Professional Documents
Culture Documents
VII GP-Sprinkler Instalacije
VII GP-Sprinkler Instalacije
_______________________
Potpis odgovornog projektanta
NASLOVNA, Obrazac 1a
A. OPŠTA DOKUMENTACIJA
D. GRAFIČKA DOKUMENTACIJA
R J E Š E NJ E
o imenovanju odgovornog projektanta
OBRAZLOŽENJE:
_________________________________
OBRAZAC 3
IZJAVA
ODGOVORNOG PROJEKTANTA DA JE TEHNIČKA DOKUMENTACIJA IZRAĐENA U
SKLADU SA VAŽEĆIM PROPISIMA
OBJEKAT:
OBJEKAT BIVŠE UPRAVNE GRADE KOŠUTE ZA POTREBE SMJEŠTAJA BIZNIS INKUBATORA I
INOVATIVNOG CENTRA
LOKACIJA:
UP3 40DUP „Industrijska zona (zona I, podzona I2)“, CETINJE
VRSTA I DIO TEHNIČKE DOKUMENTACIJE:
GLAVNI MAŠINSKI PROJEKAT STABILNE INSTALACIJE ZA GAŠENJE POŽARA VODOM
SPRINKLER INSTALACIJA
ODGOVORNI PROJEKTANT:
Aleksandar Strugar dipl.ing.maš., Licenca-Rješenje br. 05-2884/1 od 12.07.2010.godine
(Ime i prezime)
IZJAVLJUJEM
da je ovaj projekat urađen u skladu sa :
- Zakonom o uređenju prostora i izgradnji objekata i podzakonskim aktima donešenim na osnovu
navedenog zakona;
- posebnim propisima koji direktno ili na drugi način utiču na osnovne zahtjeve za objekte;
- pravilima struke i
- urbanističko-tehničkim uslovima.
1. LOKACIJA INSTALACIJE
Stabilna automatska instalacija za gašenje požara vodom – suva sprinkler instalacija
predviđena je za gašenje požara.
2. OPIS INSTALACIJE
Sprinkler instalacija spada među najefikasnije instalacije za gašenje požara. To je
automatska stabilna instalacija za gašenje požara rasprskavajućim mlazom vode, koja u
pripremnom položaju prije aktiviranja ima zatvorene mlaznice, koje se otvaraju na određenoj
povišenoj temperaturi i na taj način započinje automatsko aktiviranje instalacije.
Cjevovodi koji dovode vodu do mlaznica su pod stalnim pritiskom vazduha. Gašenje
požara se vrši određenim brojem mlaznica, zavisno od brzine širenja požara.
Pored gašenja, pri aktiviranju sprinkler instalacije istovremeno vrši i dojavu požara
davanjem alarmnog signala.
3. TIP INSTALACIJE
Usvojena je suva sprinkler instalacija, jer u objektu koji se štiti postoji mogućnost
zamrzavanja vode u cjevovodima. Prostorija za smeštaj opreme obezbijeđena je od niskih
temperatura.
Cjevovodi suve sprinkler instalacije su stalno napunjeni vodom pod pritiskom do klapne
sprinkler ventila, dok je sa gornje strane klapne cjevovod pod vazdušnim pritiskom.
Od trenutka aktiviranja instalacije, počinje da izlazi vazduh, a zatim vrlo brzo dolazi voda do
mjesta gdje se pojavio požar.
ili sistema za dojavu požara, signal ako ventil nije u odgovarajućem položaju.
Tehnološkom šemom je dat princip rada cijele instalacije sa svim svojim elementima.
6. MREŽA CJEVOVODA
Mreža cjevovoda ima osnovnu funkciju da spaja sprinkler mlaznice sa izvorom vode,
osiguravajući osnovne potrebne parametre - količinu vode i pritisak. Vodi se tako da se pokrije
cela površina koja se štiti. Izrađuje se od crnih bešavnih cijevi.
Cijevi se međusobno spajaju zavarivanjem iznad prečnika DN50 a za DN50 i manje prečnike,
spajanje je predviđeno fitingom prema preporukama CEA 4001.
7. SPRINKLER MLAZNICE
Sprinkler mlaznice su važan elemenat sprinkler instalacije, jer vrše njeno aktiviranje. One
se pri određenoj temperaturi otvaraju, a svojom konstrukcijom omogućavaju rasipanje vode tako da
ona ravnomjerno kvasi površinu na kojoj se desio požar.
Sprinkler mlaznica se sastoji od sljedećih delova:
- tijela mlaznice
- zatvarača kojeg na sjedištu drži ampula ispunjena ekspanzivnom tečnošću (ampula puca kada
temperatura oko mlaznice dostigne vrednost od 68 °C)
- raspršivača učvršćenog na vrhu tijela mlaznice
Sprinkler mlaznice se postavljaju sa deflektorom mlaza okrenutim dolje (viseća).
Minimalno dozvoljeni pritisak na sprinkler mlaznicu iznosi pmin = 0,35 bar.
Voda udara u deflektor i raspršava se tako da u kružnoj lepezi pokriva površinu koja se
štiti.
U slučaju da prvo aktivirana sprinkler mlaznica ne uspije da ugasi požar, pa se on proširi, otvaraju
se sljedeće sprinkler mlaznice u neposrednoj blizini mjesta požara.
Uslijed otvaranja mlaznice pada pritisak u gornjoj komori sprinkler ventila, podiže se
klapna u sprinkler ventilu. Voda iz gradske vodovodne mreže protiče ka sprinklerskim mlaznicama.
Preko žljeba u sjedištu sprinkler ventila voda ulazi u cjevovod prema hidrauličkom alarmnom
zvonu.
Alarmno zvono se nalazi na zidu sprinkler ventilske stanice, na visini 2 metra od poda.
Prilikom kretanja vode u cjevovodima, presostat suvog sprinkler ventila, daje impuls koji se
prenosi na centralu za dojavu požara, a ona zatim daje alarmni signal da je instalacija
proradila.
VAŽNO: Prije početka izrade instalacije moraju se pribaviti tehnički uslovi iz JP Vodovod i
kanalizacija, Žabljak, kojim se potvrđuje da je obezbijeđen pritisak u vodovodnoj mreži veći
od minimalnog potrebnog pritiska za sprinkler instalaciju, i da je mreža prečnika DN100 ili
veća. Isti se moraju priložiti u projekat. Dok se ovaj uslov ne ispuni, NE SMIJE SE početi sa
izradom sprinkler instalacije.
Odgovorni projektant:
Aleksandar Strugar, dipl. ing. maš
1. Prije ustupanja izgradnje investitor utvrđuje podobnost izvođača radova, a zatim ustupa
izgradnju objekta nadmetanjem, prikupljanjem ponuda ili neposrednom pogodbom.
2. Investitor i izvođač radova zaključuju Ugovor o izvođenju radova, koji sadrži sledeće:
- rok početka i rok završetka radova,
- način naplate izvršenih radova i ugovorene penale,
- garantni rok,
- nadzor investitora nad izvođenjem postrojenja,
- obaveze izvođača da postrojenje izradi prema odobrenom projektu i u skladu sa
postojećim standardima, tehničkim uputstvima i normama.
3. Izgradnja se može započeti tek kada investitor pribavi odobrenje za izgradnju objekta.
6. Izvođač radova vodi na propisan način građevinski dnevnik i građevinsku knjigu, u koje unosi
podatke o toku i načinu izgradnje objekta.
10. Izvođač radova nema pravo da mijenja tehničku dokumentaciju. Ako uoči nedostatke u njoj,
dužan je da o tome blagovremeno obavijesti investitora.
12. Izvođač radova je dužan da pregleda objekat i utvrdi da li su i kako su prema projektu
izvedeni svi građevinski radovi, koji su u vezi sa izvođenjem ove instalacije.
13. Ukoliko postoje znatna odstupanja, izvođač je dužan da nedostatke pismeno prijavi
investitoru i da traži od investitora prilagođenje projekta.
16. Izvođač je dužan da pruži dokaze o kvalitetu upotrebljenog materijala, opreme i izvedenih
radova, kao i da investitoru omogući kontrolu.
17. U toku izvođenja radova izvođač je dužan da primijećene nedostatke otkloni u datom roku.
19. Za sve naknadne i nepredviđene radove koji nijesu ugovoreni, a investitor zahtijeva da se
izvedu, izvođač će podneti dopunsku ponudu, posle čijeg prihvatanja se radovi mogu izvoditi.
- izvođač nije dužan da otkloni one nedostatke koji su nastali kao posledica nestručnog
rukovanja i upotrebe, odnosno nenamjenskog korišćenja instalacije.
Ovi pogodbeni uslovi su sastavni deo glavnog projekta i u svemu su obavezni za izvođača
radova, sem ukoliko nije drugačije regulisano ugovorom između investitora i izvođača.
25. Svi ostali odnosi između investitora i izvođača radova regulišu se ugovorom.
2.1.1. Cijelu instalaciju treba montirati prema ovom projektu po dobijanju saglasnosti od
nadležnog organa.
2.1.2. Sve cijevi, nosače cevovoda i opremu prije montaže treba besprekorno očistiti i zaštititi
osnovnom bojom.
2.1.3. Proveriti nečistoću cijevi i sa unutrašnje strane, te ukoliko nijesu dovoljno čiste, očistiti
ih čeličnom četkom.
2.1.4. Svi elementi cijevi, armatura i druga oprema prije ugradnje treba da posjeduje
atestiranu dokumentaciju i to cijevi na 16 bara, a armaturu na 10 bara.
2.1.6. Posle završetka kompletne montaže izvršiti probu instalacije na hidraulični pritisak.
Instalaciju treba ispitati na pritisak veći za 50% od radnog pritiska.
2.1.8. Po završetku probe obavezno napraviti zapisnik koji se čuva kao trajni dokument.
2.1.9. Posle završene montaže i probe instalacije na hidraulični pritisak, instalaciju ofarbati
završnom bojom.
2.2.6. Proba funkcionalnosti kompletnog sistema vrši se na period do jedne godine i to sve u
funkciji ostalog održavanja.
2.3.1. Važno je da voda u instalaciji bude čista (bez mehaničkih nečistoća) kako ne bi došlo
do začepljenja klapni i dr.
2.3.2. Čišćenje instalacije obaviti godišnje.
2.3.3. Sve ventile podmazati i spojeve koji cure dotegnuti i prekontrolisati.
2.3.4. Staklene ampule obavezno očistiti od prljavštine jednom u tri meseca.
Odgovorni projektant:
Aleksandar Strugar dipl. ing. maš.
2.4. Provera kvaliteta izvođenja spojeva vrši se putem predviđenog propisanog ispitivanja
instalacije.
2.6. Za sve cjevovode kod kojih postoji opasnost od smrzavanja, predviđeno je prateće
grejanje.
3.1. Izvođač radova je obavezan da uradi poseban elaborat o uređenju gradilišta i radu
na njemu.
3.3. Radna organizacija je obavezna da osam dana prije početka radova obavijesti
nadležni organ o početku radova. Radna organizacija je obavezna da izradi normativna akta
iz oblasti zaštite na radu, program za obučavanje i vaspitanje radnika iz oblasti zaštite na
radu, ispitivanjima i održavanju oruđa, uređaja i alata, kao i program mjera za unapređenje
zaštite na radu i dr. Radna organizacija je obavezna da izvrši obučavanje radnika iz materije
o zaštiti na radu i da ih upozna sa uslovima rada, opasnostima i štetnostima u vezi sa radom,
te da obavi proveru sposobnosti radnika za samostalan i bezbjedan rad.
4. ZAKLJUČAK - IZJAVA
Odgovorni projektant:
Aleksandar Strugar, dipl. ing.maš.
Pri izradi Glavnog mašinskog projekta stabilne instalacije za gašenje požara vodom –
Sprinkler instalacije, kao osnovni propis, korišćen je CEA 4001 propis za sprinkler
instalacije (u nedostatku naših propisa)
- Zakon o izgradnji i finansiranju investicionih objekata, Sl. list R. Crne Gore br.
29/90, 33/90 i 46/98
- Zakon o zaštiti na radu, Sl. list R. Crne Gore br. 35/98.
- Pravilnik o zaštiti na radu u građevinarstvu Sl. List SFRJ br. 42/1968 i 45/68.
- Pravilnik o sredstvima lične zaštite na radu i ličnoj zaštitnoj opremi Sl. List
SFRJ br. 35/69.
- JUS C.T3.072.
