Professional Documents
Culture Documents
E N Series Installation Manual
E N Series Installation Manual
E N Series Installation Manual
LIMITATIONS
This document is copyright and is provided solely for the use of the purchaser. It is
not to be copied in any way, nor its contents divulged to any third party, nor to be
used as the basis of a tender or specification without the express written permission
of the manufacturer.
DISCLAIMER
The advisory procedures and information contained within this Manual have been
compiled as a guide to the safe and effective operation of products supplied by
Nu-Lec Industries Pty Ltd.
It has been prepared in conjunction with references from sub-assembly suppliers
and the collective experience of the manufacturer.
In-service conditions for use of the products may vary between customers and
end-users. Consequently, this Manual is offered as a guide only. It should be used in
conjunction with the customers own safety procedures, maintenance program,
engineering judgement and training qualifications.
No responsibility, either direct or consequential, for injury or equipment failure can be
accepted by Nu-Lec Industries Pty Ltd resulting from the use of this Manual.
COPYRIGHT
© 2008 by Nu-Lec Industries Pty Ltd.
All rights reserved. No part of the contents of this document may be reproduced or
transmitted in any form or by any means without the written permission of the
manufacturer.
REVISION RECORD
Level Date Comment
R00 26 September, 2005 First Release
R01 23 January, 2006 Progressive updates
R02 22 November, 2006 ADVC Version 42
R03 2 September, 2008 ADVC Version 44
i
N-Series Recloser Contents
with ADVC Controller
CONTENTS
Notices ................................................................................................................................ i
ii
ii
Contents
(cont)
iii
N-Series Recloser
with ADVC Controller Contents
(cont)
iv
Contents
(cont)
v
N-Series Recloser
with ADVC Controller
vi
1 Scope of this Manual
GENERAL
This manual describes the installation and maintenance of the N-Series Automatic
Circuit Recloser and the ADVC Controller.
Whilst every care has been taken in the preparation of this manual, no responsibility
is taken for loss or damage incurred by the purchaser or user due to any error or
omission in the document.
Inevitably, not all details of equipment are provided nor are instructions for every
variation or contingency during installation, operation or maintenance.
For additional information on specific problems or requirements, please contact the
manufacturer or your distributor.
SYMBOLS
The following symbols are used throughout this manual (and others). The are
designed to give a quick way of indicating information that is designed for specific
areas of interest.
The grey box symbol indicates that the adjacent information does
not apply to all products.
1-1
N-Series Recloser
with ADVC Controller
SOFTWARE IDENTIFICATION
The software loaded into the ADVC Controller is identified by its version number
which has the form:
AXX-XX.XX.
This precisely identifies the software loaded into the microprocessor on the
controller.
In order to obtain effective technical support from the manufacturer or your distributor
it is vital to record the software version and to quote this when making your inquiry.
Without this information it is impossible for our customer service department to
identify the software and provide correct support.
The software version is shown on the Operator Control Interface “Switchgear
Wear/General Details” page, in the field “App.Ver”:
See 7 Operator Interface (page 7-1) for instructions on how to use the Operator
Interface.
ABBREVIATIONS
ACR Automatic Circuit Recloser
ADVC Advanced Controller
BDU Basic Display Unit
CAPE Control and protection enclosure
CT Current transformer
CVT Capacitive Voltage Transducer
HMI Human Machine Interface
LCD Liquid Crystal Display
LED Light Emitting Diodes (Lamps)
MCB Miniature Circuit Breaker
OCP Operator Control Panel (also known as Operator Interface)
O.I. Operator Interface
PCOM Protection and communications module
PSU Power supply unit
PSSM Power Supply & Switchgear Module
PTCC Pole top control cubicle
QAK Quick Action Keys (flexVUE only)
SCEM Switch cable entry module
SWGM Switchgear module
WSOS Windows Switchgear Operating System
1-2
2 Introduction
The N-Series remotely controlled and monitored automatic circuit recloser consists
of an N-Series automatic circuit recloser (ACR) combined with an Advanced
Controller (ADVC).
The ACR field-fitting kit includes a polymeric bushing boot and predetermined length
of 120 mm2,185 mm2, or 240 mm2 aluminium, insulated water-tight cable tail rated at
250A, 400A, 630A for each of the six bushings.
the ACR is connected to the Advanced Controller (ADVC) via a control cable
through the base of the ADVC
the ACR can be connected into an insulated or bare conductor system.
The ADVC Controller reads and displays the information which is stored in the ACR
and provides protection and communication properties for the ACR. The ADVC
Controller
consists of:
an electronic switchgear controller that monitors the ACR, and provides
communication and protection functions. (CAPE),
an operator interface mounted on the CAPE,
a power supply which also supplies power for customer equipment,
an accessories and customer equipment compartment,
is powered by an auxiliary voltage supply of 110, 220, or 240 volts AC,
is connected to the ACR via a detachable control cable.
The customer compartment provides ample room for equipment. Standard
communications cables can be used for connection to the communications ports on
the ADVC and power is readily accessible from the programmable power terminal
block. (Please refer to “4 Communications and Accessories Installation (page
4-1)”.)
2-1
N-Series Recloser
with ADVC Controller
COMPACT
ULTRA
2-2
Introduction (cont)
TERMINOLOGY
The N-Series recloser bushings are identified as U1, V1, and W1 on one side,
usually the source side, and U2, V2, and W2 on the other, usually the load side.
(Source and load side are configurable) See Figure 3 : ACR Bushings (page 3)
2-3
N-Series Recloser
with ADVC Controller
2-4
3 Installation
CONTENTS OF CRATE
Each crate includes:
ACR,
Pole mounting bracket with clamps if ordered. If a substation mounting bracket
was ordered it will be attached to the outside of the crate,
Six bushing boots with clamping rings attached,
Six tubes of electrical silicone grease to fill the bushing boots (seven tubes are
supplied with 38kV reclosers),
One clamping ring spanner to fit boots to the bushings,
caulking gun,
The appropriate mounting kit,
ADVC Cubicle (which will normally contain two batteries unless arrangements
have been made to ship batteries separately),
Control cable,
Six cable tails (where supplied by the manufacturer) pre-terminated with either a
threaded lug to screw into the bushings directly or with a flat lug for bolting to a
Ensure that the ADVC is stored indoors until
palm already fitted onto the bushings.
installation on site. If storage outdoors is
unavoidable, ensure that the ADVC is kept On receipt, the contents should be checked for shipping damage and the
in an upright position. manufacturer informed immediately if any is found.
UNPACKING PROCEDURE
Tools required:
Wrecking bar to remove nails,
Four D shackles, two slings and crane with a safe working load of 300kg to lift
the ACR,
Screw Driver or Battery Drill with 8mm socket,
16mm Spanner or Socket.
Procedure:
1: Remove the front (marked ADVC) and back panels of the crate.
2: Remove the top of the crate. Inside the top of the crate you will find a timber
brace which is fitted around and between the recloser bushings and attached to
the side walls of the crate. The brace supports the bushing boots, control cable,
accessories kit, and mounting bracket if supplied.
3: Cut each strapping holding the bushing boots, the accessories kit, and the
control cable in position. Remove the bushing boots and control cable and put
them in a clean, dry place.
Take great care not to hit the recloser 4: Unscrew the four wood screws which attach the mounting bracket (if present) to
bushings with the bracket or to drop the the top timber brace and lift the mounting bracket out of the crate.
bracket, which weighs nearly 30kg (66lb),
back into the crate 5: Unscrew the four wood screws which attach the top timber brace to the side
walls of the crate and remove the brace.
6: Remove the cable tails which are bent over the top of the ADVC.
7: Fit D-shackles to the lifting points on the circuit breaker and lift it out of the crate
and on to the ground using the crane.
The control cubicle weighs 8: Remove the two bolts securing the ADVC to its top and bottom timber braces
approximately 40 kg (88lb). and lift the unit from the crate.
3-1
N-Series Recloser
with ADVC Controller
3-2
Installation (cont)
Connecting the batteries with reverse 7: Attend to the battery using the care instructions given in Battery Care (page
polarity will cause damage to the 10-5).
electronic systems.
It may be desirable at this time to fit the cable tails and surge arresters to the ACR.
See Figure 5 : Cable Tail Installation (page 3-7).
SITE INSTALLATION
If you are replacing a pole-top control cubicle (PTCC) or an original ADVC Controller
(Ver 43 or earlier) with an ADVC Controller (Ver 44 or above), the following should be
considered:
The ADVC Controllers have different mounting points to the PTCC1.
The connection to the auxiliary supply enters the cubicle at a different point.
The earth stud is in a different position.
Accessory cables may need extending.
Unlike the PTCC which required an auxiliary power supply rating of 50VA, the
ADVC Controller requires 100VA.
