

Conciderar: D=

Seccion: 25cm

COLUMNA DEL EJE 5-5 y B-B

COLUMNA C-2 (1° Piso)


DESCRIPCION MEDIDAS
Losa Aligerada 300

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

PESO PARCIAL Muros 1350 6.58 0.15

951.55 kg Viga Principal 2400 0.25 0.4


2690.01 kg Viga Secundaria 2400 0.25 0.4
434.40 kg Columna 2400 4.60 0.25
451.20 kg piso 2100
356.83 kg cielo raso 2000
101.95 kg tarrageo col 1350
690.00 kg Carga Muerta 1°
68.82 kg
5744.76 kg Carga viva 1° 250kg/m2 6.80 m2

849.60 kg PG2 = CM2 + CV2 + PG3 =


SECCION PARA COLUMNA C - 2:
21833.66 kg
P= 1.25PE
n= 0.25
f´c= 210kg/cm2
b.D=
PTOTAL = 1.25 (PG5)
PTOTAL = 43650.36 Kg

b.D=

32750.490 kg
(210 kg/cm2) Asumo b =

40 cm D=

cm Conciderar: D=

cm Seccion: 25cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

DE CARGAS

MEDIDAS PESO PARCIAL

AREA
6.80 2039.04 kg
1.00 1156.28 kg
3.63 871.20 kg
1.88 451.20 kg
6.80 0.05 713.66 kg
6.80 0.02 203.90 kg
0.25 420.00 kg
0.25 255.00 kg
6.80 0.015 137.64 kg
Carga Muerta4 = 6247.92 kg

6.80 m2 679.68 kg

PG4 = CM4 + CV4= 6927.60 kg

P
n . f'c
PTOTAL =
8659.50 kg
0.25 (210 kg/cm2)

Por RNE asumo b = 25 cm

6.597713 cm

25 cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

x 25cm

MEDIDAS PESO PARCIAL


AREA
6.80 2039.04 kg
2.40 2775.06 kg
3.63 871.20 kg
1.88 600.00 kg
6.80 0.05 713.66 kg
6.80 0.02 203.90 kg
0.25 420.00 kg
6.80 0.015 137.64 kg
Carga Muerta 1° = 7760.50 kg

6.80 m2 1699.20 kg

PG3= CM1 + CV2 + PG4 = 16387.30 kg

P
n . f'c
PTOTAL =
20484.127 kg PTOTAL =
0.25 (210 kg/cm2)

Por RNE asumo b = 25 cm

15.61 cm

20 cm

x 20cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

MEDIDAS PESO PARCIAL


AREA

6.80 2039.04 kg
2.40 2775.06 kg Kg
3.63 871.20 kg Kg
1.88 451.20 kg Kg
6.80 0.05 713.66 kg
6.80 0.02 203.90 kg
0.25 420.00 kg
6.80 0.015 137.64 kg
Carga Muerta 1° = 5572.66 kg

6.80 m2 1699.20 kg
CM2 + CV2 + PG3 = 23659.16 kg

P
n . f'c

29573.956 kg PTOTAL =
0.25 (210 kg/cm2) PTOTAL =

Asumo b = 25 cm

22.532538 cm

25 cm

x 25cm

MEDIDAS PESO PARCIAL


6.80 2039.04 kg

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

3.60 4796.82 kg
AREA
3.63 871.20 kg
1.88 451.20 kg
0.25 690.00 kg
6.80 0.05 713.66 kg
6.80 0.02 203.90 kg
6.80 0.015 137.64 kg
Carga Muerta 1° = 9561.92 kg

6.80 m2 1699.20 kg

CM2 + CV2 + PG3 = 34920.29 kg

P
n . f'c

43650.361 kg
0.25 (210 kg/cm2) PTOTAL =
PTOTAL =
Asumo b = 25 cm

33.257418 cm

35 cm

x 35cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

METRADO DE CARGAS

COLUMNA DEL EJE 5-5 y C-C

COLUMNA C-4 (4° piso)

