THE MID-WEST CONCRETE INDUSTRY BOARD, INC.
ent
>
tog bo
=
; i
5 é
< ae
“Cigenizad For Quality Concrete”
APPROVED
STANDARD CONCRETE SPECIFICATION
SECTION 27-UNIT CONCRETE MASONRY
I. PURPOSE AND SCOPE
A. The purpose of this section is to establish minimum
standards for the design, fabrication, handling and
erection of concrete masonry units, Wherever these
provisions differ from the project specifications
the requizements set forth in the project specifi-
cations shall govern.
“IT. GENERAL
A. All other provisions of the M.C.I.B. specifications
not in conflict with this section shall apply to
concrete masonry units.
B, The following specifications, standards and codes
shall also govern except where modified herein.
1, American Conerete Institute
a, ACI Committee 531 - Concrete Masonry
Structures - Design and Construction, ACI
Title No. 67-23.
2, American Society for Testing and Materials
a, ASTM C55, Specification for Concrete
Building Brick
b. ASTM C90, Specification for Hollow
Load-Bearing Concrete Masonry Units
c. ASTM C129, Specification for Hollow Non-
Load-Bearing Concrete Masonry Units
d. ASTM C140, Methods of Sampling and Testing
Concrete Masonry Units
e. ASTM C145, Specification for Solid Load-
Bearing Concrete Masonry Units
£, ASTM C150, Specification for Portland '
Cement
JUNE, 1978 SECTION 271.
ASTM C207, Specification for Hydrated Lime
for Masonry Purposes
ASTM 270, Specification for Mortar for
Unit Masonry
ASTM C331, Specification for Lightweight
Aggregates for Concrete Masonry Units
ASTM C426, Test Method for Drying Shrinkage
of Concrete Block
ASTM C595, Specification for Blended Hydraulic
Cements
ASTM C618, Specification for Fly Ash and Raw
or Calcined National Pozzolans for Use in
Portland Cement Concrete.
3. National Concrete Masonry Association
a
e.
NCMA-TEK 16 Cold Weather Concrete Masonry
Coristruction
NCMA-TEK 20 Mortars for Concrete Masonry
NCMA-TEK 36 ASTM Specification for Concrete
Masonry Unite
NCMA-TEK 65 Field Inspection of Engineered
Concrete Masonry
NCMA-TEK 71 Cold Weather Construction with
Concrete Masonry
4. Portland Cement Association
PCA Concrete Masonry Handbook
IIL, CLASSIFICATION
A. Concrete Masonry Units manufactured in accogdance with
this specification shall conform as follows?,
1. GRADES - Two grad
a.
sume, 1978
of concrete masonry units
Grade N - Description of intended use for
different concrete masonry units is sum-
marized in Table 1.
Grade $ - Description of intended use for
different concrete masonry units is sum-
marized in Table 1.
Page 2 secrion2, ‘TYPES - Two types of concrete masonry units in
each grade shall conform
a. Type I, Moisture-Controlled Units ~ Units
designated as Type I shall conform to all
requirements of this specification includ-
ing the moisture content requirements of
Table 2
b. Type II, Nonmoisture-Controlled Units - Units
designated as Type II shall conform to all
requirements of this specification except
moisture content requirements of Table
Iv. MATERIALS
A
Materials shall conform to the following applicable
specifications:
1. Portland Cement - ASTM C150
Blended Cements - ASTM C595
Hydrated Lime, Type § - ASTM C207
Pozzolans - ASTM 0618
wren
Aggregates - Aggregates shell conform to the
ollowing specifications, except that grading
requirements shall not necessarily apply:
a. Normal Weight Aggregates - ASTM C33
b. Lightweight Aggregates - ASTM C331
6. Mortar - ASTM C270
Other Constituents ~ Air-entraining egents, coloring
pigments, integral water repellents, finely ground
silica, or other appurtenances, shail be previously
established as usable for use in concrete gnd either
shall conform to ASTM standards vhere applicable, oF
shall be shown by test or experience to bé’not detri-
mental to the durability of the concrete.