If the auxiliary supply is provided by an external VT connected through the ACR,
there are limitations to the supply ratings of equipment powered by the radio
power supply. For an external VT, the maximum continuous current drawn from
the radio supply should be limited to 0.5 amps.
The ADVC Controller (Ver 44 or above) door is held open by a door stay
mechanism which prevent door swinging or blowing shut. To disengage the door
stay follow the directions on the operator sheet located on the inside of the door.
Tools Required
Torque wrench and metric socket set, normal engineers tools.
24mm Open ended drive to fit the torque wrench (commonly known as a "Claw
Foot"). This is only required with 630A cable tails which screw directly into the
bushings and are tightened by a 24mm lock-nut.
Standard 300gm cartridge applicator, (Caulking Gun).
Bushing boot clamping spanner, (supplied by the manufacturer).
Tools to prepare pole as required.
Crane or other lift for ACR and ADVC, four D shackles and slings. A 1m spreader
bar is also useful, if the surge arresters are to be fitted onto the ACR tank, to
keep the slings away from the surge arresters when lifting.
1 An accessory mounting bracket can be purchased to allow the use of the same mounting holes as were
used with the manufacturer’s PTCC. (Part No. 99800125)
3-3
N-Series Recloser
with ADVC Controller
Mounting parts for the ADVC. Either 20mm steel strapping or 10mm galvanised
or stainless steel bolts, nuts, etc.
Fixing hardware for the control cable. This is a 27mm (1 1/16") diameter
sheathed conduit and can be fixed to the pole with ties, straps, P-clips or
saddles.
Earth wire and lugs for the earthing scheme and parts for LV mains auxiliary
power connection. See Figure 6 : (page 3-8), Figure 8 : (page 3-10) and Figure 9
: (page 3-11).
20mm sealing cable entry glands to suit auxiliary supply mains cables, 16mm
sealing cable entry glands to suit antenna or communications cable as required.
Antenna, antenna feeder cable, and surge arrester as required if a radio is fitted
(unless supplied by the manufacturer).
Aluminium jointing paste (250A and 400A cable tails only).
Heat shrink or insulating tape (800A cable tails only).
Site Procedure
To erect and test the ACR and ADVC, carry out the following steps. Mounting details
are given in Figure 7 : (page 3-9).
1: Transport to site and carry out testing prior to erection as required.
2: Connect cable tails and surge arresters before raising the ACR. See “Cable Tail
Connections (page 3-6)” and “Surge Arrester Mounting and Terminating (page
3-7)”
3: Ensure that the pole is of sufficient strength to support the ACR. A structural
engineer may be needed to calculate the stresses involved.
4: Securely mount the ACR mounting bracket on the power pole.
5: Lift the ACR into position and lower it so that it sits on the mounting bracket. See
Figure 7 : (page 3-9).
6: Bolt the ACR to the mounting bracket with the four 12mm nuts and bolts
provided. Tighten to 50 Nm.
7: Complete the high voltage connections as shown in Figure 10 : (page 3-12) or as
appropriate for the site installation.
8: Unbolt the SCEM compartment cover plate from the bottom of the ACR. Remove
the blanking plate and fit the control cable into place. Connect the control cable
to plug P1 1 on the SCEM located inside the ACR.
See “Control Cable Connection (page 3-2)” for the correct way to connect/
disconnect the control cable.
The control cable retaining plate at the ACR 9: Fit the retaining plate. 2
end is differentiated by having one corner
removed.
2
10: Run the control cable from the ACR down to the ADVC.
11: If the ADVC is to be bolted to the pole, drill the top hole and fit the bolt. If it is to be
strapped, feed the straps through the slots on the upper and lower mounting
brackets.
3-4
Installation (cont)
Note that the ADVC mounts have key holes as 12: Lift the ADVC into position and bolt or strap it to the power pole.
shown here, so that you can lift the ADVC on 13: Attach the control cable to the power pole maintaining maximum available
to the mounting bolt and slide it into position. separation from the main earth bond (at 200mm for wood and concrete poles
and 150mm for steel poles). Ensure that there is enough cable available at each
end to permit connection to the equipment.
14: Run the earth connections as described in “Earthing (Grounding) (page 3-8)”.
15: Connect the control cable from the ACR through the base of the ADVC 1
1
It is vital that the earthing scheme is
carried out as described.
16: For LV mains supply run auxiliary wiring as shown in Figure 8 : (page 3-10).
Make the connection inside the ADVC as shown in Figure 6 : (page 3-8).
17: For LV supply from a dedicated transformer supplied by the utility, connect as
shown in Figure 9 : (page 3-11).
18: For Integrated supply from an external transformer, connect as shown in Figure
9 : (page 3-11). (See also “Auxiliary Power from Integrated Transformer (page
3-8)”)
19: Power down the ADVC by switching off all MCB’s. Note that this should be done
whenever connecting or disconnecting the control cable from the ADVC.
Fitting the batteries with reverse polarity 20: Fit the batteries if they are not already in place.
will cause damage to the electronic
systems. 21: If communications equipment is to be installed go to “4 Communications and
Accessories Installation (page 4-1)”.
22: Otherwise go to “5 Testing Your Installation (page 5-1)”.
3-5
N-Series Recloser
with ADVC Controller
3-6
Installation (cont)
3-7
N-Series Recloser
with ADVC Controller
Earthing (Grounding)
Figure 8 : (page 3-10) shows the earthing (grounding) common to all installations.
This arrangement earths the ACR frame and the surge arresters directly to earth
through a main earth bond consisting of a copper conductor of 70 sq. mm. Any
surges will flow down this path.
Do not earth surge arresters by a The control cubicle is connected to this main earth bond by a tee-off. The control
different path, doing this may cause cubicle electronics are internally protected from potential differences which may
damage to the control electronics or occur between the ACR frame and control cubicle frame whilst surge currents are
ACR. Also, any antenna should be flowing down the main earth bond. No other connections to earth from the control
bonded to the ACR or the main earth bond. cubicle are allowed since surge currents will also flow in those paths. Follow this
arrangement on both conducting and insulating power poles.
Keep the main earth bond physically separated from the control cable, as they run
LINE NEUTRAL
down the power pole, by the maximum spacing available and at least 150mm.
AUX Supply This connection scheme bonds the LV and HV earths and so protects the primary
Connection insulation of the auxiliary supply transformer in the control cubicle when surge
LV Auxiliary Supply Cable currents are flowing. Fit additional LV surge arresters to all the other LV phases (if
they exist), to balance the supply for other users connected to the LV system.
If local conditions or wiring rules prohibit bonding the HV and LV systems in this way,
providing the auxiliary supply to the control cubicle from the LV mains system is not
possible. Instead, use one of the alternative arrangements detailed below.
3-8
Installation (cont)
3-9
Figure 7 ACR Mounting and Dimensions
N-Series Recloser
with ADVC Controller
3-10
Installation (cont)
3-11
Figure 9 Utility Auxiliary Transformer
N-Series Recloser
with ADVC Controller
HV termination
Figure 10
3-12
4 Communications and
Accessories Installation
Comms cable/
Radio Antenna
Entry
4-1
N-Series Recloser
with ADVC Controller
4-2
Communications and Accessories Installation
(cont)
Radio/Modem Power
The battery-backed power supply for a radio/modem is provided on the terminal
block as described above1. See Figure 12 : (page 4-2) for the correct radio
connection point.
The radio/modem power supply voltage is set by the user in the following menu page
SYSTEM STATUS - RADIO - S: Radio Supply 12 Volts
ENGINEER MENU - CONFIGURATION MENU
- RADIO SETTINGS - Radio Supply Voltage
This is a password protected parameter.
If the auxiliary power fails, battery power can be conserved by automatically shutting
down the radio/modem power supply. The shutdown takes place after the radio
holdup time, set in:
System Status - RADIO - S: Radio Hold 60 min.
ENGINEER MENU - CONFIGURATION MENU
- RADIO SETTINGS - Radio Hold Time
has elapsed. If the Radio Hold time is set to zero then the radio supply will not
shutdown, except under special circumstances or until the unit powers down. The
radio/modem power supply is restored when the auxiliary supply returns to normal.
The radio/modem power supply can be turned on or off by the operator for radio
maintenance without passwords in:
System Status RADIO - S: Radio Supply ON
ENGINEER MENU - CONFIGURATION MENU
- RADIO SETTINGS - Radio Supply ON/OFF
If the radio supply has shutdown it will be indicated on these pages.
4-3
N-Series Recloser
with ADVC Controller
IOEX2 INSTALLATION
The Input Output Expander (IOEX2) module is a die-cast, sealed enclosure that
provides optically isolated inputs and voltage free outputs to allow connection to
external devices.
The IOEX2 module is only available with the ADVC ULTRA cubicle, including the
optional upper customer tray.
IOEX2 modules, purchased at time of initial ordering, come already installed in the
cubicle, located on the optional customer tray, and powered and earthed via the
terminal block located accessory mounting rail on the side customer tray.