ELEMENTO MEDIDAS

AREA
Losa Aligerada 300 3.40
Muros 1350 3.69 0.15 1.00
Viga Principal 2400 0.25 0.4 1.81
Viga Secundaria 2400 0.25 0.4 1.88
piso 2100 3.40 0.05
cielo raso 2000 3.40 0.02
Columna 2400 2.80 0.25 0.25
muro azotea 2000 0.51 0.25
tarrageo col 1350 3.40 0.015
Carga Muerta 4 =

Carga Viva 4 100kg/m2 3.40 m2

PG4 = CM4 + CV4=

SECCION: PARA COLUMNA C - 4:

P= 1.50PE
n= 0.2
f´c= 210kg/cm2

P
b.D=
PTOTAL = 1.5 (PG4 ) n . f'c
PTOTAL = 6292.18 kg
6292.180 kg
b.D=
0.2

Por RNE asumo b =

D= 5.99 cm

Conciderar: D= 25.00 cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

Seccion: 25cm x 25cm

COLUMNA DEL EJE 5-5 y C-C

COLUMNA C-4 (3° piso)

ELEMENTO MEDIDAS
AREA
Losa Aligerada 300 3.40
Muros 1350 3.69 0.15 2.40
Viga Principal 2400 0.25 0.4 1.81
Viga Secundaria 2400 0.25 0.4 1.88
piso 2100 3.40 0.05
cielo raso 2000 3.40 0.02
Columna 2400 2.80 0.25 0.25
tarrageo col 1350 3.40 0.015
Carga Muerta 3° =

Carga Viva 3° 250kg/m2 3.40 m2

PG3 = CM3 + CV3 + PG4=

SECCION: PARA COLUMNA C - 4:

P= 1.50PE
n= 0.2
f´c= 210kg/cm2

P
b.D=
PTOTAL = 1.5 (PG6) n . f'c
PTOTAL = 14535.67 kg
14535.672 kg
b.D=
0.2

Por RNE asumo b =

D= 13.843

Conciderar: D= 15

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

Seccion: 25cm x 15cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

COLUMNA DEL EJE 5-5 y C-C

COLUMNA C-4 (2° piso)

ELEMENTO MEDIDAS
AREA

Losa Aligerada 300 3.40


Muros 1350 3.69 0.15 2.40
Viga Principal 2400 0.25 0.4 1.81
Viga Secundaria 2400 0.25 0.4 1.88
piso 2100 3.40 0.05
cielo raso 2000 3.40 0.02
Columna 2400 2.80 0.25 0.25
tarrageo col 1350 3.40 0.015
Carga Muerta 2° =

Carga viva 2° 250kg/m2 3.40 m2

PG2 = CM2 + CV2 + PG3 =

SECCION: PARA COLUMNA C - 4:

P= 1.50PE
n= 0.2
f´c= 210kg/cm2
P
b.D=
PTOTAL = 1.5 (PG5) n . f'c
PTOTAL = 22675.9383 Kg
22675.938 kg
b.D=
0.2

Asumo b =

D= 21.60 cm

Conciderar: D= 25 cm

Seccion: 25cm x 25cm

COLUMNA DEL EJE 5-5 y C-C

COLUMNA C-4 (1° Piso)

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

ELEMENTO MEDIDAS
AREA
Losa Aligerada 300 3.40
Muros 1350 3.69 0.15 3.60
Viga Principal 2400 0.25 0.4 1.81
Viga Secundaria 2400 0.25 0.4 1.88
piso 2100 3.40 0.05
cielo raso 2000 3.40 0.02
Columna 2400 4.60 0.25 0.25
tarrageo col 1350 3.40 0.015
Carga Muerta 1° =

Carga viva 1° 250kg/m2 3.40 m2

PG1= CM1 + CV2 + PG2 =

SECCION: PARA COLUMNA C - 4:

P= 1.50PE
n= 0.2
f´c= 210kg/cm2
P
b.D=
PTOTAL = 1.5 (PG1 ) n . f'c
PTOTAL = 32669.44 kg
32669.44 kg
b.D=
0.2

