No. 8555-9201-160
Edition 1010
The authors are always grateful for comments and suggestions for improving
the documentation. They can be addressed to:
Note: • This symbol is not a safety precaution but rather a reference to infor-
mation which help to better understand the separator or plant compo-
nents and the processes.
1 Timer overview 7
4 Program logic 25
1 Timer overview
Operating water valve V 3 The bowl sludge space is partial emptied by actu-
T00 Partial ejection
opens ating the operating water valve V 3. (Option) X X X
Operating water valve V 3 The bowl sludge space is emptied by actuating the
T04 Total ejection
opens operating water valve V 3. X X X
Closing water impul- Operating water valve V 3 Timer for safety water to keep the bowl closed
T06
se opens during separation. X X X
After timer is expired, product After timer is expired, the standard alarms like
T07 Alarm delay
feed valve V 1 closes. PAL1/PAH1, TAL/TAH, PAH2 ect. will be initiated. X X X
T09 Waiting after filling Timer to stabilize the system after filling process. --- X X
T11 Alarm Bridging Alarms not activated. Timer to stabilize the process conditions! X X X
T14 Closing water interval Time interval between two closing water pulses. X X X
Circulation valve
T15
close
Circulation valve V 5 closes. Timer in which the circulation valve is closed! X --- ---
Circulation valve Circulation valve V 5 opens. Timer in which the circulation valve is opened!
T16
open WMS Sensor is activated. WMS Sensor Signal is checked. X --- ---
Active in
Timer Designation Action Description
-0136- -0196- -91-
program.
Water impulse by Operating water valve V 3 Timer for closing the bowl after separator is on
T19
start opens operating speed. X X X
T20 Separation Product feed valve V 1 opens Timer for adjusting the separating time. X X X
In case of pressure drop (SMS Timer in which a system pressure drop is eva-
Min separation time PT 2) during T21 , triggering of luated as an alarm.
T21
with SMS alarm "Minimum separating X --- ---
time during SMS" Timer starts together with timer 20.
Active in
Timer Designation Action Description
-0136- -0196- -91-
Bowl is filled in intervals controlled by T37 with
Filling water valve V 2 opens filling water to check whether the sludge space is
T36 SMS pressure check in intervals until SMS sensor filled with sludge. If the sludge space is not full, X --- ---
PT 2 is activated. the SMS sensor PT 2 must respond to pressure. If
pressure is not increasing, an ejection is triggered.
Timer to set the interval between two filling water
Filling water valve V 2 closes.
T37 SMS Waiting
SMS sensor PT 2 is activated.
pulses for sludge space monitoring! See also X --- ---
SMS pressure check, above.
WMS sensor not activated.
SMS sensor PT 2 not acti- Timer to flush the sensing line after the first pro-
WMS Sensor flush-
T38
ing
vated. gram start so that it is clean and excessive filling --- X ---
Water discharge valve V 6 water is discharged!
opens.
Separator off after After delay T 39, the separa- Timer delay for separator motor stop. Function
T39
idle run tor motor is switched off. must be preselected in the program. X X X
Timer to operate the sludge pump until the sludge
T40 CU-Sludge pump On Sludge pump activated.
tank is completely emptied. X X X
T41 CU-Sludge pump Off Sludge pump not activated. Time interval between two sludge pump starts. X X X
T42 Free
T43 Free
Circulation valve V 5 closes. Timer in which the function of the SMS sensor PT
Water discharge valve V 6 2 is tested. If T44 is elapsed without SMS Sensor
T44 SMS-Sensor-Check
closes. PT 2 Signal, Alarm "SMS sensor failure during X X ---
SMS sensor PT 2 is activated. WMS-SMS check" is triggered.
T45 Free
T46 Free
When SMS Sensor PT 2 is Capacity and machine type-dependent timer
activated while T 47 is run- which determines the increse of water in the lube
ning, the water discharge oil during WMS mode. The pressure increase is
T47 Min.SMS Time
valve V 6 is opened for 3 evaluated as a function of T 47 over several --- X ---
seconds and Counter 5 successive cycles which are defined via counter 5
counts the PT 2 signal. "SMS time interval water content"
Timer to fill filling water into the bowl. This timer
runs before timer T61 and T62. Timer is required
T60 Start Impulse Filling water valve V 2 opens.
for the automatic calculation of timers 01 and 02. X X ---
Timer is protected.