- JUS C.T3.061.
- JUS C.T3.035
- JUS C.T3.040
- JUS C.T3.042
Odgovorni projektant:
Aleksandar Strugar, dipl.ing.maš.
KLASIFIKACIJA
Hidraulički parametri
Zbog neravnomjernosti rada pojedinih mlaznica na kojima pritisak vode može da varira
tako da je i potrošnja vode veća usvojeno je u skladu sa propisom povećanje kapaciteta za
40% tako da je mjerodavan kapacitet za dimenzionisanje.
Minimalni potrebni pritisak na mlaznici je 0,35 [bar]. Brzina vode ne smije prelaziti 10
[m/s] u cijevnoj mreži i 6 [m/s] u armaturi. Pritisak u cjevovodima ne smije prelaziti 10 [bar].
GLAVNI MAŠINSKI PROJEKAT STABILNE INSTALACIJE ZA GAŠENJE POŽARA 1
SPRINKLER: OBJEKAT BIVŠE UPRAVNE ZGRADE KOŠUTE ZA POTREBE
SMJEŠTAJA BIZNIS INKUBATORA I INOVATIVNOG CENTRA B.6
Qs = k × H [l/s]
gde je:
k - koeficijent isticanja mlaznice
H - pritisak ispred mlaznice, [m]
60
Odnosno, 60= k ⋅ 0,35 ⇒=k = 101, 42 ⇒ = k 80
0,35
Prilikom izbora sprinklera treba uzeti u obzir geometrijske dimenzije prostorije kao i
druge građevinske uslove, zatim postojeći pritisak u mreži cjevovoda i potrebnu količinu vode
Izabrana je mlaznica: “Spray”, proizvod »Tyco«, sprinkler mlaznica P=12 m2, T=68°C, R1/2
(DN 15).
ΔP 1 +ΔP 2 po HAZEN-WILLIAMS-u:
IZBOR KOMPRESORA
Odgovorni projektant:
Aleksandar Strugar, dipl.ing.maš.
PUMP MOTOR DIMENSIONS (mm) WEIGHT kg PUMP MOTOR DIMENSIONS (mm) WEIGHT kg
TYPE ELECTRIC TYPE ELECTRIC
33SV1/1A 2,2 90 489 268 178 164 137 16 52 68 33SV7 18,5 160 994 494 313 350 240 25 84 195
33SV1 3 100 489 288 178 164 137 16 52 71 33SV8/2A 18,5 160 1069 494 313 350 240 25 88 199
33SV2/2A 4 112 564 319 197 164 154 16 56 82,5 33SV8/1A 18,5 160 1069 494 313 350 240 25 88 199
33SV2/1A 4 112 564 319 197 164 154 16 56 82,5 33SV8 22 180 1069 494 313 350 240 25 89 210
33SV2 5,5 132 584 375 214 300 168 16 61 98,5 33SV9/2A 22 180 1144 494 313 350 240 25 93 214
33SV3/2A 5,5 132 659 375 214 300 168 16 65 103 33SV9/1A 22 180 1144 494 313 350 240 25 93 214
33SV3/1A 7,5 132 659 367 256 300 191 16 65 121 33SV9 22 180 1144 494 313 350 240 25 93 214
33SV3 7,5 132 659 367 256 300 191 16 65 121 33SV10/2A 22 180 1219 494 313 350 240 25 97 218
33SV4/2A 7,5 132 734 367 256 300 191 16 69 125 33SV10/1A 30 200 1219 657 402 400 317 25 104 319
33SV4/1A 11 160 769 428 256 350 191 16 73 143 33SV10 30 200 1219 657 402 400 317 25 104 319
33SV4 11 160 769 428 256 350 191 16 73 143 33SV11/2A 30 200 1294 657 402 400 317 40 118 333
33SV5/2A 11 160 844 428 256 350 191 16 77 147 33SV11/1A 30 200 1294 657 402 400 317 40 118 333
33SV5/1A 11 160 844 428 256 350 191 16 77 147 33SV11 30 200 1294 657 402 400 317 40 118 333
33SV5 15 160 844 494 313 350 240 16 77 179 33SV12/2A 30 200 1369 657 402 400 317 40 122 337
33SV6/2A 15 160 919 494 313 350 240 16 81 183 33SV12/1A 30 200 1369 657 402 400 317 40 122 337
33SV6/1A 15 160 919 494 313 350 240 25 81 183 33SV12 30 200 1369 657 402 400 317 40 122 337
33SV6 15 160 919 494 313 350 240 25 81 183 33SV13/2A 30 200 1444 657 402 400 317 40 127 342
33SV7/2A 15 160 994 494 313 350 240 25 84 186 33SV13/1A 30 200 1444 657 402 400 317 40 127 342
33SV7/1A 18,5 160 994 494 313 350 240 25 84 195
33sv-2p50-en_b_td
1
33SV SERIES
OPERA TING CHARACTERISTIC
OPERATING CHARACTERISTICSS AT 50 Hz, 2 POLES
AT
33SV ∼ 2900 [rpm] ISO 9906 - Annex A
H [ft]
12
280 12/1A
12/2A 900
260 11
11/1A
11/2A 800
240 10
10/1A
220 10/2A
9 700
9/1A
200 9/2A
8
8/1A 600
180 8/2A
7
160 7/1A
7/2A 500
6
140 6/1A
6/2A
120 5 400
5/1A
5/2A
100 4
4/1A 300
80 4/2A
3
3/1A 200
60 3/2A
2
40 2/1A
2/2A 100
1
20
1/1A
0 0
3 80
Pp [kW]
η [%]
η P2 1
2 60
kW/stage P2 /1
1 40
8
NPSH [m]
NPSH [ft]
20
4
10
0 0
05117_B_CH
3
0 5 10 15 20 25 30 35 Q 40
[m /h]
These performances are valid for liquids with density ρ = 1.0 Kg/dm3 and kinematic viscosity ν = 1 mm2/sec.
2
B.7 PREDMJER I PREDRAČUN RADOVA
Jed.
R.B. OPIS Kol. Jed.cijena Uk. iznos
mjere
SPRINKLER INSTALACIJA
1.1. Isporuka i ugradnja džokej pumpe tip 33SV2/1A, proizvod
LOWARA ili ekvivalent sa karakteristikama:
Q= 10,5 lit/sec
H = 22,51 m VS
N = 4 kW - 380-400V/50Hz/3ph kom. 1
1.5 Isporuka i ugradnja alarmnog zvona ulaz 3/4", izlaz 1" komplet sa
fitingom, sa odvajačem nečistoče 3/4", proizvod TYCO ili ekviv. kom. 1
Str. 1
Jed.
R.B. OPIS Kol. Jed.cijena Uk. iznos
mjere
1.15 Sigurnosni ventil za vazduh DN 20 pritisak otvaranja 5 bara kom. 1
Sigurnosni ventil za vodu DN 20 pritisak otvaranja 6 bara kom. 1
1.32 Isporuka i ugradnja fitinga crnog JUS M.B6.821 hamburški luk 90°
DN100 (ø114.3 x 3.6 mm) kom. 16
T račva DN100 (ø114.3 x 3.6 mm) kom. 8
DN80 (ø88.9 x 3.6 mm) kom. 5
DN65 (ø76.1 x 3.6 mm) kom. 4
DN50 (ø60.3 x 3.2 mm) kom. 5
Str. 2
Jed.
R.B. OPIS Kol. Jed.cijena Uk. iznos
mjere
1.34 Isporuka i ugradnja T račvi
DN40 kom. 58
DN25 kom. 275
UKUPNO :
PDV 19%:
U K U P N O SA PDV-OM:
Odgovorni projektant:
Aleksandar Strugar dipl.ing.maš.
Str. 3
C. PRILOZI
SPRINKLER: OBJEKAT BIVŠE UPRAVNE ZGRADE KOŠUTE ZA POTREBE
SMJEŠTAJA BIZNIS INKUBATORA I INOVATIVNOG CENTRA C.1
a) Trokraku slavinu poz.2 postaviti u položaj (1) sve dok ne odjekne ton alarma,
zatim ponovo postaviti slavinu u položaj (3). Isprazniti cjevovod
pritiskom na dugme (Y).
a) Svakodnevno kontrolisati
b) Nedeljno kontrolisati
- demontirati sve ventile, zasune, brzi otvarač i alarmni ventil i pregledati ih,
- izvršiti probno aktiviranje uređaja insceniranjem požara ispod sprinklera mlaznice.
Odgovorni projektanti:
Aleksandar Strugar, dipl.ing.maš.
Tables A1, A.2 and A.3 contain lists of minimum hazard classification. They shall also be used as guidance
for occupancies not specifically mentioned.
109
Table A.2 - Ordinary Hazard occupancies - continued
Ordinary Hazard group
Rubber and
plastics
NOTE 1: Where there is painting, large amount of flammable liquids or other similar high fire load areas, they
shall be treated as OH3.
NOTE 2 : Warehouses generally and high rise buildings according to annex E in order to ensure flexibility.
NOTE 3: If combustible insulated panels are used, consideration for a possible higher classification should be
taken.
110
ST1 Storage shall be confined to blocks not exceedingNone
150 m2 in plan
area (see note 2).
ST2 Aisle between rows shall be not less than 2,4 m None
wide.
ST3 Storage shall be confined to blocks not exceedingNone
150 m2 in plan area (see note 2).
ST4 Aisle separating rows are not less than 1,2m wide. Intermediate sprinklers are recommended.
(1)
Aisle separating rows are less than 1,2m wide. Intermediate sprinklers are required
ST5 Either the aisle separating rows shall be not less Intermediate sprinklers are recommended.
than 1,2m wide or storage blocks shall be not (1)
more than 150m2 in plan area (see note 2).
ST6 Either the aisle separating rows shall be not less Intermediate sprinklers are required or, if
than 1,2m wide or storage blocks shall be not this is impossible, continuous non-
more than 150 m2 in plan area (see
note 2). combustible full height vertical bulkheads
fitted longitudinally and transversally within
each shelf.
NOTE 1: when the ceiling clearance is greater than 4m, in-rack
sprinklers shall be used. NOTE 2: storage blocks shall be separated by
aisles not less than 2,4m wide.
If the height of the concealed space at roof and floor exceeds 0,8m, measured between the
underside of the roof and the top of the suspended ceiling or between the floor and the
underside of the raised floor, these spaces shall be sprinkler protected.
If the height of the concealed space at roof and floor is no greater than 0,8m, the spaces shall be
sprinkler protected only if they contain combustible materials or are constructed with combustible
materials. Electrical cables with voltage less than 250V, single phase, with a maximum of 15 cables
per tray, are allowed.
The protection in the concealed space shall be to LH when the main hazard class is LH, and OH1 in all
other cases. See 15.3 for the pipework arrangement.
6.1 General
The design density shall be not less than the appropriate value given in this clause when all the
ceiling or roof sprinklers in the room concerned, or in the area of operation, whichever is the fewer
plus any in-rack sprinklers and supplementary sprinklers, are in operation. The minimum requirements
for design density and area of operation for LH, OH and HHP classes are given in Table 4. For HHS
systems, 6.2 shall be applied.
37
NOTE: for pre-calculated systems, the correct design criteria are assumed to be achieved by
the application of water supply and piping requirements elsewhere in these rules.
Table 4: Design density and area of operation for LH, OH and HHP
6.2.1 General
The type of protection and determination of the design density and area of operation are dependent on
the combustibility of the product (or mix of products) and its packaging (including the pallet) and the
method and height of storage.
Specific limitations apply to the various types of storage methods as detailed in Clause 5.
Table 5 specifies the appropriate design density and area of operation according to the category
and maximum permitted storage height for the various types of storages with roof or ceiling
protection only. More specifically, the storage heights indicated in the table are considered the
maximum for efficient sprinkler protection where sprinklers are only provided at the roof or ceiling.
Storage heights exceeding these limits require that intermediate levels of in-rack sprinklers be provided
as per 6.2.3 below. The distance between the maximum permitted storage height and the roof or ceiling
sprinklers should not exceed 4m.
NOTE: storage height, building height and ceiling clearance (the vertical distance between the roof
or ceiling sprinklers and the top of the storage) are all significant variables contributing to
the effectiveness and required design density of sprinkler protection.
6.2.3.1 Where more than 50 intermediate level sprinklers are installed in the racks, roof or ceiling
sprinklers shall be installed with a separate set of control valves.