Asumo b =

D= 19.44609268

Conciderar: D= 20

Seccion: 40cm x 20cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

PESO PARCIAL

1019.52 kg
747.23 kg
434.40 kg
451.20 kg
356.83 kg
101.95 kg
420.00 kg
255.00 kg
68.82 kg
3854.95 kg

339.84 kg

4194.79 kg

6292.180 kg
(210 kg/cm2)

25 cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

PESO PARCIAL

1019.52 kg
1793.34 kg
434.40 kg
451.20 kg
356.83 kg
101.95 kg
420.00 kg
68.82 kg
4646.06 kg

849.60 kg

9690.45 kg

14535.672 kg
(210 kg/cm2)

25 cm

cm

cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

PESO PARCIAL

1019.52 kg
1793.34 kg
434.40 kg
451.20 kg
356.83 kg
101.95 kg
420.00 kg
68.82 kg
4577.24 kg

849.60 kg

15117.29 kg

22675.938 kg
(210 kg/cm2)

25 cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

PESO PARCIAL

1019.52 kg
2690.01 kg
434.40 kg
451.20 kg
356.83 kg
101.95 kg
690.00 kg
68.82 kg
5812.73 kg

849.60 kg

21779.62 kg

32669.44 kg
(210 kg/cm2)

40 cm

cm

cm

ING. VICTOR R. VASQUEZ ALTAMIRANO


INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

RESUMEN DE DIMENSIONES DE COLUMNAS

NIVELES COLU NIVELES


COLUMNA
1° PISO 2° PISO 3° PISO 4° PISO MNA 1° PISO 2° PISO al 4° PISO
C-1 40cm x 35cm 25cm x 45cm 25cm x 25cm 25cm x 25cm C-4 25cm x 40cm 25cm
C-2 45cm x 25cm 25cm x 35cm 25cm x 25cm 25cm x 25cm C-3 25cm x 45cm 25cm
C-3 40cm x 25cm 25cm x 30cm 25cm x 25cm 25cm x 25cm C-4 25cm x 40cm 25cm
C-4 45cm x 20cm 25cm x 25cm 25cm x 15cm 25cm x 25cm C-3 25cm x 45cm 25cm
C-5 45cm x 30cm 25cm x 35cm 25cm x 15cm 25cm x 25cm C-1 25cm x 50cm 25cm
C-6 45cm x 20cm 25cm x 25cm 25cm x 25cm 25cm x 25cm C-2 25cm x 30cm 25cm
C-7 45cm x 15cm 25cm x 20cm 25cm x 25cm 25cm x 25cm C-2 25cm x 30cm 25cm
C-8 45cm x 30cm 25cm x 35cm 25cm x 25cm 25cm x 25cm C-1 25cm x 50cm 25cm
C-9 45cm x 15cm 25cm x 20cm 25cm x 30cm 25cm x 25cm C-2 25cm x 30cm 25cm
C - 10 45cm x 15cm 25cm x 20cm 25cm x 10cm 25cm x 25cm C-2 25cm x 30cm 25cm
C - 11 45cm x 30cm 25cm x 35cm 25cm x 15cm 25cm x 25cm C-1 25cm x 50cm 25cm
C - 12 45cm x 20cm 25cm x 25cm 25cm x 25cm 25cm x 25cm C-3 25cm x 45cm 25cm
C - 13 40cm x 20cm 25cm x 25cm 25cm x 20cm 25cm x 25cm C-4 25cm x 40cm 25cm
C - 14 25cm x 35cm 25cm x 25cm 25cm x 20cm 25cm x 25cm C3 25cm x 45cm 25cm
C - 15 40cm x 20cm 25cm x 25cm 25cm x 15cm 25cm x 25cm C-4 25cm x 40cm 25cm