2.1
Separator-Type
Text Display Remarks OSE OSE OSE OSE OSE OSE
Full Text
(P = Setpoint; A = actual value) 5 10 20 40 80 120
Counter
C1 Flushing:
C01 Flushing Flushing counter 5 5 5 5 5 5
P: 5
A: 0
C2 Partial Ejection:
C02 Partial Ejection Partial ejection counter 5 5 5 5 5 5
(Option) P: 5
A: 0
C3 SMS Filling:
C03 SMS-Filling SMS fillng counter 5 5 5 5 5 5
P: 3
A: 0
C4 Sensor Check:
C04 Sensor-Check Sensor check counter 10 10 10 10 10 10
(Option) P: 10
A: 0
C5 Water content
Default settings Counter - Time records
Sludgep.-time
Time Record for Max. in 24 h 30 min
TR2 TR2 Sludgep. time sludgepump time operation 30 30 30 40 50 60
in last TR3 (24h) hours. Act. in 24 h 0 min (Act. in = actuel 24h)
Last. in 24 h 0 min (Last in = previous 24h)
Active in:
No. Designation: Status: Description:
-0136- -0196- -91-
2.3
Control Unit E40
Alarme Display Text Remarks Separator-Type
Full Text:
Control Unit:
Temperature- OSE
Monitoring DO MDO LO HFO
Separation Temperature 20 °C 40 °C 95 °C 98 °C
TAH OIL FEED
Temp. > max
TAH OIL FEED Alarm for an increase of the
Separation-Stop 30 °C 50 °C 105 °C 105 °C
Temp. > max oil temperature.
Alarm#06 press
HELP
TAL OIL FEED
Temp. < min
TAL OIL FEED Alarm for a decrease of the
Separation-Stop 10 °C 30 °C 85 °C 90 °C
Temp. < min oil temperature.
Alarm#05 press
HELP
Settings Temperature – Ejection monitoring
Ejection-
OSE 5 OSE 10 OSE 20 OSE 40 OSE 80 OSE 120
Monitoring
EJECTION
MONITORING:
Alarm for monitoring the
Eject. current < Value depending on the con-
Ejection monitoring ejection after separation or
Offset ditions of the power supply 0,5 A 0,5 A 0,5 A 3A 5A 8A
Eject. current < Offset after SMS ejection.
Separation-Stop system and the clutch shoes!
Current is monitored.
Alarm#07 press
HELP
EJECTION
MONITORING:
Alarm for monitoring the
Ejection monitoring Eject. speed < Off- Value depending on the con-
ejection after separation or
Eject. speed < Offset set ditions of the power supply 100 U/min 100 U/min 100 U/min 100 U/min 100 U/min 100 U/min
after SMS ejection.
(Option) Separation-Stop system and the clutch shoes!
Speed is monitored.
Alarm#33 press
HELP
8555-9201-160 / 1010
Maintenance-Interval:
Set: 4000 h 0m 0s
Actual: 22 h 12 m 46 s
The factory setting for "Set" is a maintenance interval of 4000 hours as specified
in the separator instruction manual. Under "Actual", the operating hours of the
separator are counted.
When the pre-set number of operating hours is reached, a common alarm is ac-
tivated and a corresponding warning appears in the display. A common alarm
does not interrupt the separating program and must be acknowledged using the
ACK key.
Note:
Please take the maintenance interval setting from the instruction manual of the
separator used.
Maintenance-Interval WMS
Set: 168 h 0m 0s
Actual: 22 h 12 m 46 s
The factory setting for "Set" is a maintenance interval of 168 hours (1 week).
Under "Actual", the operating hours of the WMS-Sensor water signal is counted.
In the case the “Actual” counter came up to the preset operating hours, a main-
tenance message will be activated with a corresponding hint that the WMS-
Sensor Check must be done! The message does not interrupt the separation
process and must be acknowledged with the „ACK“button after the WMS Sen-
sor Check. The acknowledgement resets the the “Actual” value.