6.2.3.2 The design density for the roof or ceiling sprinklers shall be a minimum of 7,5mm/min over an area
of operation of 260 m². If goods are stored above the highest level of intermediate protection,
the design criteria for the roof or ceiling sprinklers shall be taken from Table 6.
38
800-381-9312
Technical Services +1-401-781-8220
www.tyco-fire.com
FIGURE 1A
DN100 MODEL DP-V DRY PIPE VALVE
— ASSEMBLY —
TFP1090
Page 3 of 22
NO. DESCRIPTION QTY. REP. PART NO. DESCRIPTION QTY. REP. PART NO. DESCRIPTION QTY. REP. PART
1 Valve Body . . . . . . . 1 NR 5 Socket Head Cap 8 Hex Head Cap Screw
2 Air and Water Screw 5/8-11 UNC x 1" . . . 6 CH
Seat . . . . . . . . . . . . 1 NR 3/8-16 UNC x 1" . . . 8 NR 9 Clapper . . . . . . . . . . 1 See (a)
3 Water Seal 6 Handhole Cover . . . 1 NR 10 Clapper Facing . . . . 1 See (a) or (b)
O-Ring . . . . . . . . . . 1 NR 7 Handhole Cover 11 Clapper Facing
4 Air Seal O-Ring . . . . 1 NR Gasket . . . . . . . . . . 1 See (b) Retaining Plate . . . . 1 See (a)
12 Socket Head Cap
Screw
1/4-20 UNC x 1/2". . 9 See (a)
13 Clapper Hinge Pin. . 1 See (a)
14 Reset Knob . . . . . . 1 See (c)
14 15 Reset Spring . . . . . 1 See (c)
16 Reset Bushing . . . . 1 See (c)
9 17 Reset Bushing
15 O-Ring. . . . . . . . . . . 1 See (b) or (c)
18 Reset Plunger
10
CLAPPER 16 O-Ring. . . . . . . . . . . 1 See (b) or (c)
ASSEMBLY 19 Reset Plunger . . . . . 1 See (c)
11 RESET 20 Reset Latch
17 PLUNGER Subassembly . . . . . 1 See (c)
PARTS 21 Dow Corning FS3452
12 Flourosilicone
18, 21
Grease, 1.5 g . . . . . 1 See (b) or (c)
20
REPLACEMENT PARTS
NO. DESCRIPTION P/N
(a) Clapper Assembly
Includes Items 9-13 . . . 92-309-2-603
(b) Repair Parts Kit
Includes Items
7, 10, 17, 18, 21 . . . . . . 92-309-1-604
(c) Reset Plunger Parts Kit
Includes Items 14-21 . . 92-310-1-405
2
4 1
7
6
5
3
13
FIGURE 1B
DN150 MODEL DPV-1 DRY PIPE VALVE
— ASSEMBLY —
TFP1090
Page 4 of 22
100
0,08
12,8 3,1 - 3,7
DN
150
14,1 3,4 - 4,0 0,06
DN
15,5 3,8 - 4,3
0,04
16,0 4,1 - 4,6
0,03
TABLE A
SYSTEM AIR PRESSURE
—REQUIREMENTS —
0,02
Data Dry Pipe Valve are suitable for use with grooved
Approvals The DN100 and DN150, Model DPV-1 end pipe couplings that are listed or
The DN100 and DN150 TYCO Dry Pipe Valves are for vertical instal- approved for fire protection system
Model DPV-1 Dry Pipe Valves with lations (flow going up), and they are service.
or without the TYCO Model ACC-1 rated for use at a maximum service Threaded port connections are per
Dry Pipe Valve Accelerator are FM, pressure of 16 bar (VdS approval ISO 7/1 to readily accept the trim
LPCB, VdS, and CE Approved with range of supply pressure is 3 to 16 arrangement detailed in Figures 8
European Conformity Valve Trim bar). The nominal pressure loss ver- through 15.
(Ref. Figures 8 thru 15). sus flow is shown in Figure 2, and the
valve take-out dimensions are shown Components of the DN100
For more information on Agency Model DPV-1 Valve are shown in
in Figure 3.
Approvals, contact Tyco Fire Figure 1A, and components of the
Protection Products at the following Flanged connections are drilled per DN150 Model DPV-1 Valve are shown
office: ISO 2084 (PN10/16) or ANSI B16.1 in Figure 1B. The Body and Handhole
(Class 125). The grooved outlet con-
Kopersteden 1 Cover are ductile iron. The Handhole
nections, as applicable, are cut in
7547 TJ Enschede Cover Gasket is neoprene, and the
accordance with standard groove Clapper Facing is EPDM. The Air/
The Netherlands
specifications for steel pipe. They Water Seat Ring is brass, the Clapper
Tel: +31-(0)53-428-4444
Fax: +31-(0)53-428-3377
TFP1090
Page 5 of 22
CLAPPER CLAPPER
ASSEMBLY ASSEMBLY
IN SET FULLY OPEN
POSITION
AIR
SUPPLY
PORT
CLAPPER LATCH
PIVOTS TO ALLOW
CLAPPER ASSEMBLY
TO FULLY OPEN
ALARM PORT
OPEN TO
WATER ATMOSPHERE
SUPPLY ALARM PORT
PRESSURE WATERFLOW
& ALARM TO ALARM
CLAPPER
TEST PORT
ASSEMBLY
FROM FROM
WATER SUPPLY AIR WATER SUPPLY
SEAT
FIGURE 4A FIGURE 4C
SET POSITION WATER OPERATED POSITION
SEAT ALARM
PORT
DRAIN FROM
DRAIN FROM SYSTEM
SYSTEM VALVE INTERMEDIATE COMPLETE
WATERWAY CHAMBER PUSH HERE
FIGURE 4B TO RESET
VALVE
SET POSITION
INTERMEDIATE
CHAMBER RESET
KNOB
CLAPPER
ASSEMBLY
LATCHED
RESET
OPEN
ASSEMBLY CLAPPER
LATCH
PIVOTS TO
CLAPPER UNLATCH
LATCH CLAPPER
LOW ASSEMBLY
BODY
DRAIN
PORT MAIN CLAPPER
DRAIN ASSEMBLY
PORT RESEATED
FIGURE 4D FIGURE 4E
DRAIN POSITION RESET POSITION
FIGURE 4 (1 of 2)
DN100 MODEL DPV-1 DRY PIPE VALVE
— SET AND OPEN POSITIONS —
TFP1090
Page 7 of 22
CLAPPER LATCH
PIVOTS TO ALLOW
AIR CLAPPER ASSEMBLY
SUPPLY TO FULLY OPEN
PORT
ALARM PORT
OPEN TO
CLAPPER ATMOSPHERE
ASSEMBLY
IN SET
POSITION WATER
SUPPLY
PRESSURE
& ALARM
TEST PORT ALARM PORT
WATERFLOW
CLAPPER TO ALARM
ASSEMBLY AIR
FROM SEAT FROM
WATER SUPPLY WATER SUPPLY
FIGURE 4A FIGURE 4C
SET POSITION WATER OPERATED POSITION
SEAT ALARM
PORT DRAIN FROM
DRAIN FROM SYSTEM
SYSTEM INTERMEDIATE VALVE COMPLETE
CHAMBER WATERWAY
FIGURE 4B PUSH HERE
TO RESET
SET POSITION
VALVE
INTERMEDIATE
CLAPPER CHAMBER
ASSEMBLY RESET
LATCHED KNOB
OPEN RESET
ASSEMBLY
CLAPPER
LATCH
PIVOTS TO
LOW
UNLATCH
BODY
CLAPPER
DRAIN
ASSEMBLY
PORT
CLAPPER
LATCH CLAPPER
MAIN ASSEMBLY
DRAIN RESEATED
PORT
WATER SUPPLY WATER SUPPLY
SHUT OFF SHUT OFF
FIGURE 4D FIGURE 4E
DRAIN POSITION RESET POSITION
FIGURE 4 (2 of 2)
DN150 MODEL DPV-1 DRY PIPE VALVE
— SET AND OPEN POSITIONS —
TFP1090
Page 8 of 22
FIGURE 5
MODEL ACC-1 DRY PIPE VALVE ACCELERATOR
— ASSEMBLY —
TFP1090
Page 9 of 22
DIFFERENTIAL
CHAMBER
PILOT
CHAMBER
SPRING
ANTI-FLOOD VALVE
BALL FLOAT
1/2" NPT INLET
PILOT CHAMBER
INLET PORT RELIEF VALVE
INLET CHAMBER EXHAUST VALVE
1/2" NPT OUTLET OUTLET CHAMBER
FIGURE 6
MODEL ACC-1 DRY PIPE VALVE ACCELERATOR
— IN SET POSITION —
PLUNGER
LATCH
FROM
SYSTEM
PIPING
RELIEF PORT
TO DRY
PIPE VALVE
INTERMEDIATE
CHAMBER
FIGURE 7
MODEL ACC-1 DRY PIPE VALVE ACCELERATOR
— IN TRIPPED POSITION —
TFP1090
Page 10 of 22
Installation Valve Setting Step 9. Verify that there is not any air
discharging from the Automatic Drain
7
28 24
24
1
32
31 9 9
29
36 20 35
11 35
19 11
12
21 20
13
29
22 9
2 14
33 11
24 8 35 17 4
24
6
28 10
25
15 34
32
27
30 16
20
20 25
33 3
5
18
23 26
FIGURE 8
EUROPEAN CONFORMITY
MODEL DPV-1 DRY PIPE VALVE TRIM with THREE-WAY ALARM TEST VALVE
without MODEL ACC-1 ACCELERATOR
— DN100 —
TFP1090
Page 15 of 22
6
15
32
36 31
21 33
16
32 5
7 22
25 29
31
11 9 18 10
35 12
30 24
26
11 19 37
23
2 9
33
8 35 21
25 29
28 27
17
34
9 3
1
25
30
13 20
35 11
14 25
FIGURE 9
EUROPEAN CONFORMITY
MODEL DPV-1 DRY PIPE VALVE TRIM with THREE-WAY ALARM TEST VALVE
without MODEL ACC-1 ACCELERATOR
— DN150 —
TFP1090
Page 16 of 22
25
29
29
12
7 38
28 25
34
1
32
31 9 9
29
39 20 37
11 37
36 11
13
21 20
14
29
23 9
2 15
22 33 11
8 37 19 4
25
28 10
26
35
27
18
20
26
30 3
24
34
16 17
2
34
33 6
5
FIGURE 10
EUROPEAN CONFORMITY
MODEL DPV-1 DRY PIPE VALVE TRIM with STANDARD ALARM TEST VALVE
without MODEL ACC-1 ACCELERATOR
— DN100 —
TFP1090
Page 17 of 22
39
36 23
32 29
7 22
25 34
31 31
11 9 19 10
16 6
30
13 34 34
37 29
12 34
38
30 33
26
24 11 2
2 9 5
33 18
8 37 21
25 29
28 27
17
35
9 3
1
25
30
14 20
37 11
15 25
FIGURE 11
EUROPEAN CONFORMITY
MODEL DPV-1 DRY PIPE VALVE TRIM with STANDARD ALARM TEST VALVE
without MODEL ACC-1 ACCELERATOR
— DN150 —
TFP1090
Page 18 of 22
39 13
24 7 11
27
27 27
1
34 26
33 9 24 9
31
40
38 22 37
12 24 37
21 12
13
23 2 22
14
31
25 9
2 15
35 12
27 8 37 18 4
27
6
20 10
28
16 36
34
30
32 17
22
22 28
35 3
5
19
26 29
FIGURE 12
EUROPEAN CONFORMITY
MODEL DPV-1 DRY PIPE VALVE TRIM with THREE-WAY ALARM TEST VALVE
with MODEL ACC-1 ACCELERATOR
— DN100 —
TFP1090
Page 19 of 22
13
27 11 6
38
16
26 33
24 37
39 32
22 34
24 2 17
33 5
7 21 23
27 24
32
12 9 19 10
36 13
31 26
28
12 20 40
25
2 9
34
8 36 22
27 30
29
18
35
9 3
1
27
31
14 21
36 12
15 27
FIGURE 13
EUROPEAN CONFORMITY
MODEL DPV-1 DRY PIPE VALVE TRIM with THREE-WAY ALARM TEST VALVE
with MODEL ACC-1 ACCELERATOR
— DN150 —
TFP1090
Page 20 of 22
29
32
32 14
43 13
25 7 41 11
29
37 29
1
35 27
34 9 25 9
32
44
42 22 40
12 25 40
39 12
14
23 2 22
15
32
26 9
2 16
24 36 12
8 40 20 4
29
21 10
30
38
31
19
22
30
33 3
28
37
17 18
2
37
36 6
5
FIGURE 14
EUROPEAN CONFORMITY
MODEL DPV-1 DRY PIPE VALVE TRIM with STANDARD ALARM TEST VALVE
with MODEL ACC-1 ACCELERATOR
— DN100 —
TFP1090
Page 21 of 22
14
28 11
43
27
25 42
44
24 2 39 25
35 32
7 21 23
28 37
34 34
12 9 20 10
17 6
33
1 37 37
40 25
13 37
41
33 36
29
26 12 2
2 9 5
36 19
8 40 22
28 31
30
18
38
9 3
1
28
33
15 21
40 12
16 28
FIGURE 15
EUROPEAN CONFORMITY
MODEL DPV-1 DRY PIPE VALVE TRIM with STANDARD ALARM TEST VALVE
with MODEL ACC-1 ACCELERATOR
— DN150 —
TFP1090
Page 22 of 22
P/N XX—X—XX—XX—X—XX
SWITCH
TRIM
0 NONE
SIZE 88 EUR/FM w/ Three-Way Alarm Control Valve
1 PS10-1
4 101,6 mm 89 EUR/FM w/ Standard Alarm Test Valve
6 168,3 mm
7 165,1 mm
ACCESSORIES
TABLE D
MODEL DPV-1 DRY PIPE VALVE WITH EUROPEAN CONFORMITY VALVE TRIM
— FULLY ASSEMBLED —
Ordering Accessories
Specify (“description”) and P/N (from
Procedure below).