CÁLCULO DE ALTURA DE COLUMNAS RESÚMEN DE PESOS TOTALES POR


COLUMNA

A). ANALISIS ESTRUCTURAL COLUMNA EJE PESO TOTAL

1° piso C-4 1-1 Y A-A 55682.71


H1 = 0.50 + 4.20 = 4.60 m C-4 1-1 Y C-C 41419.04
2° piso C-1 2-2- Y B-B 61099.52
C-3 2-2- Y C-C 44082.35
H2 = 0.20 + 2.6 = 2.80 m C-3 3-3 Y A-A 29823.11

ING.
INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

C-1 3-3 Y B-B 61513.67


3° piso C-3 3-3 Y C-C 28959.04
H3 = 0.20 + 2.6 = 2.80 m C-1 4-4 Y B-B 62176.30
C-3 4-4 Y C-C 46748.91
4° piso C-4 5-5 Y A-A 32750.49
H4 = 0.20 + 2.86 = 2.80 m C4 5-5 Y C-C 32669.44
PESO TOTAL 496924.57

B). FUERZA POR SISMO

H5 = (H1+H2)/2 = 3.70 m

H6 = (H2+H3)/2 = 2.80 m

H7 = (H3+H4)/2 = 2.80 m

H8 = H4/2 = 1.40 m

he = 13.00 m

ING.
INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

ES
2° PISO al 4° PISO
x 40cm
x 45cm
x 40cm
x 45cm
x 50cm
x 30cm
x 30cm
x 50cm
x 30cm
x 30cm
x 50cm
x 45cm
x 40cm
x 45cm
x 40cm

kg
kg
kg
kg
kg

ING.
INGENIERIA CIVIL UNIVERSIDAD NACIONAL DE JAÉN

kg
kg
kg
kg
kg
kg
kg

ING.
METRADOS POR SISMO
Acontinuación presentamos las áreas de losa por cada cada columma, las cuales han sido obtenidas
empleando el AUTOCAD. Asimismo también el área libre (todo el área menos muros y columnas).

RESUMEN DE ALTURAS, ÁREAS TRIB. Y LIBRES PARA COL. Y PISO perimetr


AREA TRIBUT. (m2) AREA LIBRE (m2) o
COLUMNA
2°-4° PISO 1° PISO 2°-4° PISO 1° PISO
C-1 4.826 4.826 3.442 3.442
C-2 9.660 9.660 7.716 7.716 12.536
C-3 4.826 4.826 3.442 3.4424 7.451
C-4 6.690 6.690 7.094 7.0937 11.701
C-5 13.300 13.380 15.966 16.0414 16.023
C-6 6.280 6.690 6.701 5.3501 11.251
C-7 3.398 3.398 3.614 3.6135 7.6263
C-8 11.400 12.025 13.496 14.1275 16.148
C-9 3.400 5.110 3.823 5.5365 7.8227
C-10 3.398 3.398 3.609 3.6085 7.6285
C-11 12.025 12.025 14.102 14.1021 16.1355
C-12 6.797 6.797 7.207 7.207 11.826
C-13 3.398 3.398 3.556 3.5555 7.756
C-14 6.797 6.797 7.978 7.9777 12.704
C-15 3.398 3.398 3.571 3.5712 7.6012
TOTAL 99.594 102.419 105.314 106.385

RESUMEN DE ALTURAS, ÁREAS TRIBUTARIAS Y LIBRES PARA CADA PISO LONG. DE


MUROS
NIVELES AREA TRIBUT. (m2) AREA LIBRE (m2) ALT. COLUM. (m)
1° PISO 102.4188 106.3851 3.70 m 83.283
2° PISO 99.5938 105.3143 2.80 m
3° PISO 99.5938 105.3143 2.80 m
4° PISO 99.5938 105.3143 1.40 m

Acontinuación presentamos las longitudes totales por nivel de las vigas y muros. Los muros es la su
tanto en "X" y "Y" que actuan en cada piso. Se empleó el AUTOCAD para el acotado.