Under “Last water signal WMS” the operating hours of the WMS Sensor since
the last water indication are counted. Only a water signal resets the operating
hours for “Last water signal WMS”.
In the case the message „Maintenance WMS-Sensor“ occurs in the display, a manual check of the WMS-
Sensor function must be done. Please follow up the described steps!
Step
1 • Stop separation sequence by pushing touch key “Prog. OFF” on the control unit.
Step
A:
Position 1: closed
Position 2: open
In the case that the signal did not change, • Take note to the chapter „Maintenance schedule“
• Remove waterdetector (WMS-Sensor), of the instruction manual of the used separator.
clean it and check function.
8 Start of the separation process is possible by pushing the touch key „Prig. ON“ at the control unit.
4 Program logic
A A
Power supply
ON
Selftest
Control Unit
Start of
Sensor Check Sequence
Precondition:
Oil temperature > TSL setpoint
Oil temperature < TSH setpoint
LSHH not activated
Vibro II not activated
B
B
B
Start of
Separation sequence
Process
monitoring
activated
E
Ejection program
Waiting - Start (T03)
Displacement (T01)
Waiting after displacement (T08)
Total ejection (T04)
Waiting after first ejection (T12)
Total ejection (T04)
Speed recovery (T05)
C
C
Stop of separation sequence
Ejection program
Waiting - Start (T03)
Displacement (T01)
Waiting after displacement (T08)
Total ejection (T04)
Waiting after first ejection (T12)
Total ejection (T04)
Speed recovery (T05)
Separator
Ready for operation
A
D
D
Process
options
activated
Alarm
Separator OFF activated
after (T39)
A
E
E
Process
monitoring
activated
CU = Compact Unit
Alarm
PAL / PAH
TAL / TAH
LAHH
A
A
A
Power supply
ON
Selftest
Control Unit
Process
optionens
activated
D
Start of
Sensor Check Sequence
Precondition:
Oil temperature > TSL setpoint
Oil temperature < TSH setpoint
LSHH not activated
Vibro II not activated
B
B
B
Start of
Separation sequence
Process
monitoring
activated
E
Ejection program
Waiting - Start (T03)
Displacement (T01)
Waiting after displacement (T08)
Total ejection (T04)
Waiting after first ejection (T12)
Total ejection (T04)
Speed recovery (T05)
Separation program
Closing water impulse (T06)
Filling water (T02)
Waiting after filling (T09)
Separation (T20)
Sensor flushing (T38)
Bridging after ejection (T11)
C
C
Stop of separation sequence
Ejection program
Waiting - Start (T03)
Displacement (T01)
Waiting after displacement (T08)
Total ejection (T04)
Waiting after first ejection (T12)
Total ejection (T04)
Speed recovery (T05)
Separator
Ready for operation
A
D
D
Process
options
activated
Alarm
Separator OFF activated
after (T39)
A
E
E
Process
monitoring
activated
CU = Compact Unit
Alarm
PAL / PAH
TAL / TAH
LAHH
A
A
A
Power supply
ON
Selftest
Control Unit
Process
optionens
activated
D
Start of
Separation Sequence
Precondition:
Oil temperature > TSL setpoint
Oil temperature < TSH setpoint
LSHH not activated
Vibro II not activated
B
B
B
Start of
Separation sequence
Process
monitoring
activated
E
Ejection program
Waiting - Start (T03)
Displacement (T01)
Waiting after displacement (T08)
Total ejection (T04)
Waiting after first ejection (T12)
Total ejection (T04)
Speed recovery (T05)
Separation program
Closing water impulse (T06)
Filling water (T02)
Waiting after filling (T09)
Separation (T20)
Bridging after ejection (T11)
C
C
Stop of Separation sequence
Ejection program
Waiting - Start (T03)
Displacement (T01)
Waiting after displacement (T08)
Total ejection (T04)
Waiting after first ejection (T12)
Total ejection (T04)
Speed recovery (T05)
Separator
Ready for operation
A
D
D
Process
options
activated
Alarm
Separator OFF activated
after (T39)
A
E
E
Process
monitoring
activated
Alarm
PAL / PAH CU = Compact Unit
TAL / TAH
LAHH
A
KNOW-HOW PROTECTION
No GEA-specific device
No warranty by operation!
