UNIT 2 - TRANSFORMERS

C.VENKATESH KUMAR/AP/SJCE
UNIT II TRANSFORMERS

Constructional details – Principle of operation – emf


equation – Transformation ratio – Transformer on
no load – Parameters referred to HV/LV windings –
Equivalent circuit – Transformer on load –
Regulation - Testing – Load test, open circuit and
short circuit tests.

C.VENKATESH KUMAR/AP/SJCE
Transformer
An A.C. device used to change high voltage low
current A.C. into low voltage high current A.C. and
vice-versa without changing the frequency
In brief,
1. Transfers electric power from one circuit to another
2. It does so without a change of frequency
3. It accomplishes this by electromagnetic induction
4. Where the two electric circuits are in mutual
inductive influence of each other.

C.VENKATESH KUMAR/AP/SJCE
Principle of operation

It is based on
principle of MUTUAL
INDUCTION.
According to which
an e.m.f. is induced
in a coil when
current in the
neighbouring coil
changes.
C.VENKATESH KUMAR/AP/SJCE
C.VENKATESH KUMAR/AP/SJCE
Constructional detail : Shell type

• Windings are wrapped around the center leg of a


laminated core.
C.VENKATESH KUMAR/AP/SJCE
Core type

• Windings are wrapped around two sides of a laminated square


core.
C.VENKATESH KUMAR/AP/SJCE
Sectional view of transformers

Note:
High voltage conductors are smaller cross section conductors
than the low voltage coils
C.VENKATESH KUMAR/AP/SJCE
Construction of transformer from
stampings

C.VENKATESH KUMAR/AP/SJCE
Core type

Fig1: Coil and laminations of Fig2: Various types of cores


C.VENKATESH KUMAR/AP/SJCE
core type transformer
Shell type
• The HV and LV
windings are split
into no. of sections
• Where HV winding
lies between two LV
windings
• In sandwich coils
leakage can be
controlled
Fig: Sandwich windings

C.VENKATESH KUMAR/AP/SJCE
Cut view of transformer

C.VENKATESH KUMAR/AP/SJCE
Transformer with conservator and
breather

C.VENKATESH KUMAR/AP/SJCE
Working of a transformer
1. When current in the primary coil
changes being alternating in
nature, a changing magnetic field
is produced
2. This changing magnetic field gets
associated with the secondary
through the soft iron core
3. Hence magnetic flux linked with
the secondary coil changes.
4. Which induces e.m.f. in the
secondary.

C.VENKATESH KUMAR/AP/SJCE
C.VENKATESH KUMAR/AP/SJCE
Ideal Transformers
• Zero leakage flux:
-Fluxes produced by the primary and secondary currents
are confined within the core
• The windings have no resistance:
- Induced voltages equal applied voltages
• The core has infinite permeability
- Reluctance of the core is zero
- Negligible current is required to establish magnetic
flux
• Loss-less magnetic core
- No hysteresis or eddy currents

C.VENKATESH KUMAR/AP/SJCE
Ideal transformer

V1 – supply voltage ; I1- noload input current ;


V2- output voltgae; I2- output current
Im- magnetising current;
E1-self induced emf ; E2- mutually induced emf
C.VENKATESH KUMAR/AP/SJCE
EMF equation of a transformer

C.VENKATESH KUMAR/AP/SJCE
C.VENKATESH KUMAR/AP/SJCE
C.VENKATESH KUMAR/AP/SJCE
Phasor diagram: Transformer on No-
load

C.VENKATESH KUMAR/AP/SJCE
Transformer on load assuming no
voltage drop in the winding

Fig shows the Phasor diagram of a transformer


on load by assuming
1. No voltage drop in the winding
2. Equal no. of primary and secondary turns
C.VENKATESH KUMAR/AP/SJCE
Transformer on load

Fig. a: Ideal transformer on load


Fig. b: Main flux and leakage
flux in a transformer
C.VENKATESH KUMAR/AP/SJCE
Phasor diagram of transformer with
UPF load