“Supervisory Switch” for
Contact your local distributor for avail- accelerator control valve . . . . . . P/N CEDPV1ASS
ability. When placing an order, indicate “Supervisory Switch” for
the full product name and Part Number water motor alarm
(P/N). control valve. . . . . . . . . . . . . . . . P/N CEDPV1ASS
Model DPV-1 Dry Pipe Valve with “Air Pressure Relief Valve
factory-set at 3,1 bar”. . . . . . . . P/N 92-343-1-020
Assembled European
Conformity Valve Trim “Model WMA-1 Water Motor Alarm
Specify: Fully Assembled Model DPV-1 with red finish gong”. . . . . . . . . P/N 52-630-1-021
Dry Pipe Valve with European “A through Z Labels” for
Conformity Valve Trim, P/N (Table D). attaching to valve trim
components. . . . . . . . . . . . . . . P/N WS00000033
Copyright © 2005, 2012 Tyco Fire Protection Products. All rights reserved.
Appendix A of TFP1090 (02/2012)
Summary Instructions (If problems occur, consult full document)
DN100, Model DPV-1 Dry Pipe Valve with Three-Way Alarm Test Valve,
without Model ACC-1 Accelerator
G C D P
J
H
N
K
465 mm
M
B
E
F
I. Normal Conditions III. Removing System From Service Step 7. Partially open the Main Control
• The Main Control Valve (A) is opened Step 1. Close the Main Control Valve Valve (A), and then slowly close the
and locked. (A), close the Air Supply Control Valve Main Drain Valve (F).
• The sprinkler system is filled with air (K), and place the Three-Way Alarm Step 8. Fully open the Main Control
and is pressurized. Control Valve (E) in the closed position. Valve (A) and lock it open.
• The Main Drain Valve (F), and Low Step 2. Drain the system with the Main Step 9. Reset the fire alarm panel and
Body Drain Valve (L) are closed. Drain Valve (F) and by opening all auxil- notify the central alarm station.
iary drain valves in the system to make
• The Three-Way Alarm Control Valve sure that cross-mains and branch lines V. Weekly Test
(E) is in the open position. are drained. Important: Prior to closing any valves
• The Pressure Gauge Valves (B) and or activating any alarms, notify local se-
IV. Placing the System Back in curity guards and the central alarm sta-
(C) are open.
Service tion if applicable.
• The Pressure Switch Valve (J) is Step 1. Close the auxiliary drain valves
open. after water ceases to discharge, and Step 1. Place the Three-Way Alarm
leave the Main Drain Valve (F) open. Control Valve (E) in the test position,
• The Air Supply Control Valve (K) is verify that the alarm signal created by
open. Step 2. Place the Three-Way Alarm the Waterflow Pressure Alarm Switch
• System Air Pressure Gauge (G) Control Valve (E) in the open position. (M) is visible at the fire panel. If appli-
reads downstream air pressure. Step 3. Replace the sprinklers that cable, check the sound of the Water
have operated and the sprinklers close Motor Alarm — it must be clear and
• Water Supply Pressure Gauge (H) steady.
reads the upstream water pressure. to the fire.
Step 4. Push down on the reset knob Step 2. Place the Three-Way Alarm
II. Operation Control Valve (E) in the open position
When one or more sprinklers are acti- (P) to allow the Dry Pipe Valve (D) to
re-seat. and verify that the normal supply and
vated, air pressure is reduced down- system pressures are restored. If the
stream of the Dry Pipe Valve. When the Step 5. Via the Air Supply Control Valve supply pressure is below the normal,
air pressure is sufficiently reduced, the (K), pressurize the system with air to 0,7 use the instructions from the water sup-
water pressure overcomes the differen- bar, and then open and close each aux- ply to obtain the usual pressure.
tial holding the Dry Pipe Valve closed iliary drain valves in the system piping
and the Dry Pipe Valve opens to per- to drain any remaining water in trapped Step 3. Close the Pressure Switch
mit water flow into the system piping sections. Also, partially open the Low Valve (J) and verify operation of the low
and to be discharged from any open Body Drain Valve (L) to assure that the air pressure Alarm Switch (N).
sprinklers. Also, with the Dry Pipe riser is completely drained. Close the Step 4. Return the Pressure Switch
Valve open, water flows through the Low Body Drain Valve (L) as soon as Valve (J) to the normally open position
Alarm Port at the rear of the Dry Pipe water ceases to discharge. after verifying that the alarm signal is
Valve to actuate the Waterflow Pressure visible at the fire panel.
Alarm Switch (M) and, as applicable, Step 6. Open the Air Supply Control
the Water Motor Alarm. Valve (K) to restore the system to the
normal system air pressure.
Appendix B of TFP1090 (02/2012)
Summary Instructions (If problems occur, consult full document)
DN150, Model DPV-1 Dry Pipe Valve with Three-Way Alarm Test Valve,
without Model ACC-1 Accelerator
G C D
J
P N
K
510 mm
H
M
L
B
E
I. Normal Conditions III. Removing System From Service Step 7. Partially open the Main Control
• The Main Control Valve (A) is opened Step 1. Close the Main Control Valve Valve (A), and then slowly close the
and locked. (A), close the Air Supply Control Valve Main Drain Valve (F).
• The sprinkler system is filled with air (K), and place the Three-Way Alarm Step 8. Fully open the Main Control
and is pressurized. Control Valve (E) in the closed position. Valve (A) and lock it open.
• The Main Drain Valve (F), and Low Step 2. Drain the system with the Main Step 9. Reset the fire alarm panel and
Body Drain Valve (L) are closed. Drain Valve (F) and by opening all aux- notify the central alarm station.
iliary drain valves in the system to make
• The Three-Way Alarm Control Valve sure that cross-mains and branch lines V. Weekly Test
(E) is in the open position. are drained. Important: Prior to closing any valves
• The Pressure Gauge Valves (B) and or activating any alarms, notify local se-
IV. Placing the System Back in curity guards and the central alarm sta-
(C) are open.
Service tion if applicable.
• The Pressure Switch Valve (J) is Step 1. Close the auxiliary drain valves
open. after water ceases to discharge, and Step 1. Place the Three-Way Alarm
leave the Main Drain Valve (F) open. Control Valve (E) in the test position,
• The Air Supply Control Valve (K) is verify that the alarm signal created by
open. Step 2. Place the Three-Way Alarm the Waterflow Pressure Alarm Switch
• System Air Pressure Gauge (G) Control Valve (E) in the open position. (M) is visible at the fire panel. If appli-
reads downstream air pressure. Step 3. Replace the sprinklers that cable, check the sound of the Water
have operated and the sprinklers close Motor Alarm — it must be clear and
• Water Supply Pressure Gauge (H) steady.
reads the upstream water pressure. to the fire.
Step 4. Push down on the reset knob Step 2. Place the Three-Way Alarm
II. Operation Control Valve (E) in the open position
When one or more sprinklers are acti- (P) to allow the Dry Pipe Valve (D) to
reseat. and verify that the normal supply and
vated, air pressure is reduced down- system pressures are restored. If the
stream of the Dry Pipe Valve. When the Step 5. Via the Air Supply Control Valve supply pressure is below the normal,
air pressure is sufficiently reduced, the (K), pressurize the system with air to 0,7 use the instructions from the water sup-
water pressure overcomes the differen- bar, and then open and close each aux- ply to obtain the usual pressure.
tial holding the Dry Pipe Valve closed iliary drain valves in the system piping
and the Dry Pipe Valve opens to per- to drain any remaining water in trapped Step 3. Close the Pressure Switch
mit water flow into the system piping sections. Also, partially open the Low Valve (J) and verify operation of the low
and to be discharged from any open Body Drain Valve (L) to assure that the air pressure Alarm Switch (N).
sprinklers. Also, with the Dry Pipe riser is completely drained. Close the Step 4. Return the Pressure Switch
Valve open, water flows through the Low Body Drain Valve (L) as soon as Valve (J) to the normally open position
Alarm Port at the rear of the Dry Pipe water ceases to discharge. after verifying that the alarm signal is
Valve to actuate the Waterflow Pressure visible at the fire panel.
Alarm Switch (M) and, as applicable, Step 6. Open the Air Supply Control
the Water Motor Alarm. Valve (K) to restore the system to the
normal system air pressure.
Appendix C of TFP1090 (02/2012)
Summary Instructions (If problems occur, consult full document)
DN100, Model DPV-1 Dry Pipe Valve with Standard Alarm Test Valve,
without Model ACC-1 Accelerator
G C D P
J
H
N
K
465 mm
M
B
E
F
I. Normal Conditions III. Removing System From Service Step 7. Fully open the Main Control
• The Main Control Valve (A) is opened Step 1. Close the Main Control Valve Valve (A) and lock it open.
and locked. (A), and close the Air Supply Control Step 8. Reset the fire alarm panel and
• The sprinkler system is filled with air Valve (K). notify the central alarm station.
and is pressurized. Step 2. Drain the system with the Main V. Weekly Test
• The Main Drain Valve (F), and Low Drain Valve (F) and by opening all auxil- Important: Prior to closing any valves
Body Drain Valve (L) are closed. iary drain valves in the system to make or activating any alarms, notify local se-
sure that cross-mains and branch lines curity guards and the central alarm sta-
• The Alarm Test Valve (E) is in the are drained.
closed position. tion if applicable.
IV. Placing the System Back in
• The Pressure Gauge Valves (B) and Step 1. Open the Alarm Test Valve (E),
(C) are open. Service verify that the alarm signal created by
Step 1. Close the auxiliary drain valves the Waterflow Pressure Alarm Switch
• The Pressure Switch Valve (J) is after water ceases to discharge, and (M) is visible at the fire panel. If appli-
open. leave the Main Drain Valve (F) open. cable, check the sound of the Water
• The Air Supply Control Valve (K) is Step 2. Replace the sprinklers that Motor Alarm — it must be clear and
open. have operated and the sprinklers close steady.
• System Air Pressure Gauge (G) to the fire. Step 2. Close the Alarm Test Valve (E),
reads downstream air pressure. Step 3. Push down on the reset knob verify that the normal supply and sys-
(P) to allow the Dry Pipe Valve (D) to tem pressures are restored. If the sup-
• Water Supply Pressure Gauge (H) ply pressure is below the normal, use
reads the upstream water pressure. reseat.
the instructions from the water supply
II. Operation Step 4. Via the Air Supply Control Valve to obtain the usual pressure.
When one or more sprinklers are acti- (K), pressurize the system with air to 0,7
bar, and then open and close each aux- Step 3. Close the Pressure Switch
vated, air pressure is reduced down- Valve (J) and verify operation of the low
stream of the Dry Pipe Valve. When the iliary drain valves in the system piping
to drain any remaining water in trapped air pressure Alarm Switch (N).
air pressure is sufficiently reduced, the
water pressure overcomes the differen- sections. Also, partially open the Low Step 4. Return the Pressure Switch
tial holding the Dry Pipe Valve closed Body Drain Valve (L) to assure that the Valve (J) to the normally open position
and the Dry Pipe Valve opens to per- riser is completely drained. Close the after verifying that the alarm signal is
mit water flow into the system piping Low Body Drain Valve (L) as soon as visible at the fire panel.
and to be discharged from any open water ceases to discharge.
sprinklers. Also, with the Dry Pipe Valve Step 5. Open the Air Supply Control
open, water flows through the Alarm Valve (K) to restore the system to the
Port at the rear of the Dry Pipe Valve to normal system air pressure.
actuate the Waterflow Pressure Alarm
Switch (M) and, as applicable, the Step 6. Partially open the Main Control
Water Motor Alarm. Valve (A), and then slowly close the
Main Drain Valve (F).