Alarm#00 Please check:
Contact Westfalia
customer service !
MOTOR PROTECTION
Alarm#01 Please check:
Motor protection function / Brake
Thermistor relay / Operating water
Valve V2 / No. of clutch shoes
Drive blocked / Feed capacity
Press ESC then ACK
EJECTION MONITORING
Alarm#07 Please check:
Function of bowl / Hydraulics with V3
Connector valve V3 / Current offset setting/
Water quantity / TIMER 28
Current converter / Pre-strainer
Press ESC then ACK
VIBRATION STAGE 1
Alarm#11 Please check:
TIMER 25 / Solids holding space
Polyamide sealing ring / Sensor
Fixing / Limit value 1 / Correct
bowl parts / Foundation fixing
Press ESC then ACK
or
Step 2 Alarm acknowledgement
VIBRATION STAGE 2
Alarm #12 Please check:
Limit value 2 / Solids holding space
Polyamide sealing ring / Sensor
Fixing / Correct bowl parts
Foundation fixing
Press ESC then ACK
BOWL MONITORING
Alarm#18 Please check:
TIMER T06 / Current offset
Frequency power supply
Water pressure for hydraulic
Function V3
Press ESC then ACK
Note:
TR2 = Time record of sludge pump operation, TR2 will be deleted when
TR3 has expired.
TR3 = Time counter factory setting 24 h
Note:
TR1 = Time record of WMS water sensor during HFO operation, TR1 will be
deleted when TR3 has expired.
TR3 = Time counter factory setting 24 h
MAINTENANCE required
Alarm#27 Please check:
Operating hours have reached
4000; 8000; 12000; 16000 hours
or multiple / Carry out maintenance
according manual
Press ESC then ACK
EJECTION MONITORING
Alarm#33 Please check:
Function of bowl / Hydraulics with V3
Connector valve V3 / Speed offset eject.
Water quantity / TIMER 28 / Speed pick- up
defective / Pre-strainer
Press ESC then ACK
BOWL MONITORING
Alarm#34 Please check:
TIMER T06 / Water pressure
for hydraulic / Speed offset
bowl monitoring / Function V3
Speed pick- up defective
Press ESC then ACK
SEPARATOR- START
Alarm#35 Please check:
TIMER T10 / Brake unfastened / Clutch
shoes oily / Drive belt oily / Speed setting
of operation speed / Speed pick-up defective
Press ESC then ACK
BELT MONITORING
Alarm#36 Please check:
Drive belt / Motor defect electrically
Clutch shoes worn or oily
Speed pick- up defective
Press ESC then ACK
PT 1 MONITORING
Alarm#39 Please check:
Switching function PT 1
PT 1 dirty / Setpoint PAL 1
Bowl hydraulics / Ejection
monitoring / Discharge pressure
Press ESC then ACK
NO WATER SEAL
Alarm#40 Please check:
Clean oil discharge pressure
Function V2 / Filling water quantity
Valve V2 and filter / Water pressure
TIMER T06 / Setting TAL / Setting PT 2
Press ESC then ACK
EMERGENY STOP
Alarm#46 Please check:
Emergency Button
Press ESC then ACK
WATER DISCHARGE
Alarm#48 Please check:
Clean oil valve V7 / Water cont. in Oil
Filling water quantity / oil
Temperature / Regulating ring
Polyamide ring / Press. sensor PT2
Press ESC then ACK
Alarm#02
Free
Alarm#03
Free
Alarm#04
TAL PRODUCT FEED Separation Not possible Set setting higher than the • Separation
Temp. < min current temperature stop
Separation - Stop • V1 in circula-
Alarm#05 tion
• Common alarm
TAH PRODUCT FEED Separation Not possible Set setting lower than the • Separation
Temp. > max current temperature stop
Separation - Stop • V1 in circula-
Alarm#06 press ENTER tion
• Common alarm