BLACK
BLUE
WHITE
BROWN
LOW
EL
/Y
N
EE
GR
Figure 14 IOEX2 Supply and Earthing
4-4
Communications and Accessories Installation
(cont)
COMMUNICATION PORTS
The ADVC Controller has numerous communications ports available to the user:
Not all ports are available for use at the same time. The ports can be enabled/
disabled via WSOS.
Permanently available ports are:
RS232 Port D
10 base T Ethernet
Any 3 of the 5 following ports are available:
RS 232 Port A (enabled by default)
RS232 Port B (enabled by default)
RS 232 Port C (enabled by default)
RS485 (disabled by default)
V23 FSK (disabled by default)
The ports typically have three uses:
WSOS communications
SCADA communications
IOEX communications
RS232
Four RS232 ports (A to D) are provided to connect to conventional modems that
provide the correct signalling for the communications network used, e.g. optical fibre
modem, or telephone dial up modem, or RS232 radio modem. All four ports have
standard 9 pin D male connectors and have the following pin connections:
RS232 Port
Pin No Direction Use
A B C D
1 To ADVC Data Carrier Detect (DCD) Yes Yes
2 To ADVC Rx Data (RxD) Yes Yes Yes Yes
3 From ADVC Tx Data (TxD) Yes Yes Yes Yes
4 From ADVC Data Terminal ready (DTR) Yes Yes
5 0V (ground/earth) Yes Yes Yes Yes
6 Not connected
7 From ADVC Request to Send (RTS) Yes Yes
8 To ADVC Clear to Send (CTS) Yes Yes
9 Reserved Yes
Table 1. RS232 Pin Connections
Use of serial ports to connect directly to other All RS-232 ports are not isolated from one another or from the controller electronics.
devices outside the controller can cause They therefore can only be connected to devices inside the controller that are
damage and void warranty. If connections to powered by the controller radio supply, including modems, optical isolators, and
other devices are required then isolation radios.
interfaces MUST be used.
4-5
N-Series Recloser
with ADVC Controller
RS485
An RS485 port has been provided to enable higher speed multi-drop connections
that often occur within substations. The RS-485 port is a female RJ45 connector.
V23 FSK
An in-built FSK modem provides half-duplex V23 signalling at 1200 bits per second.
This interface is primarily designed for use with voice frequency radio systems and
provides additional signals for this purpose.
The Push to Talk (PTT) signal is used to key up a radio transmitter. PTT is
implemented using a Field Effect Transistor (FET) with an on resistance of 3.3 ohm.
Levels in excess of ±13V should not be When PTT is asserted the transistor is turned on and connects the PTT signal to 0V.
applied. The FET is rated for a maximum of
A busy signal can be provided by the radio to indicate receive channel busy. High
+32V and negative voltages are not
level is +2.0V to +3.3V, and low level is 0V to +0.5V. The busy signal should be
permitted.
driven by an open collector output or current limited to 10 mA.
Transmit and receive are unbalanced signals relative to
If multiple ACRs are in use in a substation application they can be connected to a
0 volts and are not isolated. If a DC level is imposed by
single radio using the 600ohm line isolator accessory available from the
the radio on the transmit line then this should be less
manufacturer.
than 2.5 VDC.
4-6
Communications and Accessories Installation
(cont)
Ethernet
If the controller is connected to a LAN or The controller has a 10 base T Ethernet port. The port is a RJ45 female connector.
WAN then it is strongly recommended that:
1. Firewalls be used to limit user access to Pin Direction Use
the controller 1 From ADVC Tx Data (Tx +)
2. Ethernet switches be used to limit the volume of 2 From ADVC Tx Data (Tx -)
Ethernet data reaching the controller’s 10Base-T port. 3 To ADVC Rx Data (Rx +)
(Use of Ethernet hubs is not recommended.)
4 Not connected
5 Not connected
6 To ADVC Rx Data (Rx -)
7 Not connected
8 Not connected
Table 4. Ethernet Pin Connections
SCADA Protocols
SCADA communications are available on the controller and supported protocols can
be assigned to any of the RS232 ports as well as the V23 port.
All currently supported protocols can be viewed in
SYSTEM STATUS - OPTIONS 4.
ENGINEER MENU - TELEMETRY - CONFIGURE COMMS
Protocols must be available before they will appear in the communications
menu.
- - - - - - - - - - OPTION 4 - - - - - - - - - - - S
DNP Available RDI Available
Trace Available
e.g.
Once you make a SCADA protocol available, the communication parameters can be
configured. Refer to the Operator Manual and protocol technical information for more
detail.
4-7
N-Series Recloser
with ADVC Controller
4-8
5 Testing Your Installation
Check that the installation and external The following sections give details of how the ACR and ADVC, installed as described
connections have been carried out as in “3 Installation (page 3-1)”, should be prepared for operation.
described in this manual and in accordance Check that no visible damage has occurred during the installation.
with local regulations.
Carry out any visual and electrical tests, such as insulation and contact resistance,
Ensure that earthing has been carried out as considered necessary to prove that the installation is sound.
described in “Earthing (Grounding) (page
3-8)”. POWERING UP THE ADVC
Figure 15. ADVC Controller PSU. Located at the bottom of the Cubicle
or
4: Turn on the VT supply to cubicle circuit breaker if the auxiliary supply is being
provided by an integrated transformer (single pole MCB above , if fitted).
5: Powering up the ADVC with the ACR connected will cause the ADVC to read
data from the ACR.
The flexVUE O.I. will create an ALERT with the same message.
6: If the configuration file containing the settings to be used in operation has not
previously been loaded, it should be loaded now using WSOS, or the settings
should be entered via the OCP.
The ACR and ADVC are now ready for operation. Prior to energising the ACR, you
should perform the following checks to confirm that the equipment is fully operational
and properly configured.
5-1
N-Series Recloser
with ADVC Controller
For this and all subsequent tests you will need BATTERY
to check settings on display group pages (See
Display Groups (page 7-3).) You may also 1: Check the Battery status which can be found on the following menu page
have to check the Event Log (See 8 Event
Log (page 8-1)) System Status - SWITCHGEAR STATUS-S
- - - - - - - SWITCHGEAR STATUS - - - - - - - - S
e.g. Work Tag OFF SF6 Normal 37kPag
Aux Supply Normal Battery Normal 27.5V
Switch Connected Switch Data Valid
1. It is possible for the Switch status to be showing "Connected" even though the control cable core is faulty,
causing the switch Data to show "Invalid".
2. A break-out cable to facilitate this measurement is available as an accessory.
5-2
Testing Your Installation
(cont)
AUXILIARY SUPPLY
1: Check Auxiliary Supply Status which can be found on the following menu page
System Status - SWITCHGEAR STATUS-S
WORK TAG
1: Check that LOCAL CONTROL is ON. This setting can be found in the following:
System Status - Operator Settings 1-S.
Press ( ) or (
and then press (ENTER
)to change the setting to Applied
) or (SELECT ) to activate the setting.
The message: "WORK TAG APPLIED" will flash at the top of the
display.
4: The flexVUE creates the "WORK TAG APPLIED" message as an
ALERT. This Alert and all others are viewable in the ALERTS MENU, which
is on the same level as OPERATOR MENU and ENGINEER MENU
5: Go to the EVENT LOG (see 8 Event Log (page 8-1) for details on how to do this)
and check that the bottom line of the display (the most recent event) contains the
Work Tag Applied event.
6: Return to WORK TAG STATUS and change the setting back to OFF.
5-3
N-Series Recloser
with ADVC Controller
- - - - TERMINAL DESIGNATION/ROTATION - - - S
A Phase = Bushings U1 + U2 Phasing ABC
B Phase = Bushings V1 + V2
C Phase = Bushings W1 + W2
3: Press the ENTER key when you have the required combination. The controller
then orientates the currents and voltages to match the selection.
4: In the Phasing field, select the phase rotation - either ABC or ACB.
5: Go to the EVENT LOG (see 8 Event Log (page 8-1) for details on how to do this)
and check that the bottom line of the display (the most recent event) contains the
Phasing order event.
6: After the phasing has been set, you should record the details on the label on the
rear of the control cubicle door (above the operator panel) to indicate the
relationship between the bushings and phases.
5-4
Testing Your Installation
(cont)
5-5
N-Series Recloser
with ADVC Controller
ENABLE/DISABLE SWITCHES
For each of the CLOSE and TRIP keys in turn, test ENABLE and DISABLE by:
1: Disable either mechanism (e.g. CLOSE) using Disabled Switches located
underneath the O.I.
2: Go to the EVENT LOG (see 8 Event Log (page 8-1) for details on how to do this)
and check that the bottom line of the display (the most recent event) contains the
Close Coil Isolate event. (For the same test of the TRIP mechanism the Event
Log should display Trip Coil Isolate.)