Appendix D of TFP1090 (02/2012)
Summary Instructions (If problems occur, consult full document)
DN150, Model DPV-1 Dry Pipe Valve with Standard Alarm Test Valve,
without Model ACC-1 Accelerator
G C D
J
P N
K
510 mm
H
M
L
B
E
I. Normal Conditions III. Removing System From Service Step 7. Fully open the Main Control
• The Main Control Valve (A) is opened Step 1. Close the Main Control Valve Valve (A) and lock it open.
and locked. (A), and close the Air Supply Control Step 8. Reset the fire alarm panel and
• The sprinkler system is filled with air Valve (K). notify the central alarm station.
and is pressurized. Step 2. Drain the system with the Main V. Weekly Test
• The Main Drain Valve (F), and Low Drain Valve (F) and by opening all aux- Important: Prior to closing any valves
Body Drain Valve (L) are closed. iliary drain valves in the system to make or activating any alarms, notify local se-
sure that cross-mains and branch lines curity guards and the central alarm sta-
• The Alarm Test Valve (E) is in the are drained.
closed position. tion if applicable.
IV. Placing the System Back in
• The Pressure Gauge Valves (B) and Step 1. Open the Alarm Test Valve (E),
(C) are open. Service verify that the alarm signal created by
Step 1. Close the auxiliary drain valves the Waterflow Pressure Alarm Switch
• The Pressure Switch Valve (J) is after water ceases to discharge, and (M) is visible at the fire panel. If appli-
open. leave the Main Drain Valve (F) open. cable, check the sound of the Water
• The Air Supply Control Valve (K) is Step 2. Replace the sprinklers that Motor Alarm — it must be clear and
open. have operated and the sprinklers close steady.
• System Air Pressure Gauge (G) to the fire. Step 2. Close the Alarm Test Valve (E),
reads downstream air pressure. Step 3. Push down on the reset knob verify that the normal supply and sys-
(P) to allow the Dry Pipe Valve (D) to tem pressures are restored. If the sup-
• Water Supply Pressure Gauge (H) ply pressure is below the normal, use
reads the upstream water pressure. re-seat.
the instructions from the water supply
II. Operation Step 4. Via the Air Supply Control Valve to obtain the usual pressure.
When one or more sprinklers are acti- (K), pressurize the system with air to 0,7
bar, and then open and close each aux- Step 3. Close the Pressure Switch
vated, air pressure is reduced down- Valve (J) and verify operation of the low
stream of the Dry Pipe Valve. When the iliary drain valves in the system piping
to drain any remaining water in trapped air pressure Alarm Switch (N).
air pressure is sufficiently reduced, the
water pressure overcomes the differen- sections. Also, partially open the Low Step 4. Return the Pressure Switch
tial holding the Dry Pipe Valve closed Body Drain Valve (L) to assure that the Valve (J) to the normally open position
and the Dry Pipe Valve opens to per- riser is completely drained. Close the after verifying that the alarm signal is
mit water flow into the system piping Low Body Drain Valve (L) as soon as visible at the fire panel.
and to be discharged from any open water ceases to discharge.
sprinklers. Also, with the Dry Pipe Step 5. Open the Air Supply Control
Valve open, water flows through the Valve (K) to restore the system to the
Alarm Port at the rear of the Dry Pipe normal system air pressure.
Valve to actuate the Waterflow Pressure
Alarm Switch (M) and, as applicable, Step 6. Partially open the Main Control
the Water Motor Alarm. Valve (A), and then slowly close the
Main Drain Valve (F).
Appendix E of TFP1090 (02/2012)
Summary Instructions (If problems occur, consult full document)
DN100, Model DPV-1 Dry Pipe Valve with Three-Way Alarm Test Valve,
with Model ACC-1 Accelerator
S G C D P
N
H 805 mm
J
B
M
F
E
A
400 mm 400 mm 195 mm
I. Normal Conditions III. Removing System From Service Step 7. Reset accelerator (Q) using the
• The Main Control Valve (A) is opened Step 1. Close the Main Control Valve instruction on its resetting label.
and locked, and the Accelerator (A), close the Air Supply Control Valve
Control Valve (S) and Air Supply Step 8. Partially open the Main Control
(K), close the Accelerator Control Valve Valve (A), and then slowly close the
Control Valve (K) are open. (R), and place the Three-Way Alarm Main Drain Valve (F).
• The sprinkler system is filled with air Control Valve (E) in the closed position.
and is pressurized. Step 9. Fully open the Main Control
Step 2. Drain the system with the Main Valve (A) and lock it open.
• The Main Drain Valve (F), and Low Drain Valve (F) and by opening all aux-
Body Drain Valve (L) are closed. iliary drain valves in the system to make Step 10. Reset the fire alarm panel and
sure that cross-mains and branch lines notify the central alarm station.
• The Three-Way Alarm Control Valve are drained.
(E) is in the open position. V. Weekly Test
IV. Placing the System Back in Important: Prior to closing any valves
• The Pressure Gauge Valves (B) and or activating any alarms, notify local se-
(C) are open. Service
curity guards and the central alarm sta-
Step 1. Close the auxiliary drain valves tion if applicable.
• The Pressure Switch Valve (J) is after water ceases to discharge, and
open. leave the Main Drain Valve (F) open. Step 1. The Three-Way Alarm Control
• System Air Pressure Gauge (G) Valve (E) in the test position, verify
Step 2. Place the Three-Way Alarm that the alarm signal created by the
reads downstream air pressure, Control Valve (E) in the open position.
Water Supply Pressure Gauge (H) Waterflow Pressure Alarm Switch (M)
reads the upstream water pressure, Step 3. Replace the sprinklers that is visible at the fire panel. If applica-
and Accelerator Air Pressure Gauge have operated and the sprinklers close ble, check the sound of the Water Motor
(R) reads the accelerator pressure. to the fire. Alarm — it must be clear and steady.
Step 4. Push down on the reset knob Step 2. Place the Three-Way Alarm
II. Operation Control Valve (E) in the open position
When one or more sprinklers are acti- (P) to allow the Dry Pipe Valve (D) to
re-seat. and verify that the normal supply and
vated, the accelerator operates to per- system pressures are restored. If the
mit system air pressure into the Dry Step 5. Via the Air Supply Control Valve supply pressure is below the normal,
Pipe Valve intermediate chamber. Doing (K), pressurize the system with air to 0,7 use the instructions from the water sup-
so will immediately overcome the ability bar, and then open and close each aux- ply to obtain the usual pressure.
of the system air pressure to hold the iliary drain valves in the system piping Step 3. Close the Pressure Switch
Dry Pipe Valve closed without having to drain any remaining water in trapped Valve (J) and verify operation of the low
to wait for system air pressure to de- sections. Also, partially open the Low air pressure Alarm Switch (N).
cay to approximately 20% of the water Body Drain Valve (L) to assure that the
supply. The Dry Pipe Valve immediately riser is completely drained. Close the Step 4. Return the Pressure Switch
opens to permit water flow into the sys- Low Body Drain Valve (L) as soon as Valve (J) to the normally open position
tem piping and to be discharged from water ceases to discharge. after verifying that the alarm signal is
any open sprinklers. Also, with the Dry visible at the fire panel.
Pipe Valve open, water flows to actuate Step 6. Open the Air Supply Control
the Waterflow Pressure Alarm Switch Valve (K) to restore the system to the
(M) and, as applicable, the Water Motor normal system air pressure.
Alarm.
Appendix F of TFP1090 (02/2012)
Summary Instructions (If problems occur, consult full document)
DN150, Model DPV-1 Dry Pipe Valve with Three-Way Alarm Test Valve,
with Model ACC-1 Accelerator
G C D N
S
P 835 mm
J
M
H
L
E
B
A
415 mm 340 mm 210 mm
I. Normal Conditions III. Removing System From Service Step 7. Reset accelerator (Q) using the
• The Main Control Valve (A) is opened Step 1. Close the Main Control Valve instruction on its resetting label.
and locked, and the Accelerator (A), close the Air Supply Control Valve
Control Valve (S) and Air Supply Step 8. Partially open the Main Control
(K), close the Accelerator Control Valve Valve (A), and then slowly close the
Control Valve (K) are open. (R), and place the Three-Way Alarm Main Drain Valve (F).
• The sprinkler system is filled with air Control Valve (E) in the closed position.
and is pressurized. Step 9. Fully open the Main Control
Step 2. Drain the system with the Main Valve (A) and lock it open.
• The Main Drain Valve (F), and Low Drain Valve (F) and by opening all aux-
Body Drain Valve (L) are closed. iliary drain valves in the system to make Step 10. Reset the fire alarm panel and
sure that cross-mains and branch lines notify the central alarm.
• The Three-Way Alarm Control Valve are drained.
(E) is in the open position. V. Weekly Test
IV. Placing the System Back in Important: Prior to closing any valves
• The Pressure Gauge Valves (B) and or activating any alarms, notify local se-
(C) are open. Service
curity guards and the central alarm sta-
Step 1. Close the auxiliary drain valves tion if applicable.
• The Pressure Switch Valve (J) is after water ceases to discharge, and
open. leave the Main Drain Valve (F) open. Step 1. Place the Three-Way Alarm
• System Air Pressure Gauge (G) Step 2. Place the Three-Way Alarm Control Valve (E) in the test position,
reads downstream air pressure, Control Valve (E) in the open position. verify that the alarm signal created by
Water Supply Pressure Gauge (H) the Waterflow Pressure Alarm Switch
reads the upstream water pressure, Step 3. Replace the sprinklers that (M) is visible at the fire panel. If appli-
and Accelerator Air Pressure Gauge have operated and the sprinklers close cable, check the sound of the Water
(R) reads the accelerator pressure. to the fire. Motor Alarm — it must be clear and
Step 4. Push down on the reset knob steady.
II. Operation
When one or more sprinklers are acti- (P) to allow the Dry Pipe Valve (D) to Step 2. Place the Three-Way Alarm
vated, the accelerator operates to per- reseat. Control Valve (E) in the open position
mit system air pressure into the Dry Step 5. Via the Air Supply Control Valve and verify that the normal supply and
Pipe Valve intermediate chamber. Doing (K), pressurize the system with air to 0,7 system pressures are restored. If the
so will immediately overcome the ability bar, and then open and close each aux- supply pressure is below the normal,
of the system air pressure to hold the iliary drain valves in the system piping use the instructions from the water sup-
Dry Pipe Valve closed without having to drain any remaining water in trapped ply to obtain the usual pressure.
to wait for system air pressure to de- sections. Also, partially open the Low Step 3. Close the Pressure Switch
cay to approximately 20% of the water Body Drain Valve (L) to assure that the Valve (J) and verify operation of the low
supply. The Dry Pipe Valve immediately riser is completely drained. Close the air pressure Alarm Switch (N).
opens to permit water flow into the sys- Low Body Drain Valve (L) as soon as
tem piping and to be discharged from water ceases to discharge. Step 4. Return the Pressure Switch
any open sprinklers. Also, with the Dry Valve (J) to the normally open position
Pipe Valve open, water flows to actuate Step 6. Open the Air Supply Control after verifying that the alarm signal is
the Waterflow Pressure Alarm Switch Valve (K) to restore the system to the visible at the fire panel.
(M) and, as applicable, the Water Motor normal system air pressure.
Alarm.