LONGITUD TOTAL DE MUROS Y VIGAS POR PISO (CONSIDERANDO EN "X" y "Y")


LONGITUD TOTAL (m)
PISO VIGAS
MUROS
V.P V.S
1° PISO 83.28 45.33 36.25
2° PISO 83.28 45.33 36.25
3° PISO 83.28 45.33 36.25
4° PISO 85.96 45.33 36.25
PRIMER PISO
indicar
DESCRIPCION PARAMETROS DE MEDIDA peso parcial
Peso de losa aligerada 300 102.4188 30726
Peso de acabado de piso 2000 106.3851 0.05 10639
Peso de tarrajeo cielorrazo 2000 106.3851 0.025 5319.26
Peso de muros 1350 83.28 m 0.15 3.70 62400
Peso de tarrajeo de muros 2000 2 0.025 308.147 30815
Peso de viga principal 2400 0.25 0.4 45.33 10878
Peso de tarrajeo en viga princ. 2000 0.025 0.2 45.33 453.27
Peso de viga secundaria 2400 0.25 0.4 36.25 8700
Peso de tarrajeo en viga sec. 2000 0.05 0.2 36.25 725
Peso de columna 2400 3.70 0.25 0.4 5 4440
2400 3.70 0.25 0.45 4 3996
2400 3.70 0.25 0.3 4 2664
2400 3.70 0.25 0.5 2 2220
Peso de tarrajeo en columna 2000 3.7000 0.025 3.25 601.25

TOTAL C.M1 = 174576 Kg

Carga viva 25%CV 0.25 100 106.3851 2659.63 Kg

TOTAL C.V1 = 2659.63 Kg

PTOTAL 1 = 177235.5 Kg
SEGUNDO PISO

DESCRIPCION PARAMETROS DE MEDIDA peso parcial


Peso de losa aligerada 300 99.5938 29878
Peso de acabado de piso 2000 105.3143 0.05 10531
Peso de tarrajeo cielorrazo 2000 105.3143 0.025 5265.72
Peso de muros 1350 83.28 m 0.15 2.80 47221
Peso de tarrajeo de muros 2000 2 0.025 233.192 23319
Peso de viga principal 2400 0.25 0.4 45.33 10878
Peso de tarrajeo en viga princ. 2000 0.025 0.2 45.33 453.27
Peso de viga secundaria 2400 0.25 0.4 36.25 8700
Peso de tarrajeo en viga sec. 2000 0.05 0.2 36.25 725
Peso de columna 2400 2.80 0.25 0.4 5 3360
2400 2.80 0.25 0.45 4 3024
2400 2.80 0.25 0.3 4 2016
2400 2.80 0.25 0.5 2 1680
Peso de tarrajeo en columna 2000 2.80 0.025 3.25 455

TOTAL C.M2 = 147508 Kg

Carga viva 25%CV 0.25 100 105.3143 2632.86 Kg

TOTAL C.V2 = 2632.86 Kg

PTOTAL 2 = 150140.6 Kg
TERCER PISO

DESCRIPCION PARAMETROS DE MEDIDA peso parcial


Peso de losa aligerada 300 99.5938 29878
Peso de acabado de piso 2000 105.3143 0.05 10531
Peso de tarrajeo cielorrazo 2000 105.3143 0.025 5265.72
Peso de muros 1350 83.28 m 0.15 2.80 47221
Peso de tarrajeo de muros 2000 2 0.025 233.192 23319
Peso de viga principal 2400 0.25 0.4 45.33 10878
Peso de tarrajeo en viga princ. 2000 0.025 0.2 45.33 453.27
Peso de viga secundaria 2400 0.25 0.4 36.25 8700
Peso de tarrajeo en viga sec. 2000 0.05 0.2 36.25 725
Peso de columna 2400 2.80 0.25 0.4 5 3360
2400 2.80 0.25 0.45 4 3024
2400 2.80 0.25 0.3 4 2016
2400 2.80 0.25 0.5 2 1680
Peso de tarrajeo en columna 2000 2.80 0.025 3.25 455