V. PRODUCT DELIVERY, STORAGE AND HANDLING
A.
UNE, 1978
When delivered to the job, concrete masonry units should
be sufficiently dry to comply with specified limitations
for moisture content. To be maintained in this dry
condition they should be stockpiled on planks or other
Page 3 section 27supports free from contact with the ground and then
be covered with roofing paper, canvas or polyethylene
tarpaulins. The top of a concrete masonry structure
should be covered with tarpaulins or plastic to pre-
vent rain or snow from entering unit cores during
construction. 7
Concrete masonry units should never be wetted im-
mediately before and during placement
VI. PHYSICAL REQUIREMENTS
A
Minimum Face-Shell and Web Thicknesses (ASTM C90
only)
1. Face-shell (FST) and web (WT) thicknesses
shall conform to the requirements listed
in Table 4
Permissible Variations in Dimensions
1. No over-all dimension (width, height, end
length) shall differ by more than 1/8 inch
from the specified standard dimensions
Strength and Absorption Requirements
1. At the time of delivery to the work site the
units shall conform to the physical require-
ments prescribed in Table 3.
Moisture Content
1. The moisture content of Type I concrete
masonry units at time of delivery shall
conform to the requirements prescribed
in Table 2
VII. ENVIRONMENTAL CONDITIONS
A
Hot-Weather Construction
1, In hot weather the main objective is to see:
that all of the materials of concrete masonry
are placed without having acquired excess heat.
That is, heat should be minimized in concrete
masonry units by storing them in a cool place,
and the mortar mixture should be relativel;
cool, Inmediately after morter has been mixed,
it begins to rise in temperature and must be
protected from heat gain during construction.
Page 4 secrion 27Mortar materials stored in the sun can become suf-
ficiently hot to significantly affect the tempera-
ture of the mortar mixture itself. Covering or
sheding such materials from the sun can be helpful.
2, Since wind and low relative humidities cause in-
creased evaporation, the use of wind screens and fog
(water) sprays can effectively reduce the severe ef-
fects of hot, dry, windy weather. Also, covering
walls immediately after construction will effective-
ly slow the rate of moisture loss from masonry.
B. Cold-Weather Construction
1, Gold-weather conerete Masonry construction generally
requires only a few changes in the mortar mixture.
Concrete masonry units used during normal tempera-
tures may be successfully used during cold weather.
2, Materials Storage - Masonry units and materials for
mortar should be kept on a platform raised to prevent
wetting from ground moisture. If not otherwise en-
closed, the materials should be covered with tarpau-
lins, plastic sheets, or equivalent. Masonry sand
which is delivered in bulk should be covered to pre-
vent entrance of water from melting ice and snow.
3. Heating Materials - The most impor:an: consideration
in heating concrete masonry mate. ial: is that suf-
ficient heat be provided to assur: hydration of the
cement content in mortar. After combining all in-
gredients, the temperature of the mortar should be
within a range of 70°F to 120°F.
4, Admixtures or Antifreeze - Admixtures or antifreeze
agents in quantities which are high enough to lower
freezing point of mortars should not be permitted.
The high content required would adversely affect
mortar strength and other desirable properties.
The use of calcium chloride as an admixture in
masonry mortars for early strength development is
persissibles however, providing the amount added
does not exceed 2 percent by weight of the portland
cement content. Calcium chloride should not be
permitted in construction where metal objects such
as ties and anchor bolts are imbedded in the mortar,
because the metal would then be subjected to in-
tensified corrosion. Care must be exercised to
avoid combination of high temperature and a con-
centration of calcium chloride which will result
in excessively rapid setting of mortar (flash set).
0x, 7 Page 5 SECTION 27woRK ay ‘CONSTRUCTION PROTECTION
TERPERATURE REQUIREMENT REQUIREMENT
5. Construction and Protection Requirements
Normal masonry procedures.
Heat mixing water to produce mortar
temperatures between 40F ~ 120F.
Heat mixing water and sand to pro-
duce wortar tecperatures between
40F = 120F.