Appendix G of TFP1090 (02/2012)
Summary Instructions (If problems occur, consult full document)
DN100, Model DPV-1 Dry Pipe Valve with Standard Alarm Test Valve,
with Model ACC-1 Accelerator
S G C D P
N
H 805 mm
J
B
M
F
E
A
365 mm 400 mm 195 mm
I. Normal Conditions III. Removing System From Service Step 7. Partially open the Main Control
• The Main Control Valve (A) is opened Step 1. Close the Main Control Valve Valve (A), and then slowly close the
and locked, and the Accelerator (A), close the Air Supply Control Valve Main Drain Valve (F).
Control Valve (S) and Air Supply (K), and close the Accelerator Control
Control Valve (K) are open. Step 8. Fully open the Main Control
Valve (R). Valve (A) and lock it open.
• The sprinkler system is filled with air Step 2. Drain the system with the Main
and is pressurized. Step 9. Reset the fire alarm panel and
Drain Valve (F) and by opening all aux- notify the central alarm station.
• The Main Drain Valve (F), and Low iliary drain valves in the system to make
Body Drain Valve (L) are closed. sure that cross-mains and branch lines V. Weekly Test
are drained. Important: Prior to closing any valves
• The Alarm Test Valve (E) is in the or activating any alarms, notify local se-
closed position. IV. Placing the System Back in curity guards and the central alarm sta-
• The Pressure Gauge Valves (B) and Service tion if applicable.
(C) are open. Step 1. Close the auxiliary drain valves
after water ceases to discharge, and Step 1. Open the Alarm Test Valve (E),
• The Pressure Switch Valve (J) is leave the Main Drain Valve (F) open. verify that the alarm signal created by
open. the Waterflow Pressure Alarm Switch
Step 2. Replace the sprinklers that (M) is visible at the fire panel. If applica-
• System Air Pressure Gauge (G) have operated and the sprinklers close ble, check the sound of the Water Motor
reads downstream air pressure, to the fire. Alarm — it must be clear and steady.
Water Supply Pressure Gauge (H)
reads the upstream water pressure, Step 3. Push down on the reset knob Step 2. Close the Alarm Test Valve (E),
and Accelerator Air Pressure Gauge (P) to allow the Dry Pipe Valve (D) to verify that the normal supply and sys-
(R) reads the accelerator pressure. re- seat. tem pressures are restored. If the sup-
Step 4. Via the Air Supply Control Valve ply pressure is below the normal, use
II. Operation the instructions from the water supply
When one or more sprinklers are acti- (K), pressurize the system with air to 0,7
bar, and then open and close each aux- to obtain the usual pressure.
vated, the accelerator operates to per-
mit system air pressure into the Dry iliary drain valves in the system piping Step 3. Close the Pressure Switch
Pipe Valve intermediate chamber. Doing to drain any remaining water in trapped Valve (J) and verify operation of the low
so will immediately overcome the ability sections. Also, partially open the Low air pressure Alarm Switch (N).
of the system air pressure to hold the Body Drain Valve (L) to assure that the
riser is completely drained. Close the Step 4. Return the Pressure Switch
Dry Pipe Valve closed without having Valve (J) to the normally open position
to wait for system air pressure to de- Low Body Drain Valve (L) as soon as
water ceases to discharge. after verifying that the alarm signal is
cay to approximately 20% of the water visible at the fire panel.
supply. The Dry Pipe Valve immediately Step 5. Open the Air Supply Control
opens to permit water flow into the sys- Valve (K) to restore the system to the
tem piping and to be discharged from normal system air pressure.
any open sprinklers. Also, with the Dry
Pipe Valve open, water flows to actuate Step 6. Reset accelerator (Q) using the
the Waterflow Pressure Alarm Switch instruction on its resetting label.
(M) and, as applicable, the Water Motor
Alarm.
Appendix H of TFP1090 (02/2012)
Summary Instructions (If problems occur, consult full document)
DN150, Model DPV-1 Dry Pipe Valve with Standard Alarm Test Valve,
with Model ACC-1 Accelerator
G C D N
S
P 835 mm
J
M
H
L
E
B
A
415 mm 460 mm 210 mm
I. Normal Conditions III. Removing System From Service Step 7. Partially open the Main Control
• The Main Control Valve (A) is opened Step 1. Close the Main Control Valve Valve (A), and then slowly close the
and locked, and the Accelerator (A), close the Air Supply Control Valve Main Drain Valve (F).
Control Valve (S) and Air Supply (K), and close the Accelerator Control
Control Valve (K) are open. Step 8. Fully open the Main Control
Valve (R). Valve (A) and lock it open.
• The sprinkler system is filled with air Step 2. Drain the system with the Main
and is pressurized. Step 9. Reset the fire alarm panel and
Drain Valve (F) and by opening all aux- notify the central alarm.
• The Main Drain Valve (F), and Low iliary drain valves in the system to make
Body Drain Valve (L) are closed. sure that cross-mains and branch lines V. Weekly Test
are drained. Important: Prior to closing any valves
• The Alarm Test Valve (E) is in the or activating any alarms, notify local se-
closed position. IV. Placing the System Back in curity guards and the central alarm sta-
Service tion if applicable.
• The Pressure Gauge Valves (B) and
(C) are open. Step 1. Close the auxiliary drain valves
after water ceases to discharge, and Step 1. Open the Alarm Test Valve (E),
• The Pressure Switch Valve (J) is leave the Main Drain Valve (F) open. verify that the alarm signal created by
open. the Waterflow Pressure Alarm Switch
Step 2. Replace the sprinklers that (M) is visible at the fire panel. If appli-
• System Air Pressure Gauge (G) have operated and the sprinklers close cable, check the sound of the Water
reads downstream air pressure, to the fire. Motor Alarm — it must be clear and
Water Supply Pressure Gauge (H,) steady.
reads the upstream water pressure, Step 3. Push down on the reset knob
and Accelerator Air Pressure Gauge (P) to allow the Dry Pipe Valve (D) to Step 2. Close the Alarm Test Valve (E),
(R) reads the accelerator pressure. re-seat. verify that the normal supply and sys-
Step 4 . Via the Air Supply Control tem pressures are restored. If the sup-
II. Operation Valve (K), pressurize the system with ply pressure is below the normal, use
When one or more sprinklers are acti- air to 0,7 bar, and then open and close the instructions from the water supply
vated, the accelerator operates to per- each auxiliary drain valves in the sys- to obtain the usual pressure.
mit system air pressure into the Dry tem piping to drain any remaining water
Pipe Valve intermediate chamber. Doing Step 3. Close the Pressure Switch
in trapped sections. Also, partially open Valve (J) and verify operation of the low
so will immediately overcome the ability the Low Body Drain Valve (L) to assure
of the system air pressure to hold the air pressure Alarm Switch (N).
that the riser is completely drained.
Dry Pipe Valve closed without having Close the Low Body Drain Valve (L) as Step 4. Return the Pressure Switch
to wait for system air pressure to de- soon as water ceases to discharge. Valve (J) to the normally open position
cay to approximately 20% of the water after verifying that the alarm signal is
supply. The Dry Pipe Valve immediately Step 5. Open the Air Supply Control visible at the fire panel.
opens to permit water flow into the sys- Valve (K) to restore the system to the
tem piping and to be discharged from normal system air pressure.
any open sprinklers. Also, with the Dry Step 6. Reset accelerator (Q) using the
Pipe Valve open, water flows to actuate instruction on its resetting label.
the Waterflow Pressure Alarm Switch
(M) and, as applicable, the Water Motor
Alarm.
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
waterflow detection valve) must be alarm line will automatically drain back
maintained at a minimum temperature Operation through the orifice which is also pro-
of 40°F/4°C. vided in the trim of the waterflow de-
Upon operation of the alarm check, dry tection valve.
Item 11. A single Water Motor Alarm pipe, deluge, or preaction valve to
may be connected to the alarm lines which the Model WMA-1 Water Motor The Water Motor Alarm does not have
from a maximum of three separate fire Alarm is connected, water will flow to to be reset after an operation. How-
protection systems. However, when the Water Motor and through the Inlet ever, if the alarm was silenced during
two or three alarm lines are intercon- Nozzle. As water flows through the In- operation by closing of an alarm con-
nected, each alarm line must be pro- let Nozzle, a high velocity jet is formed trol valve, the alarm control valve must
vided with a 3/4 inch (P/N 52-271-1- which impinges on the Impeller, caus- be reopened after the fire protection
001) Model WM-1 Y-Strainer and a 3/4 ing the Impeller and the Striker to ro- system is restored to service.
inch (P/N 52-403-1-005) Check Valve tate. With each rotation, the free swing-
with 3/32 inch orifice. The strainers ing Striker Ring hits the Gong and
must be located at the “alarm outlet” in sounds the alarm. The spent water is
the trim of each of the waterflow detec- then drained through the 1 inch outlet.
tion valves. The check valves must be
located between each strainer and the The alarm will sound as long as water
interconnection with the alarm line is flowing into the system and flowing
from another system. to the Water Motor Alarm. Water in the
TFP921 Page 3 of 4
ing onto the Sleeve. Securely tighten must be given to the owner and the fire IN NO EVENT SHALL TYCO FIRE
the Striker Shaft Bearing using a pair department, central control station, or PRODUCTS BE LIABLE, IN CON-
of channel locks on the 1-1/2 inch (38 other signal station to which the TRACT, TORT, STRICT LIABILITY OR
mm) hex end. alarms are connected. UNDER ANY OTHER LEGAL THE-
Step 11. Spin the Striker by hand and If the alarm was silenced during opera- ORY, FOR INCIDENTAL, INDIRECT,
verify that it spins freely (without any tion, the alarm control valve must be SPECIAL OR CONSEQUENTIAL
sign of binding). If not, make the nec- reopened immediately after the fire DAMAGES, INCLUDING BUT NOT
essary adjustments. protection system is restored to serv- LIMITED TO LABOR CHARGES, RE-
ice. GARDLESS OF WHETHER TYCO
Step 12. Install the gong and securely FIRE PRODUCTS WAS INFORMED
tighten the Cap Nut. The identification The Model WMA-1 Water Motor Alarm ABOUT THE POSSIBILITY OF SUCH
sign lettering must be orientated hori- must be maintained and serviced in DAMAGES, AND IN NO EVENT
zontally, accordance with the following instruc-
SHALL TYCO FIRE PRODUCTS’ LI-
Step 13. Test the Water Motor Alarm tions:
ABILITY EXCEED AN AMOUNT
by opening the alarm test valve in the Step 1. The Model WMA-1 Water Mo- EQUAL TO THE SALES PRICE.
trim of the water flow detection valve. tor Alarm does not require any regu-
The alarm must be clear and steady. If larly scheduled maintenance. Rotating THE FOREGOING WARRANTY IS
not, make the necessary adjustments. parts do not require lubrication. It is MADE IN LIEU OF ANY AND ALL
recommended, however, that fire OTHER WARRANTIES EXPRESS
NOTE alarms be periodically operated, i.e., OR IMPLIED, INCLUDING WARRAN-
Testing of the Water Motor Alarm may inspected, to verify that they generate TIES OF MERCHANTABILITY AND
result in operation of other associated a clear and steady sound. Any impair- FITNESS FOR A PARTICULAR PUR-
alarms. Consequently, notification ment must be be immediately cor- POSE.
must be given to the owner and the fire rected.
department, central control station, or
other signal station to which the
Step 2. The inspection should be
made quarterly or more frequently, as
Ordering
alarms are connected. may be necessary in the case of loca-
tions subject to vandalism. The Y-
Information
Strainer and Sump are to be cleaned
Care and out after each operation of the Water
Orders for the WMA-1, Optional Drain
Trim, and replacement parts must in-
Motor Alarm and after the alarm line
Maintenance piping has been drained.
clude the description and Part Number
(P/N).
The following procedures and inspec- The Complete Model WMA-1 Alarm
tions should be performed as indi-
cated, in addition to any specific re-
Limited Assembly includes the Model WMA-1
Water Motor Alarm, Model WM-1
quirements of the NFPA, and any
impairment must be immediately cor-
Warranty Strainer, and Standard Inlet Trim.
WMA-1 Alarm Assemblies:
rected. Products manufactured by Tyco Fire
Specify: Model WMA-1 Alarm Assem-
The owner is responsible for the in- Products are warranted solely to the
bly with Red Finish Gong,
spection, testing, and maintenance of original Buyer for ten (10) years P/N 52-630-1-001.
their fire protection system and de- against defects in material and work-
vices in compliance with this docu- manship when paid for and properly or
ment, as well as with the applicable installed and maintained under normal Specify: Model WMA-1 Alarm Assem-
standards of the National Fire Protec- use and service. This warranty will ex- bly with Aluminum Finish Gong,
tion Association (e.g., NFPA 25), in pire ten (10) years from date of ship- P/N 52-630-2-001
addition to the standards of any ment by Tyco Fire Products. No war- Optional Drain Trim:
authority having jurisdiction. The in- ranty is given for products or
stalling contractor or product manufac- components manufactured by compa- Specify: Optional Drain Trim for Model
turer should be contacted relative to nies not affiliated by ownership with WMA-1 Water Motor Alarm,
any questions. Tyco Fire Products or for products and P/N 52-630-2-002.