C.VENKATESH KUMAR/AP/SJCE
Phasor diagram of transformer with
lagging p.f load

C.VENKATESH KUMAR/AP/SJCE
Phasor diagram of transformer with
leading p.f load

C.VENKATESH KUMAR/AP/SJCE
Equivalent circuit of a transformer

No load equivalent circuit:

C.VENKATESH KUMAR/AP/SJCE
Equivalent circuit parameters referred to
primary and secondary sides respectively

C.VENKATESH KUMAR/AP/SJCE
Contd.,
• The effect of circuit parameters shouldn’t be changed while
transferring the parameters from one side to another side
• It can be proved that a resistance of R2 in sec. is equivalent
to R2/k2 will be denoted as R2’(ie. Equivalent sec. resistance
w.r.t primary) which would have caused the same loss as R2
in secondary,
I 12 R2'  I 22 R2
2
'  I2 
R  
2
 R2
 I1 
R2
 2
k

C.VENKATESH KUMAR/AP/SJCE
Transferring secondary parameters to
primary side

C.VENKATESH KUMAR/AP/SJCE
Equivalent circuit referred to
secondary side
•Transferring primary side parameters to secondary side

Similarly exciting circuit parameters are also transferred to


secondary as Ro’ and Xo’

C.VENKATESH KUMAR/AP/SJCE
equivalent circuit w.r.t primary

where

C.VENKATESH KUMAR/AP/SJCE
Approximate equivalent circuit
• Since the noload current is 1% of the full load
current, the nolad circuit can be neglected

C.VENKATESH KUMAR/AP/SJCE
Transformer Tests
•The performance of a transformer can be calculated on the basis of
equivalent circuit
•The four main parameters of equivalent circuit are:
- R01 as referred to primary (or secondary R02)
- the equivalent leakage reactance X01 as referred to primary
(or secondary X02)
- Magnetising susceptance B0 ( or reactance X0)
- core loss conductance G0 (or resistance R0)
•The above constants can be easily determined by two tests
- Oper circuit test (O.C test / No load test)
- Short circuit test (S.C test/Impedance test)
•These tests are economical and convenient
- these tests furnish the result without actually loading the
transformer

C.VENKATESH KUMAR/AP/SJCE
Open-circuit Test
In Open Circuit Test the transformer’s secondary winding is open-circuited, and
its primary winding is connected to a full-rated line voltage.

V0
Core loss  Woc  V0 I 0 cos0 R0 
Iw
Woc
cos 0  V0
V0 I 0 X0 
I
Ic or I w  I 0 cos0
I
G0  w
• Usually conducted on I mor I   I 0 sin 0  I 02-I w2 V0
H.V side I0 I
I0  V0 Y0 ;  Yo  B0 
• To find V0 V0
(i) No load loss or core Woc  V02G 0 ;  Exciting conductance G 0 
Woc
loss V02
(ii) No load current Io & Exciting susceptance B0  Y02  G02
which is helpful in
finding Go(or Ro ) and Bo
(or Xo ) C.VENKATESH KUMAR/AP/SJCE
Short-circuit Test
In Short Circuit Test the secondary terminals are short circuited, and the
primary terminals are connected to a fairly low-voltage source
The input voltage is adjusted until the current in the short circuited windings
is equal to its rated value. The input voltage, current and power is
measured.

• Usually conducted on L.V side


• To find
(i) Full load copper loss – to pre determine the
efficiency
(ii) Z01 or Z02; X01 or X02; R01 or R02 - to predetermine the
voltage regulation
C.VENKATESH KUMAR/AP/SJCE
Contd…

Fullloadcu loss  Wsc  I sc2 R01


Wsc
R01 
I sc2
Vsc
Z01 
I sc
X01  Z012  R012

C.VENKATESH KUMAR/AP/SJCE
Transformer Voltage Regulation
and Efficiency
The output voltage of a transformer varies with the load even if the input
voltage remains constant. This is because a real transformer has series
impedance within it. Full load Voltage Regulation is a quantity that compares
the output voltage at no load with the output voltage at full load, defined by
this equation:
Vs
At noload k 
Vp
V S , nl V S , fl V P / k   V S , fl
Regulation up   100 % Regulation up  x 100 %
V S , fl V S , fl
V V S , fl V P / k   V S , fl
Regulation down 
S , nl
 100 % Regulation down  x 100 %
V S , nl
V S , nl

Ideal transformer, VR = 0%.