TOTAL C.M3 = 147508 Kg

Carga viva 25%CV 0.25 100 105.3143 2632.86 Kg

TOTAL C.V3 = 2632.86 Kg

PTOTAL 3 = 150140.6 Kg
CUARTO PISO

DESCRIPCION PARAMETROS DE MEDIDA peso parcial


Peso de losa aligerada 300 99.5938 29878
Peso de acabado de piso 2000 105.3143 0.05 10531
Peso de tarrajeo cielorrazo 2000 105.3143 0.025 5265.72
Peso de muros 1350 85.96 m 0.15 1.40 24370
Peso de tarrajeo de muros 2000 2 0.025 120.344 12034.4
Peso de viga principal 2400 0.25 0.4 45.33 10878
Peso de tarrajeo en viga princ. 2000 0.025 0.2 45.33 453.27
Peso de viga secundaria 2400 0.25 0.4 36.25 8700
Peso de tarrajeo en viga sec. 2000 0.05 0.2 36.25 725
Peso de columna 2400 1.40 0.25 0.4 5 1680
2400 1.40 0.25 0.45 4 1512
2400 1.40 0.25 0.3 4 1008
2400 1.40 0.25 0.5 2 840
Peso de tarrajeo en columna 2000 1.40 0.025 3.25 227.5

TOTAL C.M4 = 108104 Kg

Carga viva 25%CV 0.25 100 105.3143 2632.86 Kg

TOTAL C.V4 = 2632.86 Kg

PTOTAL 4 = 110736.5 Kg

RESUMEN DE PESOS PARA CADA PISO


PESO
NIVELES
Kg Tn
1° NIVEL 177235.53 Kg P= 177.24 Tn
2° NIVEL 150140.59 Kg P= 150.14 Tn
3° NIVEL 150140.59 Kg P= 150.14 Tn
4° NIVEL 110736.45 Kg P= 110.74 Tn
PESO TOTAL 588253.17 Kg P= 588.25 Tn
ales han sido obtenidas
muros y columnas).

muros. Los muros es la suma


AD para el acotado.
peso parcial
Kg
Kg
Kg
Kg
Kg
Kg
Kg
Kg
Kg
Kg
Kg
Kg
Kg
Kg

174576 Kg

2659.63 Kg

2659.63 Kg

177235.5 Kg
peso parcial
Kg
Kg
Kg
Kg
Kg
Kg
Kg
Kg
Kg
Kg
Kg
Kg
Kg
Kg

147508 Kg

2632.86 Kg

2632.86 Kg

150140.6 Kg
peso parcial
Kg
Kg
Kg
Kg
Kg
Kg
Kg
Kg
Kg
Kg
Kg
Kg
Kg
Kg

147508 Kg

2632.86 Kg

2632.86 Kg

150140.6 Kg
peso parcial
Kg
Kg
Kg
Kg
Kg
Kg
Kg
Kg
Kg
Kg
Kg
Kg
Kg
Kg

108104 Kg

2632.86 Kg

2632.86 Kg

110736.5 Kg
DETERMINACION DE CORTANTE DE BASAL

Z.U.S.C ANALISIS ESTATICO


V = *P
R

DEFINICION DE CADAV VARIABLE

a) FACTOR DE ZONA "Z"


se interpreta como la aceleracion maxima horizontal en el suelo con una probabilidad de 1
excedida en 50 años (se expreza como aceleracion de la gravedad)

Descripcion del proyecto: Nueva cajamarca está ubicado en la zona "3" según el mapa me zonificación sismica
para el cual el factor es el siguiente:

Z a nivel de la superficie sera Z*S, donde S e


Z sobre roca tebemos que multiplicar por un

ZONA Z Entonces:
4 0.45
3 0.35 Z= 0.35
2 0.25
1 0.10
b) FACTOR DE USO "U" Depende de la categoria de la edificion, incrementando la aceleracion espectral de diseño
perdidas que podria ocasionar su colapso

En este caso la se ecuentra en la categoria C, llamadas edificaciones comunes seg: N E.030