EJECTION MONITORING Ejection Close manual ball valve Disconnect cable head of V3 • Separation
Current< Offset which is in front of V3 or increase offset Ejection stop
Separation – Stop shortly before and during current during discharge • V1 in circula-
ALARM#07 discharge cycle T04. cycle T04. tion
• Common alarm
LAHH SLUDGE TANK Control Immerse or dampen Disconnect cable head of • Separation
Sludge tank - full Active sensor LSHH. LSHH Sensor stop
Separation - Stop • V1 in circula-
Alarm#08 tion
• Common alarm
FEED PUMP FAULT Control Not possible Trigger motor protection • Separation
Motor protection Active switch stop
Separation - Stop • V1 in circula-
Alarm#09 press ENTER tion
• Common alarm
SLUDGE PUMP FAULT Control Not possible Trigger motor protection • Separation
Program - stop Active switch stop
• V1 in circula-
Alarm#10 tion
• Common alarm
Alarm#14
WMS SYSTEM FAULT Separation Open valve V2 to add Bridge WMS Sensor and set • Separation
Too much water water into bowl until pressure sensor PT2 switch- stop
Separation - Stop Timer 22 is elapsed. ing point to 0 or bridge. • V1 in circula-
Alarm#15 tion
• Common alarm
• Ejection
Free
Alarm#16
Free
Alarm#17
BOWL MONITORING Separation Not possible. Extend T06 during separa- • Common alarm
Current too high tion and shorten T14 to •
during TIMER 06 300sec.! Wait until T14 is
Alarm#18 elapsed and Alarm appears.
SEPARATOR MOTOR OFF Circulation Not possible. Set TIMER 39 to 10 seconds • Common alarm
Sep. in circulation and push program stop • Motor off
T 39 expired M. off button.
Alarm#19
Free
Alarm#20
Free
Alarm#21
EXCESSIVE RUNNING Control Set TR2 to 1 minute and Set TR2 to 1 minute • Common alarm
TIME OF SLUDGE PUMP Active immerse or dampen LSH Trigger testfunction with
In TR3 hours Sensor to start sludge magnet at testpoint of LSH
Alarm#22 pump until Alarm ap- sensor until Alarm appears.
pears.
WMS ACTIVATED Separation Set T22 to 300sec. and Set T22 to 300sec., TR1 to 1 • Common alarm
TOO OFTEN TR1 to 1 minute and minute and bridge WMS
open valve V2 to add sensor until Alarm appears.
Alarm#23 water into bowl until
Alarm appears.
Free •
Alarm#24
Free •
Alarm#25
Free •
Alarm#26
Maintenance Separation Not possible. Set value to actual value • Message in the
required see manual plus 1hour and wait 1hour. display
Alarm#27
WARNING Separation Set T17 to 1s and Set T17 to 1s and • Message in the
WATER CONTENT set counter 5 to 1 and set counter 5 to 1 and display
T47 to 60sec.than open bridge pressure sensor • V6 opens
Alarm#28 valve V2 for 10sec. to PSL2 or set optional PT2 to
add water into bowl until 0 and 1 in short intervals
warning appears. during T47 for minimum 2
times, so that warning ap-
pears.
Free
Alarm#29
Free
Alarm#30
Free
Alarm#31
Free
Alarm#32
EJECTION MONITORING Ejection Close manual ball valve Disconnect cable head of V3 • Separation
Eject. speed < Offset which is in front of V3 or increase offset Ejection stop
Separation – Stop shortly before and during speed during discharge • V1 in circula-
Alarm#33 discharge cycle T04. cycle T04. tion
• Common alarm
BOWL MONITORING Separation Not possible. Extend T06 during separa- • Common alarm
Speed drop too high tion and shorten T14 to •
during TIMER 06 300sec.! Wait until T14 is
Alarm#34 elapsed and Alarm appears.