Mortar on boards should be main
‘talned abave 40F.
Heating mixing water and sand to
produce mortar temperatures between
for + 120F.
NCMA-TEK 71
Cover walls with plastic or canvas at end of work
day to prevent water entering sasonry.
Cover walls and materials to prevent wetting and
freezing. Covers should be plastic or canvas.
With wind velocttfes over 15 mph provide windbreaks
during the work day and cover walls and materials
AE the end of work day to prevent wetting and frees
ing.
Maintain masonry above freezing for 24 hours using
‘auxtTtary beat or insulated blankets.
Provide enclosures and supply sufficient heat to
maintain sasonry enclosure above 32F for 24 hours.
a. When air temperatures are 25°F - 20°F utilize
sources of heat on both sides of walls under
construction. Employ windbreaks when wind is
in excess of 15 mph.
b. Temperature of units when laid shall not be
less than 20°F.
¢, All protection for masonry shall be for 24
hours
ceptable methods.
VII. CONSTRUCTION TECHNIQUES
Ae
UNE, 1978
Supplementary heat may be electric heating
lankets, infrared heat lamps or other ac-
The cooperation of the owner, architect, engineer,
contractor, and material supplier are important to
obtain a quality structure. The masonry contractor
should give the work his personal supervision and
keep a competent foreman on the job at all tities.
Masonry construction should proceed smoothly #ith
the contractor following recommended procedures as
outlined in ACI Committee 531, Chapter 7 Masonry
Construction; NCMA and PCA
Masonry should be protected at the end of the day's
work. “The top of wall and ends of construction
should be protected with polyethylene or a water-
proof covering until work is continued. ~~.
Page 6
SBCTION 27IX. INSPECTION AND TESTING
A.
JUNE, 1978
Visual Inspection
et
All units shell be sound and free of cracks or
other defects that would interfere with the proper
placing of the unit or impair the strength or
Permanence of the construction. Minor eracks
incidental to the usual method of manufacture, or
minor chipping resulting from customary methods of
handling in s' pment: and delivery, shall not be
deemed grounds for rejection.
Units that are intended to serve as a base for
plaster or stucco shall have a sufficiently rough
surface to afford a good bond.
Where units are to be used in exposed wall con-
struction, the face or faces that are to be ex-
osed shail be free of chips, cracks, or other
Emperfect ions. Tf more than '5 percent of a
shipment contains slight cracks or small chips
larger then one inch this shall be grounds for
rejection.
Sampling and Testing
ee
Sample end test units in accordance with ASTM
Methods C140.
When Type I, moisture-controlled units are
specified, moisture-content requirements shall
conform with Table 2 requirements and shall be
tested in accordance with ASTM C426. Tests shall
be conducted within 12 months prior to delivery
of units.
Rejection
1.
If the shipment fails to conform to the specified
requirements, the manufacturer may sort, it, and
new specimens shall be selected by thepurchaser
from the retained lot and tested at the’ expense
of the manufacturer. In case the second set of
specimens fails to conform to the test require-
ments, the entire lot shall be rejected.
Expense of Test
1.
Except as specified in Section IX C, or otherwise
agreed, the expense of inspection and testing
shall be borne by the purchaser.
Page 7 secTion 27x. TABLES
TABLE 1 Types And Grades Of Concrete Masonry Units For Various Uses
Far general use such as in exterior
walTs below and above grade that may yeneer and facing units,
‘OF may not be exposed to moisture pen~ Yaextertor walls and for
tration or the weather and for inter= ‘use where high strength
or walls and back-up. and resistance to moisture
penetration and severe
frost action are desired.
For use above grade in exterior walls For general use where mod-
with weather-protective coatings and erate strength and resist=
jn walls not exposed to the weather. ance to frost action and
moisture penetration are,
required.
Sel, SIT
TABLE 2 Moisture-Content Requirements for Type I Units
Yoisture Content, Maximum, Percent
of Total Absorption
(Average of 3 Units)
Humidity Conditions at Job Site or
Point of Use*
AS
40
40 35
35 30
*Arid--Average annual relative humidity less than 50%
Intermediate--Average annual relative humidity 50-75%
Humid--Average annual relative humidity above 75%
Linear Shrinkage, Percent
0.03 or less...
