FM200 OPERATING INFORMATION 

 
MAJOR OPERATION BUTTON AND CONTROL 

Control  Button  Description  Control  Button  Description 

Change from manual Mode to Automatic   Access Level 2  Enable Key ‐  
Mode Vice Versa.   strictly for Maintenance team 
Default – Automatic Mode  only 
Manual mode Extinguishant will not   
 
  Released by automatic Detection 

Silence Alarm /fault warning buzzer sound.   Plus Enable Key Reset Alarm 
Control Panel after:  
 
1. System Fault corrected  
2. Extinguishant Released 
   

On Standby mode activates fire condition  Caution 
with sounder /flasher on. 
Manually release The 
On Alarm Mode activate Silence mode  Extinguishant  after time 
  with sounder/flasher off    displayed countdown elapsed 

 
KEY  EVENT AND SYSTEM OPERATION 

A. FAULT Condition:  Fault Alarm/ Beeping Sounder  

In the event of system fault, general fault indicator lights with specific fault flash – AMBER.  Buzzer/ Beeping sound 
on continuously 

S/N  Operator/ Occupant  Do THIS 



Occupant          Call Maintenance team/ Fire Team 
   
1. Turn Mode Key to  Manual 
2  Maintenance team 
2. Press Silence alarm /Warning Fault to silence Buzzer sound. 
3. Correct the system Fault  
4. Press  Reset to rest the system  
5. Return Mode key to Automatic 
    1. Turn Mode Key to Manual 
3  Fire  Team  2. Press Silence alarm /Warning Fault to silence Buzzer sound. 
3. Notify Maintenance team to correct  
4. Return Mode key to Automatic 
 
B. FALSE  Alarm/ FIRE Condition : 
An event normally accompanied by Fire Indicator Lights with specific zones Fire indicator lights – RED.  
Bell, Sounder and Flasher on continuously. 

S/N  Operator/ Occupant  Do THIS 



Occupant   1.  Call Fire Team on ‐‐‐‐‐‐‐‐‐‐ 
2.  Evacuate  the room and close Doors 
   
1st Stage ALARM. – Call from Auto Dialer or Occupant to Fire Station 
2  Fire Team  
1. Turn Mode Key to  Manual 
2. Evaluate the Protected Area for cause of Alarm – Real/False 
Real Fire: Automatic Extinguish 
1.  Turns Mode key back to Automatic. 
2. System Extingushant activate after the Second Stage Alarm and Timer 
countdown – 30secs  
3. Allow 10mins  hold time before vent  protect area  
Real Fire : Manual Extinguish 
1. Pull down the yellow flap and press button to release Extinguishant 
2. Allow 10mins hold time before vent protects area. 
False Alarm:  
1. Mode control on manual  
2. Evaluate  the cause of False Alarm 
3. Press silence/sound alarm to cancel all sounder/ flasher/Bell 
4. Notify Maintenance Team to correct the cause of False alarm and rest the 
Panel 
 

EMERGENCY NUMBER FM200 MAINTENANCE TEAM 

       
       
       
       
       
       
       
       
       
 