3: With both mechanisms disabled, check that pressing each of the CLOSE and
TRIP keys is ineffective.
4: Enable both CLOSE and TRIP mechanisms.
MECHANICAL TRIP
1: Use a hook stick to manually trip the ACR via the manual trip lever.
2: Go to the EVENT LOG (see 8 Event Log (page 8-1) for details on how to do this)
and check that the bottom line of the display (the most recent event) contains the
Mechanical Trip event.
5-6
Testing Your Installation
(cont)
The correct power flow setting can be confirmed by energising the ACR while it is
open.
2: With the recloser energized but still open, Check the Source Side Voltages at:
System Measurement - SOURCE SIDE VOLTAGES-M.
PHASE/LINE SRC-LD
6950 V A-E < 2000 V
- - - - - - - LIVE/DEAD INDICATION - - - - - - S
A1 Live A2 Dead
B1 Live B2 Dead
C1 Live C2 Dead
5: If Steps 3 and 4 indicate an incorrect power flow setting, return to Step 1, change
the setting and repeat Steps 2-4.
5-7
N-Series Recloser
with ADVC Controller
ON LOAD CHECKS
Once the ACR is closed and taking load, the following on-load checks can be carried
out. To confirm correct operation, check the current against a known reading.
1: Check system currents on :
System Measurement - CURRENT
- - - - - - - - - - - CURRENT - - - - - - - - - - M
A Phase 123 Amp Earth 8 Amp
B Phase 123 Amp Ipps
C Phase 123 Amp Inps
e.g.
OPERATOR MENU - MEASUREMENTS
- CURRENT
(requires you to scroll through values)
Use these pages to confirm that system measurements and power flow signs are as
expected.
3: Check the source and load side voltages at:
System Measurement - SOURCE VOLTAGE LOAD
SOURCE - - - - - - VOLTAGE - - - - - - - LOAD M
11000 Volt A-P 11000 Volt
11000 Volt B-P 11000 Volt
11000 Volt C-P 11000 Volt
e.g.
PHASE/LINE SRC-LD
e.g.
6950 V A-E < 2000 V
(requires you to scroll through values)
5-8
6 Control Electronics Operation
The ADVC is designed for outdoor pole mounted operation. Both the ULTRA and
COMPACT cubicles are vented and insulated to minimise internal temperature variation
and maximise battery life. Cubicle dimensions are given in Figure 30 : (page B-2).
CONTROLLER
The controller consists of three modules. (See Figure 16 (page 6-3) and Figure 17
(page 6-3)):
Power supply unit (PSU)
Control and protection enclosure (CAPE) with Operator Interface (O.I.)
Customer Compartment
The ADVC block diagram is given in Figure 18 (page 6-4).
PSU Module
The PSU module supplies power to the CAPE, and controls the supply from external
auxiliary sources
The power supply module encloses all 115/230 Vac mains connections. Internally it
provides terminals for auxiliary power supply connection. Cable-tie points are
provided to secure the auxiliary supply cables. Circuit breakers are used to protect
and switch the battery and auxiliary power supplies on/off. A durable cover is used to
enclose all the terminations.
CAPE Module
The main module of control electronics is the Control and Protection Enclosure
(CAPE). The CAPE digitises the current transformer (CT) signals and capacitive
voltage transformer (CVT) signals from the recloser. These are used to provide a
variety of data for the operator.
The CAPE module contains the PCOM board, PSSM board, trip/close capacitors
and O.I. assembled into a housing that provides protection from the environment,
sealing and EMC shielding.
The CAPE performs the following functions:
Holding & operating the O.I.
Operating the external communications interface to allow monitoring and control
from a remote computer or operator over a communications link.
6-1
N-Series Recloser
with ADVC Controller
CUSTOMER COMPARTMENT
The compartment is fitted with a panel tray that facilitates the mounting of your
equipment e.g. a radio or modem including any special interfaces. See Figure 18 :
(page 6-4). The compartment has a terminal block for the radio supply and power for
accessories such as an IOEX2. An accessory heater can also be fitted which is
controlled by the PSU.
WSOS5 Interface
To use WSOS5 to upload or download data, connect your PC serial port to Port A
located above the operator interface. Use an RS232, DB9 female to DB9 female,
Crossover (also known as Null Modem).
6-2
CUSTOMER COMPARTMENT(S)
The COMPACT cubicle compartment is fitted with an accessory tray that facilitates the
mounting of your equipment e.g. a radio or modem. Figure 16 (page 6-3)
The ULTRA cubicle has one standard, and one optional accessory compartment to
allow for more equipment. and Figure 17 (page 6-3). The standard compartment
has a terminal block for the radio power supply and power for accessories such as
an IOEX2.
flexVUE Operator Interface
erface (O.I.)
(O.I.
I.))
Customer Compartment
om
mpar
p tment
Control and
C
Protection
P
Enclsure
Enc (CAPE)
(Including O.I.)
B
Batteries
Control
C and
Protection
Protect
Enclosure
Encclosure (CAPE)
(Including
(I
Including O.I.)
B
Batteries
6-3
N-Series Recloser
with ADVC Controller
6-4
7 Operator Interface
The ADVC can be remote controlled via modems or other communications devices,
controlled using a laptop computer connected directly via serial or USB connections
to the ADVC, or by the Operator Interface. (O.I.). The O.I. offers full functionality to
change settings, trip and close the switchgear or display current values or past
events related to the switchgears function.
The Operator Interface (O.I.) is mounted on the CAPE inside the ADVC Controller
and accessed by opening the cubicle door. The O.I. consists of a liquid crystal
display (LCD) and key pad and light emitting diodes (LEDs). Together these
hardware features provide a user interface to monitor and control the ACR.
setVUE
A traditional O.I. that provides a 4 × 40 character LCD and simple navigation with
four user configurable quick keys.
flexVUE
This O.I. provides the user with 20 indicator lights and 12 Quick Action Keys (Each
with configurable LEDs) that are totally configurable by the user through WSOS5.
This provides the user with instant feedback about the switchgear, and minimises the
need to navigate through layers of menu structure.
Both the setVUE and flexVUE O.I.’s, and their operation are described in detail on
the following pages.
If the door proximity switch is installed, the O.I. turns ON automatically when the door
is opened and OFF and when it is closed. The O.I. also turns OFF automatically if no
keys are pressed for 10 minutes. Pressing the PANEL ON key will reactivate the
panel.
This manual contains examples of display interface screens. In general, the
language chosen for these examples is International English. In some cases, screen
text will differ if the configured language is English (USA).
7-1
N-Series Recloser setVUE Panel
with ADVC Controller Operator Interfaces (cont)
setVUE PANEL
1 2 3 4 5
# Item Description
1 Display Back-lit LCD, 4 line with 40 characters per line.
2 LEFT scroll key Select the previous screen in a display group or, if a
setting is selected, decrease its value
3 SELECT Key Press to SELECT a data field/setting so that it can be
changed.
4 RIGHT scroll key Select the next screen in a display group or, if a setting
is selected, increase its value.
5 PANEL ON key Turns the O.I. on. The O.I. will turn on when the cubicle
door is opened.
6 Trip key Generates a Trip request to the CAPE when the panel
6 7 8 9 10 11 12 13 14 15 16
is active. A LED is embedded in the key to indicate its
Figure 19 setVUE O.I. operation. Another LED is used to indicate whether this
keys operation is DISABLED.
17 18 7 Close key Generates a Close request to the CAPE when the panel
is active. A LED is embedded in the key to indicate its
operation. Another LED is used to indicate whether this
keys operation is DISABLED.
8 Custom Menu key Gives access to the custom menu which was
configured using WSOS5. The custom menu is
configured to provide a regular, updated data display by
allowing a cycle of up to 12 screens.
9 ALT The alternative function key gives access to an
Figure 20 Trip/Close Enable Switches alternative Event Log display.
Located below the O.I.
10 System OK The 3 System OK LEDs flash while the controller is
operating normally.
11 MENU scroll key Displays the first page of the next group. Pressing the
MENU key after changing a setting causes the setting
change to take effect.
12 Configurable Default linkage is to LOCAL/REMOTE.
Quick Key
13 Configurable Default linkage is to AUTO ON/OFF.
Quick Key
14 ENTER key Press this key in order to commit a setting change that
has been made. (Unlike the adjacent Quick Keys, the
ENTER key is not configurable.)
15 Configurable Default linkage is to PROT. GROUP
Quick Key
16 Configurable Default linkage is to EARTH PROT.
Quick Key
17 Enable/ Disable Disables ALL Trip Operations. When the switch is in
TRIP switch the Disable position the trip coil in the recloser is
electrically disconnected from the control electronics.
Thus the switch provides a physical isolation point for
the control circuitry. The recloser cannot be opened,
and an audible alarm in the panel will sound and the
DISABLED LED in the TRIP key will flash. The TRIP
key operates normally when the switch is in the Enable
position.