From 0.03 to 0.045.
0.045 te 0.065 (Max).
NOMA TEK 36
UNE; 178 Page 8 sucrion 27‘Wininun Compressive Various Water Absorption in Tb/Te
Strength in psi on for units of Different Weight Class-
Average Gross Aren SFleattons Based upon Oven Dry Unit
‘Average of
‘three units}
HO ABSORPTION LIMTT
TABLE 4 Minimum Thickness of Face-Shel? and Hebs
{Applies to ASTM ¢ 90-70 Oniy)
Web Thickness (WT)
Equivalent Web
Thickness, min,
in./lineal ft.**
Face-Shel1 Thickness
Nominal Width (Wl)
(FST) min, in.*
of Units, in.
3 and 4 1-5/8
6 21,
8 2-1/1
10 2-1/2
2
* Average of measurements on 3 units taken at the thinnest point.
++ Sum of the measured thickness of ai] webs in the unit, multiplied by 12,
and divided by the length of the unit.
set This face-shel] thickness (FST) is applicable where allowable design load
4s reduced in proportion to the reduction in thickness from basic face-shel!
thicknesses shown.
uve, 17 Page 9 section 77TABLE 5
Parte by Volume Parts by Volume | Aggregate, Compressive
of Hesony of Hydrated Lime | Heasured Stenath
Cement ime Putty Damp, Los G
Condition 28 Days Psi
Not less than
2 and not
more than
3 times the
sum of the
volumes of
the cements
and lime used.
Bax ea a |
i 14
1 cee over & to
pee 1 (Type 11) ose
1 oo cover & tols
| ° | 1 (Type Tor 11...
see over 1% to 1s
ee Tore
TABLE 6
ASTH
Mortar Type
Designation | Construction Suitability
Nasonry subjected to high compressive loads, severe frost
action, or high lateral loads from earth pressure, hurricane
winds, or earthquakes. Structures below grade, manholes.
and catch basins.
Structures requiring high flexural bond strength, but subject
only to normal compressive Toads.
General use in above grade masonry. Residential basenent
construction, interior walls and partitions. Concrete
masonry veneers applied to frame construction,
Non-load-bearing walls and partitions. Solid I¢ad bearing
masonry of allowable compressive strength not exceeding
| | 100 pst
NCMA TEK 20
Interior non-load-bearing partitions where low compressive
and bond strengths are permitted by building codes.
JUNE, Ym Page 10 section 27THE MID-WEST CONCRETE INDUSTRY BOARD, INC.
eet ay
“APPROVED
STANDARD CONCRETE SPECIFICATION
SECTION 27-UNIT CONCRETE MASONRY
I. PURPOSE AND SCOPE
AL
The purpose of this section is to establish minimum
The Berus for the design, fabrication, handling and
erection of concrete masonry units. Wherever these
Stovisions differ from the project specifications
Pre requirements set forth in the project specifi-
cations shall govern.
It, GENERAL
A.
JUNE, 1973
All other provisions of the M.C.1.B. specifications
att in conflict with this section shall apply to
concrete masonry units.
the following specifications, standards and codes
TeiToaiso govern except where modified herein.
1. American Concrete Institute
a. ACI Committee 531 - Concrete Masonry
Structures - Design and Construction, ACT
Title No. 67-23.
2, American Society for Testing and Materials
a, ASTM 055, Specification for Concrete
Building Brick
b. ASTM C90, Specification for Hollow
Load-Bearing Concrete Masonry Units
c. ASTM C129, Specification for Hollow Non-
foad-Bearing Concrete Masonry Units
. ASTM C140, Methods of Sampling and Testing
Concrete Masonry Units
ec. ASTM C145, Specification for Solid Load-
Bearing Concrete Masonry Units
£, ASTM C150, Specification for Portland
Cement
section 27