Professional Documents
Culture Documents
Heat Recovery From Blow Down
Heat Recovery From Blow Down
Note: 1 kJ / s = 1 kW
Example 3.13.1
To put the energy flowrate into context, in North West Europe the average domestic central heating system
is rated at approximately 13 kW, so the energy flowrate blown down in Example 3.13.1 is sufficient to heat
19 houses.
For clarity the above calculation utilises steam tables where water at 0°C is the datum.
In reality, make-up water to replace the blowdown will be supplied at a temperature greater than this, so the
energy blow down will be slightly less. For example, if the make-up water were at 10°C the energy blown
down would be 228 kW.
Flash steam
The blowdown water released from the boiler is water at the saturation temperature appropriate to the boiler
pressure. In the case of the boiler in Example 3.13.1 - 10 bar g, this temperature is 184°C. Clearly, water
cannot exist at 184°C under atmospheric conditions, because there is an excess of enthalpy or energy in the
blowdown water.
Assuming the blowdown water is released to a flash steam system operating at 0.5 bar g, steam tables may
be used to quantify this energy excess:
Specific enthalpy of water at 10 bar g = 782 kJ / kg (hf at 10 bar g)
The quantity of flash steam is readily determined by calculation or can be read from tables or charts.
Example 3.13.2
The specific enthalpy of evaporation at 0.5 bar g (hfg) from steam tables is 2 226 kJ / kg.
Therefore 14.1% of the water blown down from the boiler will change to steam as its pressure drops from 10
to 0.5 bar g across the blowdown valve.
1. Vent this flash steam to atmosphere via the blowdown vessel with the associated waste of energy
and potentially good quality water from the condensed steam.
2. Utilise the energy in the flash steam, and recover water by condensing the flash steam. It is useful
to quantify the energy flowrate in the flash steam. This can be done using steam tables.
Example 3.13.3
Rate of flash steam generation = 1 111 kg / h x 14.1%
Rate of flash steam generation = 157 kg / h (0.043 5 kg / s)
Total energy per kg of steam = 2 694 kJ / kg (hg at 0.5 bar g)
Energy flowrate in flash steam = 0.043 5 kg / s x 2 694 kJ / kg
Energy flowrate in flash steam = 117 kW
Compare this to the 241 kW rate of energy blown down from the boiler.
It may be possible to use this flash steam: in this example it represents almost 49% of the energy flowrate in
the blowdown, and 14.1% of the water blown down.
Using values from steam tables for the above calculations assumes that feedwater will be supplied at a
temperature of 0°C. For greater accuracy, the actual change in feedwater temperature should be used.
The design of the flash vessel is important not only from a steam / water separation point of view, but
structurally it should be designed and built to a recognised pressure vessel standard, such as PD 5500.
This is not only good engineering practice, the boiler inspector will also insist upon this if the plant is to be
insured.
The most obvious place for the flash steam to be used is in the boiler feedtank, which is usually nearby.
The water temperature in the feedtank is important. If it is too low, chemicals will be required to de-
oxygenate the water; if it is too high the feedpump may cavitate. Clearly, if heat recovery is likely to result in
an excessive high feedtank temperature, it is not practical to discharge flash steam into the tank. Other
solutions are possible, such as feedwater heating on the pressure side of the feedpump, or heating the
combustion air.
Figure 3.13.2 shows a simple installation, which makes recovery of the 117 kW of energy flow, and 157 kg /
h of boiler quality water, extremely cost effective.
Equipment required
• Flash vessel - Manufacturers will have sizing charts for vessels. Note: the steam velocity in the
top section of the vessel should not exceed 3 m / s.
• Steam trap to drain the vessel - A float trap is ideal for this application as it releases the
residual blowdown water as soon as it reaches the trap.
The flash vessel is working at low pressure so there is virtually no energy to lift the residual
blowdown after the steam trap, so this must drain by gravity through the trap and discharge
pipework.
Note: because of the low pressure, the trap will be fairly large. This has the additional advantage
that it is unlikely to be blocked by the solids in the residual blowdown water.
Sometimes strainers are preferred before the steam trap; for this application the strainer cap should
be fitted with a blowdown valve to simplify maintenance, and the strainer screen should not be too
fine.
•
2. Steam distributor.
3. Sparge pipe.
Design considerations
A problem with the arrangement shown in Figure 3.13.3 is that the simultaneous flow of incoming cold
make-up water and residual blowdown from the flash vessel may not be guaranteed.
One preferred arrangement is shown in, where a cold water break tank is used as a heat sink. A thermostat
is used to control a small circulating pump so that when the residual blowdown is at a high enough
temperature, water is pumped through the heat exchanger, raising the average tank temperature and saving
energy.
addition, 14% (by mass) of the water has been recovered, making a further contribution to savings.