This switch also prevents a close operation, so that the
switchgear cannot be carrying load without the ability to trip.
18 Enable/ Disable Disables ALL Close Operations. When the switch is
CLOSE switch in the Disable position the close coil in the recloser is
electrically disconnected from the control electronics.
Thus the switch provides a physical isolation point for
the control circuitry. The recloser cannot be closed and
an audible alarm in the panel will sound and the
DISABLED LED in the CLOSE key will flash. The
CLOSE key operates normally when the switch is in the
Enable position.
7-2
setVUE Panel
Operator Interface (cont)
DISPLAY GROUPS
The setVUE displays are organized into logical groups called Display Groups. Within
each group is a menu of pages and some pages have sub-pages.
The next three lines are the data on display. Most displays have six data fields.
A field may contain either:
a setting, which can be changed - ON/OFF is the most common; or
a status.
7-3
N-Series Recloser
with ADVC Controller
CHANGING SETTINGS
Three types of settings can be changed:
Operator settings
Password protected settings
Protection settings
Operator Settings
Find the display page containing the setting to be changed:
1: Press the MENU key to display the group you require.
2: Communications Group (only) is divided into subgroups for different protocols.
Press SELECT to display the subgroup you require.
3: Press to display the page you require.
4: Press SELECT to highlight the setting. A highlighted setting “blinks”.
Alternatively, if a QUICK KEY is linked to the setting, you can use it to go directly
to the relevant display page where you will find the highlighted setting.
5: Once you have selected the setting to be changed, use
setting.
or to change its
6: Press ENTER to activate the new setting.
7-4
setVUE Panel
Operator Interface (cont)
Protection Settings
Protection settings are password protected. To change a protection setting, follow
the steps detailed in the Operator Settings section above but, in addition, enter the
password when prompted. When you have completed the setting change by
pressing ENTER, the following message will flash at the top of the screen:
QUICK KEYS
The operator settings that you will frequently change can each be linked to a QUICK
KEY. You use a QUICK KEY for instant display and selection of the linked setting
which, otherwise, you would have to find by navigation.
You can link operator settings to individual Quick Keys using the Operator Interface
or WSOS5.
A QUICK Key can be set to Blank, if it is not required.
Otherwise, any one of the settings tabled below can be linked to one of the four
Quick Keys.
How to configure the Quick keys is described in the ADVC Controller Operations
manual.
7-5
N-Series Recloser flexVUE Panel
with ADVC Controller Operator Interfaces (cont)
flexVUE PANEL
1 2 3 4 5 6
# Item Description
1 Display Back-Lit LCD. 2 × 20 Character
For example:
LOCKOUT A SOURCE LIVE
A - PHASE O/C B SOURCE LIVE
B - PHASE O/C C SOURCE LIVE
C - PHASE O/C MECH LOCK
GROUND FAULT CONTROL OK
SENSITIVE G/F AC POWER
BATTERY PWR
ALARM
10 LAMP DATA Key LAMP DATA is a future feature that will provide the
operator with additional data specific to each status
lamp.
The feature is currently under development.
11 LAMP RESET Key Resets the Status Lamps. Lamps requiring further
attention from the operator remain lit.
Note that some of the status lamps such as “controller
power” and “terminal live” are continuously updated and
therefore not affected by the reset command.
12 EVENT LOG Key Displays the Switchgear and Controller Event Log on
the LCD display.
Older events can be viewed by pressing the UP arrow
key.
7-6
flexVUE Panel (cont)
13 Quick Action Key To use the Quick Action Keys, an operator must first
Unlock press the Unlock key. The LED above the unlock key
will remain lit while the quick action keys are active.
To deactivate the Quick Action Keys an operator can
press the unlock key again. The LED will turn off.
Alternatively the Quick Action Keys will be deactivated
automatically a short configurable delay after the last
Quick Action Key was selected.
14 Quick Action Keys Quick Action Keys allow the user to activate/deactivate
QAK functions directly from the interface without having to
use the menu.
The status of the function is indicated by the LED next
to the button. The LED can be configured to be red,
green or orange in colour and flashing.
Before using the Quick Action Keys it is necessary to
unlock the keys using the unlock button described
above. (Configuration)
Pressing a Quick Action Key will apply that action
without any further confirmation and the LED next to the
key will indicate the new status.
15 Enable/ Disable Disables ALL Trip Operations. When the switch is in
TRIP switch the Disable position the trip coil in the recloser is
electrically disconnected from the control electronics.
Thus the switch provides a physical isolation point for
the control circuitry. The recloser cannot be opened,
and an audible alarm in the panel will sound and the
DISABLED LED in the TRIP key will flash. The TRIP
key operates normally when the switch is in the Enable
position.
This switch also prevents a close operation, so that the
switchgear cannot be carrying load without the ability to trip.
16 Enable/ Disable Disables ALL Close Operations. When the switch is
CLOSE switch in the Disable position the close coil in the recloser is
electrically disconnected from the control electronics.
Thus the switch provides a physical isolation point for
the control circuitry. The recloser cannot be closed and
an audible alarm in the panel will sound and the
DISABLED LED in the CLOSE key will flash.The
CLOSE key operates normally when the switch is in the
Enable position.
7-7
N-Series Recloser
with ADVC Controller
DEFAULT CONFIGURATION
The Status Lamps and the Quick Action Keys are programmed in the factory to a
default configuration. This can be changed to suit the needs of the user through
Windows Switchgear Operating System (WSOS5).
Status Lamps
These lamps are used to indicate the controller and switchgear status. The default
configuration is shown below. Each lamp indicates the state of the function described
next to it. When a state is active, the lamp is lit.
For example, when the recloser is in Lockout the lamp next to “Lockout” will be on.
Conversely if the lamp is off, the recloser is not in a lockout state.
c
Protection Status and
cause of Tripped Status
It is possible that more than one lamp will be lit at a given time.
Example, when a recloser tripped to lockout due to an overcurrent fault on Phase A,
both “Lockout” and “A-Phase O/C” lamps may be lit.
The table below describes the default function of each lamp.
7-8
flexVUE Panel (cont)
Remote
then Control
7-9
N-Series Recloser
with ADVC Controller
7-10
flexVUE Panel (cont)
DISPLAY GROUPS
The O.I. displays are organized into three logical groups. Within each group is a
menu of pages and those pages have many various sub-menus.
Figure 24 flexVUE O.I. Display Screen The top line of the display is the page title. The top line of the display shows the
current menu position and the second line shows the lists the options available one
option at a time. An operator uses the UP and DOWN arrows to scroll through the list
of options. The RIGHT arrow will progress to the next level of the option shown on
the second line of the display. Use the LEFT arrow to go back one level.
When an operator is editing a setting, the top line of the display shows a few basic
Please Note: Screen sizes between instructions and the bottom line shows the setting value.
flexVUE and setVUE are not to scale in this
manual. EDIT,ESC, or SELECT
The character size is approximately the same but the <<setting to change>>
flexVUE is shown larger in this manual for readability.
CHANGING SETTINGS
Three types of settings can be changed:
Operator Settings
Password protected settings
Protection settings
Operator Settings
Find the display page containing the setting to be changed:
1: Press the MENU key to enter the Menu structure
2: arrow, then the arrow to enter the Operator Menu.
Press the
3: Use the /arrow keys to navigate to the setting to be changed.
4: Press the SELECT key
5: Use the /arrow keys to change the setting
6: Press the SELECT key to accept the change; or
6a: Press the
arrow to escape and leave the setting unchanged.
Alternatively, if a QUICK ACTION KEY operates the setting you wish to change:
1: Press the QAK UNLOCK
2: Press the required Quick Action Key within 10 seconds (Configurable)
Actions are executed without any confirmation via the arrow or select keys. The LED
indicates the new state.
7-11
N-Series Recloser
with ADVC Controller
While the Operator Panel remains ON you will not be required to enter the password
again.
The default factory password is AAAA but you can change it using Windows
Switchgear Operator System (WSOS5) software. The factory password does not
need to be remembered - the controller prompts you for it automatically.
ALERTS MENU
The flexVUE panel provides the user with a specific location to deal with alerts from
the controller. The ALERTS menu is found as part of the MAIN MENU on the O.I.
You can view these Alerts in the same way you would view any other menu options,
using the / keys to rotate through the available alerts.
Alerts will be split into 2 categories, Critical and Normal.
Normal Alerts
All Normal alerts will go into the Alerts menu. The activation of a Normal Alert will
cause the Title line of the current display to show:
xx Alerts Active
This will alternate with the current display title at a sufficient rate that the current
display is easily readable so that panel usage and field editing can easily continue.
xx is the number of Alerts that are present at the time.
The displayed number of Normal Alerts may change from one flash to the next if a
new alert is added or an old one is removed.