U= 1.0

c) FACTOR DE AMPLIFICACION DE SUELO "S"

c1) factor del suelo s


ZONA SUELO S0 S1 S2
Z3 0.80 1.0 1.15

Entonces: S= 1.15 SUELOS INTERMEDIOS


c2)Perfil de suelo: SUELOS INTERMDIO

Perfil de suelo valores de "TP" Y "TL"


perfil de suelo
S0 S1 S2 S3
TP (S) 0.3 0.4 0.6 1.0
TL (S) 3.0 2.5 2.0 1.6

Entonces: TP = 0.6 TABLA N°4


E 0.30
Entonces: TL = 2.0

d) FACTOR DE AMPLIFICACION SISMICA "C" Se difine de acuerdo a las condiciones de sitio y se interp
de amplificacions sismica se acelera ©
Calculo del periodo fundamental "T":
NOTA
T= Hn Hn = 13 m
C C = 35 m

T= 13 m Donde:
35 m he= Altura del Edificio.

T = 0.37 Seg. Sistema Resistente al Corte


Solo proticos
Calculo de "C" T < TP →
Porticos, cajas de ascensores, escaleras
Muros de corte
Cumple C = 2.50 Seg.
Condicion

e) FACTOR DE REDUCCION DE LA FUERZA SISMICA "R"

Es el producto del coeficiente R0 determindao a parir de la tabla N°7 y los factores I a y Ip


obtenidos de la tablas N°7 y N°9.

R=�_0∗�_�∗�_�
Calculo de R0:

R0 = Para estructuras de concreto armado , con un


8 sistema estructural de PORTICOS

ANALISIS DE IRREGULARIDADES EN ALTURA


1. Irregularidad de Masa o Peso I=0.9
Cuando el peso es mayor que 1.5 piso adyacente

�_�>𝟏.𝟓∗�_𝟏

NIVEL PESO
4 P= 110.7365 Tn
3 P= 150.1406 Tn
2 P= 150.1406 Tn
1 P= 178.6833 Tn
total P= 589.7010 Tn

Observamos que los pesos del segundo, tercer y cuarto piso son iguales. El unico
analisis se dará para el primer piso, pues el criterio de esta irregularidad no se
aplica a azoteas.

P2 P1 x 1.5
150.14 268.02
De los resultados obtenidos, observamos que P2 < 1.5P1; por lo tanto no
existe irregularidad.

Ia = 1
2. Irregularidad de Geometría Vertical I= 0.9
Lad imenciones en planta de la estructura resiste a cargas laterales es mayor que 130% de la c
dimension en un piso adyacente, NOTA no es aplicable en azoteas ni en zotanos

�_𝟏> 〖𝟏 .𝟑∗� 〗
_�

La edificacion en análisis presenta una planta tipica en todos sus niveles, no sufre variaciones en
el diafragma; por lo tanto

Ia = 1.00

3. Discontinuidad de los sistemas resistentes I= 0.80


Desalineamiento de elementos verticales, tanto por un cambio de orientacion, como por un desplazamie
de magnitud mayor que la dimencion del elemento que resita mas de 10% de la fuerza cortante

∆=𝟎.�𝟓� �_�>𝟎.𝟏𝟎∗�_�𝑰𝑺�

IA =

La seccion de las columnas es uniforme; por lo tanto no existe irregualridad.

Ia = 1.00

Analisis de irregualridades en Planta:

1. Esquinas entrantes I= 0.90


La configuracion en platnta y en el sistema resistente de la estructura, tiene esquinas entrante
dimenciones en ambas direeciones, son mayores que el 20% de la correspondiente dimencion e

�_𝟏>𝟎.�∗�_� NOTA: Irregular para esquinas entrantes en X y en

Observamos que las dimensiones de la esquina entrante no supera el 20% de la


dimension total en planta, por lo tanto no existe irredularidad

Ip = 1.00
2. Discontinuidad de diafragma I= 0.85
Diafragma con discontinuidades bruptas o variaciones en rigidez, incluyendo areas abiertas
mayores a 50% dek area bruta de difragma.
PRIMERA CONDICION
(𝐴_1+𝐴_2)/𝐴_𝑇𝑂𝑇𝐴𝐿 >50%
𝐴_1+𝐴_2>0.5∗𝐴_𝑇𝑂𝑇𝐴𝐿