SEPARATOR-START Separator Set Timer 10 to 10 sec. Set setting for min. speed • Motor off
monitoring Motor Start and press motor start higher than the normal • Message in the
during T10 button. operating speed. display
Alarm#35 • Common alarm
BELT MONITORING Separator Not possible. Disconnect speed pick-up • Motor off
Drive belt broken Motor Start sensor and press motor • Message in the
during start up start button. display
Alarm#36 • Common alarm
MAX.- SPEED Separator Not possible. Set setting for Max. Speed • Motor off
MONITORING Motor Start lower than normal operating • Message in the
during operation and Separa- speed, during start up or display
Alarm#37 tion during operation. • Common alarm
•
MIN.- SPEED Separator Not possible. Set setting for Min. Speed • Motor off
MONITORING Motor Start higher than normal operat- • Message in the
during operation and Separa- ing speed, display
Alarm#38 tion during start up or during • Common alarm
operation. •
PT 1 MONITORING Ejection Not possible. Set pressure sensor PT1 • Separation
clean oil discharge switching point to 0 while stop
Separation - Stop ejection sequence is run- • V1 in circula-
Alarm#39 ning. tion
• Common alarm
•
NO WATER SEAL Separation Reduce T34 and T35 to 5 Set pressure sensor PT2 to • Separation
during TIMER 35 sec. and close hand 0 and disconnect cable of stop
Separation - Stop valve before V2 during WMS sensor. • V1 in circula-
Alarm#40 T02. tion
• Common alarm
• Ejection
MIN. SEPARATING TIME Separation Not possible. Disconnect cable head on • Separation
< 10 Min pressure sensor PT2 during stop
Separation - Stop T21. • V1 in circula-
Alarm#41 tion
• Common alarm
• Ejection
SMS SENSOR FAULT Sensor Close hand valve at V2 Disconnect cable head on • Common alarm
during SMS Check Check while test is running. pressure sensor PT2 while • Ejection
during TIMER 44 test is running.
Alarm#42
PT2 SENSOR ACTIVE Circulation Open valve V2 until pres- Set pressure sensor PT2 to • Message in the
in Idle run sure increase on pres- 0 during idle run. display
sure sensor PT2 during • Common alarm
Alarm#43 idle run. • Ejection
PAL1 CLEAN OIL DISCHARGE Separation Open clean oil discharge Disconnect cable head on • Separation
Pressure < setting valve V7 pressure sensor PT1 stop
Separation - Stop • V1 in circula-
Alarm#44 tion
• Common alarm
• Ejection
PAH 1 CLEAN OIL DISCHARGE Separation Close clean oil discharge Set pressure sensor PT1 • Separation
Pressure > setting valve V7 switching point to a lower stop
Separation - Stop value than the current value. • V1 in circula-
Alarm#45 tion
• Common alarm
• Ejection
EMERGENCY STOP Control Not possible. Push emergeny button. • All electric
Button pushed Active components
are shut down
ALARM#46 like Motors,
Control Units
ect!
FREE
ALARM#47
WATER DISCHARGE: Separation Close clean oil discharge Set pressure sensor PT1 • Separation
Overflow valve V7. Set optional PAH1 switching point to 0 while stop
Separation - Stop (PT1) in clean oil discharge separation sequence is
to 10 bar.
• V1 in circula-
Alarm#48 running. tion
• Common alarm
• Ejection
MAINTENANCE required Circulation Not possible. Set value to actual value • Message in the
WMS Sensor plus 1minute and wait display
1minute. Add extra water to
Alarm#49 get WMS Signal if neces-
sary.
Free
Alarm#50
For a simulation, the function must be activated and must be valid for the product.
ATTENTION:
After the simulation, all changes must be reset to the initial conditions!!!!
8.1 Bowl-Volumes
Separator type
3
Volumes in dm
Bowl volume 1,00 1,00 2,00 2,00 3,60 3,60 10,00 10,00 23,00 23,00 40,00 40,00
Sludgespace volume 0,50 0,50 0,90 0,90 1,60 1,60 4,00 4,00 10,00 10,00 14,60 14,60
Fillingwater volume 0,20 0,50 0,30 0,90 0,40 1,60 0,50 4,00 1,00 10,00 3,00 14,60
Displacementwater
volume
0,50 0,50 1,10 1,10 2,00 2,00 6,00 6,00 13,00 13,00 25,40 25,40
Separator type
OSE 5 / OSE 10 / OSE 20 OSE 40 OSE 80 OSE 120
Speed in U/min
Max. Speed 12 200 8 400 7 000 6 100
Min. Speed 11 500 7 800 6 300 5 400
Rated Speed 12 000 8 200 6 800 5 900
Speed -Offset
100 100 100 100
Ejection monitoring
Speed -Offset
100 100 100 100
Bowl monitoring