The Title of the Alert Menu will contain the number of Alerts that are present. This will
be shown as
A Normal Alert message will generally be longer than 20 characters and will
automatically scroll to allow viewing of the complete message. If a Normal Alert is
present a beep will occur at a fixed time interval.
All buttons will function normally whilst a Normal Alert is present.
Critical Alerts:
A Critical Alert will completely subvert the operation of the LCD display regardless of
what is being displayed. There will be no way to remove the Critical Alert from the
display whilst it is active.
If a Critcial Alert is present a Beep will occur at a fixed time interval.
All buttons with the exception of the navigation buttons ( ,
, , , MENU,
SELECT, LAMP DATA, EVENT LOG) will operate normally whilst a Critical Alert is
present.
7-12
flexVUE Panel (cont)
Settings Changed
SELECT to activate, continue change
Settings Changed
Activate? Y/N
The operator has to press the UP or DOWN ARROW key. That will display the
following:
EDIT, or SELECT
ACTIVATE? Yes
or
EDIT, or SELECT
ACTIVATE? No
When the operator scrolls to YES and presses SELECT, the settings are put in
service. If the operator selects NO and presses the SELECT key, the following
message is displayed: (scrolling)
Continue
Settings activate on panel shutdown
7-13
N-Series Recloser
with ADVC Controller
7-14
8 Event Log
INTRODUCTION
The ADVC maintains a log of up to 30,000 events that reflect changes to the status of
the switchgear, control electronics, and ADVC logic. The log also records setting
changes.
The events can be seen via the Event Log O.I. display group. The event log display
will update automatically with new events. The most recent event appears on the
bottom line of the screen and older events can be viewed by scrolling upwards.
When the event log is full, newest events replace oldest events.
All events are date and time stamped to a 10ms resolution and displayed in the order
that they occurred. The source of each event is also recorded.
It is possible to apply event category filters when viewing events.
WSOS5 software can also be used to read and display the event log. In addition to
O.I.-like time stamp, source identification and filter category features, it also has text
searches and go to a particular date/time. The event log can be saved as a text file or
as a csv file. Refer to the WSOS5 help file for more information.
On the flexVUE panel, the event log is found via an dedicated key on the O,I.
The Event Log is navigated slightly differently depending on which O.I. is installed. A
navigation diagram for the setVUE O.I. is shown in Figure 25 (page 8-1) and for the
flexVUE O.I. in Figure 26 (page 8-1).
The following table indicates the differences between setVUE and flexVUE event log
navigation
Description
Figure 25 setVUE Navigation Diagram
View additional information about event (if available) ALT EVENT LOG
Figure 26 flexVUE Navigation Diagram
Switch between DATE/TIME, TIME/EVENT &
EVENT DESCRIPTION -
&
8-1
N-Series Recloser
with ADVC Controller
8-2
Event Log (cont)
Display of Events
The difference in the display on the setVUE and flexVUE are shown in the following
example.
Consider the following events, as shown on the setVUE:
09/01/05 10:39:12.49 B Max 302 Amp
09/01/05 10:39:12.49 C Max 301 Amp
Please Note: Screen sizes between 09/01/05 10:39:12.50 Automatic Reclose
flexVUE and setVUE are not to scale in this 09/01/05 10:39:22.50 Sequence Reset
manual.
The flexVUE, by default, would display the bottom two lines (the most recent)
The character size is approximately the same but the first. See below:
flexVUE is shown larger in this manual for readability.
10:39 Automatic Recl
10:39 Sequence Reset
From this screen, a complete TIME or EVENT DESCRIPTION is available by
pressing the or keys respectively:
09/01/05 10:39:12.50
09/01/05 10:39:22.50
For the EVENT DESCRIPTION press :
Automatic Reclose
Sequence Reset
In this example, pressing the twice would scroll to the next two events.
10:39 B Max 302 Amp
10:39 C Max 301 Amp
Setting Change Events
A settings change can come from a variety of sources - WSOS5, Operator Interface,
SCADA protocol, and IOEX. The controller includes in its log, information regarding
the source of each setting change.
If the ALT key ( ) or EVENT LOG key ( ) is pressed whilst the event log is on the
display then the date and time details are replaced with extra information that
includes the setting source and, if applicable, the protection group, curve, and trip
number. Pressing the ALT ( ) or EVENT LOG ( )key again will redisplay the
date and time information.
The identification codes for sources are:
Identifier Settings change source
WSOS WSOS5 change
OCP Operator Control Panel (Operator Interface) change
PTCL SCADA protocol change
IOEX IOEX change
As it is possible for multiple WSOS5 applications to be simultaneously connected to
the controller via Ethernet, a source identification of “WSOS” can be insufficient
information. For WSOS5 over Ethernet connections the first four letters of the PC’s
login name are logged. The usage of “WSOS” is therefore restricted to serial port
point to point communication links only.
8-3
N-Series Recloser
with ADVC Controller
For example, a setVUE event log display may look like this:
becomes:
WSOS PHASE TRIP 2 D VERY INV IEC255
OCP RS232-B PARITY EVEN
PTCL WORK TAG APPLIED
LOAD SUPPLY ON
8-4
9 Power System Measurements
The current transformer (CT) signals and voltage screen (CVT) signals from the
recloser are digitised by the ADVC Controller and used to provide a variety of data
for the operator.
The ADVC Controller measures up to 10 power system components:
A, B, C, phase and spill currents,
phase-earth voltage on all six terminals.
The ADVC Controller uses the above measurements to derive many system
measurements including:
frequency,
phase to phase voltages,
total and per phase power (kW, kVA, kVAR),
total and per phase power factor,
harmonics,
earth current, and
sequence components.
In addition, the ADVC Controller also measures internal values such as:
CAPE temperature,
switchgear temperature1
auxiliary voltage,
gas pressure,
battery voltage.
1 The ADVC measures the temperature of the SCEM in the ACR and from that, calculates the switchgear
temperature.
9-1
N-Series Recloser
with ADVC Controller
System Measurements
SYSTEM MEASUREMENTS-M
- - - - - - - SYSTEM MEASUREMENTS - - - - - - M
Current 100 Amp Power (P) 1633 kW
Voltage 6350 Volt Power (Q) 478 kVAR
Frequency 50.0Hz Power Factor 0.86
e.g.
OPERATOR MENU - MEASUREMENTS
- SYSTEMS MEASUREMENTS
(Scroll through AVG Current, AVG Voltage, Frequency, Power Factor, 3PH Power P [Kw], #PH Power Q [kVAr])
Current
In the ADVC Controller current angles are taken with respect to their Phase
voltage angle.
SYSTEM MEASUREMENTS - Current-M
- - - - - - - - - - - CURRENT - - - - - - - - - - M
A Phase 123 Amp Earth 6 Amp
B Phase 123 Amp Ipps 120
C Phase 121 Amp Inps 10
e.g.
ENGINEER MENU - MEASUREMENTS - CURRENT
(Scroll through Magnitude & Angle-a, B, C & Earth and Sequence-I1 (Ipps),I2 (Inps))
These screens display, for each phase, the current and phase angle, earth
current. and Positive Phase Sequence Current (Ipps) and Negative Phase
Sequence Current (Inps).
Voltage
SYSTEM MEASUREMENTS - Voltage-M
SOURCE - - - - - - - VOLTAGE - - - - - - -LOAD M
11,000 Volt A-P 11,000 Volt
11,000 Volt B-P 11,000 Volt
11,000 Volt C-P 11,000 Volt
e.g.
To change between the display voltage being
shown as Phase- Phase or Phase-Earth you ENGINEER MENU - MEASUREMENTS - VOLTAGE - PHASE/
must change the setting at the following LINE\SRC-LD
location: (Scroll through A, B & C-Phase)
SYSTEM STATUS - PHASE VOLTAGE and
POWER FLOW - Display Ph-Ph Vol
ENGINEER MENU - CONFIGURATION MENU
-SYSTEM SETTINGS - METERING PARAMETERS
- Display Voltage Ph/Earth V or Ph/Ph
Volt
9-2
Power System Measurements
(cont)
Sequence Voltage
SYSTEM MEASUREMENTS -
Sequence Voltage-M
- - - - - - - - SEQUENCE VOLTAGE - - - - - - - M
Vzps 100 Volt
Vpps 11,000 Volt
Vnps 200 Volt
e.g.
ENGINEER MENU - MEASUREMENTS - VOLTAGE
- SEQUENCE
(Scroll through Vpps, Vnps & Vzps)
These screens display the Zero, Positive and Negative phase sequence
voltages.
Power
SYSTEM MEASUREMENTS - Power-M
- - - - - - - - - - - - POWER - - - - - - - - - - M
AP 540 kW Q 158 kVAR PF 0.88
B P 549 kW Q 166 kVAR PF 0.88
C P 546 kW Q 156 kVAR PF 0.88
e.g.