AT 129 m2
A1= 9.94 m2
A2= 4.52 m2

I= no hay irregulridad

SEGUNDO CONDICION

𝐿_�<0.25𝐿_𝑇
LT = 8.00 m 67%
LR = 5.35 m

I= no hay Irregularidad

La relacion es del 67% a lo establecido en la Norma (25%); por lo tanto no existe irregularidad:

IP= 1

DATO MUY IMPORTANTE:. ‴SI LA EDIFICACION NO HAY IRREGULARIDAD SE TOMA 1


‴ SI LA EDIFICACION TIENE IRREGULARIDAD Y MAS DE UNA SE TOMA EL MENOR VALOR VALE
f) Peso de la Edificación.
PT= 589.70 TN

CALCULO DE LA FUERZA SISMICA


Donde el valor de C/R no debera considerar
�=((𝒁∗𝑼∗𝑺∗𝑪)/𝑹)∗��

V= 74.17 TN

𝑪/𝑹≥ 0.125
COMPROBANDO RESULTADO EL VALOR SE CONSIDERA

DISTRIBUCION DE LA FUERZA SISMICA EN ALTURA

Determinacion de "ai": �_𝒊= 𝜶_𝒊∗�

Determino "K": En este caso T es menor que 0.5 segundos:


CASOS:
T< 0.5 Seg. a) Para T menor o igual a 0.5
0.37 0.5 Seg. Ok!!! b) Para T mayor que 0.5 segu

K= 1.00

PISO hi (m) Pi (Tn) k (hi)k Pi (hi)k


1° 4.60 178.68 1.00 4.60 821.94
2° 7.40 150.14 1.00 7.40 1111.04
3° 10.20 150.14 1.00 10.20 1531.43
4° 13.00 110.74 1.00 13.00 1439.57
å= 4903.99

Fuerza que soportara cada piso:

PISO Qi ACUMULADO ∑FI


4° Piso ® Q4 = F4 =
3° Piso ® Q3 = F4 + F3 =
2° Piso ® Q2 = F4 + F3 + F2 =
1° Piso ® Q1 = F4 + F3 + F2 + F1 =
ENTONCES V = F(1°PISO)
74.17 TN = 74.17 TN

21.77 TN

44.94 TN

61.74 TN

74.17 TN
DE BASAL

LISIS ESTATICO

con una probabilidad de 10% de ser

zonificación sismica

erficie sera Z*S, donde S es el tipo de suelo


mos que multiplicar por un factor
racion espectral de diseño, en funcion a las

seg: N E.030

S3 Tabla N| 3
1.20 E 0.30

ELOS INTERMEDIOS
diciones de sitio y se interpreta como el factor

Depende del periodo

te al Corte CT
35
escaleras 45
60

R = factor de reduccion de la fuerza


R0 = Coeficiente basico de reduccion
IA = Irregularidad en altura
IP = Irregularidad en planta

EN ALTURA
ELEVACION
mayor que 130% de la correspondiente

ELEVACION

como por un desplazamiento


a fuerza cortante

n Planta:
tiene esquinas entrantes, cuyas
espondiente dimencion en planta

nas entrantes en X y en Y.

VISTA EN PLANTA
uyendo areas abiertas

RIMERA CONDICION

𝐴_
1

𝐴_
2
R=R0∗ IA∗ IP = 8

EL MENOR VALOR VALE


C/R no debera considerarse menor que 𝑪/𝑹≥ 0.125

Para T menor o igual a 0.5 segundos: K=1,0


Para T mayor que 0.5 segundos: K= (0.75 + 0.5*T)≤2.0

ai V Fi
0.1676 74.173 12.43
0.2266 74.173 16.80
0.3123 74.173 23.16
0.2936 74.173 21.77
å= 74.17

FUERZA
21.77 TN
44.94 TN
61.74 TN
74.17 TN