C.VENKATESH KUMAR/AP/SJCE
no - load voltage  full - load voltage
Voltage regulation 
no - load voltage
Vs N s
recall 
Vp N p
N 
Secondary voltage on no-load V2  V1  2 
 N1 
V2 is a secondary terminal voltage on full load

Substitute we have  N2 
V1    V2
 N1 
Voltage regulation 
 N2 
V1  
 N1 
C.VENKATESH KUMAR/AP/SJCE
Transformer Phasor Diagram
To determine the voltage regulation of a transformer, it is necessary
understand the voltage drops within it.

C.VENKATESH KUMAR/AP/SJCE
 Aamir Hasan Khan
Transformer Phasor Diagram
Ignoring the excitation of the branch (since the current flow through the
branch is considered to be small), more consideration is given to the series
impedances (Req +jXeq).
Voltage Regulation depends on magnitude of the series impedance and the
phase angle of the current flowing through the transformer.
Phasor diagrams will determine the effects of these factors on the voltage
regulation. A phasor diagram consist of current and voltage vectors.

Assume that the reference phasor is the secondary voltage, VS. Therefore the
reference phasor will have 0 degrees in terms of angle.
Based upon the equivalent circuit, apply Kirchoff Voltage Law,
VP
 V S  R eq I S  jX eq I S
k

C.VENKATESH KUMAR/AP/SJCE
 Aamir Hasan Khan
Transformer Phasor Diagram
For lagging loads, VP / a > VS so the voltage regulation with lagging loads is > 0.

When the power factor is unity, VS is lower than VP so VR > 0.

C.VENKATESH KUMAR/AP/SJCE
 Aamir Hasan Khan
Transformer Phasor Diagram

With a leading power factor, VS is higher than the referred VP so VR < 0

C.VENKATESH KUMAR/AP/SJCE
 Aamir Hasan Khan
Transformer Phasor Diagram
For lagging loads, the vertical components of Req and Xeq will partially
cancel each other. Due to that, the angle of VP/a will be very small, hence
we can assume that VP/k is horizontal. Therefore the approximation will
be as follows:

C.VENKATESH KUMAR/AP/SJCE
Formula: voltage regulation
In terms of secondary values
0 V2  V 2 I 2 R 02 cos  2  I 2 X 02 sin  2
% regulation  
0 V2 0 V2

where ' ' for lagging and '-' for leading


In terms of primary va lues
V1  V 2' I 1 R 01 cos 1  I 1 X 01 sin 1
% regulation  
V1 V1
where ' ' for lagging and '-' for leading

C.VENKATESH KUMAR/AP/SJCE
Transformer Efficiency
Transformer efficiency is defined as (applies to motors, generators and
transformers):
P out
   100 %
P in
Pout
  100 %
Pout  Ploss
Types of losses incurred in a transformer:
Copper I2R losses
Hysteresis losses
Eddy current losses
Therefore, for a transformer, efficiency may be calculated using the following:
VS I S cos 
 x100%
PCu  Pcore  VS I S cos 

C.VENKATESH KUMAR/AP/SJCE
Losses in a transformer
Core or Iron loss:

Copper loss:

C.VENKATESH KUMAR/AP/SJCE
Condition for maximum efficiency

C.VENKATESH KUMAR/AP/SJCE
Contd.,

The load at which the two losses are equal =

C.VENKATESH KUMAR/AP/SJCE
All day efficiency
out put in watts
ordinary commercial efficiency 
input in watts

output in kWh
 all day  ( for 24 hours)
Input in kWh

•All day efficiency is always less than the commercial efficiency

C.VENKATESH KUMAR/AP/SJCE