ENGINEER MENU - MEASUREMENTS - POWER
- 3-PHASE, A,B & C-PHASE
(Scroll through Real Power, Apparent & Reactive Power, Power Factor)
These screens display real and reactive power, as well as the power factor on a
per phase basis.
Real Power (kW) is a signed quantity unless Power Flow Unsigned has been
selected on page:
SYSTEM STATUS - PHASE VOLTAGE and POWER FLOW:
Power Flow Signed/Unsigned
ENGINEER MENU - CONFIGURATION MENU
- SYSTEM SETTINGS - METERING PARAMETERS
- Power Signed/Unsigned
These screens display real and reactive power, as well as the power factor on a
per phase basis.
Daily, Weekly and Monthly Demand Indicators display collected historical data,
while the Maximum Demand Indicator contains a mixture of real-time and
historical data.
9-3
N-Series Recloser
with ADVC Controller
9-4
10 Maintenance
Be careful to ensure that if working on the Maintenance can be carried out using standard electricians’ and mechanics’ tools.
ADVC with the door open in heavy rain,
water does not enter the circuit breakers
or general power outlet.
ACR MAINTENANCE
No user maintenance of the ACR mechanism is required.
The ACR should be returned to the manufacturer for refurbishment if the mechanical
duty or breaking duty is exceeded. This is checked by examining the remaining
contact life on the Operator interface. When the remaining contact life in any phase
approaches zero, the ACR has reached the end of its life and must be replaced.
A warning is displayed in the event log when the Every five years the bushing boots should be checked, cleaned if necessary and the
remaining contact life reaches 20%. pointer checked to ensure it is free from mechanical obstructions. In areas of high
atmospheric pollution more frequent cleaning may be appropriate.
At suitable intervals check the gas low alarm is not showing on the operator
interface. If gas low is showing, this may indicate a leak which must be found.
Recharging the ACR SF6 using a gas fill adaptor is described below.
Safety
Do not attempt to recharge the gas without Removal from Service
first removing the ACR from service.
The gas fill valve is located between the ACR body and the mounting bracket.
Ensure that the ACR is removed from service before fitting the gauge and taking a
reading.
Equipment Required
ACR SF6 recharging is carried out using a Gas Fill Adaptor (GFA) and Tool, and a
standard size-D SF6 cylinder. See “Appendix A Replaceable Parts & Tools (page
A-1)” for these part numbers.
10-1
10-1
N-Series Recloser
with ADVC Controller
Procedure
Preparation
This procedure should be performed
under controlled conditions using
appropriate SF6 reclamation equipment.
The gas filling procedure may be conducted on an ACR either in the field or within a
workshop.
Tank pressure gauge and
sshut-off
sh
shu t-off valve
v If to be conducted in the field, ensure that the ACR is removed from service until the
procedure is complete.
Cylinder pressure gauge and
regulator
re
reg valve
ulator valv Record the ambient temperature as this will be required when calculating the fill
pressure.
10-2
Maintenance
(cont)
SWITCHGEAR DATA
e.g.
SF6 Normal 31kPag
10-3
N-Series Recloser
with ADVC Controller
ADVC MAINTENANCE
Take care to ensure, when accessing the
cubicle compartment in heavy rain, that water Maintenance of the ADVC is required every five years. The manufacturer
does not penetrate the circuit breakers. recommends the work described below.
CLEANING
Check for excessive dirt on the cubicle, particularly the roof, and clean off.
Ensure that the mesh covering the air vents and the water drainage holes in the base
are clean.
BATTERY REPLACEMENT
Battery replacement is recommended after a period of five years. See “Battery Care
(page 10-5)” .
The procedure is:
1: Turn off the battery circuit breaker.
Ensure that battery polarity is correct. 2: Unplug batteries and replace with new batteries.
3: Turn on the battery circuit breaker and ensure that “BATTERY NORMAL” status
is restored via:
SYSTEM STATUS - Switchgear Status-S
- - - - - - - - SWITCHGEAR STATUS - - - - - - - S
Work Tag OFF SF6 Normal 31kPag
Aux Supply Normal Battery Normal 27.5V
SWGR Connected SWGR Data Valid
e.g.
SWITCHGEAR DATA
Battery Normal 27.3V
e.g.
10-4
Maintenance
(cont)
Door Seal
Check the door sealing rubber for perishing or undue hardening. If necessary renew
the seal.
10-5
N-Series Recloser
with ADVC Controller
FAULT FINDING
ADVC Controller Check
Fault finding within the ADVC involves determining whether the fault lies in the
electronic modules, the wiring or elsewhere. The electronic modules are user
replaceable items. Other faults require the ADVC to be returned to the factory.
A suggested fault finding approach is as follows:
1: If the System OK LED(s), located on the on the operator interface (O.I.), are
flashing then the CAPE microprocessor is running. If the O.I. does not operate
then follow Step 4.
System OK LEDs are located in different places on the setVUE and flexVUE
panels:
System OK
10-6
11 Ratings and Specifications
ACR
Rated Voltage
N15 15.5 kV
N27 27 kV
N38a 38 kV
Rated Continuous Current 800 Amp
Emergency Load Current - carrying capability (8 Hours) 850 Amp
Rated Frequency 50/60 Hz
Rated Load Breaking Current 800 Amp
Rated Cable Charging Breaking Current (N15 and N27) 25 Amp
Rated Cable Charging Breaking Current (N38) 40 Amp
Rated Single Capacitor Bank Breaking Current 250 Amp
Rated No-Load Transformer Breaking Current 22 Amp
Rated Symmetrical Interrupting Current 12.5 kA
Rated Asymmetrical Short-circuit Making Current (peak) 31.5 kA
Rated Symmetrical Making Current (rms) 12.5 kA
Rated Short-time Withstand Current (rms) 12.5 kA
Rated Duration of Short-circuit 3 sec
11-1
11-1
N-Series Recloser
with ADVC Controller
BREAKING DUTY
The duty limits of the ACR are shown in the table below. It is rated for ANSI C37.60
duty cycle.Contact wear is automatically calculated for each interrupter by the ADVC
on the basis of fault current and mechanical operations.
The remaining contact life is shown on the operator interface.
11-2
Ratings and Specifications
(cont)
Duty Cycle
Maximum allowable duty cycle at full short circuit current rating:
Open-0.5s-Close.
Open-2s-Close.
Open-2s-Close.
Open followed by 300 second recovery time.
Bushing Boots
The ACR is normally supplied with outdoor elastomeric bushing boots. The boots
suit insulated cable sized 16-33 mm diameter and comprise an unscreened
insulated system.The characteristics of the boot alone (disregarding the cable
insulation) are detailed in the following table.
HV Cables
Cable is usually provided by the manufacturer pre-cut and terminated to fit the ACR
bushings and rated to suit the requirements of the utility.
Alternatively cable can be supplied by the utility if appropriate (e.g. to terminate HV
Aerial Bundled Cable). The manufacturer warrants the equipment only if suitably
insulated and watertight cable and terminations are used. Contact the manufacturer
or your local distributor to check cable type for suitability.
Standard cable supplied by the manufacturer is detailed in the following table.
Current Transformers
There is no access to current transformer connections on the equipment. This data is
supplied for information only and is applicable to both standard and SEF CTs.
Ratio 2000:1
Accuracy 10 Amp - 800 Amp ±0.5%
Accuracy 800 Amp - 12500 Amp ±2.5%
Environmental
11-3
N-Series Recloser
with ADVC Controller
ADVC
General Specifications
Cubicle material 304 stainless steel
ULTRA 316 stainless steel
Cubicle shell sealing IP 44
Electronic enclosure sealing IP 65
Wind loading resistance of structure >160km/hr
Wind loading on door when latched in open position >60km/hr
Angle of door opening 1350
Standard ambient operating temperature range -100C to 500C
Extended operating temperature range (battery heater -400C to 500C
required) ULTRA Only
Electronics Temperature Range -400C to 500C
Maximum radiation 1.1kW/m2
Humidity 0 to 100%
Standard control cable lengtha 7m (23')
Maximum vertical separation from ACR with standard 5m (16.4')
control cable.
Maintenance intervalb 5 years
Auxiliary supply voltage (LV AC mains supply) As Ordered 115/230 Vac
nominal
-20% to +10%
Required auxiliary supply rating 100 VA
Battery (With battery heater option, 12AH batteries are 2 x 12V 7.2Ah
standard.)
Battery hold up time from fully charged at 250C 26 hours with 7Ah
44 hours with 12Ah
Capacity available for communications, hold up time 20 hours
(no heater, OCP or IOEX) 13.8V TX:2.1A, 15min, RX
320mA
Battery recharge time (new battery to 80% nominal 10 hours
capacity)
Battery replacement intervalb 5 years
Battery Low Voltagec 23V
Battery High Voltagec 33V
Earthingd 10mm earth stud
Battery Heater Power (where fitted) 10W
Battery Heater Element Life 30,000hrs
Radio/Modem
A radio or modem may be fitted by the manufacturer or by the utility, for remote
communications. Space, power and data interfaces are provided within the control
cubicle.