It is recommended that automatic components which have been subject Separately Ordered Alarm Control
sprinkler systems be inspected, to misuse, improper installation, corro- Valve:
tested, and maintained by a qualified sion, or which have not been installed, Specify: UL/FM 3/4 Inch Ball Valve,
Inspection Service in accordance with maintained, modified or repaired in ac- P/N 92-300-1-006.
local requirements and/or national cordance with applicable Standards of Separately Ordered Parts for
codes. the National Fire Protection Associa- Multiple Systems:
tion, and/or the standards of any other Specify: Model WM-1 Y-Strainer, P/N
NOTES Authorities Having Jurisdiction. Mate- 52-271-1-001. (1 required for two sys-
Before closing a fire protection system rials found by Tyco Fire Products to be tem, 2 required for 3 systems.)
main control valve for maintenance defective shall be either repaired or
replaced, at Tyco Fire Products’ sole Specify: 3/4 Inch Check valve with
work on the fire protection system that 3/32 Inch Orifice, P/N 52-403-1-005 (2
it controls, permission to shut down option. Tyco Fire Products neither as-
sumes, nor authorizes any person to required for two system, 3 required for
the affected fire protection systems 3 systems.)
must first be obtained from the proper assume for it, any other obligation in
authorities and all personnel who may connection with the sale of products or Replacement Parts for
be affected by this decision must be parts of products. Tyco Fire Products Water Motor Alarm:
notified. shall not be responsible for sprinkler (Specify description) for use with
system design errors or inaccurate or Model WMA-1 Water Motor Alarm,
Testing of the Water Motor Alarm may P/N (see Figure 1).
result in operation of other associated incomplete information supplied by
alarms. Consequently, notification Buyer or Buyer’s representatives.
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Installation
Notes
The Model F350 Sectional Test & Drain
must be installed in a readily visible
and accessible location, preferably not
over seven feet above the floor.
Wet pipe fire protection systems must
be maintained at a minimum tempera-
ture of 40°F (40°C).
The outlet of the F350 must be con-
nected to a drain sized to accept full
flow during a sectional flow test.
The Model F350 Sectional Test & Drain
is to be installed in accordance with
the following criteria:
Step 1. Apply pipe thread sealant
sparingly to male pipe threads only.
Use of a Teflon* based pipe joint seal-
ant is recommended.
Step 2. The F350 may be installed in Figure 1
any position; however, the arrow on Typical Sectional control arrangement
the Label must point in the direction of
flow (towards drain) and there must be
no restriction to the full movement of
the valve handles (Ref. Figure 2).
Step 3. To prevent distortion of the
valve bodies, make the inlet pipe con-
nection by wrenching on the Shut-off
Valve only and make the outlet pipe
connection by wrenching on the Sight
Glass Assembly fitting only.
Step 4. Do not use the F350 to force a
pipe- line into position. Doing so may
result in distortion of the valves.
Figure 2
Model f350 sectional test & drain
Limited Ordering
Warranty Procedure
Products manufactured by Tyco Fire Orders must include the description
& Building Products (TFBP) are war and Part Number (P/N). Contact your
ranted solely to the original Buyer for local distributor for availability.
ten (10) years against defects in mate
rial and workmanship when paid for Sectional Test & Drain:
and properly installed and maintained Specify: 1-1/4 inch NPT Model F350
under normal use and service. This Sectional Test & Drain with K5.6 (K80)
warranty will expire ten (10) years from test orifice, P/N 54-350-1-001.
date of shipment by TFBP. No warran-
ty is given for products or components
manufactured by companies not af-
filiated by ownership with TFBP or for
products and components which have
been subject to misuse, improper in-
stallation, corrosion, or which have not
been installed, maintained, modified or
repaired in accordance with applicable
Standards of the National Fire Protec-
tion Association, and/or the standards
of any other Authorities Having Juris-
diction. Materials found by TFBP to be
defective shall be either repaired or re-
placed, at TFBP’s sole option. TFBP
neither assumes, nor authorizes any
person to assume for it, any other ob-
ligation in connection with the sale of
products or parts of products. TFBP
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer’s representatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam
ages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP’s liability exceed an amount
equal to the sales price.
The foregoing warranty is made in lieu
of any and all other warranties, ex-
press or implied, including warranties
of merchantability and fitness for a
particular purpose.
This limited warranty sets forth the ex
clusive remedy for claims based on
failure of or defect in products, materi
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex
tent permitted by law. The invalidity,
in whole or part, of any portion of this
warranty will not affect the remainder.
TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale Pennsylvania 19446
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
5
2-1/4" 2-3/16"
4
(57,2 mm) (55,6 mm)
2
1-9/16" WRENCH 3
(39,7 mm) FLATS
1
7
SSP *
DEFLECTOR CROSS
PENDENT UPRIGHT SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame.
Screw
** Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 1
STANDARD RESPONSE SERIES TY-B UPRIGHT (TY1151) AND PENDENT (TY1251) SPRINKLERS
2.8 K-FACTOR, 1/2 INCH NPT
7/16" 5
2-3/16" (11,1 mm)
(55,6 mm) NOMINAL 4
MAKE-IN
1-1/2" 2
2-3/16"
(38,1 mm)
(55,6 mm)
WRENCH 3
FLATS
1
SSP DEFLECTOR * 2-7/8" (73,0 mm) DIA. 1/2" NPT **
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw
** Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 2
STANDARD RESPONSE SERIES TY-B UPRIGHT (TY3151) AND PENDENT (TY3251) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT
TFP151 Page 3 of 8
1/2" 5
2-5/16" (12,7 mm)
(58,7 mm) NOMINAL 4
MAKE-IN
2
1-9/16" 2-1/4"
(39,7 mm) (57,2 mm)
3
WRENCH
FLATS
1
SSP DEFLECTOR * 2-7/8" (73,0 mm) DIA. 3/4" NPT **
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
*6
5
2-1/4" 2-3/16"
(57,2 mm) (55,6 mm) 4
1-9/16" WRENCH 2
(39,7 mm) FLATS
3
1
SSP *
DEFLECTOR CROSS
PENDENT UPRIGHT SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw
** Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 4
STANDARD RESPONSE SERIES TY-B UPRIGHT (TY4851) AND PENDENT (TY4951) SPRINKLERS
8.0 K-FACTOR, 1/2 INCH NPT
Page 4 of 8 TFP151
135°F/57°C Orange
PENDENT
155°F/68°C Red
2.8 (TY1251) 1, 2, 3 N/A
1/2" and 175°F/79°C Yellow
NPT UPRIGHT 200°F/93°C Green
(TY1151)
286°F/141°C Blue
360°F/182°C Mauve 1, 2
135°F/57°C Orange
PENDENT
155°F/68°C Red
(TY3251) 1, 2, 3, 4, 5, 6, 7 1, 2, 3, 5 1, 2, 3, 5 1, 2, 3, 5
and 175°F/79°C Yellow
UPRIGHT 200°F/93°C Green
(TY3151)
5.6 286°F/141°C Blue 1**,2**, 3**, 5** 1**, 2**, 3**, 5**
1/2"
NPT 360°F/182°C Mauve N/A
135°F/57°C Orange
RECESSED
155°F/68°C Red
PENDENT 1, 2, 3, 4, 5 N/A
(TY3251)* 175°F/79°C Yellow
Figure 4 200°F/93°C Green
286°F/141°C Blue 1, 2
135°F/57°C Orange
PENDENT
155°F/68°C Red
(TY4251) 1, 2, 5 1, 2, 3, 5 1, 2, 5
and 175°F/79°C Yellow 1, 2, 3, 4, 5, 6, 7
UPRIGHT 200°F/93°C Green
8.0
(TY4151)
3/4" 286°F/141°C Blue 1**,2**, 3**, 5** 1**, 2**, 5**
NPT
360°F/182°C Mauve N/A
135°F/57°C Orange
RECESSED
155°F/68°C Red
PENDENT 1, 2, 3, 4, 5 N/A
(TY4251)* 175°F/79°C Yellow
Figure 5 200°F/93°C Green
286°F/141°C Blue 1, 2
135°F/57°C Orange
PENDENT
155°F/68°C Red
8.0 (TY4951)
1/2" and 175°F/79°C Yellow 1, 2, 3, 4, 5, 6 N/A
NPT UPRIGHT 200°F/93°C Green
(TY4851)
286°F/141°C Blue
360°F/182°C Mauve
NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL).
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL).
3. Approved by Factory Mutual Research Corporation (FM).
4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/03).
5. Approved by the City of New York under MEA 354-01-E.
6. VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377).
7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/05).
8. Where Polyester Coated, Lead Coated, Wax Coated, and Wax over Lead Coated Sprinklers are noted to be UL and C-UL Listed, the
sprinklers are UL and C-UL Listed as Corrosion Resistant Sprinklers. Where Lead Coated, Wax Coated, and Wax over Lead Coated
Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as Corrosion Resistant Sprinklers.
* Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable.
** 150°F/66°C Maximum Ceiling Temperature.
*** Frame and deflector only. Listings and approvals apply to color (Special Order).
TABLE A, LABORATORY LISTINGS AND APPROVALS
TFP151 Page 5 of 8
SPRINKLER FINISH
K TYPE NATURAL CHROME WHITE LEAD WAX WAX OVER
BRASS PLATED POLYESTER COATED COATED LEAD COATED
NOTE:
1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories, Inc. (UL); the Listing by
Underwriters Laboratories, Inc. for use in Canada (C-UL); and, the Approval by the City of New York.
Technical Operation
Data The glass Bulb contains a fluid which
expands when exposed to heat. When
Approvals the rated temperature is reached, the
UL and C-UL Listed. fluid expands sufficiently to shatter the
FM, LPCB, VdS, and NYC Approved. glass Bulb, allowing the sprinkler to
(Refer to Table A for complete ap- activate and water to flow.
proval information including corrosion
resistant status.)
Maximum Working Pressure
Design
Refer to Table B. Criteria
Discharge Coefficient
K = 2.8 GPM/psi1/2 (40,3 LPM/bar1/2) The Series TY-B Pendent and Upright
K = 5.6 GPM/psi1/2 (80,6 LPM/bar1/2) Sprinklers are intended for fire protec-
K = 8.0 GPM/psi1/2 (115,2 LPM/bar1/2) tion systems designed in accordance
with the standard installation rules rec-
Temperature Ratings ognized by the applicable Listing or
Refer to Table A. Approval agency (e.g., UL Listing is
Finishes based on the requirements of NFPA
Sprinkler: Refer to Table A. 13, and FM Approval is based on the
Recessed Escutcheon: White Coated, requirements of FM’s Loss Prevention
† DuPont Registered Trademark
2-7/8" DIA.
(73,0 mm) 3/4" (19,1 mm)
5/8±1/4"
(15,9±6,4 mm) 1/4" (6,4 mm) WRENCH RECESS
2-1/4" DIA. (END "A" USED FOR
(57,2 mm) 1/2" NPT MODELS)
FACE OF MOUNTING
SPRINKLER PLATE
FITTING
1/8" WRENCH RECESS
(3,2 mm) (END "B" USED FOR
3/4" NPT MODELS)
FIGURE 7
W-TYPE 6 SPRINKLER
WRENCH
MOUNTING
SURFACE
WRENCH
SERIES 1-1/4" (31,8 mm) RECESS
CLOSURE
TY-B 3/4" (19,1 mm)
FIGURE 5
SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
2-7/8" DIA.
WITH SPRINKLER
(73,0 mm) 3/4" (19,1 mm) WRENCHING AREA
5/8±1/4"
(15,9±6,4 mm) 2-1/4" DIA. 1/4" (6,4 mm)
FIGURE 8
(57,2 mm) W-TYPE 7 RECESSED
FACE OF MOUNTING
SPRINKLER PLATE SPRINKLER WRENCH
FITTING
1/8"
(3,2 mm)
Installation
The Series TY-B Sprinklers must be
installed in accordance with the follow-
ing instructions:
MOUNTING NOTES
SURFACE Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
CLOSURE SERIES 1-5/16" (33,3 mm) liquid from the bulb. With the sprinkler
TY-B held horizontally, a small air bubble
13/16" (20,6 mm) should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135°F/57°C to 3/32
FIGURE 6 inch (2,4 mm) for the 360°F/182°C
SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY temperature ratings.
