Ejemplo Cal Culo de Contra Pres I On
150.6 Pipe
+ 243.8 Silencer (see note 1)
394.4 Total
762.0 Maximum Allowable Backpressure
1) CAUTION: Silencer Backpressure is based upon a Clarke USA provided Silencer. Actual Silencer Backpressure will vary
depending upon the actual Silencer used (manufacturer, size, type and model). If the total Backpressure from the pipe,
Silencer and orifice plate (if required) is close to the engine Maximum Allowed Backpressure, it is highly recommended you
obtain the actual Backpressure (for the engine exhaust flow given above) on the Silencer being used and then confirm that the
total Backpressure is still under the Maximum Allowed Backpressure.
2) Schedule 40 pipe used in calculations