Radio/Modem Power Supply Voltage (set by user) 5 - 15 V DC
Radio/Modem Power Supply Continuous Currente 3 Amp
Radio/Modem Power Supply Max Current 8 Amp for 30 sec with
10% duty cycle
Radio/Modem Power Supply continuous power 45 W
Radio/Modem Power Supply peak power 120 W for 15 mins @
10% duty cycle
Radio/Modem Space on Radio Panel 300 x 250 x 150 mm
Radio/Modem Interface V23, RS232, RS485
Radio/Modem Power Shutdown Time (user 1 - 1440 min
configurable)
Shutdown time increment 10 sec
11-4
Ratings and Specifications
(cont)
Control Electronics
Continuous Primary current 800A
Continuous secondary current 0.8 Amp
Short time primary current 16kA for 3s
Short time secondary current 12 Amp for 3 sec
Short time current recovery time 60 sec
Required auxiliary supply rating 32VAC, 100VA
Real time clock hold time 20 days
Recloser Operations 20 in 1 minute, 1 per
minute thereafter
a. Other control cable lengths available-4, 11 and 20 meters.
b. Battery replacement interval is influenced by environmental temperature.
c. Temperature compensated at 48mV/°C.
d. Earthing details in “Earthing (Grounding)” on page 3-7 must be strictly adhered to.
e. For an external VT, the maximum continuous current drawn from the radio supply should be limited to 0.5
amps.
11-5
N-Series Recloser
with ADVC Controller
11-6
Ratings and Specifications
(cont)
11-7
N-Series Recloser
with ADVC Controller
11-8
Appendix A
Replaceable Parts & Tools
All replacement parts listed in the following table are available from the
manufacturer.
A-1
A-1
N-Series Recloser
with ADVC Controller
A-2
Appendix B Dimensions
ACR DIMENSIONS
ACR
Top
View
ACR
Side
View
B-1
B-1
N-Series Recloser
with ADVC Controller
ADVC COMPACT
ADVC ULTRA
B-2
Appendix B Dimensions
(cont)
B-3
N-Series Recloser
with ADVC Controller
IOEX2 DIMENSIONS
IOEX 2 Dimensions
Figure 34
B-4
Appendix C Safety Data Sheet -
Sulphur Hexafluoride (SF6)
Gas and Engineering
Linde Gas Division
C-1
N-Series Recloser
with ADVC Controller
14 TRANSPORT INFORMATION
ADR/RID Labelling
Class 2 Classification Code 2A - Symbols
UN number and proper shipping name No symbol required.
UN 1080 Sulphur hexafluoride - Risk Phrases
UN 1080 Sulphur hexafluoride RAs Asphyxiant in high concentrations.
ADR/RID-Labels 2.2 Hazard number 20 - Safety Phrases
Packing Instruction P200 S9 Keep container in well ventilated place.
S23 Do not breathe the gas.
IMDG S36/37/39 Wear suitable protective clothing, gloves and
Class 2.2 eye/face protection.
UN number and proper shipping name
UN 1080 Sulphur hexafluoride Further national regulations
ADR/RID-Labels 2.2 Pressure Vessel Regulation
Packing Instruction P200 Regulations for the prevention of industrial accidents
EmS FC, SV Water pollution class
Not polluting to waters according to VwVwS from 17.05.99.
IATA
Class 2.2 16 OTHER INFORMATION
UN number and proper shipping name Ensure all national/local regulations are observed. The hazard of
UN 1080 Sulphur hexafluoride asphyxiation is often overlooked and must be stressed during
ADR/RID-Labels 2.2 operator training. Before using this product in any new process or
Packing Instruction P200 experiment, a thorough material compatibility and safety study
Other transport information should be carried out.
Ensure vehicle driver is aware of the potential hazards of the load Advice
and knows what to do in the event of an accident or an emergency. Whilst proper care has been taken in the preparation of this
Before transporting product containers ensure that they are firmly document, no liability for injury or damage resulting from its use can
secured and: - cylinder valve is closed and not leaking - valve outlet be accepted. Details given in this document are believed to be
cap nut or plug (where provided) is correctly fitted - valve protection correct at the time of going to press.
device (where provided) is correctly fitted - there is adequate Further informations
ventilation. - compliance with applicable regulations. Linde safety adivce
No. 3 Oxygen deficiency
15 REGULATORY INFORMATION No. 7 Safe handling of gas cylinders and cylinder bundles
No. 11 Transport of gas receptacles in vehicles
Number in Annex I of Dir 67/548
Not included in Annex I.
EC Classification: Not classified as dangerous substance.
C-2
Appendix D
Silicone Grease Hazard Data
SUPPLIER: Manufacturer:
Name: Bluestar Silicones Shanghai Co., Ltd.
Address: 3966 Jin Du Road
Xinzhuang Industrial Zone
Shanghai, 201108
CHINA
Telephone Number: 86 21 5442 6600
Fax number: 86 21 5442 3733
MANUFACTURING SITE:
Factory: Bluestar Silicones Shanghai Co., Ltd.
Address: 3966 Jin Du Road
Xinzhuang Industrial Zone
Shanghai, 201108
CHINA
Telephone Number: 86 21 5442 6600
Fax number: 86 21 5442 3733
Emergency Contact Number: 24hr hotlines:
Mainland China: 86 21 62679090 Shanghai Chemical&Toxic consultant center
Outside China (English): + 33 4 72737404 Bluestar Silicones USRA France
3 Hazards identification
Adverse human health effects Slightly irritating to eyes.
Environmental effects: Presents no particular risk to the environment, provide the disposal
requirements and national or local regulation are complied with.
D-1
D-1
N-Series Recloser
with ADVC Controller
Extinguishing media
- Suitable Carbon dioxide ( CO2 )
Foam
Powders
Water spray.
- Not suitable None to our knowledge. If there is a fire close by, use suitable
extinguishing agents.
Specific hazards: Combustible.
Specific fire fighting methods Cool down the containers/equipment exposed to heat with a water
spray.
Handling
Technical measures: Does not require any specific or particular measures.
Storage
Technical measures: Does not require any specific or particular technical measures.
Storage conditions:
- Recommended Stable under normal storage conditions
Incompatible products Strong oxidizing agents
packaging - Steel drums varnished with epikote.
- Aluminum tubes ( outer packaging – cardboard box).
- Plastic box
D-2
Appendix D Silicone Grease Hazard Data
(cont)
Appearance
Physical state: Translucent, light grey paste
Specific Gravity: 1 ( water = 1)
Flash Point: >200oC
Flamm. Limit LEL Non-flammable
Solubility
- in water Insoluble
- in organic solvents Insoluble in:
- acetone
- alcohol ( ethanol )
Dispersible ( partial solubilisation
- ethers
- aromatic hydrocarbons.
- Aliphatic hydrocarbons.
Chlorinated solvents.
11 Toxicological information
12 Ecological information
13 Disposal consideration
14 Transport information
International regulation None Allocated
-- Land - rail / road (RID/ADR) Not restricted
-- Sea (IMO / IMDG) Not restricted
-- Air ( ICAO-IATA) Not restricted
NOTE: The user’s attention is drawn to the possible existence of local
regulations regarding disposal
15 Regulatory information
LABELLING
EEC regulation: Mandatory labeling (self – classification) of hazardous preparations: Not
applicable.
The regulatory information given above only indicates the principal
regulations specifically applicable to the product describe in the Safety
Data Sheet.
The user’s attention is drawn to the possible existence of additional
provisions which complete these regulations
D-4
Appendix D Silicone Grease Hazard Data
(cont)
16 Other information
Uses:
- Recommended uses: Isolation of electrical or electronic material.
( For further information, refer to the product technical data sheet)
Registration numbers: These polymer are not concerned by the EINECS inventory.
The corresponding monomers are registered in the EINECS inventory
All the other constituents of this preparation are registered in the
EINECS inventory.
All the components of this preparation are registered in the TSCA
inventory.
This safety data sheet should be used in conjunction with technical sheets. It does not replace them. The information given is
based on our knowledge of this product, at the time of publication. It is given in good faith. The attention of the user is
drawn to the possible risks incurred by using the product for any other purpose other than that for which it was intended.
This does not in any way excuse the user from knowing and applying all the regulations governing his activity. It is the sole
responsibility of the user to take all precautions required in handling the product. The aim of the mandatory regulations
mentioned is to help the user to fulfill his obligations regarding the use of hazardous products. This information is not
exhaustive. This does not exonerate the user from ensuring that legal obligations, other than those mentioned, relating to the
use and storage of the product, do not exist. This is solely his responsibility.
D-5
N-Series Recloser Notes
with ADVC Controller
Notes
N-Series Recloser Notes
with ADVC Controller