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON A 1/2 inch NPT sprinkler joint should
8.0 K-FACTOR, 3/4 INCH NPT be obtained with a minimum to maxi-
mum torque of 7 to 14 ft.lbs. (9,5 to
19,0 Nm). A 3/4 inch NPT sprinkler
joint should be obtained with a mini-
mum to maximum torque of 10 to 20
ft.lbs. (13,4 to 26,8 Nm). Higher levels
of torque may distort the sprinkler inlet
and cause leakage or impairment of
the sprinkler.
Do not attempt to make-up for insuffi-
cient adjustment in the escutcheon
plate by under- or over-tightening the
TFP151 Page 7 of 8
sprinkler. Readjust the position of the The Series TY-B Recessed Pendent and after installation. Sprinklers dam-
sprinkler fitting to suit. Sprinklers must be installed in ac- aged by dropping, striking, wrench
cordance with the following instruc- twist/slippage, or the like, must be re-
The Series TY-B Pendent and Up-
tions. placed. Also, replace any sprinkler
right Sprinklers must be installed in
that has a cracked bulb or that has lost
accordance with the following instruc- Step A. After installing the Style 10 or
liquid from its bulb. (Ref. Installation
tions. 40 Mounting Plate, as applicable, over
Section).
the sprinkler threads and with pipe
Step 1. Pendent sprinklers are to be
thread sealant applied to the pipe Frequent visual inspections are rec-
installed in the pendent position, and
threads, hand tighten the sprinkler into ommended to be initially performed for
upright sprinklers are to be installed in
the sprinkler fitting. corrosion resistant coated sprinklers,
the upright position.
after the installation has been com-
Step B. Tighten the sprinkler into the
Step 2. With pipe thread sealant ap- pleted, to verify the integrity of the cor-
sprinkler fitting using only the W-Type
plied to the pipe threads, hand tighten rosion resistant coating. Thereafter,
7 Recessed Sprinkler Wrench (Ref.
the sprinkler into the sprinkler fitting. annual inspections per NFPA 25
Figure 8). With reference to Figure 3
should suffice; however, instead of in-
Step 3. Tighten the sprinkler into the or 4, the W-Type 7 Recessed Sprinkler
specting from the floor level, a random
sprinkler fitting using only the W-Type Wrench is to be applied to the sprinkler
sampling of close-up visual inspec-
6 Sprinkler Wrench (Ref. Figure 7), wrench flats.
tions should be made, so as to better
except that an 8 or 10 inch adjustable
Step C. After the ceiling has been in- determine the exact sprinkler condi-
Crescent wrench is to be used for wax
stalled or the finish coat has been ap- tion and the long term integrity of the
coated sprinklers. With reference to
plied, slide on the Style 10 or 40 Clo- corrosion resistant coating, as it may
Figures 1, 2, 3, and 4 the W-Type 7
sure over the Series TY-B Sprinkler be affected by the corrosive conditions
Sprinkler Wrench or the adjustable
and push the Closure over the Mount- present.
Crescent wrench, as applicable is to
ing Plate until its flange comes in con-
be applied to the wrench flats.
tact with the ceiling. The owner is responsible for the in-
When installing wax coated sprinklers spection, testing, and maintenance of
with the adjustable Crescent wrench, their fire protection system and de-
additional care needs to be exercised Care and vices in compliance with this docu-
to prevent damage to the wax coating ment, as well as with the applicable
on the sprinkler wrench flats or frame Maintenance standards of the National Fire Protec-
arms and, consequently, exposure of tion Association (e.g., NFPA 25), in
bare metal to the corrosive environ- The Series TY-B Sprinklers must be addition to the standards of any other
ment. The jaws of the wrench should maintained and serviced in accord- authorities having jurisdiction. The in-
be opened sufficiently wide to pass ance with the following instructions: stalling contractor or sprinkler manu-
over the wrench flats without damag- facturer should be contacted relative
ing the wax coating. Before wrench NOTES to any questions.
tightening the sprinkler, the jaws of the Before closing a fire protection system
main control valve for maintenance Automatic sprinkler systems should be
wrench are to be adjusted to just con-
work on the fire protection system that inspected, tested, and maintained by
tact the sprinkler wrench flats. After
it controls, permission to shut down the a qualified Inspection Service in ac-
wrench tightening the sprinkler, loosen
affected fire protection system must be cordance with local requirements
the wrench jaws before removing the
obtained from the proper authorities and/or national codes.
wrench.
and all personnel who may be affected
After installation, the sprinkler wrench by this action must be notified.
flats and frame arms must be in-
spected and the wax coating re- The owner must assure that the sprin-
touched (repaired) whenever the coat- klers are not used for hanging of any
ing has been damaged and bare metal objects; otherwise, non-operation in
is exposed. The wax coating on the the event of a fire or inadvertent opera-
wrench flats can be retouched by gen- tion may result.
tly applying a heated 1/8 inch diameter Absence of an escutcheon, which is
steel rod to the areas of wax that have used to cover a clearance hole, may
been damaged, to smooth it back over delay the time to sprinkler operation in
areas where bare metal is exposed. a fire situation.
NOTES Sprinklers that are found to be leaking
Only retouching of the wax coating ap- or exhibiting visible signs of corrosion
plied to the wrench flats and frame must be replaced.
arms is permitted, and the retouching Automatic sprinklers must never be
is to be performed only at the time of painted, plated, coated or otherwise
the initial sprinkler installation. altered after leaving the factory. Modi-
The steel rod should be heated only to fied sprinklers must be replaced.
the point at which it can begin to melt Sprinklers that have been exposed to
the wax, and appropriate precautions corrosive products of combustion, but
need to be taken, when handling the have not operated, should be replaced
heated rod, in order to prevent the if they cannot be completely cleaned
installer from being burned. by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
Page 8 of 8 TFP151
TABLE C
PART NUMBER SELECTION
SERIES TY-B PENDENT AND UPRIGHT SPRINKLERS
© 2007 TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
Close
Close
Close
Close
Close
Close
Close
Close
D. GRAFIČKA DOKUMENTACIJA
REKAPITULACIJA
68 kom.
met.
120
40
60
OSNOVA SPRATA/ novoprojektovano stanje
P1 P1 P1a P1 P1 P1a P1 P1 R1 P9 P9 R1 P1a P1a P1 P1a P1a P1 P1a P1 P1 P1a
100
100
242
242
145
145
145
145
145
145
145
145
145
145
145
145
145
145
145
145
145
145
162
162
162
162
162
162
162
162
162
162
162
162
162
162
162
162
162
162
p-85 p-85 p-85 p-85 p-85 p-85 p-85 p-85 p-85 p-85 p-85 p-85 p-85 p-85 p-85
LEGENDA - SIMBOLI
45
V
- Indikator protoka
IP
R6
- Set za testiranje indikatora protoka
p-85
28 145
162 P1a TIP
29
- Test ventil sa K faktorom sprinkler mlaznice
R6
44a 44 47 145
46 162 P1
NAPOMENA:
+ 3.81
33
33 145
P1
V
162
42 27 30 R6
USKLADITI SA OSTALOM OPREMOM.
31
+ 3.81 + 3.81
41
ms
43 R6
35
p-85
40 38 32 145
P1a
36 162
34
energy team d.o.o.
PRIJESTONICA CETINJE
37 Tel./Fax: +382.20.67 59 53; +382 69 429 848
E-mail: energyteam.me@gmail.com
39
p-85 p-85 p-85 p-85 p-140 p-175 p-175 p-85 p-85 p-85 p-85 p-80 p-85 p-85
OBJEKAT: LOKACIJA:
UP3, DUP "Industrijska zona
205
251
145
145
145
145
100
100
100
100
145
145
145
145
145
145
145
145
145
162
162
162
162
162
162
162
162
162
162
162
162
162
80
80
80
80
238
345
P1a P1 P1 P1a P5 P3 P3 P3 P3 P1 P1a P1 P1 P1 P1a P1 R5 P1a P1
(zona I, podzona I2)" CETINJE
P4
Maj 2017.
REKAPITULACIJA
68 kom.
met.
120
40
+ 0.26
670.82
80
OSNOVA PRIZEMLJA/ novoprojektovano stanje - 0.18
670.38
+ 0.54 VR3
VR2 VR2
P8a P8 P8 P2 P2a P2 P2 P2a 22 671.10 P2a P2 P2a P2a P2 P2a P2
100
+ 0.54
260
100
100
260
260
R1 R1 R3
195
195
195
195
195
195
195
195
195
195
195
195
195
195
195
260
260
260
R2 23
100
100
100
100
100
100
100
100
100
100
100
100
671.10
mikroskop
LEGENDA - SIMBOLI
saltmetar
AWmetar
kupatilo
vodeno
kalorija
+ 0.54
671.10
inkubator
156 P7
V
238
23 - Indikator protoka
24 IP
inkubator
A
IJ
TIP
OL
inkubator
18 19
BI
20 21 22 ms
RO
autoklav
1 R8
M
laminarna komora
PRANJE
autoklav
246 P6
+ 0.04 238
homogenizator
25 25 26 + 0.54
vortex
vaga
mlin
+ 0.54
NAPOMENA:
5
17 + 0.54
13 1 100
260
VR3 USKLADITI SA OSTALOM OPREMOM.
+ 0.04
R7
spektrofotometar
10c 9 8 7
6
gerthard
klupica klupica
2 - 0.18
11 670.38 PROJEKTANT: INVESTITOR:
16 PROJEKTANT DIJELA TEHNI
ormar ormar
15
10a
+ 0.54
3 energy team d.o.o.
PRIJESTONICA CETINJE
Tel./Fax: +382.20.67 59 53; +382 69 429 848
aparat za vino 4
12 10 E-mail: energyteam.me@gmail.com
OBJEKAT: LOKACIJA:
195
195
195
195
195
260
195
260
UP3, DUP "Industrijska zona
260
260
100
100
R4
100
260
P8a P8a P8 P8 P2 P2 - 0.38
(zona I, podzona I2)" CETINJE
+ 0.54
VR3 670.18
671.10
sprinkler kalorifer
5 kW
DATUM IZRADE I M.P.
Maj 2017.
DATUM REVIZIJE I M.P.
podstanica
PREMA MLAZNICAMA
IZ GRADSKOG VODOVODA
RC-1
220V,
50 Hz
POGLED A-A
11. REDUCIR VENTIL DN 100 SA 6,5 BARA IZ VODOVODA NA 4 BARA U INSTALACIJU Maj 2017.
M
220V,
50 Hz
M
M
OBJEKAT: LOKACIJA:
UP3, DUP "Industrijska zona
M
(zona I, podzona I2)" CETINJE
Maj 2017.
FIKSNI OSLONAC
Dno grede
M
DN100
DN
mlaznica
x
L
1
NAPOMENA:
4
DN d M NAPOMENA:
mm mm mm
25 8 M8
32 10 M10
3
40 10 M10 PROJEKTANT: PROJEKTANT DIJELA TEHNI INVESTITOR:
DN
energy team d.o.o.
50 12 M12
PRIJESTONICA CETINJE
Tel./Fax: +382.20.67 59 53; +382 69 429 848
E-mail: energyteam.me@gmail.com
65 12 M12
OBJEKAT: LOKACIJA:
80 12 M12 UP3, DUP "Industrijska zona
DN L M DN L M
mm mm mm mm mm mm (zona I, podzona I2)" CETINJE
100 12 M12
20 73 M8 65 128.4 M10 GLAVNI PROJEKAT ADAPTACIJE
125 12 M12
ODGOVORNI PROJEKTANT: RAZMJERA:
25 76 M8 80 153.4 M10
150 16 M12 Aleksandar Strugar, SPRINKLER INSTALACIJE 1:100
32 89 M8 100 200.4 M10 PRILOG:
SARADNIK: BROJ PRILOGA: BROJ STRANE:
Marijan Vojinovi , Spec. DETALJ OSLONACA I MLAZNICA
40 99 M8 125 198.5 M12 05
4. FERUM ANKER TIP FC-10 50 114 M8 150 226.5 M12 Maj 2017.